Community Partnerships STRONGER COMPANIES. STRONGER COMMUNITIES.
STRONGER THAN STEEL SM -...
Transcript of STRONGER THAN STEEL SM -...
BlazeFrame® product catalog
I N T E G R AT E D F I R E S T O P S Y S T E M S
S T R O N G E R T H A N S T E E LSM.
clarkdietrich.com/BlazeFrame
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
What is BlazeFrame? BlazeFrame products are innovative steel framing profile/intumescent composites, that combine ease of installation, inspection, life safety and joint protection dependability into one unique product.
How does it work? Using a cured factory metered dosage intumescent material, BlazeFrame profiles provide fire stopping, smoke and sound dampening that is effective immediately after framing components are installed. When exposed to heat above 375° F, the intumescent material expands up to 35 times its size. This provides additional protection from heat and flame passage during a fire event.
What does it replace? BlazeFrame's factory metered dosage intumescent material eliminates elastomeric fire proofing caulks and spray. The cured intumescent tape eliminates VOC's and off gases associated with caulked spray fire proofing. With the intumescent tape factory applied it eliminates both overage and underage often associated with the messy caulks and sprays.
BlazeFrame Advantages:• Installed&inspectedas" jointframing"
(before obstructions)• Unaffectedbydirty,oily,wetorfreezing
conditions• Curedintumescenteffectiveimmediately
(no VOC)• Nofatiguetojointorsubstratematerialsforlife
of assembly
BlazeFrame Design Advantages
One to three hour assembly
BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING
5/8” TYPE XGYPSUM WALLBOARD
CONCRETE DECK
2
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
Fire Stopping• UL2079Classifiedandlistedforupto3hr
assemblies• Protectionforupto3"overallmovement
capability(1-1/2"upand1-1/2"down)• Eliminatesfireproofingcaulksandsprays• ShaftwallAssembliescertifiedforusewithall
ULlisted"liner"boardsandfinishsidegypsumproducts
Sound Dampening• NVLAPcertifiedtoprovideuptoSTC62
(based on wall assembly)• Openunencumberedjoints(nocaulkrequired)• FluteddeckexposedwithonlyBlazeFrame
Deck PlugorFluteCoverSTC=50+
Smoke barrier-air leakage - IBC 2009 BlazeFrameassemblieshavebeenULClassified withthelowestpossibleL-Rating(lessthan1CFM/lft).
Seismic Requirements BlazeFrameisUL2079ClassifiedforClassIIICycling of 500 cycles at 30 cycles per minute of vertical movement which may be capable of meeting seismic design and building code requirements.
Code Compliance BlazeFrame joint protection complies with up to date building codes and is listed by Underwriters LaboratoriesInc.
UL2079 TestsforFireResistanceofBuildingJointSystemsASTME-1966 StandardTestMethodforFireResistiveJointSystemsASTME-814 StandardMethodofFireTestsofFireStopSystemsULCS115-M95 StandardMethodofFireTestsofFireStopSystemsASTME-119 EvaluationofaNon-LoadBearingWallAssemblywithaControlJointBackerASTME-2837 RatedWallAssembliesInstalledtoNon-RatedAssemblies(pending)
Expandedintumescentstripafterfiretest
BlazeFramedeflectiontrack&deckplugsinsoundtest
3
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
M E TA L D E C K CO N D I T I O N
CO N C R E T E D E C K CO N D I T I O N
• Head of Wall assembly complete before studs are installed.
• Mineralwoolonlyneededforflutefill.
• Earlier,easier,andaccurateinspection.
• Clean transition from wall sheathing to substrate.
• Exposedandfinishedjointsarefireandsoundrated.
BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING
5/8” TYPE XGYPSUM WALLBOARD
CONCRETE DECK
MINERAL WOOLFLUTE FILL
BLAZEFRAME FIRE STOP DEEP LEG
DEFLECTION TRACK(DL2, DSL2)
1, 2, 3, LAYERSFOR 1, 2, 3, HR
RATING
ATTACH GYPSUM PER UL DESIGN REQUIREMENT
STEEL STUD
BlazeFrame Design Advantages
4
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
B E A M P E N E T R AT I O N CO N D I T I O N
• Eliminatescontourcuttingofwallsheathing,caulks/sprays.
