Submittal Ref. #: 514501.2 rev3
Design envelope split coupled vertical in line pump
Model: Series Design Envelope Sensorless 4300 0308-005.0
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: P-1/2 Pipe orientation: Single
Suction pressure: 0 ftService: Heating Loop
Location: Fluid: Water:
Quantity: 2 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 190 USgpm
Specific gravity: 1.0000Duty head: 48 ft
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 3 in, Outlet: 3 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Supplier: Factory Choice Insulation class: Class F Insulation
Size: 5 hp Inverter motor type: Inverter Duty
Frame number: 184TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Operating speed @ 100% flow: 1714 rpm
Motor Electrics: 575/3/60 Operating speed @ 50% flow: 1242 rpm
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12 Analog outputs: 1 (current)
Fused disconnect switch: No 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
BHP at 50% load/flow and 55% of design head:
0.76 hp IVSAmbTemp1txt
Meets ASHRAE 90.1: No EMI/RFI control: Integrated fliter to meet EN61800-3
Min. maintained sys. pressure: 19.2 ft Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.
** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does notguarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the systemelectrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrongcan also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 1 of 42
Ambient Temp Digital Inputs:
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-1/2 Service: Heating Loop Location:
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 190 usgpm Head: 48 ft Impeller: 7.38 in
--- Performance Data ---• NPSHR: 6.2162 ft• Eff. @ Design: 75.87 % • BHP @ Design: 3.04 hp• Mtr Capability @ Rated Spd: 4.46 hp• %Mtr Safety: 46.99%• BEP @ Design Imp.:
79.91 % @ 265.8 usgpm• %max imp. range: 63.16 %• Outlet Velocity: 8.25 ft/s• VFD Op.Speed: 1714 rpm• VFD Setting: 58.3 Hz
Series 4300Design Envelope: 0308-005.0 @ 58.3 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 80 160 240 320 400 4800
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
8.19 in
6.00 in
System
7.38 in
3 hp
5 hp
7.5 hp
80
80
78
78
73
73
65
65%
5440
Water:, spgr= 1.0000
PT72-2-0 (3.20.1.2)ANSI/HI 14.6.3.4.1
81
--- Admin Data --- Tag Num: P-1/2 Service: Heating Loop Location:
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 190 usgpm Head: 48 ft Impeller: 7.38 in
--- Control Data ---1. Hmax @ 58.3 Hz:• 190 @ 48, 3.04 hp2. Control (QPC) @ 54.1 Hz:• 168 @ 41.7, 2.37 hp3. Control (QPC) @ 50.0 Hz:• 145.3 @ 36, 1.82 hp4. Control (QPC) @ 45.9 Hz:• 120.6 @ 30.8, 1.35 hp5. Control (QPC) @ 41.5 Hz:• 89.4 @ 25.6, 0.92 hp6. Index @ 37.3 Hz:• 47.5 @ 21, 0.57 hp7. Hmin: 19.2 ft 35.7 Hz:• Setting= 40.00% Hmax
Series 4300Design Envelope: 0308-005.0
Integrated Intelligent Variable Speed with Sensorless Control
0 80 160 240 320 400 4800
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
63.0 Hz
37.3 Hz
35.7 Hz
18.0 Hz
System
Avg.Load (QPC)
58.3 Hz
5 hp
8080
80
77
77
73
73
6555
Index Flow (25.0% Duty Flow)
Water:, spgr= 1.0000
PT72-2-0 (3.20.1.2)ANSI/HI 14.6.3.4.1
1
2
3
4
5
6
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 2 of 42
22500
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 190 USgpm 56.9 ft 73.85 %
Design point 190 USgpm 48 ft 75.87 %
50% average flow (with default load profile) 95 usgpm 26.4 ft 64.26 %
Dimensional data (not for construction)
Top viewSide view
Weight: 349 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 3 7.5ANSI-125 4 0.6256
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
.
