![Page 1: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/1.jpg)
WATTS BAR NUCLEAR PLANT
SURVEILLANCE INSTRUCTION
SI-4.0.5.67.p
ESSENTIAL RAW COOLINGWATER PUMPS
UNITS 1 AND-2
"REVISION 0 OF-THIS PROCEDURE WAS ',
ORIGINALLY ISSUED AS SI-4.0.5.6"
Prepared By W. E. Webb. Jr.
PORC Review - '-
Approved By
Date Approved
Supervisor5, - / 2-1
Date
t-Superintendent
....1,-, 7,
0
IC Plant Master FileSuperintendentAssistant SuperintendentMaintenance Supervisor
IC Results SupervisoriC Operations SupervisorIC Quality Assurance Supervisor
iC Health PhysicistAdministrative SupervisorChemical LaboratoryInstrument Shop
IC Shift Engineer's Office
2C Unit Control RoomHealth Physics LaboratoryChief Storekeeper
IC Mechanical EngineerReactor EngineerChemical EngineerInstrument Engineer
3u Chief, Nuclear Generation Bran1 - Assistant Maintenance Supervisor
DPP Central Office FileiC P PROn TNnining rennrIU, NRC '2C Industrial Engineer
Rev. No. Date Revised Pages
0 5/23/78 All
1 10/10/78 All
The last page of this instruction isnumber 14
E111090395 811ios .'DR ADOCK 0500390 M
11030p MC-DR. .. .. I I
![Page 2: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/2.jpg)
WSI-4,,0.5.67.p
Puiwh List
Page 1 of 1Revision 1WBNP
Punch List
i. WBNP Draft Technical Specifications
2. The tolerence on acceptance criteria to be determined later.
3. ASME Section XI, IWP compliance and exceptions to be approved by NRC.
Specific Edition and Addenda to be specified in license. Test is written
to 1974 Edition.
4. Pump Curve in Appendix B to be verified by TVA-18. Bands denoting
acceptable and alert criteria tobe added later by results.
5. Relief will have to be requested from vibration testing ofASME Section XI program.
Signature
ERCW pump in
Da e
- ~. .
.......- .. ~ I.
![Page 3: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/3.jpg)
WBNPSI-4.0.5.6
7 .p
Page 1 of 3
Revision 1
0
1.0 STATEMENT OF APPLICABILITY
1.1 The purpose of this instruction is to demonstrate that the
essential raw cooling water pumps are OPERABLE. Their operability
is determined by verifying that the sum of the flow rates obtained
from the measured pump differential pressure and the verified
pump curve in Appendix A is equal to the sum of the flow rates in
the headers being used.
1.2 For operation in Modes 1, 2, 3, 4, 5, and 6 each essential raw
-cooling water pump shall be demonstrated operable once per month
in accordance with Surveillance Requirement 4.0.5 and the ASME
Boiler and Pressure Vessel Code, Section XI, Edition and Addenda
later.
This instruction satisfies Surveillance Requirement 4.0.5 for these
pumps.
NOTE: For operation in modes 1, 2,
shall be operable. In modes
NEEDED for the heat load are
2.0 REFERENCES
3, or 4 two5 or 6 onlyrequired to
independent ERCW loopsthe number of pumpsbe operable.
TVA Drawings 47W845-1 R547W610-67-1 R247W611-67-1 R2
3.0 PREREQUISITES AND TEST EQUIPMENT
3.1 Prerequisites
3.1.1 None
3.2 Test Equipment
3.2.1 None
4.0 PRECAUTIONS
4.1 Appendix A of this instruction is for
pump to service following maintenanceperformance.
use only when returning awhich could affect pump
1-
![Page 4: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/4.jpg)
WBNP
SI-4.0.5.67.pPage 2 of 3
týevision 1
5.0 INSTRUCTIONS
NOTE: This procedure is written for testing any number of pumpsoperating on the same train.
5.1 Note on the data sheet the ERCW pumps that are running and supplying
the same train by crossing out the identification letters of thepump (s) not running.
