SYMMETRICAL COMPONENETS OF POWER SYSTEM

36
1 SYMMETRICAL COMPONENETS OF SYMMETRICAL COMPONENETS OF POWER SYSTEM POWER SYSTEM

description

SYMMETRICAL COMPONENETS OF POWER SYSTEM. OUTLINE OF THE PRESENTATION. INTRODUCTION NEED FOR THE SYMMETRICAL COMPONENET METHOD TECHINQUES USED TO ANALYSIS SYMMETRICAL SYMMETRICAL METHODS USED TO STUDY POWER SYSTEM FAULTS CONCLUSION REFERENCES. INTRODUCTION. - PowerPoint PPT Presentation

Transcript of SYMMETRICAL COMPONENETS OF POWER SYSTEM

Page 1: SYMMETRICAL COMPONENETS OF POWER SYSTEM

11

SYMMETRICAL COMPONENETS SYMMETRICAL COMPONENETS OF POWER SYSTEMOF POWER SYSTEM

Page 2: SYMMETRICAL COMPONENETS OF POWER SYSTEM

22

OUTLINE OF THE PRESENTATIONOUTLINE OF THE PRESENTATION

INTRODUCTIONINTRODUCTION NEED FOR THE SYMMETRICAL COMPONENET NEED FOR THE SYMMETRICAL COMPONENET

METHODMETHOD TECHINQUES USED TO ANALYSIS TECHINQUES USED TO ANALYSIS

SYMMETRICAL SYMMETRICAL SYMMETRICAL METHODS USED TO STUDY SYMMETRICAL METHODS USED TO STUDY

POWER SYSTEM FAULTSPOWER SYSTEM FAULTS CONCLUSIONCONCLUSION REFERENCESREFERENCES

Page 3: SYMMETRICAL COMPONENETS OF POWER SYSTEM

33

INTRODUCTIONINTRODUCTION

The normal operating conditions of an electric power The normal operating conditions of an electric power system are occasionally disrupted because of faults.system are occasionally disrupted because of faults.

Analysis of power systems usually implies the Analysis of power systems usually implies the computation of network voltages and currents under a computation of network voltages and currents under a given set of conditions.given set of conditions.

Under many circumstances we tend to ignore the Under many circumstances we tend to ignore the unbalanced operation in the system and unbalanced unbalanced operation in the system and unbalanced operation is always present.operation is always present.

Page 4: SYMMETRICAL COMPONENETS OF POWER SYSTEM

44

An organization of power system analysis problemAn organization of power system analysis problem

Source (Reference #1)Source (Reference #1)

Page 5: SYMMETRICAL COMPONENETS OF POWER SYSTEM

55

Effects of faults on power systemEffects of faults on power system

Flow of excessive currentFlow of excessive current Abnormal voltagesAbnormal voltages Voltage elevation of system neutralVoltage elevation of system neutral Induce over voltages on Induce over voltages on

neighbouring equipments .neighbouring equipments . Hazards to human, equipment and Hazards to human, equipment and

animals.animals.

Page 6: SYMMETRICAL COMPONENETS OF POWER SYSTEM

66

Need for fault analysisNeed for fault analysis

Design of protection system requires Design of protection system requires the knowledge of fault current.the knowledge of fault current.

The information obtained from the The information obtained from the fault studies are used:fault studies are used:

to select the sizes of circuit breaker,to select the sizes of circuit breaker, fuse and characteristic,fuse and characteristic, setting of relay.setting of relay.

Page 7: SYMMETRICAL COMPONENETS OF POWER SYSTEM

77

Normal types of fault are:Normal types of fault are:

Fault due to lightningFault due to lightning Tree limbs falling on the lineTree limbs falling on the line Wind damageWind damage Insulation deteriorationInsulation deterioration VandalismVandalism

Page 8: SYMMETRICAL COMPONENETS OF POWER SYSTEM

88

Types of faultTypes of fault

Symmetrical fault :Symmetrical fault : Usually three phase to ground faultUsually three phase to ground fault

Unsymmetrical faultUnsymmetrical fault The fault is unbalanced in natureThe fault is unbalanced in nature

Page 9: SYMMETRICAL COMPONENETS OF POWER SYSTEM

99

Sources of Asymmetrical fault are: Sources of Asymmetrical fault are: (Reference#2)(Reference#2)

Page 10: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1010

Sources of Asymmetrical fault are (cont.)Sources of Asymmetrical fault are (cont.)

