Submittal Review Summary
Transcript of Submittal Review Summary
Page 1 of 1
2429 Members Way Lexington KY 40504 859.253.0892 www.cmta.com
MEP Engineering | Performance Contracting | Zero Energy Engineering | Technology | Commissioning
Submittal Review Summary
Project: Transy Strickland Auditorium Renovation
Submittal: RTU
CMTA Project Code: XTSA20 Reviewed by: RSJ
Date Received: 2021-05-26 Date Returned: 2021-06-14
Corrections or comments made on the shop drawings during this review do not relieve the contractor
from compliance with requirements of the drawings and specifications. This check is only for
review of general compliance with the information given in the contract documents. The contractor is
responsible for confirming and correlating all quantities and dimensions; selecting fabrication processes
and techniques of construction; coordinating his work with that of all other trades; and performing his
work in a safe and satisfactory manner.
Reviewed Furnish as Corrected
Rejected Revise and Resubmit
COMMENTS:
1. Revise feeder to be 4-#8, #10 G in ¾” conduit with 50/3 breaker. Coordinate 120V field
power to service receptacle.
Submittal Data
Project: Strickland Auditorium
Bid Category: HVAC
Project Number:
Construction Manager: Churchill Mcgee
Spec Section: HVAC
Submittal For: RTU
Manufacturer: Diakin
Supplier: Thermal Equipment
Contact Name & Phone #: Jay Mckinney
The attached submittal data has been reviewed by C&C Industrial for compliance with the specifications
and plan schedule for this project.
In order to maintain the project schedule, we request that this submittal be returned to C&C Industrial
within 7 days.
_____x__ Reviewed
_______ Drawing
_______ Rejected
5/25/21 Date
By James Randall
C&C Industrial
LEXINGTON 680 Bizzell Drive, Lexington KY 40510 859.255.9665 LOUISVILLE 13151 Middletown Industrial Boulevard, Louisville KY 40223 502.473.0829 PADUCAH 115 Eaglet Cove, Paducah KY 42003 270.898.6976
JOB NAME: STRICKLAND AUDITORIUM RENOVATION Transylvania University 300 North Broadway Lexington, KY 40508 ARCHITECT: ROSSTARRANT ARCHITECTS 101 Old Lafayette Avenue Lexington, KY 40502 ENGINEER: CMTA, INC. 2429 Members Way Lexington, KY 40504 CONTRACTOR: C&C INDUSTRIAL 280 Midland Trail Mount Sterling, KY 40353 SPECIFICATION SECTION: 23 02 00 HVAC EQUIPMENT AND
HYDRONIC SPECIALTIES – Section 2A Rooftop Equipment SALESMAN: Jay McKinney Rodney Sproul TES FILE #: 17068
S
U
B
M
I
T
T
A
L
17068 Strickland Auditorium Renovation Page 1 of 20 5/25/2021
ONE (1) DAIKIN APPLIED – Packaged Applied Heat Pump with Electric Aux Heat Unit (TAGGED: RTU-1) Current Lead Time ~ 12 to 14 weeks Unit weight is approximately 1,411 lbs (67.0” l x 40.8” h x 87.0” w)
• Exterior: Painted Galvanized Steel • Insulation and Liners: 1" injected foam, R-7, Galvanized Steel Liner • Heat Pump with Electric Aux Heat • Vertical Return and Supply connections • Approval Listing: cETLus • Unit Voltage: 460v / 60hz / 3ph
o 65kA SCCR non-fused disconnect per specification o Phase failure monitor o 115v GFCI receptacle – field powered
• Economizer with Comparative enthalpy control and barometric relief • Control System: Microtech III, BACnet protocol card – BACnet MSTP
o Variable Volume control o Supply – Direct Drive - ECM Motor - Premium efficiency
• Filter Section o Combo filter rack 2”/4” configuration o 2” MERV 8 Filters
• Indoor Coil Section o Copper tube / aluminum fin o BTU/hr Total Capacity o Stainless steel drain pan with condensate overflow switch
• Hot Gas Reheat Coil Section o Modulating hot gas reheat with duct humidity sensor o Aluminum tube micro-channel