5.2 Verify on data sheet that the diesel generator heat exchanger
valves are closed.
5.3 Record the flow rate of each discharge header being supplied
by the pumps on data sheet.
5.4 Add the header discharge flow rates and record on data sheet.
5.5 Obtain the latest river level from Watts Bar Hydro 365-6300 orPax 217-2111.and record on-data sheet.
5.6 Calculate the ERCW pump suction pressure on data sheet.
5.7 Record the discharge pressure of each pump being tested on datasheet.
5.8 Compute the differential pressure across each pump and record on
data sheet.
5.9 Using the differential pressure from Step 5.8 and the curve inAppendix B for each specific pump, find the flow rate in gpm andrecord on data sheet.
5.10 Add the pump flow rates from 5.9.
5.11 Determine the difference between the pump flow rates in step 5.4
Step 5.10.
5.12 Verify on data sheet that the difference in the pump flow rates meet
the acceptance criteria of 6.0. I5.13 If pumps other than those running are to be tested, transfer the
running pump (s) with those not running per SOI-67. Insure that therequired number of pumps for the heat load are operating at alltimes. Repeat Steps 5.1 through 5.12 for the remaining pumps in'the train until all have been tested. Record the values for each
tested configuration on a separate data sheet.
5.14 If any value is not within the acceptable range specified in Section0'- re check-caic u Iations -then notify the shift'enginar. .
-2-
![Page 5: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/5.jpg)
0SI-4.0.5.67.pPage 3 of 3Revision 1WBNP
6.0 ACCEPTANCE CRITERIA
6.1 If the value obtained from the intersection of the pump differential
pressure and the pump flow rate falls within the "alert band" on the
curve in Appendix B, the frequency of testing will be increased to
twice a month until the cause of deviation is determined and corrected
and either the existing reference values verified or a new set established.
6.2 If the value at the intersection of the values is in the "Required
Action" range, the pump shall be declared inoperative and not
returned to service until the condition has been corrected.
-3-" " -- ' . 2 .i , ÷-
V
![Page 6: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/6.jpg)
* WBNPSI-4.0.5.67.pAppendix AP- age 1 of 2Revision 1
APPENDIX A
I. PURPOSE
I.1 The purpose of this appendix is to establish a procedure forverifying a point on the pump curve for an inoperable pumpfollowing maintenance which would affect pump performance.Since the pump cannot be tested individually, the test isperformed by obtaining the flow rate of the operable pump (s)from the pump curve and subtracting it from the total measuredflow rate of the headers. The resulting flow rate for theinoperable pump is used to deuermine the differential pressurefrom the pump curve. The measured differential pressure ofthe ihoperable pump is then compaired to the value from the pumpcurve to determine whether the pump performance is now satisfactory.
II. PROCEDURE
II.1 Determine from QA records that the pump (s) chosen to be testedwith the inoperable pimp is operable per Surveillance Instruction4.0.5.67.p. Verify on Data Sheet A.
11.2 Verify on Data Sheet A that the diesel generator heat exchangervalves are closed.
11.3 Transfer one running pump with the inoperable pump per SOI 67.Insure that the required number of pumps for the loop are
operating at all times.
11.4 Record the flow rate of each discharge header being supplied bythe pumps on Data Sheet A.
11.5 Add the header discharge flow rates and record on Data Sheet A.
11.6- Obtain the latest river level from Watts Bar Hydro 365-6300 orPax 217-2111 and record on Data Sheet A.
11.7 Calculate the ERCW pump suction pressure on Data Sheet A.
11.8 Record the discharge pressure of each pump being tested onData Sheet A.
11.9 Compute the differential pressure across the operable pump (s)and record on Data Sheet A.
II.I0_ Using the differential pressure from Ste 11.9 and the curve inAppendix B, find the flow rate in gpm -for. the operable pump (s)
and record on Data Sheet A.
- -4-
![Page 7: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/7.jpg)
SI-4.0.5.67.pAppendix A
Page 2 of 2Revision 1WBNP
II. PROCEDURE (Continued)
II.11 Add the flow rates obtained in Step II.10 and record on Data
Sheet A.