Selected options Environmental Application: Indoors
Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-43 (516860-020)
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 3 of 42
Submittal Ref. #: 514501.2 rev3
Design envelope split coupled vertical in line pump
Model: Series Design Envelope Sensorless 4300 0408-010.0
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: P-3/4 Pipe orientation: Single
Suction pressure: 0 ftService: Chilled Water Loop
Location: Fluid: Water:
Quantity: 2 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 485 USgpm
Specific gravity: 1.0000Duty head: 52 ft
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416
Connections: Inlet: 4 in, Outlet: 4 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data
Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data
Supplier: Factory Choice Insulation class: Class F Insulation
Size: 10 hp Inverter motor type: Inverter Duty
Frame number: 215TC Efficiency: NEMA Prem (12.12)
Enclosure: ODP Operating speed @ 100% flow: 1681 rpm
Motor Electrics: 575/3/60 Operating speed @ 50% flow: 1180 rpm
IVS102 controller data
Sensorless control: Yes-Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12 Analog outputs: 1 (current)
Ambient temperature:Fused disconnect switch: No Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
BHP at 50% load/flow and 55% of design head:
2.01 hp IVSAmbTemp1txt
Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated fliter to meet EN61800-3
Min. maintained sys. pressure: 20.8 ft Harmonic suppression: Integrated DC link reactor**
*If minimum maintained system pressure is not known, default is 40% of design head.
** The IVS 102 control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This does notguarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If supplied with the systemelectrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrongcan also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 4 of 42
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: P-3/4 Service: Chilled Water Loop Location:
--- Motor Data --- Motor Size: 10 hp
--- Design Duty Point --- Flow: 485 usgpm Head: 52 ft Impeller: 8.19 in
--- Performance Data ---• NPSHR: 11.1 ft• Eff. @ Design: 79.38 % • BHP @ Design: 8.02 hp• Mtr Capability @ Rated Spd: 8.74 hp• %Mtr Safety: 8.97%• BEP @ Design Imp.:
79.51 % @ 510.5 usgpm• %max imp. range: 100.00 %• Outlet Velocity: 12.22 ft/s• VFD Op.Speed: 1681 rpm• VFD Setting: 57.0 Hz
Series 4300Design Envelope: 0408-010.0 @ 57.0 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 0.2 0.4 0.6 0.8 10
10
20
30
40
50
60
70
80
Flow ( 1,000 usgpm)
Head
(ft)
8.19 in
6.00 in
System
8.19 in
5 hp
7.5 hp
10 hp
79
79
76
76
72
72
64
64%
53
53%
39
Water:, spgr= 1.0000
PT87-3-0 (3.20.1.2)ANSI/HI 14.6.3.4.1
80
--- Admin Data --- Tag Num: P-3/4 Service: Chilled Water Loop Location:
--- Motor Data --- Motor Size: 10 hp
--- Design Duty Point --- Flow: 485 usgpm Head: 52 ft Impeller: 8.19 in
--- Control Data ---1. Hmax @ 57.0 Hz:• 485 @ 52, 8.02 hp2. Control (QPC) @ 52.5 Hz:• 428.3 @ 45.1, 6.17 hp3. Control (QPC) @ 48.1 Hz:• 368.7 @ 38.8, 4.61 hp4. Control (QPC) @ 43.4 Hz:• 298.8 @ 32.6, 3.22 hp5. Control (QPC) @ 39.0 Hz:• 224.3 @ 27.5, 2.16 hp6. Index @ 34.5 Hz:• 121.3 @ 22.8, 1.28 hp7. Hmin: 20.8 ft 32.3 Hz:• Setting= 40.00% Hmax
Series 4300Design Envelope: 0408-010.0
Integrated Intelligent Variable Speed with Sensorless Control
0 0.2 0.4 0.6 0.8 10
10
20
30
40
50
60
70
80
Flow ( 1,000 usgpm)
Head
(ft)
60.0 Hz
34.5 Hz
32.3 Hz
18.0 Hz
System
Avg.Load (QPC)
57.0 Hz
10 hp
8079
79
76
76
72
72
6453
Index Flow (25.0% Duty Flow)
Water:, spgr= 1.0000
PT87-3-0 (3.20.1.2)ANSI/HI 14.6.3.4.1
1
2
3
4
5
6
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 5 of 42
22500
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 485 USgpm 59.1 ft 79.01 %
Design point 485 USgpm 52 ft 79.38 %
50% average flow (with default load profile) 242.5 usgpm 28.6 ft 73.39 %
Dimensional data (not for construction)
Top viewSide view
Weight: 484 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 4 9ANSI-125 8 0.6257.5
Outlet 4 9ANSI-125 8 0.6257.5
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
.
