Substation hardened programmable logic controller · Document and software archiving toolset to...
Transcript of Substation hardened programmable logic controller · Document and software archiving toolset to...
487
Spec
ializ
ed P
rote
ctio
n &
Cont
rol
g Digital Energy
• Powerfulanddeterministicprogrammablelogicsuitableforcreatingmostcustomizedautomatedsubstationcontrolsolutions
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• Reducedbayorstationwiringthroughtheuseofhigh-speedpeer-to-peercommunicationforsendingandacceptingcontrolcommandsfromotherrelays
• ModularhardwarearchitectureallowingforflexibilityintheI/Oconfigurationtosupportmostbaymanagementapplications
• AdvancedSequenceofEventsanddisturbancerecording
providingaccurateloggingofstationeventsthuseliminatingtheneedforexternalrecordingdevices
• SimplifiedsystemintegrationandaccesstoinformationthroughtheuseofmultiplecommunicationoptionsandprotocolsnotfoundinindustrialgradePLCs
• EmbeddedIEC61850Protocol• Ambienttemperaturemonitoringwithalarmingwhenoutside
temperatureexceedsupperthresholds• RobustnetworksecurityenablingCriticalInfrastructure
Protectionthroughusercommandlogging,anddualpermissionaccesscontrol
• Baycontrolandsubstationautomation• ProgrammableLogicControl
• URI/Oexpansion• SequenceofEvents(SOE)recorderreplacement
• Oscillography–analoganddigitalparametersat64samples/cycle
• EventRecorder-1024timetaggedeventswith0.5msscanofdigitalinputs
• DataLogger-16channelswithsamplingrateupto1sample/cycle
• SettingSecurityAuditTrailfortrackingchangestoC30configuration
Monitoring and Metering
EnerVistaTM Software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure
referencematerialanddeviceutilitiesareup-to-date• EnerVistaTMIntegratorprovidingeasyintegrationofdata
intheC30intoneworexistingmonitoringandcontrolsystems
Protection and Control• Programmablelogic,timers,counters• Distributedlogic,remoteI/Oexpansion• User-definableprotectionelements• Upto96digitalinputand64digitaloutputs• TransducerI/Os(RTD,dcmA)
Communication• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–secure,high-speedexchangeofdatabetween
URsforDirectTransferTripandI/OExtensionapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
FEATURES
APPLICATIONS
KEY BENEFITS
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingC30functions• Redundantarchitecturefordependabilityandsecurity
IEC 61850 Process Bus Interface
C30Multilin™
CONTROLLER SYSTEM
Substationhardenedprogrammablelogiccontroller
488
C30Controller SystemSp
ecia
lized
Pro
tect
ion
& Co
ntro
l
www.GEDigitalEnergy.com
Protection and ControlTheC30ControllerSystemisasubstationhardened device designed to performsubstation Control Logic that can alsoexpand the I/O capability of protectiondevicesandreplaceexistingSequenceofEvents(SOE)Recorders.TheC30providesfast and deterministic execution ofprogrammablelogicwithI/Ocapabilitiesfar above an average protection relay.Graphicalprogrammingtools,supportedbyalibraryof logicoperators,maketheC30simple touseandconfigure. Usinghigh-speedpeer-to-peercommunicationsfor inter-devicemessaging, theC30canalsoacceptsignalsandcommandsfromotherprotectionandcontroldevicesatafractionof thecostofhard-wiring thesesignals.Control, automation, I/O expansion anddatagatheringare ideallysuited for theC30inthefollowingapplications:
• Baycontrol
• Substationautomation
• RemoteI/O
Advanced Automation
The C30 incorporates advancedautomation features including powerfulFlexLogic™ programmable logic, peer-to-peer communications and SCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragePLCorcontroller.TheC30integratesseamlesslywithotherURrelaystoextendtheI/OcapabilitiesandperformcompleteBaymanagementandcontrol.
FlexLogic™
FlexLogic™ is the powerful UR-platformprogramming logicengine thatprovidesthe ability of creating customizedprotectionandcontrol schemes therebyminimizingtheneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.The execution of all logic is performedevery 2ms regardless of the complexityoramountoflogicusedtherebyprovidingthe determinist operation required forutilitypowersystemcontrolschemes.
Scalable Hardware
The C30 is available with a multitudeof I/O configurations to suit the most
demanding application needs. Theexpandable modular design allows foreasyconfigurationandfutureupgrades.
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• RTDsandDCmAinputsareavailabletomonitorequipmentparameterssuchastemperature&pressure
IEC 61850 Process BusThe IEC 61850 Process Bus module isdesigned to interface with the MultilinHardFiberSystem,allowingbi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existingUniversal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.