11.12 Subtract the total flow rate (Step II.11) from the total header
discharge flow rate (Step 11.5) and record on Data Sheet A.
11.13 Using the flow rate from Step 11.12 and the curve in Appendix B
find the differential pressure and record on Data Sheet A.
11.14 Compute the differential pressure across the inoperable pump
from Steps 11.7 and 11.8.
11.15 Determine the difference between the inoperable pump differential
pressures from Step 11.13 and 11.14.
11.16 Verify that the pump meets the Acceptance Criteria of III and is
now operable.
11.17 If the pump does not meet the acceptance criteria, recheck
calculations then notify the shift engineer.
III. ACCEPTANCE CRITERIA
III.1 The actual pump differential pressure and the differential
pressure determined from the curve in Appendix B shall be
equal + (later).
[
*1
![Page 8: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/8.jpg)
SI-4.0.5. 6 7.p
Data PackageA •m Page 1 of 2
Revision IWBNP
DATA PACKAGE COVER SHEET
APPENDIX A
ESSENTIAL RAW COOLING WATER PUMP POST MAINTENANCE TEST - TRAIN A
Performed By DateResults Engineering Aide
Was the acceptance criteria satisfied? Yes No
If criteria were n6t satisfied, notify the shift engineer who completes thefollowing:
Was a limiting condition for operation violated?
Yes (explain in remarks) No (explain in remarks)
Verified By __Date
Shift Engineer
Reason for test:
___ R~quired by schedule
Maintenance complete -on ..... .... ...
____Another system ( ) inoperable
- Plant condition (explain) "_ __._ _
_Other (explain)
---- -- -- -- -- -- -- -- ---- -- -- -- -- -- -- ---- -- ------
Review of Test Results
Asst. Shift Engineer Date.1
Review and Approval of Test Results
Alert Scheduling Required Yes No
Cognizant Engineer - - Date_ _
(Mechanical Results).... Rescheduled
QA S ta ff . ..... . .. .. ... .. .. .... . .... . -.. .. D a te
Remarks.
-6-
![Page 9: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/9.jpg)
Initials
11.2 Diesel generator heat exchanger valves closed. (1-FCV-67-66,2-FCV-67-66, l-FCV-67-67, 2-FCV-67-67)
11.4 Discharge header flow rate
11.5 Total header flow rate
11.6 River level
11.7 Pump suction pressure (river level - 653.33) x (0.43) =
psig
11.8
11.9
I1.10
II.11
)-653.33] x [0.4-P
Note: Cross out- inoperable _..... Operable Pump(s)pump or pumps not running A-A B-A C-A D-AInstrument Number PI 67-37A PI 67-41A PI 67-33A PI 67-29ADischarge PressureSuction Pressure (from 11.7)Differential Pressure
II
.I
11.12 Total header flow rate - total pump flow rate =( ) - ( ) = psig
11.13 Inoperable pump differential pressure from Appendix.B =_ psig
11.14 Discharge pressure - Suction pressure (Step 11.7)=.( )- ( .) psig
11.15 Differential pressure (Step 11.14) -/Differential pressure
. . (Step II.13)=
11.16 Pump is now operable
.... -7- -.. I
Header Inst. No. Flow Rate (gpm)IA I-FI 67-61
1B 1-FI 67-622A 2-FI 67-61
2B 2-FI 67-62
Operable Pumps Flow Rate from App. B (gpm)A-A
B-A
C-A
D-ATotal Flow Rate
* SI-4.0.5.67.pAppendix APage 2 of 2Revision 1WBNP
Data Sheet A Date
ESSENTIAL RAW COOLING WATER PUMP POST MAINTENANCE TEST - TRAIN A
Step
II.1 Pumps to be tested with inoperable pump
psig
![Page 10: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/10.jpg)
SI-4.O.5. 67.p
Data PackagePage 1 of 2Revision1WBNP
DATA PACKAGE COVER SHEET
APPENDIX A
ESSENTIAL RAW COOLING WATER PUMP POST MAINTENANCE TEST -TRAIN B.