Selected options Environmental Application: Indoors
Additional equipment Flotrex: FTV-6FA (570200-480) Suction Guide: SG-64 (516860-023)
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 6 of 42
Project #: 514501.2 rev3
Submittal
Product: User Defined Products
Model: DE START-UP
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2
Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor: Order No:
Submitted by: Dave Haskell Approved by: Date:
This page is intentionally left blank. A submittal is unavailable for this product.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 7 of 42
Submittal Ref. #: 514501.2 rev3
Close coupled vertical in-line pump
Model: Series 4380-3x3x6-1.5 hp Pump (Motor supplier: Armstrong choice)
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: P-5/6 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: Water:
Quantity: 2 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 140 USgpm
Specific gravity: 1.0000Duty head: 21 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: BF Impeller: Bronze (B584-844)
Rating: ANSI-125 Shaft sleeve: 316 SS
Connections: Inlet: 3 in, Outlet: 3 in Casing gasket: Confined Non-Asbestos Fiber
Casing (volute): Cast Iron (A48-30) Flush line: Braided Stainless Steel
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon
Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel
Motor electrical data
Supplier: Factory Choice Insulation class: Class F Insulation
Size: 1.5 hp Inverter motor type: Not applicable
Frame number: 145JM Efficiency: NEMA Prem (12.12)
Enclosure: ODP Speed: 1760 rpm
Motor Electrics: 208/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 8 of 42
Performance curve
--- Admin Data --- Tag Num: P-5/6 Service: Location:
--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 140 usgpm Head: 21 ft Impeller: 5.37 in
--- Performance Data --- • NPSHR: 10.5 ft • Eff. @ Design: 72.87 % • BHP @ Design: 1.02 hp • Mtr Capability @ Rated Spd: 1.50 hp • %Mtr Safety: 47.23% • BEP @ Design Imp.: 73.56 % @ 161.5 usgpm • Impeller Max BHP @ Flow: 1.21 hp @ 234.2 usgpm • %max imp. range: 51.54 % • Outlet Velocity: 6.08 ft/s
Series 4380
3x3x6 @ 1760 rpm
0 50 100 150 200 250 3000
8
16
24
32
40
Flow (usgpm)
Head
(ft)
6.19 in
4.50 in
System
5.37 in
0.75 hp1 hp
1.5 hp
2 hp
3 hp
0.5 hp
77
77
74
74
70
70
62
62
52
52%
39
Water:, spgr= 1.0000
PT70-1-0 (3.20.1.2)ANSI/HI 14.6.3.4.1
77
Dimensional data (not for construction)
Top viewSide view
Weight: 209 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 9 of 42
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 3 7.5ANSI-125 4 0.6256
Outlet 3 7.5ANSI-125 4 0.6256
*Equally spaced straddling centreline
Special instructions
.
