surge arrester.pptx

download surge arrester.pptx

of 40

Transcript of surge arrester.pptx

  • 7/28/2019 surge arrester.pptx

    1/40

    Surge Arrester

    M. M. Meraat

    Spring 1392

  • 7/28/2019 surge arrester.pptx

    2/40

  • 7/28/2019 surge arrester.pptx

    3/40

    introduction Surge arresters constitute an indispensable aid to insulation

    coordination in electrical power supply systems.

    The overvoltages that can affect the power system can be classified

    into: lightning overvoltages (seconds)

    switching overvoltages (mseconds)

    temporary overvoltages (seconds)

    highest continuous system oper. voltage.

  • 7/28/2019 surge arrester.pptx

    4/40

    Overvoltages in the power system

  • 7/28/2019 surge arrester.pptx

    5/40

  • 7/28/2019 surge arrester.pptx

    6/40

    overvoltage Temporary overvoltage

    conversion into standard voltage:

    A sinusoidal voltage with frequency between 48 Hz and62 Hz

    T1 = 60 s

  • 7/28/2019 surge arrester.pptx

    7/40

    overvoltage Transient overvoltage

    Short-duration overvoltage of few milliseconds or less,

    oscillatory or non-oscillatory, usually highly damped.

    May be followed by temporary overvoltages. In this

    case, both events are considered as separate events.

    Types: Slow front

    Fast front

    Very fast front

  • 7/28/2019 surge arrester.pptx

    8/40

    overvoltage Transient overvoltage

    Slow front

    Transient overvoltage, usually unidirectional

    5000 s Tp > 20 s

    T2 20 ms

    Main reasons: line faults, switching

    Conversion into standard:

    An impulse voltage of

    Tf = 250 s

    tT = 2500 sCurrent standard impulse:

    Tf = 30 s

    tT = 70 s

  • 7/28/2019 surge arrester.pptx

    9/40

    overvoltage Transient overvoltage

    Fast front

    Transient overvoltage, usually unidirectional

    20 s T1 > 0.1 s

    T2 300 s

    Main reasons: lightning strokes

    Conversion into standard:

    An impulse voltage of

    Tf = 1.2s

    tT= 50sCurrent standard impulse:

    Tf = 8 s

    tT = 20 s

  • 7/28/2019 surge arrester.pptx

    10/40

    overvoltage Transient overvoltage

    Very Fast front

    100 ns Tf > 3 ns

    tT 3 ms

    superimposed oscillations 30 kHz f 100 MHz

    Main reasons: switching of disconnectors in GIS

    Conversion into standard:

    not standardized

  • 7/28/2019 surge arrester.pptx

    11/40

    Temporary OvervoltagesEarth Faults

    In case of earth faults the overvoltage amplitudesdepend on

    neutral earthing

    fault location

    Important parameter: Earth fault factor k

  • 7/28/2019 surge arrester.pptx

    12/40

    Temporary OvervoltagesEarth Faults

    Earth fault factork

  • 7/28/2019 surge arrester.pptx

    13/40

    Temporary Overvoltages Load Rejection:

    When a transmission line ora large inductive load that is fedfrom a power station is suddenly switched off, the generatorwillspeed up and the bus barvoltage will rise. The amplitude ofthe overvoltage can be evaluated approximately by

  • 7/28/2019 surge arrester.pptx

    14/40

    Load Rejection:

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    15/40

    Load Rejection:

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    16/40

    Load Rejection:

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    17/40

    Load Rejection:

    Voltage increase factors due to load rejection:

    moderately extended systems: < 1.2 p.u. for up to severalminutes

    widely extended systems: 1.5 p.u. for some seconds close to turbo generator: 1.3 p.u.

    close to salient pole generator: 1.5 p.u.

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    18/40

    Resonance:

    Temporary overvoltages caused by resonance

    phenomena generally arise when circuits with large

    capacitive elements, such as:

    Lines

    Cables series compensated lines

    and inductive elements having non-linear

    magnetizing characteristics, such as

    Transformers

    shunt reactors

    are energized, or as result of load rejections.

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    19/40

    Resonance:

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    20/40

    Resonance:

    Temporary Overvoltages

  • 7/28/2019 surge arrester.pptx

    21/40

    Temporary Overvoltages and Surge Arresters

    Surge arresters cannot limit TOV!

    Exception: resonance effects may be suppressed or

    even avoided by MO arresters. Care has then to be

    taken not to thermally overload the arresters!