Performed By _________________Date ________
Results Engineering Aide
Was the acceptance criteria satisfied? _____Yes ____No
If criteria were not satisfied, notify the shift engineer who completes the
following:
Was a limiting condition for operation violated?
Yes (explain in remarks) ___No (explain in remarks)N
Verified By ________________Date________
Shift Engineer
Reason for test:
______ R~quired by schedule
Maintenance complete on
Another system ()inoperable
_______Plant condition (explain)______________________
______Other (explain) -
Review of Test Results"
Asst. Shift Engineer Date _______
Review and Approval of Test Results
Alert Scheduling Required -______Yes _____No
Cognizant Engineer _____________________ Date______
~.~,.~.(Mechanical Results)
Rescheduled
Remarks-
![Page 11: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/11.jpg)
0 SI-4.0.5.67.pAppendix APag". 2 of 2Revision 1WBNP
Data Sheet A Date
ESSENTIAL RAW COOLING WATER PUMP POST MAINTENANCE TEST - TRAIN B
Step
II.1 Pumps to be tested with inoperable pump
Initials
11.2 Diesel generator heat exchanger valves closed. (1-FCV-67-66,2-FCV-67-66, 1-FCV-67-67, 2-FCV-67-67)
11.4 Discharge header flow rate
11.5 Total header flow rate
11.6 River level ft
11.7 Pump suction pressure = (river level - 653.33) x (0.43) =
psig
11.8
11.9
653.33] x [0.43
II110 Operable PumpsE-9
11.11 Total Flow Rate
Flow Rate from App. B (pm)
LL.L2 Total header flow rate.- total pump flow rate = ( ) - ( ) = psig
11.13 Inoperable pump differential pressure from Appendix B = . psig
11.14 Discharge pressure -Suction pressure (Step 11.7) = ( ) - ( )= _-
_-
_ psig
11.15 Differential pressure (Step 11.14) - Differential pressure .. -" .... . ....... . ...... ...... (Step HI.13)= ... . . . .psig.i
11.16 Pump is now operable
---------------------. .| ,
Header Inst. No. Flow Rate (gpm)IA I-FI 67-61IB I -F I 6 7 -6 2 .. . ... ...2A 2-FI 67-61 _
2B 2-FI 67-62
Note: Cross out inoperable Operable Pump(s)pump or pumps not running E-B F-B G-B H-BInstrument Number PI 67-60A PI 67-56A PI 67-48A PI 67-52ADischarge Pressure
Suction Pressure (from 11.7)Differential Pressure
![Page 12: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/12.jpg)
EM
0
![Page 13: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/13.jpg)
* SI-4.0.5.6 7 .pWData Package
P-'ge 1 of 2
Revision 1WBNP
DATA PACKAGE COVER SHEET
ESSENTIAL RAW COOLING WATER PUMP - TRAIN A
Performed By Date
Unit Operator
Was the acceptance criteria satisfied? Yes No "
If criteria were not satisfied, notify the shift engineer who completes thefollowing:
Was a limiting condition for operation violated?
Yes (explain in remarks) No (explain in remarks)
Verified By DateShift Engineer
Reason for test:
___ R~quired by schedule
_ _ Maintenance complete on
____Another system ( ) inoperable
__________ Plant condition (explain) ....... ............. . .. _.
Other (explain)
Review of Test Results
Asst. Shift Engineer Date
Review and Approval of Test Results
Alert Scheduling Required -Yes No
" Cogniai EngiDate~___________(Mechanical Results)
Rescheduled"-
QA Staff Date
Remarks
.-".. ... .,•: < ' i• -• ... .. : . . . .• -, • . •: •. . .. 1. 71.._ . . . •. .. ,• . .- . . . .. . . _ . , -
![Page 14: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/14.jpg)
0 SI-4.0.5.67.pData PackagePage 2 of 2Revision IWBNP Unit
Mode
Date
ESSENTIAL RAW COOLING WATER PUMPS - TRAIN A
Step
5.1 Cross out pump(s) not running A-A B-A C-A D-A
Initials
5.2 Diesel generator heat exchanger
2-FCV-67-66, I-FCV-67-67, 2FCV-,
5.3 Discharge header flow rate
5.4 Total header flow rate
5.5 River level ft
closed . (1-FCV-67-66,
Header Inst. No. Flow Rate (gpm)
IA I-FI 67-61lB 1-FI 67-62
2A 2-FI 67-612B 2-FI 67-62
5.6 Pump suction pressure = (river level - 653.33) x (0.43) = [ )- 653.33] x.['4
psig
~PumpA-A B uA C-A D-A
Instrument Number PI 67-37A PI 67-41A PI 67-33A PI 67-29A
Discharge Pressure
Suction Pressure (from 5.6).
[Differential Pressure j
Pump Flow Rate from Graph (gpm)A-AB-AC-AD-A
Total flow
5.11 Step 5.4 - Step 5.10 = ( gpm,
5.12 Pump flow rate meets the acceptance criteria of 6.0
REMARKS: ............. .
- q2, - -. "I' I" ,
5.7
5.8
5.9
5.10
![Page 15: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/15.jpg)
* SI-4.0.5.6 7.pW •Data Package
Page 1 of 2Revision 1WBNP
DATA PACKAGE COVER SHEET
ESSENTIAL RAW COOLING WATER PUMP - TRAIN B
Performed By Date
Unit Operator
Was the acceptance criteria satisfied? Yes No
If criteria were not satisfied, notify the shift engineer who completes thefollowing.:
- Was a limiting condition for operation violated?
__Yes (explain in remarks) No (explain in remarks)
Verified By Date
Shift Engineer
Reason for test:
Required by schedule
Maintenance complete on
Another system ( ) inoperable
Plant condition (explain) ....... ... ... .... ..... . .. .... _-
Other (explain) _,
-----------------------------------------
Review of Test Results'
Asst. Shift Engineer Date
Review and Approval of Test Results
Alert Scheduling Required _ _ Yes No'-Cognizant Engineer.
Date*. (Mechanical Results)
Q A S t a f f -. D a te.. . . . . .. . . . . .. .Date
R e m a r k s " " . " ... - -
- 2 -
![Page 16: 'Surveillance Instruction - Essential Raw Cooling Water Pumps.' · 2012. 11. 30. · Operable Pumps Flow Rate from App. B (gpm) A-A B-A C-A D-A Total Flow Rate * SI-4.0.5.67.p Appendix](https://reader036.fdocuments.us/reader036/viewer/2022071509/612a190471c4c558ee005a34/html5/thumbnails/16.jpg)
SI-4.0.5.67.p
Datp PackagePage 2 of 2Revision 1WBNP
Mode
Date
ESSENTIAL RAW COOLING WATER PUMPS - TRAIN B-
Step
5.1 Cross out pump(s) not running E-B F-B" G-B H-B
Initials
5.2 Diesel generator heat exchanger valves closed.2-FCV-67-66, *1-FCV-67-67, 2-FCV-67-67)
5.3 Discharge header flow rate
5.4 Total header flow rate
5.5 River level ft
(1-FCV-67-66,
5.6 Pump suction pressure = (river level - 653.33) x (0.43) ) - 653.33] x[0.4j,
psig
Pum_ Flow Rate from Graph (gpm)
5.9 _-_
F-oG-B
5.10 Total flow
5.11 Step 5.4 - Step 5.10 = ( gpm-*
,5.12 _*Pump. flow rate meets the acceptance criteria of 6.0
REMARKS:
-14-
U
Header Inst. No. Flow Rate (gpm)
IA I-FI 67-61
lB I-FI 67-622A 2-F1 67-61
2B 2-FI 67-62
Pump
E-B F-8 H-B
Instrument Number PI 67-60A PI 67-56A PI 67-48A PT 67-52A
Discharge Pressure
Suction Pressure (from 5.6),
Differential Pressure
Unit