Submittal Package FTA200-AF - Firetrol

7
Publication SBP200AF-60 Rev. C (DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARD CONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER FROM THOSE SEEN HERE). Submittal Package Remote Alarm Panels For Use With 1-Electric and 1-Diesel Engine Fire Pump Controller FTA200-AF While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved. 3412 Apex Peakway Apex, North Carolina 27502 P 919 460 5200 F 919 460 5250 www.firetrol.com Project Information

Transcript of Submittal Package FTA200-AF - Firetrol

Page 1: Submittal Package FTA200-AF - Firetrol

Publication SBP200AF-60 Rev. C

(DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARDCONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER

FROM THOSE SEEN HERE).

Submittal Package

Remote Alarm Panels For Use With 1-Electric and 1-Diesel Engine Fire Pump Controller

FTA200-AF

While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.

3412 Apex PeakwayApex, North Carolina 27502P 919 460 5200F 919 460 5250www.firetrol.com

Project Information

Page 2: Submittal Package FTA200-AF - Firetrol

Firetrol Remote Alarm Panelsfor Use With Diesel Engine and Electric Fire Pump ControllersFTA200-A, 200-AA, 200-F, 200-FF & 200-AFSpecifications

1.0 Alarm PanelThe main fire pump controller shall be a factory assembled, wired and tested unit.

1.1 Standards, Listings & ApprovalsThe controller shall conform to all the requirements of the latest editions of:NFPA 20, Standard for the Installation of Stationary Pumps for Fire ProtectionNFPA 70, National Electrical Code.Factory Mutual (FM)

The controller shall be listed by:Underwriters Laboratories, Inc., in accordance with UL508, Standard for Industrial ControlsCanadian Standards Association CSA-C22.2, Standard for Industrial Control Equip-ment (cUL)

1.2 EnclosureThe controller components shall be housed in a NEMA Type 1 (IEC IP20) drip-proof, wall mounted enclosure with bottom entry gland plate.

1.3 OperationThe alarm panel shall have individual LED lights to indicate its alarm condition which shall remain lighted until the alarm condition has been corrected. The alarm panel shall also have an audible alarm which will sound when the alarm conditions occur and may be silenced by pressing a SILENCE ALARM push-button.Each alarm initiation shall be subsequent to any and all previous alarm conditions so that the silence push-button acknowledgment of any one alarm will not prevent the audible alarm from sounding on successive alarm conditions.The alarm panel shall have a PUSH-TO-TEST push-button for manually testing all LED lights, audible alarms and output circuits. All alarm LED’s and push-buttons shall be plainly marked for identification.

1.4 ManufacturerThe alarm panel shall be a Firetrol model FTA200-A for use with electric fire pump controllers, FTA200-AA for use with 2 electric fire pump controllers or model FTA200-F for use with diesel engine fire pump controllers, FTA200-FF for use with 2 diesel en-gine fire pump controllers or a FTA200-AF for use with 1 electric fire pump controller and 1 diesel engine fire pump controller.

Publication SP200-60

3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.

Page 3: Submittal Package FTA200-AF - Firetrol

Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 speci-fications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is un-der supervision at all times.

Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in ac-cordance with UL508, Standard for Indus-trial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL) and approved by Factory Mutual. They are designed to meet or exceed the require-ments of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps.

Standard Features—The following are in-cluded as standard with each controller:Type A Section - Provides audible and visible alarm indication for the following conditions:• Supervisory Power On (Visible Only)• Power / Phase Failure (Audible and Visible)• Phase Reversal (Audible and Visible)• Motor Trouble (Audible and Visible)• Pump Room Alarm (Audible and Visible)• Pump Running (Audible and Visible)

Type F Section - Provides alarm indication for the following conditions:• Main Switch In Hand or Off (Audible and

Visible)• Controller Trouble (Audible and Visible)• Pump Room Alarm (Audible and Visible)• Engine Trouble (Audible and Visible)• Engine Running (Audible and Visible)

Construction - FTA200 alarm panels make use of printed circuit boards which pro-vide reliable and trouble free service. The enclosures are NEMA Type 1 (IEC IP20) for indoor wall mounting. A bottom entry gland plate is provided in the enclosure. The standard enclosure color is red. Mounted on the enclosure door are the LED lights for visible alarm indication, the SILENCE ALARM push-button and the LAMP TEST push-button. An alarm bell for audible indication is mounted on the side of the enclosure. Each LED will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal con-dition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the LED. If another alarm condi-tion occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condi-tion has been corrected. The LAMP TEST push-button is supplied for manually testing the LED’s.

