![Page 1: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/1.jpg)
System GroundingImpact on reliability and Safety
Presented by:Daleep MohlaSergio Panetta Jim ChannonScott Lee
![Page 2: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/2.jpg)
Agenda
• System Grounding Considerations for 600 Volts and less system
• Types of System Grounding available
• Pros and Cons of each
• Mitigation strategies
• Selection guideline for mitigation
• Questions
![Page 3: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/3.jpg)
Systems Grounding Considerations
• Cost?
• Safety?
• Reliability ?
• Impact of unintended outages?Production loss?Environmental?Safety?
![Page 4: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/4.jpg)
Types of System Grounding
• Ungrounded
• Solid Grounded
• Impedance Grounded
![Page 5: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/5.jpg)
UNGROUNDED (DELTA) SYSTEM
L
O
A
D
Transformer Secondary
Feeder (with capacitance to ground)
![Page 6: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/6.jpg)
Normal operation Ground fault on phase C
Neutral point establishedby distributed capacitance
• Phase C at ground potential• No fault current (no return path to source)
All phases are atline‐to‐neutral voltageabove ground (eg: 347V) •A & B phases are
at line‐line voltageabove ground(eg: 600V)
UNGROUNDED SYSTEM:NORMAL OPERATION & FAULTED OPERATION
![Page 7: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/7.jpg)
Normal operationIntermittent ground fault on phase C
•A & B phases are:> Line‐line voltage above ground
• Phase C > ground voltage• Intermittent fault current • Personnel danger
UNGROUNDED SYSTEM:FAULTED OPERATION WITH TRANSIENT OVERVOLTAGE
![Page 8: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/8.jpg)
UNGROUNDED SYSTEMS:Pros and Cons
Pros
• Minimum Initial cost
•Ability to run with one phase faulted to ground
•Isolation of Primary and Secondary currents ( harmonics)
Initially used by the industry to prevent unplanned outages
![Page 9: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/9.jpg)
Ungrounded Systems
• Cons
• Difficult to detect ground‐ faults — no fault current
• Running with a ground‐fault increases stress on insulation, leading to phase‐to‐phase faults
• Intermittent fault may cause transient overvoltage
![Page 10: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/10.jpg)
Wye‐Connected Transformer Secondary
Feeder (with capacitance to ground)
L
O
A
D
SOLIDLY GROUNDED SYSTEM
![Page 11: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/11.jpg)
Solidly Grounding System
Pros
• Minimum first costs
• Immediate isolation of faulted system
• Voltage stabilization
• Allows use of neutral for single phase loads
• Visible detection of faulted equipment
• Equipment insulated rated for phase to ground voltage
![Page 12: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/12.jpg)
Solidly grounded Systems
CONS• Unplanned outages
• Voltage dips during fault conditions
• High arcing currents through grounding systems
• Motor terminal box covers have been reported blown away
• Fire Hazard especially in Hazardous (Classified) Areas
• High repair cost and time
![Page 13: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/13.jpg)
Wye‐Connected Transformer Secondary
Feeder (with capacitance to ground)
L
O
A
D
NGR
RESISTANCE GROUNDED SYSTEM
![Page 14: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/14.jpg)
NGRTransformer Secondary Feeder (with
capacitance)
L
O
A
D
Current Limited to NGR Let‐Through
RESISTANCE‐GROUNDED SYSTEMWITH A GROUND FAULT
IF X
![Page 15: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/15.jpg)
Resistance ( Impedance) Grounded Systems
Pros• Reduces unplanned outages
• Transient stability of the system
• Eliminates undesired voltage dips during fault conditions
• Allows fault detection of the faulted equipment
• Minimizes arcing fault current and arc flash hazard
![Page 16: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/16.jpg)
Resistance ( Impedance) Grounded Systems
• CONS
• Initial investment
• Fault detection and removal required
• System Integrity maintenance required
• Equipment insulation rated for phase to phase voltages
![Page 17: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/17.jpg)
Protection or Prevention:Which is more effective?
• Seat belts, Airbags , *Accident avoidance?• *alarm and automatic response when close to another car)
• NFPA 70E/CSA Z 462 primarily address protection of personnel to minimize personnel injury due to electrical hazards : Shock and Arc Flash by removing power with some soft suggestion on reduction of hazards
• Engineering controls minimize the potential of electrical incidents
• Safety By design minimizes injury potential.• Role of High Resistance Grounding?