One phase open circuitOne phase open circuit

Unbalanced in load mainly the arc Unbalanced in load mainly the arc loadsloads

Page 11: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1111

Sources of Asymmetrical fault are (cont.)Sources of Asymmetrical fault are (cont.) One phase open circuitOne phase open circuit

Page 12: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1212

Sources of Asymmetrical fault are (cont.)Sources of Asymmetrical fault are (cont.)

SLG faultSLG fault

Page 13: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1313

Need for the symmetrical component Need for the symmetrical component analysisanalysis

Negative sequence relay in generator has Negative sequence relay in generator has helped in protecting the generator from helped in protecting the generator from over heating in the event of unbalanced over heating in the event of unbalanced loads.loads.

The positive sequence segregating The positive sequence segregating network is used to supply the sensing network is used to supply the sensing voltage to generator voltage regulatorsvoltage to generator voltage regulators

Certain connections of CT and PT develop Certain connections of CT and PT develop zero sequence components that are used zero sequence components that are used in protective ground relaying scheme.in protective ground relaying scheme.

Page 14: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1414

Method of adopted for symmetrical Method of adopted for symmetrical component analysis (cont)component analysis (cont)

Mathematically:Mathematically: VVaa= V= Va1+ a1+ VVa2+ a2+ VVa3+---------- a3+---------- VVanan

VVbb= V= Vb1+ b1+ VVb2+ b2+ VVb3+---------- b3+---------- VVbnbn ;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;;

VVnn= V= Vn1+ n1+ VVn2+ n2+ VVn3+---------- n3+---------- VVnnnn Where:Where:

VVa, a, VVb……. b……. VVn are unbalanced set of phosorsn are unbalanced set of phosors

VVa1, a1, VVb1…… b1…… VVn1 first set of n balanced phasors with an angle 2pi/n n1 first set of n balanced phasors with an angle 2pi/n between components a,b,…..nbetween components a,b,…..n

Page 15: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1515

Method of adopted for symmetrical Method of adopted for symmetrical component analysis (cont)component analysis (cont)

Mathematically:Mathematically: VVa2, a2, VVb2…… b2…… VVn2 second set of n balanced phasors with an angle 4pi/n n2 second set of n balanced phasors with an angle 4pi/n

between components a, b………,…..nbetween components a, b………,…..n

………………………………………………………………………………………………………………..

VVa(n-1), a(n-1), VVb(n-1)…… b(n-1)…… VVn(n-1)are (n-1)th set of n balanced phasors with an n(n-1)are (n-1)th set of n balanced phasors with an

angle 2pi(n-1)/n between components a, b………,…..nangle 2pi(n-1)/n between components a, b………,…..n

Page 16: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1616

Phasor a or a-operatorPhasor a or a-operator

The phasor notation of a-operatorThe phasor notation of a-operator

Page 17: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1717

Phasor a or a-operatorPhasor a or a-operator

Page 18: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1818

Phasor a or a-operatorPhasor a or a-operator

Page 19: SYMMETRICAL COMPONENETS OF POWER SYSTEM

1919

Equation in matrix formEquation in matrix form

Page 20: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2020

Symmetrical components for three Phase systemSymmetrical components for three Phase system

The n-phase system presented above is of The n-phase system presented above is of academic interest only and only the academic interest only and only the practical three phase system will be practical three phase system will be emphasised.emphasised.

Power is generated, transmitted and Power is generated, transmitted and consumed mostly in three phase only.consumed mostly in three phase only.

