Susol & Metasol Air Circuit BreakersSusolSusol & & MetasolMetasol Air Circuit BreakersAir Circuit Breakers
&
1 / 30
Overview
1. Structure
2. Rating
3. Feature
4. Digital Trip Relay
5. Accessories
6. Certificates
2 / 30
1. Structure (1/4)1. Structure (1/4)
SUSOL & METASOL ACB are developed to meet high breaking capacity required for elevated electricity demend, to satisfy compact distribution panel size demanded in makers, to achieve 100% N phase current conducting capacity on single phaseLload and to increase user’s convenience by providing various accessories and connecting method.
SUSOL Seriese ACB has high breaking capacity and multi-function product and at the world class level which is used withP and S type of digital trip relay.
• AH type
2000 AF 4000 AF 6300 AF
• Ics=100%Icu at 500V
85KA 100KA 150KA
SUSOL Series
METASOL Seriese ACB has AS type product for the highest breaking capacity for its domestic market, and AN type productFfor concentrating on fundamental functions at affordable price.
• AS type
2000 AF 4000 AF 6300 AF
• Ics=100%Icu at 500V
70KA 85KA 120KA
METASOL Series
• AN type
2000 AF 4000 AF
• Ics=100%Icu at 500V
65KA 70KA
Introduction
150KA
3 / 30
1. Structure (2/4)1. Structure (2/4) External View
①
⑤
③
⑥
②
④
⑭
⑦
⑧
⑮
⑫
⑪⑨
⑩
⑬
■ Fixed type
■ Draw-out type
① ON button
② OFF button
③ Series name
④ Rated name plate
⑤ Charge Discharge indicator
⑥ ON/OFF indicator
⑦ Arc box
⑧ Charge handle
⑨ Draw-out handle
⑩ Handle storage space
⑪ Pad lock button
⑫ Position indicator
⑬ Arc cover
⑭ Digital trip relay
⑮ Terminal cover
4 / 30
1. Structure (3/4)1. Structure (3/4) Internal configuration
1
2
3
4
5
6
7
8
9
10
11
12 13 14 15 16 17 18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Control terminal block
Auxiliary switchesClosing, Trip, UVT coilTrip relay
Front cover
Mechanism
Closing springDraw in-out deviceArc extinguishing partMoving contactFixed contact
Conductor on Source side
Power supply CT
Connecting conductor tocircuit breakers
Charge handle
Cradle Finger
Conductor on load side
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Control terminal block
Control terminal
Cradle
Trip spring
5 / 30
1. Structure (4/4)1. Structure (4/4) Terminal configuration
There are many possible terminal configurations when connecting bus bar of distribution panel, vertical, horizontal, planetype, etc.
Horizontal type Vertical type Horizontal / Vertical type
Horizontal/Vertical – Front type Front - Horizontal/Vertical type Front type
6 / 30
2. Rating (1/2)2. Rating (1/2)
A, P, SP
5000
10000
12
85
100
630A~4000A
AH-E
N, A, P
5000
10000
12
85
85
630A~4000A
AS-E
N, A, P
5000
10000
12
65
70
630A~3200A
AN-EModel
150120100857065500Vac
Breaking Capacity, Icu
(kA)
A, P, SP
2000
5000
12
100
4000A~6300A
AH-G
N, A, P
2000
5000
12
100
4000A~6300A
AS-GAS-G
N, A, P
2000
5000
12
85
5000A
AH-DAS-DAN-D
A, P, SPN, A, PTrip Relay
5000
12000
12
65
200A~2000A
5000
12000
12
65
200A~2000A
100 %Rated current ofNeutral pole (%)