Additional equipment Flotrex: FTV-3FA (570200-477) Suction Guide: SG-33 (516860-019)
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 10 of 42
Submittal Ref. #: 514501.2 rev3
Wet rotor circulator
Model: Part number: 110223-307Series ASTRO 250CI FLG
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: P-7/8 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: PropyleneGlycol:30
Quantity: 2 Operating temperature: 60 F
Viscosity: 37.213 SSUDuty flow per pump: 10 USgpm
Specific gravity: 1.0248Duty head: 10 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: STD125 Impeller: Polyether Imide (PEI)
Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada
Motor electrical data
Supplier: Factory Choice Insulation class: Not applicable
Size: 0.157 hp Inverter motor type: Not applicable
Frame number: Not applicable Efficiency: Std
Enclosure: ODP Speed: 3600 rpm
Motor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 11 of 42
Performance curve
--- Admin Data --- Tag Num: P-7/8 Service: Location:
--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm
--- Design Duty Point --- Flow: 10 usgpm Head: 10 ft
--- Pump Data --- Pump Size: Astro 250CI Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 10.5 usgpm Projected Head: 10.9 ft
Series Astro MultiSpeed
Astro 250CI @ Discrete Speeds
0 4 8 12 16 200
5
10
15
20
25
30
Flow (usgpm)
Head
(ft)
System
Projected
[1] 2300
[2] 2900
[3] 3600
PropyleneGlycol:30, spgr= 1.0248
PT620-0-228 (3.20.1.2)
Dimensional data (not for construction)
Side viewFront view
Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 12 of 42
Special instructions
.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 13 of 42
Submittal Ref. #: 514501.2 rev3
Wet rotor circulator
Model: Part number: 110223-305Series ASTRO 230CI FLG
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: P-9 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: PropyleneGlycol:30
Quantity: 1 Operating temperature: 60 F
Viscosity: 37.213 SSUDuty flow per pump: 8 USgpm
Specific gravity: 1.0248Duty head: 7 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: STD125 Impeller: Polyether Imide (PEI)
Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada
Motor electrical data
Supplier: Factory Choice Insulation class: Not applicable
Size: 0.13 hp Inverter motor type: Not applicable
Frame number: Not applicable Efficiency: Std
Enclosure: ODP Speed: 3600 rpm
Motor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 14 of 42
Performance curve
--- Admin Data --- Tag Num: P-9 Service: Location:
--- Motor Data --- Motor Size: 0.13 hp Motor Speed: [3] 3600 rpm
--- Design Duty Point --- Flow: 8 usgpm Head: 7 ft
--- Pump Data --- Pump Size: Astro 230CI Impeller: 2.36 in Suction Head Req: 0 ft Projected Flow: 9.125 usgpm Projected Head: 9.1073 ft
Series Astro MultiSpeed
Astro 230CI @ Discrete Speeds
0 4 8 12 16 200
4
8
12
16
20
Flow (usgpm)
Head
(ft)
System
Projected
[1] 2300
[2] 2900 [3] 3600
PropyleneGlycol:30, spgr= 1.0248
PT617-0-225 (3.20.1.2)
Dimensional data (not for construction)
Side viewFront view
Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 15 of 42
Special instructions
.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 16 of 42
Submittal Ref. #: 514501.2 rev3
E.2 series dry motor circulator
Model: Part number: 182202-658Series E8.2B brz 120V
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: PDR-1/2 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: Potable/Drinking Water
Quantity: 2 Operating temperature: 60 F
Viscosity: 31 SSUDuty flow per pump: 15 USgpm
Specific gravity: 1.0000Duty head: 20 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: AB Impeller: 30% Glass-filled Noryl
Rating: Not applicable Bearings: Permanently lubricated SS
Connections: Inlet: 1.25 in, Outlet: 1.25 in
Mechanical seal data
Manufacturer: Armstrong Seal: Silicon Carbide
Seal type: Bellows-style Silicon Carbide
Motor electrical data
Supplier: Factory Choice Insulation class: Not applicable
Size: 0.167 hp Inverter motor type: Not applicable
Frame number: Not applicable Efficiency: Std
Enclosure: ODP Speed: 3380 rpm
Motor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 17 of 42
