    ISRAEL Energy AuditAndreas Iliou - measurements analysis, connectors

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    2/21

    01Module Circuit Design

    Different strings

    Iso fault measurements

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    3/21

    Powador Inverters modules STP 210 18 Ud

    It is highly important to measure one module only against frame , either isolatedwith wood or similar isolator

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    4/21

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    5/21

    Measuring + Pole and Pole seperate against frame or/ and structure

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    6/21

    01

    Earthing structure several times earthed towards the roof structure , thereforeIf the wiring to bond with the earth near inverter is not big enough ,after

    Kirchhoff s law, current will flow according the lowest resistance.

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    7/21

    7 Module Circuit Design Analysing

    Measured 25,9 MOhm with normal Isolationtester Megger ~okIf still mounted on the structure

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    8/21

    8 Module Circuit Design Analysing

    Measured (isolated) real values / 1 module but + and - shortcut

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    9/21

    9 Module Circuit Design Isolation fault

    Measured 625 MOhm with Isolationtester HT 420

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    10/21

    10 Module Circuit Design Analysing/ImpedanceImpedance

    The current will flow in any direction, if earth wire (back) is to small

    UL = 25V0.71 Ohm (RS)

    338 Ik

    UL = 25V1.04 Ohm (RS)

    230 Ik

    UL = 25V0.18 Ohm (RS)

    1315 Ik

    230V +50A*0,71Ohm~265,5V AC

    230V + 50A*1,04Ohm~282 V AC

    230V + 50A*0,18Ohm~239 V AC

    Overcoming earthing (Ri)and Impedance (Rn)problems-

    -with a existing value of 1,02 OhmRn~ max 10,791 kW 3 phase can be realised

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    11/21

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    12/21

    01

    Earthing with Aluminium corrosion protected

    Different clamp variations

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    13/21

    01

    Earthing with Aluminium corrosion protected

    Lightning rods can be used to bond , without corrosion- like sample here

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    14/21

    14 Modules checked , earthing concept

    Value to high 13, 79 Ohm measured, flow will divert into the Pillars

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    15/21

    15 Modules checked , earthin concept

    Value to high 4,8 Ohm measured, flow will divert into the Pillars

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    16/21

    16 Modules checked , earthing concept

    Value here 0,08 Ohm measured, flow will divert into the Pillars-The other earthing point not good

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    17/21

    17 Module 816W/m 25degrees angle

    1. Row 2,4A ~ 7A

    816 W 46,4 degree C

    Cloudy but values ok

    2 rows always checked with temperatures 44 degree C

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    18/21

    18 Bypass Diodes

    Bypass diodes getting hotter, heating up- normal values

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    19/21

    19 Conclusion

    -During dry period all measurements done showed > 199 Ohm

    -When we poured water over the surface and tested with PV Benningvalues stayed longer on safe side

    because of it s triggering capacity and adjustment regards PV

    Megger testing device not purely for PV onlyEarth loop and Neutral Impedance has to be checked on site

    - Earth Rod has to be done via Tri Pod or 45 degrees angled( wrong/false readings from Inverter )

    During operationthe module somehow accumulated static loads.

    With a massive grounding ( way below 1 Ohm) we can dischargequickly any static or impedance driven faulty readingsand

    faulty Phantom Iso fault will disappear.The inverter if configured upfront Suisse Mode by that a emf friendly version

  • 7/31/2019 Suntech Engineer Visits RCS Solar Customers in Israel

    20/21

    20 Conclusion I

    Equal to the new israely local requirements ( since 2012 )Earth wiring should be done via a aluminium wire only,

    - The earthing structure won t corrode over time otherwisewe will face the same problem every year once the earth will

    loose it s conductivity over time.- 10sqmm or 16sqmm are sometimes not enough it should be strong enough

    to bring any problems ( leakage currents) back to source withoutstray currents involved direct or indirect.

    - The surface of the installed m should not exceed 60. Afterwards the structure should be broken to let not to many modules ran parallel over the same area