ElectricalLife cycle
Rated impulse withstand voltage (kV)
Rated short time withstand current, Icw,
1sec (A rms)
Susol & Metasol
200A~1600A
12
12000Mechanical
5000
50
Rated current, In
A, P, SP
5000
10000
12
85
100
630A~4000A
AH-E
N, A, P
5000
10000
12
85
85
630A~4000A
AS-E
N, A, P
5000
10000
12
65
70
630A~3200A
AN-EModel
150120100857065500Vac
Breaking Capacity, Icu
(kA)
A, P, SP
2000
5000
12
100
4000A~6300A
AH-G
N, A, P
2000
5000
12
100
4000A~6300A
AS-GAS-G
N, A, P
2000
5000
12
85
5000A
AH-DAS-DAN-D
A, P, SPN, A, PTrip Relay
5000
12000
12
65
200A~2000A
5000
12000
12
65
200A~2000A
100 %Rated current ofNeutral pole (%)
ElectricalLife cycle
Rated impulse withstand voltage (kV)
Rated short time withstand current, Icw,
1sec (A rms)
Susol & Metasol
200A~1600A
12
12000Mechanical
5000
50
Rated current, In
7 / 30
2. Rating (2/2)2. Rating (2/2)
85kA 100kA 150kA
630~2000AF 2000~4000AF 4000~6300AF
334mm 412mm 785mm
430
mm
375m
m
N phase100%
8 / 30
3. Feature (1/4)3. Feature (1/4)
▶Various Acessories Possession
▶Appropriate products for confronting IECand ANSI standard
▶Acquire multi-rating (690Vac, 500Vac)standard for all models
▶Impulse Withstand Voltage (Uimp) : 12kV
▶Ics = 100% Icu
▶N phase current conducting capacity :100 %
▶Suitable for installment with IT system
▶Possess various customer orienteddigital trip(N,A,P,S)
Feature
SUSOL & METASOL ACBs are the one of next generation in the world class equipped with various accessories andoutstanding performaces.
9 / 30
3. Feature (2/4)3. Feature (2/4)
Main Nameplate
▶ Ui : Rated Insuation Voltage
▶ Uimp : Impulse Withstand Voltage
▶ Ue : Rated Operational Voltage
▶ Icu : Ultimate Breaking Capacity
▶ Ics : Service Breaking Capacity
▶ Icw : Short Time Withstand Current
▶ MFG. Date : Manufacturing Date
Nameplate
10 / 30
By dispersing evenly through arch voltage occurred in case of breaking fault current by arc shute, it prevents to save the insulation recovery time; simultaneously, it shows outstanding breaking performance by reducing arc that can be occurred in arc contact board.
3. Feature (3/4)3. Feature (3/4)
11 / 30
Comm.
RS-485
종단저항
150Ω
Local Systems
RTUPLC
Terminationgresistance
1 2
3 4
5
6
Subject Function
1 Comm. Terminal block
RS-485
LED
LED
DIP Switch
PowerTerminal Block
2
CB/ DO control, Communication
Profibus-DP, MODBUS
Temperature Information
CB/DO condition, TRIOU condition
Comm speed setting, Add setting
3
4
5
6Control power, DI, TemperatureSesor Terminal
TRIO unit
▶Protocol : MODBUS, Profibus-DP
3. Feature (4/4)3. Feature (4/4)
It allows executing remote input, breaking, temperature monitoring, etc. through the communication network using TRIO (Temperture & Remote I/O).But in case of using only communication function of measurment and protection, communication is possible with OCR only.
12 / 30
4. Digital Trip Relay (1/5)4. Digital Trip Relay (1/5)
OCR with Multi-functions is to Satisfy Using Conditions for Devise Customers’ Demend.