• Sprayfireproofingormineralwoolaretheeasyoptionforbeamcavityfill.
METAL PAN DECK
BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION
TRACK (DL2)
STEEL STUD
ANGLE OR Z-CLIPCENTERED
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOFINGor MINERAL WOOL
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME OFFSET DEEP LEG DEFLECTION TRACK
(ODL2, ODSL2)
14GA STRAP / ANGLEOUTRIGGER
STEEL STUD
• Eliminatesz-clips,lathbasket,voidsinfireproofing.
• 14gaangleoutrigger/profilepreassembledpriortoinstallation.
PA R A L L E L O FF S E T CO N D I T I O N
5
BlazeFrame Sample Profiles
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
*4”leglengthisnotavailablefor2-1/2”widesystem
*4”leglengthisnotavailablefor2-1/2”widesystem
DSL 2 (DEEP LEG - SLOT TED BOTH SIDES)
SL 1 (DEEP LEG - SLOT TED ONE SIDE)
Profile with two slotted legs w/ fire stop on both sides CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Legswithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.
Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
Profile Leg Length (L)
Tape Width (I)
Slot Height (S)
Joint Protection
DSL 2 3.00” 1.00” 1.50” 0.75”DSLW 2 3.00” 1.25” 1.50” 1.00”DSLX 2 4.00” * 1.75” 2.00” 1.50”
Profile with one slotted leg and one solid leg w/ fire stop on slotted side CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Onelegwithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.
Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
Profile Slotted Leg Length (L1)
Solid Leg Length (L2)
Tape Width (I)
Slot Height (S)
Joint Protection
SL 1 3.00” 2.00” 1.00” 1.50” 0.75”SLW 1 3.00” 2.00” 1.25” 1.50” 1.00”SLX 1 4.00” * 2.50” 1.75” 2.00” 1.50”
(L)
Width
(L)
(S)
(I)
(L)
.22”1.00”Fastener mid-height of exposed slot
(L2)
Width
(L1)(I)
(I)
6
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
(DL 1 Series)
(DL 2 Series)
*4”leglengthisnotavailablefor2-1/2”widesystem
DL (DEEP LEG - SOLID)
JR (J-RUNNER)
CompositeFireStop/Framingforuseinfireratedwallassemblies. Provides 100%unencumberedjointprotection.Accommodatesupto3”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Twosolidlegssupporting“freefloating”studsperlistedassembliesinULFireResistanceDirectory.
Widths: 2-1/2",3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
(DL 1 Series) Profile with two solid legs w/ fire stop on one side (DL 2 Series) Profile with two solid legs w/ fire stop on both sides
Profile Leg Length (L)
Tape Width (I)
Joint Protection
DL 2.00” 1.00” 0.75”DLW 2.00” 1.25” 1.00”
DLX 2.50” 1.75” 1.50”DLZ 3.00” 2.25” 2.00”DLY 4.00” * 3.25” 3.00”
Profile with two solid legs w/ fire stop on one side CompositeFireStop/Framingforuseinupto3hrfireratedshaftwallassemblies.Provides100%unencumberedjointprotection.Accommodatesupto11/2”overallmovementwithUL2019LevelIIICertification.MinimumCP60coating.Oneleg(front)havingintumescentperlistedassembliesinULFireResistanceDirectory.
Widths: 2-1/2",4"and6" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
Profile Front Leg Length (FL)
Back Leg Length (BL)
Tape Width (I)
Joint Protection
JR 1 2.00” 3.00” 1.00” 0.75”JRW 1 2.00” 3.00” 1.25” 1.00”
JRX 1 2.00” 3.00” 1.75” 1.50”
(L) (L)(I)(I)
(BL)(FL)
(I)
Width
Width
7
BlazeFrame Sample Profiles
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
ODL 2 (OFFSET DEEP LEG)
ODSL 2 (OFFSET DEEP SLOT TED LEG)
Profile with two solid legs w/ fire stop on both sides CompositeFireStop/Framingwith“offsetstep”accommodates1-1/4”thick fireproofing in head of wall and wall to wall (column) assemblies. (Other offset depths available to accommodate other sprayed thicknesses). Provides100%unencumberedjointprotection.Accommodatesupto2”overallmovementwithUL2079LevelIIICertification.MinimumCP60coating.TwosolidlegsperlistedassembliesinULFireResistanceDirectory.