TheMultilinHardFiberSystemoffers thefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingC30’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
Visit theHardFiberSystemproductpageontheGEDigitalEnergywebsiteformoredetails.
Monitoring and MeteringThe C30 provides high resolutionmeasuringofthestatusofexternaldeviceswiredtoitscontactinputs.ThechangingofaContactInputstatuscanbemeasuredandtimestampedwitha0.5msresolutionmakingtheC30idealforbayorsubstationsequenceofeventrecording.
Fault and Disturbance Recording
The advanced disturbance and eventrecording features within the C30 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.
Advanced Device Health Diagnostics
The C30 performs comprehensivedevice health diagnostic tests duringstartup and continuously at runtime totest its ownmajor functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresent
The C30 is a complete solution for controlling and monitoring substation devices and can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown
489
C30Controller System
Spec
ializ
ed P
rote
ctio
n &
Cont
rol
www.GEDigitalEnergy.com
devicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issueshelps improve systemuptime.
CommunicationsThe C30 p rov ides advancedcommunicationstechnologiesforremotedata and engineering access,making iteasyandflexibletouseandintegrateintonew and existing infrastructures. Directsupport for fiberoptic Ethernetprovideshigh-bandwidthcommunicationsallowingfor low-latency controls andhigh-speedfiletransfersofrelayfaultandeventrecordinformation. The available redundantEthernet option and the embeddedmanaged Ethernet switch providethe means of creating fault tolerantcommunicationarchitectures inaneasy,cost-effectivemannerwithouttheneedforintermediarycommunicationhardware.TheC30supportsthemostpopularindustrystandardprotocolsenablingeasy,directintegrationintoDCSandSCADAsystems.
• IEC61850
• DNP3.0
• EthernetGlobalData(EGD)
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
Interoperability with Embedded IEC 61850
Use the C30 with integrated IEC 61850to lower costs associated with breakerprotection, control and automation. GEEnergy’s leadership in IEC 61850 comesfrom thousandsof installeddevicesandfollows on seven years of developmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVistaTMViewpointEngineer
• IntegrateMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVistaTMViewpointMonitoring
Direct I/O Messaging
DirectI/Oallowsforsharingofhigh-speeddigital information betweenmultipleURrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexer channel bank. Regardlessoftheconnectionmethod,DirectI/Oprovidescontinuousreal-timechannelmonitoringthatsuppliesdiagnostics informationonchannelhealth.Direct I/O provides superior relay-to-relaycommunications that canbeusedin advanced interlocking, generationrejection and other special protectionschemes.
• Communicationwithupto16URrelaysinsingleorredundantringsratherthanstrictlylimitedtosimplisticpoint-to-pointconfigurationsbetweentwodevices
• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections
• Noexternalorhandheldtesterrequiredtoprovidechanneldiagnosticinformation
Multi-Language
TheC30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVistaTMsetupsoftware,andproductmanual. Easily switch between Englishandanadditional languageonthe localdisplayswithoutuploadingnewfirmware.
EnerVistaTM SoftwareTheEnerVista™Suiteisanindustry-leadingsetof softwareprograms that simplifieseveryaspectofusingtheC30relay.TheEnerVistaTM suite provides all the toolsto monitor the status of the protectedasset ,maintain the relay, and integrateinformation measured by the C30 intoDCS or SCADA monitoring systems.Convenient COMTRADE and Sequenceof Events viewers are an integral partof the UR Setup software includedwitheveryURrelay,tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswith
FlexLogicTM Designer
Flexlogic allows for creating customized C30 substation control schemes that include receiving interlock and lockout functionality using locally measured inputs along with receiving information received from external devices through communications
490
C30Controller SystemSp
ecia
lized
Pro
tect
ion
& Co
ntro
l
www.GEDigitalEnergy.com
allofthesetupandsupporttoolsneededfor configuring andmaintaining Multilinproducts. The setup software withinLaunchpadallowsconfiguringdevices inreal-timebycommunicatingusingserial,Ethernet , or modem connections, orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQs
• ServiceBulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint Engineer
Viewpoint Engineer is a set of powerfultools that will allow the configurationandtestingofURrelaysatasystemlevelin an easy-to-use graphical drag-and-drop environment . Viewpoint Engineerprovides the followingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetreival
EnerVista™ Integrator
EnerVistaTM Integrator is a toolkit thatallows seamless integration of Multilindevices intonewor existingautomationsystems.IncludedinEnerVistaIntegratoris:
• OPC/DDEServer
• MultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
User InterfaceThe C30 front panel provides extensivelocalHMIcapabilities.Thelocaldisplayisused for monitoring, status messaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
The Viewpoint Monitoring software can merge the Events logged by the C30 with those logged in other Multilin relays to create a station wide sequence of event record.