N type A type P/S type
Susol Metasol Susol Metasol Susol Metasol
OCR Characteristics by Each type
• ZSI / Override/ MCR• L / S / I / Thermal• Self Power• Timer mounted• Fault info. Kept by Battery (LED)• 12bit ADC
• ZSI / Override/ MCR• L / S / I / Thermal• Communication (RS485)• SMPS : 110~220V• DC24/48V• Self Power• Timer mounted• Fault info. Kept by Battery
(10faults + LED)
• ZSI / Override/ MCR• L / S / I / Thermal / Earth leakage• UV/OV/OF/UF/rP/ Vun/lun• Measurement:V/A/W/Wh/F/PI• Harmonics (63rd)• Communication (RS485)
fault wave form• SMPS : 110~220V• DC24/48V• Self Power• Timer mounted• Fault info. Kept by Battery
(256faults + LED)
Operate as a current relay with its self-power Current Meter + Current relay + DO Control +Communication
Current / Voltage / Frequency / Energy Meter Type +Current relay + Voltage + Frequency relay + Communication
Every function of P type + Harmonics Analysis (63th) +Record Fault Frequency
13 / 30
N type P/S typeA type
4. Digital Trip Relay (2/5)4. Digital Trip Relay (2/5)
14 / 30
No Type of knob Mode setting step
① Long-time current setting Iu (0.5-0.6-0.7-0.8-0.9-1.0) × In
② Long-time current setting Ir (0.8-0.83-0.85-0.88-0.89-0.9-0.93-0.95-0.98-1.0) × Iu
③ Long-time trippng delay tr (0.5-1-2-4-8-12-16-20-off)× Ir@ 6 Ir
④ Short-time current setting Is (1.5-2-3-4-5-6-8-10-off)× Ir
⑤ Short-time tripping delay tsd I²t off : (0.05-0.1-0.2-0.3-0.4)×IrI²t on : (0.1-0.2-0.3-0.4) ×Ir
⑥ Instantaneous pick-up Ii (2-3-4-6-8-10-12-15-off)× In
⑦ Ground-fault pick-up Ig (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)× In
⑧ Ground-fault tripping delay tg I²t off시: (0.05-0.1-0.2-0.3-0.4)I²t on시: (0.1-0.2-0.3-0.4)
② ③
④ ⑤ ⑥
⑦
①
⑧
② ③① ④ ⑤
⑥ ⑦ ⑧
4. Digital Trip Relay (3/5)4. Digital Trip Relay (3/5)
N, A type Knob Configuration
15 / 30
No Type of knob Mode setting step
① Long-time current setting Ir (0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In
② Long-time tripping delay tr (0.5-1-2-4-8-12-16-20-off)× Ir@ 6 Ir
③ Short-time current setting Is (1.5-2-3-4-5-6-8-10-off)× Ir
④ Short-time tripping delay tsd I²t off : (0.05-0.1-0.2-0.3-0.4)×IrI²t on : (0.1-0.2-0.3-0.4) ×Ir
⑤ Inatantaneous pick-up Ii (2-3-4-6-8-10-12-15-off)× In
⑥ Ground-fault pick-up Ig (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1-off)× In
⑦ Ground-fault tripping delay tg I²t off시: (0.05-0.1-0.2-0.3-0.4)I²t on시: (0.1-0.2-0.3-0.4)
②
③ ④ ⑤
⑥ ⑦
①
P, S type Knob Configuration
②① ③ ④
⑤ ⑥ ⑦
4. Digital Trip Relay (4/5)4. Digital Trip Relay (4/5)
16 / 30
Electric Energy
Power calculation
Voltage/Current vector diagram
Harmonics Calculation
4. Digital Trip Relay (5/5)4. Digital Trip Relay (5/5)
17 / 30
5. Accessories (1/13)5. Accessories (1/13)
Thanks to various accessories, it is much easier to secure the safe usage and system upgrade so that it can be spec-in in the high-end market.
ACB Main
1. Trip Relay(OCR)
2. Charge Motor
3. Closing Coil
4. Shunt Coil(SHT1, SHT2)
5. Under Voltage Trip Device
6. Door Interlock
7. Mechanical Operated Cell SW
8. Mechanical Interlock
9. Aux Switch
10. Key Lock
11. Counter
12. ON/OFF Button Lock
13. Miss insertion prevent device
14. Automatically discharge mechanism
15. Manual Reset
18 / 30
5. Accessories (2/13)5. Accessories (2/13)
ACB Cradle
1. Safety Shutter2. Control connector3. Zero Arc Space4. Insulation barrier5. Cell Switch6. Door Interlock7. Mechanical operated cell switch8. Mechanical Interlock9. Miss insertion prevent device10. Cradle mounting block11. Shorting "b" contact12. Safety control cover13. Automatically discharge mechanism14. Racking Interlock15. Safety shutter lock16. Capacitor trip device17. Door Frame18. Dust cover19. OCR Tester20. ATS Controller21. Lift Hook22. Dummy ACB23. UVT Delay Controller
19 / 30
5. Accessories (3/13)5. Accessories (3/13)
ON/OFF Button Lock
To prevent the manual operation of closing / Trip button by mistake.