Widths: 3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
Profile Lower Leg Length (L)
Tape Width (I)
Joint Protection
ODL 2 2.00” 1.00” 0.75”ODLW 2 2.00” 1.25” 1.00”
ODLX 2 2.50” 1.75” 1.50”ODLZ 2 3.00” 2.25” 2.00”
Profile with two slotted lower legs w/ fire stop on both sides CompositeFireStop/Framingwith“offsetstep”accommodates1-1/4”thick fireproofing in head of wall and wall to wall (column) assemblies. (Other offset depths available to accommodate other sprayed thicknesses). Provides100%unencumberedjointprotection.Accommodatesupto1-1/2”overallmovementwithUL2079LevelIIICertification.MinimumCP60coating.Twolegswithslotsspaced1”o.c.forpositiveattachmentofstudsperlistedassembliesinULFireResistanceDirectory.
Widths: 3-5/8",4",6"and8" Thicknesses: 33mils(20ga),43mils(18ga)and54mils(16ga)
Profile Lower Leg Length (L)
Tape Width (I)
Slot Height (S)
Joint Protection
ODSL 2 3.00” 1.00” 1.50” 0.75”ODSLW 2 3.00” 1.25” 1.50” 1.00”
ODSLX 2 4.00” 1.75” 2.00” 1.50”
Width
(L)0.75”0.75”
(1-1/4”)*
Width
(L)
0.75” 0.75”(1-1/4”)*
* Other offset step depths available
* Other offset step depths available
(I)
(I)
8
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
C JB (CONTROL JOINT BACKER) Profile for protection of control joints CompositeFireStop/ControlJointBackerforusetoprotectArchitecturaldesignjoints(optionalcontroljointovergap)forupto2hrratedassemblies.MinimumG40coating.Providesa metal profile which supports intumescent materials located inside and spanning gap between opposing drywall edge at control jointlocations.Alsoeliminatestheneedforasecondstudinthegypsum assembly.
Width: 3-1/4" Length: 10'-0" Thicknesses: 18mils(25ga) Packaging: 14Pcs./Ctn.
Profile Intumescent Width
Profile Width
Thickness
CJB-18 1.25" 3.25" .018"
FC (FLUTE COVER) Profile strap for under fluted decks Corrugated strap for horizontal use to span fluted areas of unprotected or protected metal decks in up to 2 hr rated assemblies. Profile attached to deck“valley”surfacesamax16”o.c.onbothsides.Profilesprovidea surface area for attachment of head of wall partition track profiles centered or offset underneath and parallel to deck fluted areas per listed assemblies in ULFireResistanceDirectory.
Sizes: 675(6-3/4”)or700(7”) Length: 10'-0" Thicknesses: 33mils (20ga)
1.50” 1.50”0.875” 0.875”
Width varies to match flute opening
0.56
3”
WallboardSteel Stud
093 Control Joint CJB - Control Joint Backer
Eliminates the need for a second stud in
the gypsum assembly
BLAZEFRAME COMPOSITE(DL2, DSL2)
BLAZEFRAME (FC)FLUTE COVER(continuous)
5/8” TYPE XGYPSUM WALLBOARD STEEL STUD
FLUTED DECK
9
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL1, SL1)
5/8” TYPE XGYPSUM WALLBOARD
CONCRETE DECK
STEEL STUD
BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION
TRACK (DL2, DSL2)
STEEL STUD
1, 2, 3, LAYERSFOR 1, 2, 3 HR RATING
5/8” TYPE XGYPSUM WALLBOARD
CONCRETE DECK
Post Tension or Structural Concrete Overhead
PT-1HW-D-0498
Chase Wall Post Tension or Structural Flat Concrete
PT-2 HW-D-0505
METAL PAN DECK
BLAZEFRAME FIRE STOP DEEP LEG DEFLECTION
TRACK (DL2)
STEEL STUD