Product Description FTA200-AF

Remote Alarm Panels for use with 1 Electric and 1 Diesel Engine Fire Pump Controller

Publication PD200-62 Rev. A

3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.

For Model Number Information and Options & Modifications see Publication SD200-62

Page 4: Submittal Package FTA200-AF - Firetrol

FTA NUMBER FTA200

Alarm Panel Type -AF Type AF Alarm Panel (For use with 1 Electric Controller and 1 Diesel Controller

FTA200-AF-__ (Example: FTA200-AF-Y)

Remote Alarm Panels For Use With Electric and Diesel Engine Fire Pump Controllers

Model Number Selection Guide

FTA200-AF

-Q Enclosure, NEMA Type 2 (IP22), Painted Steel

SPECIAL ENCLOSURES DescriptionOption

-EX Enclosure, NEMA Type 4 (IP66), Painted Steel

-FXP Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, Painted Finish

--- Enclosure, NEMA Type 1 (IP20), Painted Steel

Options & Modifications

-AM Alarm, Audible/Visible, Fail To Start

Optional Alarms - ELECTRIC DescriptionOption

-BY1 Alarm, Audible/Visible, Overcurrent -EJ1 Alarm, Audible/Visible, Flow Meter Open -Y Alarm, Specify Number Of Alarms, Function of Each & Nameplate Marking

-AV Alarm, Audible/Visible, Low Pump Room Temperature

Optional Alarms - DIESEL DescriptionOption

-AW Alarm, Audible/Visible, Reservoir Low -AY1 Configurable Low Suction Pressure Visible/Output Contacts with External Digital Input -AK Alarm, Audible/Visible, Low Oil Pressure -AL Alarm, Audible/Visible, High Water Temperature -AM Alarm, Audible/Visible, Fail To Start -AP1 Alarm, Audible/Visible, Main Switch In Manual -AR Alarm, Audible/Visible, Main Switch In Off -AS1 Alarm, Audible/Visible, Main Switch In Auto -BTC Alarm Output Contacts, Charger #1 & #2 Failure (Form-C, SPDT) -CFC Alarm Output Contacts, Battery #1 & #2 Failure (Form-C, SPDT) -LC Alarm, Audible/Visible, High Fuel Level -LE1 Alarm, Audible/Visible, Fuel Spill -Y Alarm, Specify Number Of Alarms, Function of Each & Nameplate Marking

-F Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, Brushed Finish

Page 5: Submittal Package FTA200-AF - Firetrol

Publication SD200-62 Rev. B

3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.

INFORMATION REQUIRED WITH ORDER1) Catalog number of alarm panel.2) Catalog number of controller to be

used with alarm panel.3) Modifications if any.

-BS Fire Pump Start Push-button

Miscellaneous DescriptionOption

-BA AC Input, 220-240V

Page 6: Submittal Package FTA200-AF - Firetrol

Dimensions andShipping Weight

Remote Alarm Panels For Use With 1 Electric & 1 Diesel Engine Fire Pump Controllers

FTA200AF

Page 7: Submittal Package FTA200-AF - Firetrol

Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.