  • 7/28/2019 surge arrester.pptx

    22/40

    Slow front overvoltages

    Slow-front overvoltages have front durations of some

    tens to some thousands of microseconds and taildurations in the same order of magnitude and are

    oscillatory by nature. They generally arise from:

    line energization and re-energization;

    faults and fault clearing; switching of capacitive or inductive currents;

    distant lightning strikes to the conductor of overhead lines.

    The representative voltage stress is characterized by:

    a representative voltage shape 250/2500 S a representative amplitude which can be either

    an assumed maximum overvoltage or

    a probability distribution of the overvoltage amplitudes.

  • 7/28/2019 surge arrester.pptx

    23/40

    Slow front overvoltages

    Slow-front overvoltages have front durations of some

    tens to some thousands of microseconds and taildurations in the same order of magnitude and are

    oscillatory by nature. They generally arise from:

    line energization and re-energization;

    faults and fault clearing; switching of capacitive or inductive currents;

    distant lightning strikes to the conductor of overhead lines.

    The representative voltage stress is characterized by:

    a representative voltage shape 250/2500 S a representative amplitude which can be either

    an assumed maximum overvoltage or

    a probability distribution of the overvoltage amplitudes.

  • 7/28/2019 surge arrester.pptx

    24/40

    Slow front overvoltages

    Thestatistical BSL is the crest value of a standard

    switching impulse for which the insulation exhibits a90% probability of withstand, a 10% probability offailure.

    The conventional BSL is the crest value of a

    standard switching impulse forwhich the insulationdoes not exhibit disruptive discharge whensubjected to a specific number of applications ofthis impulse.

  • 7/28/2019 surge arrester.pptx

    25/40

    Slow front overvoltages

    SOV for a 500kV line

  • 7/28/2019 surge arrester.pptx

    26/40

    Slow front overvoltages

    Statistical SOV: E2 is the "statistical switching

    overvoltage. The probability that the SOV equalsor exceeds E2 is 0.02.

  • 7/28/2019 surge arrester.pptx

    27/40

    Fast front overvoltages

    Fast-front overvoltages may be:

    lightning overvoltages affecting overhead lines;

    lightning overvoltages affecting substations;

    Reasons for lightning overvoltages affecting OHL:

    direct lightning strikes to the phase

    lightning strikes to tower/ground wire and subsequent

    back flashover;

    induced by lightning strikes to ground nearby the

    OHL.

  • 7/28/2019 surge arrester.pptx

    28/40

    Fast front overvoltages

    The representative voltage stress is characterized

    by:

    a representative voltage shape : 1.2/50s;

    a representative amplitude which can be either

    an assumed maximum overvoltage or

    a probability distribution of the overvoltage amplitudes.

    Amplitudes and rates of occurrence depend on:

    Lightning performance of the OHLs connected to it;

    Substation layout, size and in particular number of

    OHLs connected to it; instantaneous value of the operating voltage (at the

    moment of strike).

  • 7/28/2019 surge arrester.pptx

    29/40

    Very Fast Front Overvoltages

    originate from disconnector operations or faults within

    GIS due to the fast breakdown of the gas gap and thenearly undamped surge propagation within the GIS.

    Amplitudes are rapidly damped and front times

    increased when leaving the GIS through the bushing.

    VFFO are usually not a concern or a dimensioningparameter for the hv insulation. Therefore no

    standardized test has yet been defined (and is not under

    consideration, either).

    Mainly an EMI problem, as external electric fields may

    appear between the metal enclosure and ground .

    problem for secondary control circuits.

    Countermeasures: usual means of EMC.

  • 7/28/2019 surge arrester.pptx

    30/40

    overvoltage

  • 7/28/2019 surge arrester.pptx

    31/40

    Metal Oxide (MO) Arresters Even though a great number of arresters which are

    gapped arresters with resistors made of silicon-carbide(SiC), are still in use, the arresters installed today are almostall metal-oxide (MO) arresters without gaps

    The distinctive feature of an MO resistor is its extremelynon-linear voltage-current or U-I characteristic, renderingunnecessary the disconnection of the resistors from the

    line through serial spark-gaps, as is found in the arresterswith SiC resistors.

    The currents passing through the arrester within the rangeof possibly applied power-frequency voltages are so smallthat the arrester almost behaves like an insulator.

    If, however, surge currents in the kiloampere range areinjected into the arrester, such as is the case whenlightning or switching overvoltages occur, then theresulting voltage across its terminals will remain lowenough to protect the insulation of the associated devicefrom the effects of overvoltage.