Insulation Barriar Between Poles / Phase
Prevent the arc which may arise and result in short-circuit between phase in advance
Draw-out type Fixed type
20 / 30
5. Accessories (4/13)5. Accessories (4/13)
Mechanical Interlock
It interlocks two or three circuit breajers mechanically by controlling and closing and trip operation mutually.
Door Interlock
It is a safety device which dose not allow the panel door to open when a circuit breaker is in the “ON”positon.
Interlocking with PNL door
Interlocking with ACB
21 / 30
5. Accessories (5/13)5. Accessories (5/13)
MOC (Mechanical Operated Cell Switch, MOC)
It is the contacts (10a10b) which indicate the ON/OFF condition of ACB by operating mechanicallyonly when ACB is in “CONNECTED” position and two types are available, Standard type and High capacity type.
Safety Shutter Lock
It is a locking device which prevents safety shutter from being opened when it is closed.
Shutter plateShutter plateKey lockKey lock
Guide shutterGuide shutter
Shutter lockShutter lock
22 / 30
5. Accessories (6/13)5. Accessories (6/13)
Cell Switch, C
It is a contact which indicates the prevent position of ACB (CONNECTED, TEST, DISCONNECTED)
Lift Hooking
It is a device for easy transport of ACB.
“C”contact“C”contact
23 / 30
Miss Insertion Prevent Device (MIP)
If the ratings of ACB dose not match ith cradle, it mechanically prevents ACB from being inserted intocradle of ACB.
A
C
E
G
B
D
F
1357
246
Cradle Body
Naming holes accordingTo the position
5. Accessories (7/13)5. Accessories (7/13)
24 / 30
ATS Controller with ACBs
The mechanical interlock has two types, Bar type, Wire type and ATS Controller is required additionallyto achieve the function of electrical onterlock.
5. Accessories (8/13)5. Accessories (8/13)
Operating Status
Operating Status
25 / 30
5. Accessories (9/13)5. Accessories (9/13)
UVT Time Delay Controller
It is a device which makes ACB tripped automatically to prevent the accident on load side due to underVoltage or power breakdown. There are two types, Instantaneous type and time delay type.
OCR Tester
It is an exclusive testing device which can test the function of OCR.
26 / 30
5. Accessories (10/13)5. Accessories (10/13)
Door Frame
It is used as an external guide when structuring the protrude type of panel and it improves the appear-ance of ACB by attaching it to the panel door.
Condenser Trip Device (CTD)
It gets a circuit breaker tripped electrically within regular time when control power supply is broken down and is used with Shunt coil, SHT.
Circuit Diagram
27 / 30
5. Accessories (11/13)5. Accessories (11/13)
Key lock : K1
It is locking device which prevents a certain circuit breaker from being operated y user’s discretionWhen two or more circuit breakers are used at the same time.
3 Circuit breakers can be arranged for the continuous power supply to the load side and be interlockedMutually by using key lock embedded in each curcuit breaker.
Key Interlock lock : K2
ACB1ACB1 ACB2ACB2 ACB3ACB3
28 / 30
5. Accessories (12/13)5. Accessories (12/13)
Only when two Key Interlocks are released at the same time, circuit breakers operate.Installation method is same as K1.
It is to monitor ON/OFF position of ACB from remote place.
Auxiliary contact (AX)
Key Interlock Double
Resistive Load Inductive Load Resistive Load Inductive Load
490V 5A 6A 5A 2.5A
250V 10A 6A 10A 10A
125V 10A 6A 10A 10A
250V 0.3A 0.3A 3A 1.5A
125V 0.6A 0.6A 10A 6A
30V 10A 6A 10A 10A
AX
HX
AC
HC
Standard ChargingType
Rapid Auto-reclosingCharging Type
Supply Method Standard Option
5a5b -
-
5a5b
-
5a4b
-
5a5b
AC
DC
ContactCapacity
No. of Contactthat can be used
ClassificationStandard High Capacity
Remark
29 / 30
5. Accessories (13/13)5. Accessories (13/13)
It displays the total number of ON/OFF operation of ACB.
Charge the closing spring of a circuit breaker by the external power source.Operating voltage range is in the range of 85%~110% Vn.
Charging Motor
Counter
30 / 30
6. Certificates6. Certificates
Susol & Meatsol ACB meet international standards such as IEC(KEMA).