Performance curve
--- Admin Data --- Tag Num: PDR-1/2 Service: Location:
--- Motor Data --- Motor Size: 0.167 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 15 usgpm Head: 20 ft
--- Pump Data --- Pump Size: E8.2B Impeller: 2.9 in Projected Flow: 16.4 usgpm Projected Head: 23.9 ft
Series E.2
Selected Size: E8.2B @ 3380 rpm
0 20 40 60 80 100 120 140 1600
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
System
Projected
E8.2B
Water, spgr= 1.0000
PT204-0-68 (3.20.1.2)
Dimensional data (not for construction)
Back viewSide view
Weight: 15 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 18 of 42
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.25 5N/A 4 0.53.88
Outlet 1.25 5N/A 4 0.53.88
*Equally spaced straddling centreline
Special instructions
.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 19 of 42
Submittal Ref. #: 514501.2 rev3
Wet rotor circulator
Model: Part number: 110223-308Series ASTRO 250SS FLG
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: PDR-3 Pipe orientation: Single
Suction pressure: 0 ftService:
Location: Fluid: Potable/Drinking Water
Quantity: 1 Operating temperature: 60 F*
Viscosity: 31 SSUDuty flow per pump: 8 USgpm
Specific gravity: 1.0000Duty head: 12 ft
Total dissolved solids: 0 ppm
* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.
Materials of construction
Construction: SS150 Impeller: Polyether Imide (PEI)
Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada
**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)
Motor electrical data
Supplier: Factory Choice Insulation class: Not applicable
Size: 0.157 hp Inverter motor type: Not applicable
Frame number: Not applicable Efficiency: Std
Enclosure: ODP Speed: 3600 rpm
Motor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 20 of 42
Performance curve
--- Admin Data --- Tag Num: PDR-3 Service: Location:
--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm
--- Design Duty Point --- Flow: 8 usgpm Head: 12 ft
--- Pump Data --- Pump Size: Astro 250SS Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 8.4619 usgpm Projected Head: 13.4 ft
Series Astro MultiSpeed
Astro 250SS @ Discrete Speeds
0 4 8 12 16 200
5
10
15
20
25
30
Flow (usgpm)
Head
(ft)
System
Projected
[1] 2300
[2] 2900
[3] 3600
Water, spgr= 1.0000
PT620-0-228 (3.20.1.2)
Dimensional data (not for construction)
Side viewFront view
Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 21 of 42
Special instructions
.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 22 of 42
Submittal Ref. #: 514501.2 rev3
Design Envelope Booster System
Series : 6800 G/E Design Envelope Model: N250222-7.5 hp
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Tag number: DBP-1 Water Supply: Tank
Suction (supply) pressure: 46.2 ftService:
Location: Total flow capacity: 330.0 USgpm
Quantity: 1 System boost pressure rating: 93.0 ft
Power Supply: Discharge pressure: 139.2 ft575/3/60
System construction data
System description: Duplex Piping material: Stainless Steel 304
Header size: 4 in Valve type Check valve only
Header connections: Grooved Maximum working pressure: 536.0 ft
Suction orientation: Right* Discharge orientation: Right*
*when facing booster controller Low lead certification: NSF 372
Pump data N250222Number of pumps: 2 Duty flow per pump: 165 USgpm
Operation: 2 Duty Duty head: 93 ft
Series: 4700 Motor size: 7.5 hp
Size: VMS-32:02-2 Motor speed: 3600 rpm
Motor efficiency: NEMA Premium (12.12)Construction: Stainless Steel 304
Motor enclosure: ODP
Booster control panel data
Enclosure: NEMA 12 Painted steel Human Machine Interface: Alpha-Numeric
Selected features: BMS Port (serial communication port for connection to BMS - BacNet (MS/TP))HMI: Alpha-Numeric
IVS-102 variable frequency control data
Quantity: 2 (integrated with motors) EMI/RFI control: Integrated filter to meet EN61800-3
Enclosure: UL Type 12 Cooling: Fan cooled through back channel
Harmonic suppression: Integrated DC link reactor Ambient temperature: -10C to +45C(upto 1000m elevation)
Drawdown tank data
Size and rating: 132 US Gallon Non-ASME Mounting: Remote Mounted
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 23 of 42