ANGLE OR Z-CLIPCENTERED
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOFINGor MINERAL WOOL
MINERAL WOOLFLUTE FILL
BLAZEFRAME FIRE STOP DEEP LEG
DEFLECTION TRACK(DL2, DSL2)
1, 2, 3, LAYERSFOR 1, 2, 3, HR
RATING
ATTACH GYPSUM PER UL DESIGN REQUIREMENT
STEEL STUD
Perpendicular Unprotected Deck (UD) – Mineral Wool Fill
UD-1 HW-D-0513
Head of Wall Beam Penetration SS-1
HW-D-0495
BlazeFrame Sample Details
10
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
BLAZEFRAME COMPOSITE(DL2, DSL2)
BLAZEFRAME (FC)FLUTE COVER(continuous)
5/8” TYPE XGYPSUM WALLBOARD STEEL STUD
FLUTED DECK
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL2, DSL2)
FIRE PROOFING
5/8” TYPE XGYPSUM WALLBOARD
MINERAL WOOL
STEEL STUD
Centered Under Flute Unprotected Deck (UD) – Flute Cover
UD-6 HW-D-0544
Perpendicular Protected Deck (PD) – Mineral Wool Flute Fill
PD-12 HW-D-0513
Parallel Under Structural Support (Z-Clips)
SS-16 HW-D-0502
Wall to Wall Gypsum to Protected Steel (I-Beam)
VM-3Design Based on
WW-S-0055HW-D-0558
BLAZEFRAME COMPOSITETRACK/FIRE STOP
(DL2, DSL2)
5/8” TYPE XGYPSUM WALLBOARD
Z-CLIPS
STEEL STUD
STEEL COLUMN
BLAZEFRAME “OL” PROFILE(ODL2)
5/8” TYPE XGYPSUM WALLBOARD
FIRE PROOF COATING
11
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
CONCRETE COLUMN / WALL
5/8” TYPE XGYPSUM WALLBOARD
STEEL STUD
BLAZEFRAME COMPOSITE TRACK / FIRESTOP
(DL2)
Wall to Wall Gypsum to Concrete Column/Wall
VM-1 WW-S-0055
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME COMPOSITETRACK / FIRE STOP
“OL” - SERIES(ODL2, ODSL2)
STEEL STUD 5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME OFFSET DEEP LEG DEFLECTION TRACK
(ODL2, ODSL2)
14GA STRAP / ANGLEOUTRIGGER
STEEL STUD
5/8” TYPE XGYPSUM WALLBOARD
093 CONTROL JOINT(optional)
SHAFT LINER BOARD
BLAZEFRAME COMPOSITETRACK / FIRE STOP
(JR1)
CH, CT, OR I STUD
Parallel Under Structural Support (Offset Leg Profile)
SS-2 HW-D-0502
Edge of Structural Support with Angle (Offset Leg Profile)
SS-28 HW-D-0631
Hollow Steel Shape - Non RatedSS-21
Design Based on HW-D-0543 HW-D-0559
BlazeFrame Sample Details
12
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
Under UL G500 Series DesignVM-6
HW-D-0503
BLAZEFRAME COMPOSITE TRACK / FIRE STOP
(DL2, DSL2)
5/8” TYPE XGYPSUM WALLBOARD
FURRING CHANNEL
STEEL STUD
5/8” TYPE XGYPSUM WALLBOARD
Bottom of WallVM-12
BW-S-0021
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME COMPOSITETRACK / FIRE STOP
(DL2) CONCRETE FLOOR
STEEL STUD
Flat Strap PatchVertical Cavity Obstructions
ECA - End Cap AngleExterior Corner Application
FIELD MODIFIED - VERTICAL OBSTRUCTION
TOP VIEW SIDE VIEW
FASTEN FSP TO OUTERSURFACE OF TRACK LEG
BLAZEFRAME FSP(Flatstrap Patch)
TOP VIEW TOP VIEWINSERT ECA
SIDE VIEW INSERT ECA
ECA ATTACHED WITH FASTENER
INTERSECTING WALL BLAZEFRAME “BUTTED”
13
The technical content of this literature is effective 9/10/12 and supersedes all previous information.Pub. No. CD-BlazeFrame 9/12 clarkdietrich.com
CONCRETE DECK
BLAZEFRAME COMPOSITETRACK / FIRE STOP
(JR1)
3 LAYERS FOR3 HOUR RATING
CH, CT, OR I STUD
LINER BOARD
MINERAL WOOL
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAMECOMPOSITE
TRACK / FIRE STOP(JR1)
FASTENER AT BOTTOMOF OBSTRUCTION
(when exists)CT, CH, OR I STUD
LINER BOARD
MINERAL WOOL
MINERAL WOOL orFIRE PROOFING
5/8” TYPE XGYPSUM WALLBOARD
093 CONTROL JOINT
5/8” TYPE XGYPSUM WALLBOARD
BLAZEFRAME “CJB”CONTROL JOINT BACKER
STEEL STUD5/8” TYPE X
GYPSUM WALLBOARD
BLAZEFRAME “CJB”CONTROL JOINT BACKER
093 CONTROL JOINT
STEEL STUD
Shaft Wall Post Tension or Structural Concrete
PT-3HW-D-0496
CJB - Control Joint Backer one side 1-hour
12033
Shaft Wall Perpendicular to Unprotected Deck
UD-10HW-D-0504
CJB - Control Joint Backer two sides 2-hour
12033
BlazeFrame Sample Details
14
The technical content of this literature is effective 9/10/12 and supersedes all previous information. The technical content of this literature is effective 9/10/12 and supersedes all previous information. Pub. No. CD-BlazeFrame 9/12clarkdietrich.com
UL Approvals
UL Control - R25833 (US)- 1, 2 and 3 hr designs - UL 2079 standard compliant
UL Listings
HW-D-0495 Protected Beam Penetration HW-D-0496 Under Flat Concrete (shaft wall) HW-D-0497 Parallel to Protected Beam (shaft wall) HW-D-0498 Under PT or Structural Concrete HW-D-0499 Parallel to Unprotected Fluted Metal Deck HW-D-0500 Perpendicular Unprotected Fluted Metal Deck HW-D-0501 Parallel to Beam (standard wall) HW-D-0502 Parallel & Edge Overlap Under Structural Support HW-D-0503 Under Layer “Type C” UL 500 Series Designs HW-D-0504 Under Unprotected Fluted Metal Deck (shaft wall) HW-D-0505 Under PT or Structural Concrete (chase wall) HW-D-0506 Under Fluted Metal Deck (chase wall) HW-D-0512 Perpendicular Protected Deck w/Fire Proofing Flute Fill HW-D-0513 Perpendicular Unprotected Deck w/Mineral Wool only Flute Fill HW-D-0543 Stair Shaft (093 Control Joint Optional) HW-D-0544 Parallel under Flute (Flute Cover Plate) HW-D-0558 Offset Leg Standard Wall Protected Roof Deck/Substrate HW-D-0559 Offset Leg Shaft Wall Protected Roof Deck/Substrate HW-D-0597 Parallel to Beam (Z-clip & Drywall Rip) HW-D-0631 Shaft Wall Parallel & Edge Overlap Under Structural Support HW-D-0632 PT or Structural Concrete Bare Slotted with Caulks HW-D-0633 Fluted Metal Deck Bare Slotted with Flute Plate/Caulks WW-S-0055 Vertical Wall to Wall Joint BW-S-0021 Bottom of Wall
Details shown are a limited sample of assemblies based on UL certified and listed assemblies. Additional assembly details, submittal sheets, and constructability designs are periodically added upon design and approval. Information can be viewed, downloaded, and printed from www.clarkdietrich.com/BlazeFrame.
Project Information
Name:
Address:
City/ST/ZIP:
Contractor Information
Name:
Contact:
Phone:
Fax:
Architect Information
Name:
Contact:
Phone:
Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
® (CJB)
“CJB” (Control Joint Backer)
Composite Fire Stop/Control Joint Backer for use to protect Architectural
design joints (optional control joint over gap) for up to 2 hr rated assemblies.
between opposing drywall edge at control joint locations. Also eliminates the
need for a second stud in the gypsum assembly.