TB6-

NTB

6-C

TB5-

NTB

5-C

TB4-

NTB

4-C

TB3-

NTB

3-C

TB2-

NTB

2-C

TB1-

NTB

1-C

J5-2

J5-1

SW1-

5SW

1-4

SW1-

3SW

1-2

SW1-

1 J2-1J2-2

A

AR9-

NC

ON: Bell activated by input

Red

Black

OFF: Input does NOT activate bell

SW1 POSITIONS

MO

TOR

TR

OU

BLE

POW

ER/P

HAS

E FA

ILU

RE

PUM

P R

OO

M A

LAR

M

AR10

-NC

PHAS

E R

EVER

SAL

J5-G

AR11

-C

AR1-

CAR

1-N

CAR

1-N

O

AR12

-NO

TB12

-NTB

12-C

TB10

-CTB

9-N

TB9-

C

TB8-

CTB

7-N

AR2-

C

SW1-

11

SW1-

9

AR2-

NC

SW1-

8

POW

ER O

N

AR2-

NO

AR3-

CAR

3-N

CAR

3-N

OAR

4-C

AR4-

NC

AR4-

NO

AR5-

CAR

5-N

CAR

5-N

OAR

6-C

AR6-

NC

AR6-

NO

AR7-

CAR

7-N

CAR

7-N

OAR

8-C

AR8-

NC

AR8-

NO

AR9-

C

AR9-

NO

AR10

-C

11

AR10

-NO

14 12

AR11

-NO

AR11

-NC

AR12

-CAR

12-N

C

TB11

-N

MAI

N S

WIT

CH

IN

TB7

TB11

-CTB

10-N

TB8-

N

TB7-

C

SW1-

10

SUPE

RVI

SOR

Y

SW1-

7

4

Power Supply

ELECTRIC

ALARM PANEL ELECTRIC &

SUPERVISORY

DIESEL FIRE PUMPS

REVERSAL

POWER ON

LAMP TEST

PHASE

SILENCE

MOTOR

TROUBLE

TROUBLE

CONTROLLER

DIESEL PUMPRUNNING

MAIN SWITCH INHAND OR OFF

ENGINETROUBLE

DIESEL FIRE PUMP CONTROLLER

TB1

11

ENG

INE

TRO

UBL

E

TB6

ENG

INE

RU

N

1111

(Fai

l saf

e re

lay)

CO

NTR

OLL

ER T

RO

UBL

E

1414

11

14

CO

NTR

OLL

ER T

RO

UBL

E

RU

NN

ING

PUMP ROOMALARM

ENG

INE

TRO

UBL

E

ELECTRIC FIRE PUMP CONTROLLER

POW

ER A

VAIL

ABLE

(Fai

l saf

e re

lay)

TB2TB1

PHAS

E R

EVER

SAL

PUM

P R

OO

M A

LAR

M

MO

TOR

TR

OU

BLE

TB4

11 1111

TB3

14 14

11

12 14

MO

TOR

RU

N

11

14

TB2

PUM

P R

OO

M A

LAR

M

MAI

N S

WIT

CH

IN

HAN

D O

R O

FF

RU

NN

ING

PUM

P R

OO

M A

LAR

M

POWER / PHASEFAILURE

HAN

D O

R O

FF

ELECTRIC PUMP

PUMP ROOM

RUNNING

ALARM

MOTOR RUN

DIESEL

TB5

120Vac or220-240Vac

Dipswitch Selected(SW4)

SW4

SW4 POSITIONS120V: 120Vac240V: 220-240Vac

DIE

SEL

PUM

P

ELEC

TRIC

PU

MP

NOTES :: Internal Terminals

-Wire Size :-Torque :

-Type :-Wire Size :-Torque :

-Wire Size :-Torque :

- Power Supply :

- Alarm Contact :

- Field Connections :

12-24 AWG0.4Nm

SPDT14-24 AWG0.4Nm

12-22 AWG0.4Nm

: Related Controller Terminals-Wire Size :-Torque :

- Field Connections : 12-24 AWG0.5Nm

APPROVALFINAL

DRAWN BY

BY DATEECN NO

ECNNO

SIZE

DRAWING NUMBER

DWGREV

A REV

SHEET OF

BY APP DATEREVISION DESCRIPTION

PROJECTIONTHIRD ANGLE

© Firetrol, Inc. Not for construction.Subject to change without notice.

WS200AF-60- - 1 1

CIR 11-5-19

CIR 11-5-19

RELEASED - - CIR CIR 11-5-19

Wiring SchematicField Connections

Remote Alarm Panels For Use With 1 Electric & 1 Diesel Engine Fire Pump Controllers

FTA200AF