• Electric Heat Section o 18kW capacity o 4 step control
• Air Cooled Condensing Section o (1) Inverter scroll compressor o Capacity Control: Modulating control with inverter compressor o Refrigerant Type: R-410a o Condenser Coil: Aluminum Microchannel 23 fpi o 1 Condenser Fan ECM Motor
Ship loose items included in the quotation (field installed by others)
• Combination digital temperature and humidity sensor with adjustable setpoint and tenant override • 18” insulated roofcurb for flat roofs
Start-up and warranty:
• Check, Test and Startup and Owner Training by Thermal Equipment Sales • 1st year parts only warranty by Daikin Applied • 5-Year compressor parts warranty by Daikin Applied
Specific Exclusions
• Labor warranty • Unit powered GFI is not available with 65kA fused disconnect – requires field power
17068 Strickland Auditorium Renovation Page 2 of 20 5/25/2021
SUBMITTAL NOTES:
UNIT CONFIGURATION: This unit is configured as single zone VAV, mixed air or 100% outside air unit, heat pump unit with hot gas reheat and electric heating. Unit is shipped as a bottom supply / bottom return unit that is to be mounted on the shipped loose knock-down roof curb for flat roofs for field install by others. Please ensure curb is level and square side to side, front to back.
SINGLE POINT POWER and DISCONNECT: Power required for these units is 460v / 3ph / 60hz. We are providing factory mounted 65kA SCCR non-fused disconnect and phase failure monitor. A FIELD powered 115v GFCI outlet is provided.
FIELD PIPING: Contractor, please note, units DO NOT have condensate traps, a properly sized external trap with a depth of at least 2 times the unit ESP as a rule of thumb is required for proper drainage. External piping is not provided and assumed to be by others.
FILTERS AND FILTER RACKS: A combo 2/4” filter rack with access door with 2” MERV-8 filters being provided; the unit is provided with (1) set of filters. All others are assumed to be by others.
TCC/BMS CONTRACTOR: The unit is being provided with a factory Microtech III controller with BACnet MSTP communication card. A shipped loose combination humidity and temperature sensor is provided with the unit for field installation by others. Any additional control requirements are assumed to be by others including smoke detectors.
CHECK, TEST and START-UP: Thermal Equipment Sales, Inc. is providing factory authorized startup for quality control purposes.
WARRANTY and LABOR WARRANTY: The unit has a ONE YEAR (entire unit parts), and a FIVE YEAR (compressor) parts only warranty, this is provided by Daikin. This warranty begins at substantial completion. Thermal Equipment Sales is not providing labor warranty for the equipment.
17068 Strickland Auditorium Renovation Page 3 of 20 5/25/2021
SUBMITTAL DATA for
17068 Transy Strickland Auditorium
Prepared for
CMTA, INC.
Job Number: MZL2HP
Prepared by
Jay McKinney
Rodney Sproul
Thermal Equipment Sales
5/25/2021
17068 Strickland Auditorium Renovation Page 4 of 20 5/25/2021
Table of Contents
Item Summary for RTU-1 ........................................................................................................................................................... 4
Technical Data Sheet for RTU-1 .................................................................................................................................................. 6
Fan Curve - Supply for RTU-1 ................................................................................................................................................... 10