Page 21: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2121

Symmetrical components for three Phase system Symmetrical components for three Phase system (cont)(cont)

The phasor representation of three The phasor representation of three phase system (source reference#2)phase system (source reference#2)

Page 22: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2222

Symmetrical components for three Phase system Symmetrical components for three Phase system (cont)(cont)

The positive sequence set consisting of three components The positive sequence set consisting of three components of equal magnitude, displaced by 120 & 240of equal magnitude, displaced by 120 & 240oo respectively respectively and having the phase sequence of abca.and having the phase sequence of abca.

The negative sequence set consisting of three components The negative sequence set consisting of three components of equal magnitude displaced by 240 & 120of equal magnitude displaced by 240 & 120o o respectively, respectively, having phase sequence of acba.having phase sequence of acba.

The zero sequence set of the component of which being The zero sequence set of the component of which being equal both in magnitude and and phase.equal both in magnitude and and phase.

Page 23: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2323

Symmetrical components for three Phase system Symmetrical components for three Phase system (cont)(cont)

Relations of voltage components in Relations of voltage components in matrix formmatrix form

Page 24: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2424

Symmetrical components of generatorSymmetrical components of generator

Page 25: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2525

Symmetrical components of generatorSymmetrical components of generator

Page 26: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2626

Symmetrical components of transformer (zero)Symmetrical components of transformer (zero)

Page 27: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2727

Fault analysis using symmetrical components Fault analysis using symmetrical components

The most common type of fault is the The most common type of fault is the single line to ground fault:single line to ground fault:

Page 28: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2828

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

The sequence component connection The sequence component connection for the single line to ground fault:for the single line to ground fault:

Page 29: SYMMETRICAL COMPONENETS OF POWER SYSTEM

2929

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

The sequence component connection for The sequence component connection for the single line to ground fault:the single line to ground fault:

The sequence components are connected The sequence components are connected in series.in series.

The three currents in the case of SLG fault The three currents in the case of SLG fault are equal.are equal.

Page 30: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3030

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

LL fault:LL fault:

Page 31: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3131

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

LL fault:LL fault: There is no zero sequence There is no zero sequence

component due to absence of ground component due to absence of ground return path.return path.

The positive and negative sequence The positive and negative sequence components are connected in components are connected in parallel.parallel.

Page 32: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3232

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

LLG fault:LLG fault:

Page 33: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3333

Fault analysis using symmetrical components Fault analysis using symmetrical components (cont) (cont)

LLG fault:LLG fault: For the zero sequence component it For the zero sequence component it

requires to add an external requires to add an external impedance of Zimpedance of Zff+3Z+3Zgg

The networks are connected in The networks are connected in parallel.parallel.

Page 34: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3434

Software available for carrying fault analysis Software available for carrying fault analysis

The most commonly used soft ware are:The most commonly used soft ware are:

MATLABMATLAB

EDSAEDSA

ETAPETAP

CYMECYME

Page 35: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3535

Conclusion Conclusion

Power system analysis using symmetrical Power system analysis using symmetrical component is very helpful in improving the component is very helpful in improving the reliability of the power system.reliability of the power system.

The principle adopted for the analysis of The principle adopted for the analysis of unbalanced fault system is symmetrical unbalanced fault system is symmetrical component method.component method.

By knowing the principle, the results By knowing the principle, the results obtained from the computer can be obtained from the computer can be analysed.analysed.

Page 36: SYMMETRICAL COMPONENETS OF POWER SYSTEM

3636

References: References:

1. Paul M. Anderson, Analysis of Faulted Power 1. Paul M. Anderson, Analysis of Faulted Power Systems.Systems.

2. W.D. Stevenson, Elements of Power System 2. W.D. Stevenson, Elements of Power System Analysis.Analysis.

3. A.P.S Meliopoulos, Power System Grounding and 3. A.P.S Meliopoulos, Power System Grounding and Transients.Transients.

4. Olle. I. Elgerd, Electric Energy Systems Theory.4. Olle. I. Elgerd, Electric Energy Systems Theory.

5. IEEE Transactions 5. IEEE Transactions