Performance curve
Dimensional data (not for construction)
WEIGHTS (lb) NOT for CONSTRUCTION
Weights
976
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 24 of 42
Booster controller wiring diagram
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 25 of 42
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 26 of 42
Project #: 514501.2 rev3
Submittal
Product: User Defined Products
Model: BOOSTER START-UP
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2
Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor: Order No:
Submitted by: Dave Haskell Approved by: Date:
This page is intentionally left blank. A submittal is unavailable for this product.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 27 of 42
Project #: 514501.2 rev3
SubmittalProduct : Vortex Air Separators
Model: VA-4-U
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2
Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Order No: Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Submitted by: Dave Haskell Approved by: Date:
Technical Data
Max.Working Temperature 375° F (190° C)
Connection Type 150# Flanged ANSI (RFSO)
Max.working Pressure4"-6" Models:160 psi(1103 kPa), 8"-12" Models:165 psi(1140 kPa)
Materials Of Construction
Gasket Non-Asbestos
Shell4"-6" Models:Cast Iron, 8"-12" Models:Fabricated Steel
DIMENSIONAL DATA (in, lb ) NOT for CONSTRUCTION
A B C D E F H J K N WeightVelocity
(ft/s)Max.Flow
RateStrainer.
sq. in
4 1.5 9.5 18 2.25 6.8 22.25 10.75 16 9 170 4 160.0 USgpm N/A
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 28 of 42
Project #: 514501.2 rev3
SubmittalProduct : Vortex Air Separators
Model: VA-6-U
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2
Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Order No: Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Submitted by: Dave Haskell Approved by: Date:
Technical Data
Max.Working Temperature 375° F (190° C)
Connection Type 150# Flanged ANSI (RFSO)
Max.working Pressure4"-6" Models:160 psi(1103 kPa), 8"-12" Models:165 psi(1140 kPa)
Materials Of Construction
Gasket Non-Asbestos
Shell4"-6" Models:Cast Iron, 8"-12" Models:Fabricated Steel
DIMENSIONAL DATA (in, lb ) NOT for CONSTRUCTION
A B C D E F H J K N WeightVelocity
(ft/s)Max.Flow
RateStrainer.
sq. in
6 1.5 12.5 24 4 9.85 32.24 16 22 12 331 4 360.0 USgpm N/A
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 29 of 42
Project #: 514501.2 rev3
Submittal
Product: User Defined Products
Model: ABX050-40
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BC V3K 6X2Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor: Order No:
Submitted by: Dave Haskell Approved by: Date:
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 30 of 42
ABX - BRAZED PLATE HEAT EXCHANGERS
Armstrong’s ABX brazed plate heat exchangers are designed to facilitate heat transfer between two media of different temperatures. ABX produces high heat transfer rates that allow for a compact, corrosion resistant and robust design.
TYPICAL SPECIFICATION
Furnish and install on the plans and described herein, an Armstrong ABX050-_40_____ brazed plate heat exchanger. Each heat exchanger must be designed to have the capacity and pressure/temperature rating as detailed in the schedule. The heat exchanger must utilize 316L stainless steel plates and copper braze to separate the two fluids while transferring heat and preventing corrosion.
Each heat exchanger shall be Armstrong ABX050-_40_________ or approved equal.
C
E
L
D
A B
A1 B1
B2A2
QUANTITY TAG No. MODEL No. COMMENTS 2 HX-1, HX-2 ABX050-40
Project #: 514501.2 rev3Submittal
Product: User Defined ProductsModel: ABX030-30
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BC V3K 6X2Reference: 514501.2.3Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Order No:Submitted by: Dave Haskell Approved by: Date:
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 31 of 42
ABX - BRAZED PLATE HEAT EXCHANGERS
Armstrong’s ABX brazed plate heat exchangers are designed to facilitate heat transfer between two media of different temperatures. ABX produces high heat transfer rates that allow for a compact, corrosion resistant and robust design.