LEDIndicators
Multi-LanguageDisplay• English• Russian• French• Chinese
UserProgrammablePushbuttons
491
C30Controller System
Spec
ializ
ed P
rote
ctio
n &
Cont
rol
www.GEDigitalEnergy.com
Typical Wiring
C30-H00-HCH-F6B-H6E-M6G-P6K-U6D-W6D
DC
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTOR
2 23 34 45 56 67 78 89 9
RS-232
1PowerSupply
9
CPU
6Input/output
Input/output
*
JU MX LW KV BHT DN G FPS R
C30 CONTROLLER
I
V
I
V
6BH1b
H2b
H3b
H4b
H5b
H6b
H1a
H2a
H3a
H4a
H5a
H6a
H1c
H2c
H3c
H4c
H5c
H6c
H1
H5
H2
H6
H3
H4
H8a
H7b
H7a
H8c
H7c
SURGEH8b
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
3a
1b
8a
6b
8b
6a
BBBBBBBBBB
3b
1a2b
5b
SURGE
H6a
H8a
H5b
H7b
H8b
H5a
H7a
H6c
H8c
H5c
H7c
H1a
H2b
H1cH1b
H2c
H2a
H4a
H4c
H3bH3a
H4b
H3c
H1
H2
H3
H4
6E
M1a
M2b
M1cM1b
M2c
M2a
M4a
M4c
M3bM3a
M4b
M3c
SURGE
M6a
M8a
M5b
M7b
M8b
M5a
M7a
M6c
M8c
M5c
M7c
M1
M2
M3
M4
I
V
I
V
I
V
I
V
6G
U6a
U8a
U5b
U7b
U5a
U7a
U6c
U8c
U5c
U7c
SURGE
U1a
U8b
U4c
U2c
U3aU3c
U1c
U3b
U1b
U4a
U2a
6D
P7a
P1a
P2b
P7c
P1c
P7b
P1b
P8cP8b
P2c
P8a
P2a
P4a
P5b
P4c
P6b
P3bP3a
P6a
P4b
P5c
P5a
P3c
P6c
6K P1
P5
P2
P6
P3
P7
P4
P8
W6a
W8a
W5b
W7b
W5a
W7a
W6c
W8c
W5c
W7c
SURGE
W1a
W8b
W4c
W2c
W3aW3c
W1c
W3b
W1b
W4a
W2a
6D
Minimum
PROVIDED
TC
TC
2
1
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
Multilin
Input/output
*
Input/output
*
Input/output
*
6Input/output
*
492
C30Controller SystemSp
ecia
lized
Pro
tect
ion
& Co
ntro
l
www.GEDigitalEnergy.com
Ordering C30 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal MountC30 BaseUnitCPU E RS485+RS485 G RS485+Multi-modeST10BaseF H RS485+Mutli-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 01 EthernetGlobalData 03 IEC61850 04 EthernetGlobalData(EGD)+IEC61850Mount/Coating H Horizontal(19”rack)-Standard A Horizontal(19”rack)-HarshChemicalEnvironmentOption V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshChemicalEnvironmentOptionUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DCpowersupply L 24-48V(DConly)IEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX XX Nomodule 4A 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4B 4B 4B 4B 4B 4B 4SolidState(Voltagew/optCurrent)MOSFETOutputs 4C 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 67 8 Form-A(NoMonitoring)Outputs 6A 6A 6A 6A 6A 6A 2Form-A(Voltagew/optCurrent)&2Form-COutputs,8DigitalInputs 6B 6B 6B 6B 6B 6B 2Form-A(Voltagew/optCurrent)&4Form-COutputs,4DigitalInputs 6C 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 6F 8FastForm-COutputs 6G 6G 6G 6G 6G 6G 4Form-A(Voltagew/optCurrent)Outputs,8DigitalInputs 6H 6H 6H 6H 6H 6H 6Form-A(Voltagew/optCurrent)Outputs,4DigitalInputs 6K 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 6M 2 Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6P 6 Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5A 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputs 5C 5C 5C 5C 5C 5C 8RTDInputs 5D 5D 5D 5D 5D 5D 4RTDInputs,4dcmAOutputs 5E 5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs 5F 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 2A C37.94SM,1300nmsingle-mode,ELED,1channelsingle-mode 2B C37.94SM,1300nmsingle-mode,ELED,2channelsingle-mode 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7R G.703,1Channel 7S G.703,2Channels 7T RS422,1Channel 7W RS422,2Channels 76 IEEEC37.94,820nm,multimode,LED,1Channel 77 IEEEC37.94,820nm,multimode,LED,2Channels 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
Accessories for the C30 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• BuyaC30online
• ViewtheURFamilybrochure
Visit www.GEMultilin.com/C30 to:
110503-v3
Ordering Note: ToviewthelatestoptionsavailablefortheC30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.