3-6 DoorSwing No ERW_Drawing for RTU-1 ............................................................................................................................. 11
Drawings(1) for RTU-1 ............................................................................................................................................................. 12
Drawings(2) for RTU-1 ............................................................................................................................................................. 13
Drawings(3) for RTU-1 ............................................................................................................................................................. 14
Small and Medium Cabinet Rebel Base Rail_Drawing for RTU-1 .............................................................................................. 15
Cabinet AB Sensor Locations_Drawing for RTU-1 ..................................................................................................................... 16
Rebel 910191961_Drawing for RTU-1 ...................................................................................................................................... 17
17068 Strickland Auditorium Renovation Page 5 of 20 5/25/2021
Item Summary for RTU-1 Item Summary for RTU-1
Job Information Item Summary
Job Name 17068 Transy Strickland Auditorium Date 5/25/2021 Model DPS006A Software Version 09.00 Unit Tag RTU-1
Unit Options Code Item
Code Value
Description
1 DPS UNIT TYPE; Daikin Rebel Rooftop 2 006 UNIT SIZE; 6 ton 3 A VINTAGE; Vintage 1 4 H COOLING EFFICIENCY; High 5 H UNIT STYLE; Heat Pump 6 E HEAT; Electric heat 7 4F VOLTAGE/POWER CONNECTION; 460/60/3 power with fused disconnect [65 KAIC] 8 W APPLICATION; Variable Volume Space Control 9 V AIRFLOW PATTERN; Vertical Discharge and Return
10 A CONTROLS; Microtech III Controls 11 T COMMUNICATION CARDS; BACnet/MSTP card, Factory installed 12 1CY OUTSIDE AIR; Economizer, Comparative Enthalpy 13 R EXHAUST TYPE; Barometric Relief 14 A FILTERS; 2 inch, MERV 8 15 4 DX COIL; 4 row 16 T DRAIN PAN; Stainless Steel with Overflow Switch 17 G LINERS; Galvanized Steel 18 M HOT GAS REHEAT; Modulating Hot Gas Reheat 19 Y COIL OPTIONS; None 20 Y INTELLIGENT EQUIPMENT; None 21 HM SUPPLY FAN MOTOR; 4.0 HP ECM Fan Motor 22 16DY SUPPLY FAN; 16 inch, Direct Drive 23 1692 SUPPLY FAN RPM; Fan RPM 24 018Y4 HEAT; 18 KW Heat, 4 stage control 25 1 LOW AMBIENT CONTROL; Low Ambient Control 26 J ELECTRICAL OPTIONS; Field powered GFI Receptacle Phase Volt Monitor 27 Y SMOKE DETECTORS; None 28 Y OA MONITORING; None 29 Y UV LIGHT; None 30 F ECON DIAGNOSTICS; Economizer with Fault Detection Diagnostics 31 Y COMPRESSOR ISOLATION VALVES; None 32 YYY HEAT WHEEL OPTIONS; None 33 YY ENERGY WHEEL CONTROL; None 34 Y ENERGY WHEEL FILTRATION; None 35 YY EXHAUST FAN MOTOR; None 36 YYYY EXHAUST FAN; None 37 AYD UNIT APPROVALS; ETL Unit, AHRI Certified, ASHRAE 90.1-2016 38 Y OUTDOOR COIL OPTIONS; None 39 S EXPANSION VALVE; Electronic Expansion Valve 40 A PARTS WARRANTY; Standard one year 41 Q COMPRESSOR WARRANTY; Additional Four year, Five year total 42 Y GAS HEAT EXCHANGER WARRANTY; None 43 02000 SAF CFM; SAF CFM 44 009 SAF BHP; SAF BHP 45 548 DISCHARGE AIR TEMP; SAF DAT
17068 Strickland Auditorium Renovation Page 6 of 20 5/25/2021
Item Summary for RTU-1 Code Item
Code Value
Description