TYPICAL SPECIFICATION
Furnish and install on the plans and described herein, an Armstrong ABX030-_30_____ brazed plate heat exchanger. Each heat exchanger must be designed to have the capacity and pressure/temperature rating as detailed in the schedule. The heat exchanger must utilize 316L stainless steel plates and copper braze to separate the two fluids while transferring heat and preventing corrosion.
Each heat exchanger shall be Armstrong ABX030-_30_________ or approved equal.
C
E
L
D
A B
A1 B1
B2A2
QUANTITY TAG No. MODEL No. COMMENTS 1 HX-3 ABX030-30
Project # : 514501.2 rev3Submittal
Product: Expansion
Model: Expansion Equipment
Project Number: 514501.2.3
Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3
Date:
Location: Vancouver, BC
1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Representative: Con-Cur West Marketing Inc. 71A Clipper Street
Coquitlam, BC
V3K 6X2
Phone: 604-540-5088, Fax: 604-540-5084 Order No:
Submitted by: Dave HaskellApproved by: Date:
SYSTEM DATATag Num : EXT-1 Service : Location : Qty : 1Selection Method : Manual
Application: Heating
This has been a Manual Selection, so no data is available.
Expansion Tank:AX-40VTank Model : 1Tank Qty
Tank Volume :25.0 us gal Max. Working Pres. : 346.6 ft
Charge Pressure: 26.8 ft • Not for Domestic Potable Water Systems
• California Code Sight-Glass available upon request.Standard factory charge is 12 psi (83 kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII, Division 1.
• This submittal supercedes 37.51 and 37.50
Shell : Steel WORKING TEMPERATURE : 240°F (115°C)
Diaphragm : Heavy Duty Butyl WORKING PRESSURE : 150 psi (1034 kPa)
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 32 of 42
Project # : 514501.2 rev3Submittal
Product: Expansion
Model: Expansion Equipment
Project Number: 514501.2.3
Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3
Date:
Location: Vancouver, BC
1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Representative: Con-Cur West Marketing Inc. 71A Clipper Street
Coquitlam, BC
V3K 6X2
Phone: 604-540-5088, Fax: 604-540-5084 Order No:
Submitted by: Dave HaskellApproved by: Date:
SYSTEM DATATag Num : EXT-2 Service : Location : Qty : 1Selection Method : Manual
Application: Heating
This has been a Manual Selection, so no data is available.
Expansion Tank:AX-20VTank Model : 1Tank Qty
Tank Volume :11.0 us gal Max. Working Pres. : 346.6 ft
Charge Pressure: 26.8 ft • Not for Domestic Potable Water Systems
• California Code Sight-Glass available upon request.Standard factory charge is 12 psi (83 kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII, Division 1.
• This submittal supercedes 37.51 and 37.50
Shell : Steel WORKING TEMPERATURE : 240°F (115°C)
Diaphragm : Heavy Duty Butyl WORKING PRESSURE : 150 psi (1034 kPa)
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 33 of 42
Project # : 514501.2 rev3Submittal
Product: Expansion
Model: Expansion Equipment
Project Number: 514501.2.3
Name: CC-15409 Parc Elise - 4400 Cambie Reference: 514501.2.3
Date:
Location: Vancouver, BC
1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor:
Representative: Con-Cur West Marketing Inc. 71A Clipper Street
Coquitlam, BC
V3K 6X2
Phone: 604-540-5088, Fax: 604-540-5084 Order No:
Submitted by: Dave HaskellApproved by: Date:
SYSTEM DATATag Num : EXT-3 Service : Location : Qty : 1Selection Method : Manual
Application: Heating
This has been a Manual Selection, so no data is available.