  • 7/28/2019 surge arrester.pptx

    32/40

    Metal Oxide (MO) Arresters

  • 7/28/2019 surge arrester.pptx

    33/40

    U-I Characteristic of MO Arrester U-I-characteristic of a typical MO arrester connected between phase

    and ground in a solidly earthed neutral 420-kV-system. (voltage peak

    value is depicted linearly, while current peak values are given in alogarithmic scale.)

  • 7/28/2019 surge arrester.pptx

    34/40

    Arrester parameters The power-frequency voltage, while continuously

    applied to the arrester, is the highest phase-to-earthvoltage of the system. In this case the peak value is:

    At the same time, the so-called leakage current flows

    through the arrester. This consists of a large capacitiveand a considerably smaller, resistive component.

  • 7/28/2019 surge arrester.pptx

    35/40

    Arrester parameterscontinuous operating voltage

    the power-frequency voltage which the arrestercan be operated at, without any type ofrestrictions

    the continuous operating voltage is greater than the

    highest continuously occurring phase-to-earth voltage.An allowance of at least 5% (IEC 60099-5, clause 3.2.1)

    is recommended. With this, possible harmonics in the

    system voltage are taken into account.

    rated voltage (Ur):

    is somewhat misleading. Instead it characterizes the

    capability of the arrester to deal with temporary

    overvoltages in the system. It can only be applied

    temporarilyfor a time period of 10 seconds.

  • 7/28/2019 surge arrester.pptx

    36/40

    Arrester parameterscontinuous operating voltage

    the power-frequency voltage which the arrestercan be operated at, without any type ofrestrictions

    the continuous operating voltage is greater than the

    highest continuously occurring phase-to-earth voltage.An allowance of at least 5% (IEC 60099-5, clause 3.2.1)

    is recommended. With this, possible harmonics in the

    system voltage are taken into account.

    Rated voltage (Ur):

    is somewhat misleading. Instead it characterizes the

    capability of the arrester to deal with temporary

    overvoltages in the system. It can only be applied

    temporarilyfor a time period of 10 seconds.

  • 7/28/2019 surge arrester.pptx

    37/40

    Arrester parametersRated voltage (Ur):

    The actual cause of the temporary time limit is thesudden great increase in the temperature and the

    frequent rise in leakage current (the UI-characteristic is

    temperature-dependence), after, for example, the

    arrester has diverted a current impulse to the ground

    (that is, after it had to "operate").

    In this case an extensive application of the rated

    voltage could render the arrester incapable of

    recooling; instead it would become thermally unstable

    and would continually heat up until it reached self-destruction (so-called thermal runaway).

  • 7/28/2019 surge arrester.pptx

    38/40

    Arrester parameters Lightning impulse protective level

    This depicts the voltage which drops across the arresterterminals when the nominal discharge current flows through the

    arrester.

    The aforementioned is a lightning current impulse of a

    standardized shape, whose amplitude is assigned to different

    classes from 1.5 kA to 20 kA, according to the IEC standard60099-4. For high-voltage arresters (in systems with Us 123 kV)only classes 10 kA and 20 kA are common.

    Two "10-kA-arresters" can have very different properties.When selecting an arrester the nominal discharge currenttherefore cannot be considered on its own.

    The statement "lightning impulse protective level = 823 kV"means the following: a voltage at a maximum of 823 kVdrops across the terminals when impressing a lightningcurrent impulse of 8 sof virtual front time, 20 sof virtualtime to half-value on the tail and a peak value of 10 kA

  • 7/28/2019 surge arrester.pptx

    39/40

    Arrester parameters Lightning impulse protective level

    This depicts the voltage which drops across the arresterterminals when the nominal discharge current flows through the

    arrester.

    The aforementioned is a lightning current impulse of a

    standardized shape, whose amplitude is assigned to different

    classes from 1.5 kA to 20 kA, according to the IEC standard60099-4. For high-voltage arresters (in systems with Us 123 kV)only classes 10 kA and 20 kA are common.

    Two "10-kA-arresters" can have very different properties.When selecting an arrester the nominal discharge currenttherefore cannot be considered on its own.

    The statement "lightning impulse protective level = 823 kV"means the following: a voltage at a maximum of 823 kVdrops across the terminals when impressing a lightningcurrent impulse of 8 s of virtual front time, 20 s of virtualtime to half-value on the tail and a peak value of 10 kA

  • 7/28/2019 surge arrester.pptx

    40/40