46 00000 EAF RPM; EAF RPM 47 000 EAF BHP; EAF BHP 48 Y SPECIAL; None 49 Y IBC SEISMIC; None 50 YYYYY CHILLED WATER COIL; None 51 Y WATER ISOLATION VALVE; None 52 YY UNIT LABOR WARRANTY; None 53 YY COMPRESSOR LABOR WARRANTY; None 54 E SUPPLY FAN MOTOR RPM; ECM Fan 55 YY FUTURE USE; None 56 YY FUTURE USE; None
Accessories Part Number Description Qty Ext Qty
910191961 Combo Digital Temp and Humidity Sensor w/Adj setpoint and tenent override
1 1
17068 Strickland Auditorium Renovation Page 7 of 20 5/25/2021
Technical Data Sheet for RTU-1 Technical Data Sheet for RTU-1
Job Information Technical Data Sheet Job Name 17068 Transy Strickland Auditorium Date 5/25/2021 Submitted By Tom Erpenbeck Software Version 09.00
Unit Tag RTU-1
Unit Overview
Model Number Voltage V/Hz/Phase
Design Cooling Capacity
UOM_OSelected_CoilTotal
AHRI360 Standard Efficiency ASHRAE 90.1 EER IEER
DPS006A 460/60/3 76260 11 18.8 ASHRAE 90.1-2016
compliant
Unit
Model Number: DPS006A Model Type: Heat Pump
Heat Type: Electric Hot Gas Reheat: MHGRH with Combination Space Temperature and Humidity Sensor
Energy Recovery: None Application: Variable Air Volume, Single Zone (Mixed Air or 100% OA)
Controls: Microtech III Outside Air: 0-100% Economizer with Comparative Enthalpy Control
Altitude: 0 ft Approval cETLus
Physical Dimensions and Weight
Length Height Width Weight
67.0 in 40.8 in 87.0 in 1411 lb Corner Weights
L1 L2 L3 L4
266 lb 261 lb 438 lb 447 lb Construction
Exterior Insulation and Liners Air Opening Location Return Supply
Painted Galvanized Steel 1" Injected Foam, R-7, Galvanized Steel Liner
Bottom Bottom
Electrical Unit FLA MCA MROPD SCCR
33.4 A 40.5 A 45 A 65 kAIC
Note: Use only copper supply wires with ampacity based on 75° C conductor rating. Connections to terminals must be made with copper lugs and copper wire.
Return/Outside/Exhaust Air Outside Air Option
Type Damper Pressure Drop Exhaust Air Type
90.1 and California Title 24 Compliant Economizer
0.05 inH₂O Barometric Relief
17068 Strickland Auditorium Renovation Page 8 of 20 5/25/2021
Technical Data Sheet for RTU-1
Filter Section Physical
Type Quantity / Size Face Area Face Velocity Air Pressure Drop
Combo 2"/4" rack with 2" MERV 8
4 / 16 in x 16 in x 2 in 7.1 ft² 281.7 ft/min 0.12
DX Cooling Coil Physical
Coil Type Refrigerant Type Fins per Inch Rows Face Area Face Velocity Air Pressure drop
Drain Pan Material
Cu Tube/ Al Fin
R410A 16 4 6.0 ft² 331.1 ft/min 0.34 inH₂O Stainless
Steel Cooling Performance
Capacity Indoor Air Temperature Ambient air Temperature
°F Total
Btu/hr Sensible Btu/hr
Moisture Removal
lb/h
Entering Leaving Dry Bulb
°F Wet Bulb
°F Dry Bulb
°F Wet Bulb
°F Dewpoint
°F
76260 55104 18.2 80.0 67.0 54.8 54.7 54.6 95.0
Condensate Connection Size: 3/4 in. Male NPT Heating Performance
Total Capacity Btu/hr
Refrigerant Type
Indoor Air Temperature Dry Bulb Ambient Air Temperature
°F Entering
°F Leaving
°F
67994 R410A 57.0 88.1 47.0
Hot Gas Reheat Coil Section Type Face Area Air Pressure Drop Total Capacity Leaving Air Temperature
Dry Bulb Wet Bulb
Aluminum Tube Micro-Channel
5.5 ft² 0.07 inH₂O 32976 Btu/hr 70.0 °F 60.3 °F
Fan Section Fan
Type Fan Wheel Diameter Fan Isolation
SWSI AF 16 in None Performance
Airflow Total Static Pressure Fan Speed Brake Horsepower Altitude
2000 CFM 1.7 inH₂O 1692 rpm 0.92 HP 0 ft Motor Drive
Type Horsepower Efficiency FLA Type
ECM Motor 4.0 Premium 4.0 A Direct Drive
17068 Strickland Auditorium Renovation Page 9 of 20 5/25/2021
Technical Data Sheet for RTU-1 Electric Heat Section
Physical Electrical
Airflow Size Control FLA A
2000 CFM 18 kW 4 Stages 21.7 Performance
Capacity Btu/hr
Air Temperature Air Pressure Drop Entering
°F Leaving
°F inH₂O
61434 57.0 85.3 0.36
Unit Discharge Conditions AirTemperature