Expansion Tank:AST-80Tank Model : 1Tank Qty
Tank Volume :35.0 us gal Max. Working Pres. : 346.6 ft
Charge Pressure: 40 psi • For Domestic Potable Water Systems & Draw down tanks for Pressure Booster Systems.Standard factory charge is 40 psi (276
kPa) unless otherwise specified. • Designed and Constructed per ASME Section VIII,Division 1.
Shell : Carbon SteelWORKING TEMP. : 240°F (115°C)
WORKING PRESSURE Liner : Polypropylene: 150 psi (1034 kPa)
System Conn. : Stainless Steel Fixed Diaphragm : Butyl-FDA approved
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 34 of 42
Project #: 514501.2 rev3
Submittal
Product: User Defined Products
Model: SEISMIC CLIPS
Project Number: 514501.2.3 Representative: Con-Cur West Marketing Inc.
Name: CC-15409 Parc Elise - 4400 71A Clipper StreetCoquitlam, BCV3K 6X2
Reference: 514501.2.3
Phone: 604-540-5088, Fax: 604-540-5084Vancouver, BCLocation:
Date: 1/7/2016Engineer: Cada & Associates
Date: 1/7/2016 Contractor: Order No:
Submitted by: Dave Haskell Approved by: Date:
This page is intentionally left blank. A submittal is unavailable for this product.
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 35 of 42
Submittal Ref. #: 514501.2 rev3
Flo-trex valve
Model: FTV-F (2.5 to 12 inch)
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Designflowrate
Tag Qty Model Size Config Flange ratingPressure
Drop*Associated pump
P-1/2 2 FTV-4FA 4 in Angle ANSI-125 190.0 USgpm 2.8 ft P-1/2 Design Envelope Sensorless 4300 0308-005.0
P-3/4 2 FTV-6FA 6 in Angle ANSI-125 485.0 USgpm 2.8 ft P-3/4 Design Envelope Sensorless 4300 0408-010.0
P-5/6 2 FTV-3FA 3 in Angle ANSI-125 140.0 USgpm 3.4 ft P-5/6 4380-3x3x6-1.5 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 O rings: BUNA (STEM) Elastomers & EPDM
Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
Operating limits (temperature - pressure)
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Maximum pressure: 175 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 36 of 42
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 37 of 42
Dimensional data (not for construction)
Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb
Side view Front view
Model: FTV-6FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 167 lb
Side view Front view
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 38 of 42
Model: FTV-3FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 39 lb
Side view Front view
Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 39 of 42
Submittal Ref. #: 514501.2 rev3
Suction guide
Model: SG (2 to 12 inches)
Project name: CC-15409 Parc Elise - 4400 Cambie Street
Location: Vancouver, BC Representative:
Date submitted: 1/7/2016 Phone number:
Engineer: Cada & Associates e-mail:
Contractor: Submitted by:
Con-Cur West Marketing Inc.
604-540-5088
Dave Haskell
Application design data
Design flowrate
Tag Qty Model System PumpPressure
Drop*Associated pump
P-1/2 2 SG-43 4 in 3 in 190.0 USgpm 1.5 ft P-1/2 Design Envelope Sensorless 4300 0308-005.0
P-3/4 2 SG-64 6 in 4 in 485.0 USgpm 2.9 ft P-3/4 Design Envelope Sensorless 4300 0408-010.0
P-5/6 2 SG-33 3 in 3 in 140.0 USgpm 0.8 ft P-5/6 4380-3x3x6-1.5 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
SG-43
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-64
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
SG-33
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
SG-43-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 40 of 42
Dimensional data (not for construction)
SG-43 Weight: 52 lb
Side view Top view
SG-64 Weight: 85 lb
Side view Top view
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 41 of 42
SG-33 Weight: 45 lb
Side view Top view
Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 1/7/2016, Ref. # 514501.2 rev3 Page 42 of 42