17
![Page 18: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/18.jpg)
Ground Faults
• There has been documentation over the years indicating that between 80% and 95% of all electrical faults initiate as ground faults. By limiting the ground fault current to a small magnitude, a great majority of all phase‐to‐phase arcing faults can be eliminated.
• Informal numbers are that less than 1% of the faults are initially start as three phase faults (jumpers left installed, snakes etc)
18
![Page 19: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/19.jpg)
• 120.3 FPN No. 3:…high-resistance grounding of low-voltage and 5 kV (nominal) systems, … are techniques available to reduce the hazard of the system
Power System Grounding
Mitigation Electric Shock and Arc Flash Energy‐ A Total System Approach for Personnel and Equipment Protection IEEE IAS PCIC 2010
![Page 20: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/20.jpg)
• 4.3.1.1 Note (3)…high-resistance grounding of low-voltage and 5 kV (nominal) systems, … are techniques available to reduce the hazard of the system
Power System Grounding
Mitigation Electric Shock and Arc Flash Energy‐ A Total System Approach for Personnel and Equipment Protection IEEE IAS PCIC 2010
![Page 21: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/21.jpg)
70E‐ 130.5
• Informational Note No. 3: The occurrence of arcing fault• inside an enclosure produces a variety of physical phenomena
For example, the arc energy resulting from an arc developed in the air will cause a sudden pressure increase and localized overheating.
• Equipment and design practices are available to minimize• the energy levels and the number of at‐risk procedures that• require an employee to be exposed to high level energy• sources. Proven designs such as arc‐resistant switchgear,• remote racking (insertion or removal), remote opening and• closing of switching devices, high‐resistance grounding of• low voltage and 5 kV (nominal) systems, current limitation,• and specification of covered bus within equipment are
techniques available to reduce the hazard of the system
21
![Page 22: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/22.jpg)
High Resistance Grounding SystemsHigh‐Resistance Grounded
• There is minimal arc flash hazard, as there is with solidly grounded systems on the first fault, since the fault current is normally limited to a very low value
22
![Page 23: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/23.jpg)
High Resistance Grounding
• Does Resistance Grounding really reduce:
• Unplanned System outages?
• Potential of arc flash hazard?
Engineer’s answer “ It depends”
23
![Page 24: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/24.jpg)
High Resistance Grounding
• Yes if and only if
• Neutral grounding system Integrity is maintained .AND
• first fault is cleared before inception of second fault. (Second fault on the system will result in a phase to phase fault IF the FIRST FAULT IS NOT CLEARED)
![Page 25: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/25.jpg)
25
Possible Loss of Neutral Path
• Open or Shorted Neutral Path to Ground
ResistorFailure
LooseConnection
Broken Wire
Broken orGrounded Wire
Corrosion
Excerpt from a technical paper presented at 2009 IEEE IAS Electrical Safety Workshop
![Page 26: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/26.jpg)
Hazard Control Measures
![Page 27: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/27.jpg)
Hazard Control Measuresoutlined in ANSI Z10
Elimination Substitution EngineeringControls
Warnings AdministrativeControls
PPE
Addressed in NFPA 70E
Addressed in 70E Tables
Prevention Protection
An effective electrical safety program incorporates all control measures
![Page 28: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/28.jpg)
Loss of Ground in HRG Systems 28
AØ BØ
CØ
N N
HRGCØ
BØAØ AØ BØ
CØHRG
N
HRGCØ
Open Circuit:
• Desired fault current cannot flow.
• Ungrounded System.
Open Circuit:
• Desired fault current cannot flow.
• Grounded thru high inductive transformer.
• Resonance System.
Short Circuit:
• Undesired fault current can flow.
• Place CT close to N, >costs (elevated N).
• Solidly Grounded System.
Warning of Risk
![Page 29: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/29.jpg)
Loss of Ground in HRG Systems 29
AØ BØ
CØHRG
N
SensingResistor
Relay
• Ground Fault Relay & Sensing Resistor– Detects Open / Short Circuits and maintains Grounding
Automatic Reduction of Risk
![Page 30: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/30.jpg)
Avoiding Second Ground Fault
• To reduce arc flash hazard, it is critical to reduce the possibility of two faults at the same time.