Motor Heat Btu/hr
Moisture Removal lb/h
Unit Leaving Dry Bulb °F
Unit Leaving Wet Bulb °F
Unit Leaving Dewpoint °F
3351 18.2 56.4 55.2 54.6
Condensing Section Compressor
Type Quantity Refrigerant Charge lb
Total Power Capacity Control Compressor Isolation
Inverter Scroll 1 19.7 4.82 kW Mod Control with
Inverter Compressors Rubber in Shear
Compressor Amps: Compressor 1 6.8 A
Condenser Coil
Type Fins per Inch Fin Material
Copper Tube 23 Aluminum
Condenser Fan Motors
Number of Motors Full Load Current (Total)
1 0.9 A
AHRI 360 Certified Data at AHRI 360 Standard Conditions
Net Capacity EER IEER Heat Net Capacity at 47°F
COP at 47°F Heat Net Capacity at 17°F
COP at 17°F
67000 Btu/hr 11 18.8 66000 Btu/hr 3.69 39000 Btu/hr 2.54
Internal Pressure Drop Calculation External Static Pressure: 0.75 inH₂O
Filter: 0.12 inH₂O Outside Air: 0.05 inH₂O
DX Coil: 0.34 inH₂O Hot Gas Reheat: 0.07 inH₂O
Electric Heat: 0.36 inH₂O Total Static Pressure: 1.70 inH₂O
Sound Sound Power (db)
Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Inlet 73 71 79 74 76 70 65 59
Discharge 73 74 82 79 82 76 73 67
Radiated 82 82 78 75 73 68 61 54
17068 Strickland Auditorium Renovation Page 10 of 20 5/25/2021
Technical Data Sheet for RTU-1 Options
Electrical
Field Connection: Fused Disc: 65 kAIC - 208/230/460V: 22 kAIC 575V Powered Receptacle: Field powered 115V GFI outlet
Power Options: Phase Failure Monitor Controls
Communication Card: BACnet/MSTP card, Factory installed
Factory Installed Sensors
Leaving Coil/Entering Fan Temperature Sensor Duct High Limit Switch BACnet/MSTP Card Return Air Temperature Sensor Discharge Air Temperature sensor – Wired in unit, mounted in supply duct Outside Air Temperature Sensor Return Air Enthalpy Sensor Outside Air Enthalpy Sensor Dirty Filter On/Off Switch Supply Fan Air Proving Via Modbus Condensate Overflow Switch
Warranty
Parts: Standard One Year
Compressor: Additional Four Year, Five Year Total
AHRI Certification
All equipment is rated and certified in accordance with AHRI 360.
Notes
Accessories Mandatory
Part Number Description
910191961 Combo Digital Temp and Humidity Sensor w/Adj setpoint and tenent override
17068 Strickland Auditorium Renovation Page 11 of 20 5/25/2021
Fan Curve - Supply for RTU-1 Fan Curve - Supply for RTU-1
17068 Strickland Auditorium Renovation Page 12 of 20 5/25/2021
3-6 DoorSw
ing No ERW
_Draw
ing for RTU-1
3-6 D oorSwi ng No ERW_Drawi ng for RTU-1
Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 13 of 20 5/25/2021
Draw
ings(1) for RTU-1
Drawings(1) for RTU-1
Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 14 of 20 5/25/2021
Drawings(2) for RTU-1 Drawings(2) for RTU-1
Product Drawing Unit Tag: RTU-1
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 15 of 20 5/25/2021
Draw
ings(3) for RTU-1
Drawings(3) for RTU-1
Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 16 of 20 5/25/2021
Small and Medium Cabinet Rebel Base Rail_Drawing for RTU-1 Small and Me dium Ca binet Rebel Base Rail_Dra wing for RTU-1
Product Drawing Unit Tag: RTU-1
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 17 of 20 5/25/2021
Cabinet AB Sensor Locations_Drawing for RTU-1 Cabi net AB Sensor Locations_ Drawing for RTU-1
Product Drawing Unit Tag: RTU-1
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 18 of 20 5/25/2021
Rebel 910191961_Draw
ing for RTU-1
Rebel 9101 9196 1_Drawi ng for RTU-1
Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00
Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
17068 Strickland Auditorium Renovation Page 19 of 20 5/25/2021