• How?Warning of risk
• Either make sure maintenance people remove the ground fault immediately
• Automatic reduction of risk• Provide sensing equipment to prioritize feeders to avoid second simultaneous ground fault
30
![Page 31: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/31.jpg)
FAULT INDICATION USING 3 LAMPS
![Page 32: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/32.jpg)
Indication of first Feeder fault
AN
LOAD 1 LOAD 2
ZSCTZSCT
M1 M2
GMMETER
GMMETER
FAULTED FEEDER INDICATION
![Page 33: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/33.jpg)
- Alarm on first faultTrip on second faultCannot prioritize essential feeders Difficult to locate fault(s)
R R R
R 2.5APICKUP
100APICKUP
100APICKUP
100APICKUP
5A NGR
MGFRrelays
![Page 34: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/34.jpg)
Minimizing Second Simultaneous Ground Fault
35
![Page 35: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/35.jpg)
Faulted FeederFirst Fault Alarm
Faulted Phase Indication
Second Fault TripSelective Inst. Feeder TrippingGround Current as % of Let
Through
DDAI
DDR2
NGRALARM
FM1 FM2 FM3 FM4CM
DSP MKII
![Page 36: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/36.jpg)
Combined DSA/DSPIdentifies individual faultedload and PhaseSecond Fault Protection Backup
DDR2SWGR
DDR2 DSA
ALARM
ALARM
CM FM1 FM2 FM3 FM4
CM FM1
DSP MKII
TRIPS
![Page 37: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/37.jpg)
DSP RelayDouble ended Unit sub Application
![Page 38: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/38.jpg)
Parallel Generators
GENERATORS 600V
600V
DDR2-6
DSA
15-20A, 3P100 kAIC
5A, 347V NeutralGrounding Resistor
G G G G
To BMS
To BMS
TYPICAL PARALLEL GENERATOR HIGH RESISTANCE GROUNDING SCHEME
Zero Sequence Current Sensors(one per feeder; one per generator)
OptionalPulsing Resistor
5A, 600VZig-Zag GroundingTransformer
2 - #16AWG, 24 Vdcfor pulsing control
See Notes 1 and 2.
Notes:1. NGR/Zig-Zag assembly w ith pulsing resistor, IPC Part Number: OHMNI-6PM-5-ZZ2. NGR/Zig-Zag assembly w ithout pulsing resistor, IPC Part Number: NTR600-5-ZZ
DS-P
M2
Optional DS-PM2 Pulsing Card
AWG#8 as perCEC 10-1108(3)
![Page 39: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/39.jpg)
Mitigation Strategies
• Good System maintenance practices
• Better ‐WarningsAlarms Procedures PPE
• Best ‐Automatic Reduction of RiskEliminationEngineering Controls
![Page 40: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/40.jpg)
Mitigation Strategies selection
• Which one to use?
• “ It Depends”
• Consider safety/cost/benefit
• Impact due to failure in the systemCan system be shut down immediately?Cost of shutdown?
• Maintenance practices?
• Environmental conditions?
• Liability considerations of design?
![Page 41: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/41.jpg)
Risk reduction
• Key strategy in 70E/ CSA Z 462 is risk analysis
• Risk = Frequency X Consequences
• Use of HRG reduces the probability of frequency and thus reduces the risk
42
![Page 42: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/42.jpg)
Risk Analysis
• Does HRG reduces the incident energy required to be put on label?
NO. Label is based on 3 phase bolted fault
BUT• it does reduce probability of high incident energy (80‐ 95%) of the time and can be utilized in Risk Analysis.
43
![Page 43: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/43.jpg)
Questions ?
Thank you for being here !!
• Thanks for providing me with a forum for preaching electrical safety by design
• Daleep Mohla ,IEEE Fellow , P.E
44
![Page 44: System Grounding Impact on reliability and Safetysite.ieee.org/sas-pesias/files/2016/03/IEEE-Canada... · System Grounding Impact on reliability and Safety ... Power System Grounding.](https://reader030.fdocuments.us/reader030/viewer/2022040211/5e79adc918f1ab65f1742427/html5/thumbnails/44.jpg)