Material:
Yield Strength: Grade 33ksi
Coating:
G40
18mils: 25 Gauge, 0.0188” Design Thickness, 0.0179“ Min. Thickness
Dimensions:
Width:
3-1/4”
Length:
10’-0”
Packaging:
14 Pieces/Carton
Intumescent
Width
Width
Gap
Width
Flange
Width
CJB-181.25”
3.25”.75”
1.25”
ASTM A1003, C955
WFCI 12033
is available @ www.clarkdietrich.com
CD-BlazeFrame-CJB © 08/12 ClarkDietrich Building Systems
Wallboard
Eliminates the need
for a second stud in
the gypsum assembly
Steel Stud
093 Control Joint
CJB - Control Joint Backer
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206
Sales: 800-543-7140
clarkdietrich.com
Project InformationName: Address: City/ST/ZIP:
Contractor InformationName: Contact: Phone: Fax:
Architect InformationName: Contact: Phone: Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
Material: Yield Strength: Grade 33ksi for 33mils & 43mils, 50ksi for 54mils
Coating: CP60 (G90 available)
33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness
43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness
54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness
Dimensions: Inside width: Equal to the outside width of the stud
Widths (W): 3-5/8”, 4”, 6” and 8”
Track length: 10’-0”
Lower Leg Length (L)
Tape Width (I)
Slot Height (S)
Joint Protection
ODSL 2 3.00” 1.00” 1.50” 0.75”
ODSLW 2 3.00” 1.25” 1.50” 1.00”
ODSLX 2 4.00” * 1.75” 2.00” 1.50”
ASTM A1003, C955
UL2079, E814, E1966, E119
is available @ www.clarkdietrich.com
CD-BlazeFrame-ODSL2 © 08/12 ClarkDietrich Building Systems
Width (W)
(L)0.75” 0.75”
(1-1/4”) **
®
“ODSL 2” (Offset Slotted Leg)
Two offset slotted lower legs
Composite F
up to 1-1/2” thick in head of wall and wall to wall (column) assemblies. Pro-
vides 100% unencumbered joint protection. Accommodates up to 3” overall
legs with slots spaced 1”o.c. for positive attachment of studs per listed
assemblies in UL Fire Resistance Directory.
provides air, smoke and sound seals. When exposed to heat above 325
degrees Fahrenheit, the intumescent material expands up to 35 times its size.
* 4” leg length is not available for 2-1/2” wide system** Other offset step depths available
(I)
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206Sales: 800-543-7140
clarkdietrich.com
Project InformationName: Address: City/ST/ZIP: Contractor Information
Name: Contact: Phone: Fax: Architect InformationName: Contact: Phone: Fax:
- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste
stream. The contribution to LEED must be calculated by the contractor based on weight or volume.
- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to
report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.
®
Composite Fire Stop/Framing for
100% unencumbered joint protection. Accommodates up to 1 1/2” overall
with slots spaced 1”o.c. for positive attachment of studs per listed assemblies
in UL Fire Resistance Directory.
provides air, smoke and sound seals. When exposed to heat above 325
degrees Fahrenheit, the intumescent material expands up to 35 times its size.
Material: Yield Strength: Grade 33ksi for 33mils & 43mils
Grade 50ksi for 54mils
Coating:
CP60 (G90 available)
33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness
43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness
54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness
Dimensions: Inside width: Equal to the outside width of the stud
Widths (W): 2-1/2”, 3-5/8”, 4”, 6” and 8”
Vertical slots: 0.22” wide & spaced every 1”o.c.
Track length: 10’-0”
Leg Length (L) Tape Width (I) Slot Height (S) Joint Protection
DSL 23.00”
1.00”1.50”
0.75”
DSLW 23.00”
1.25”1.50”
1.00”
DSLX 24.00” *
1.75”2.00”
1.50”ASTM A1003, C955UL2079, E814, E1966, E119
is available @ www.clarkdietrich.com
CD-BlazeFrame-DSL2 © 08/12 ClarkDietrich Building Systems
(L)
(W)
(L)
(S)
(I)
(L)
.22”1.00”
Fastener mid-height of exposed slot
* 4” leg length is not available for 2-1/2” wide system
Product Submittal Sheet
Technical Services: 888-437-3244
Engineering Services: 877-832-3206 Sales: 800-543-7140clarkdietrich.com
NEED TO SEND PRODUCT SUBMIT TALS?Build BlazeFrame Product Submittals for your next project. UseClarkDietrich'sSubmittalPro®ProductSubmittalSystemtocreateandsend a PDF package of BlazeFrame's product information and technical submittals based on your project's layout conditions.
Launch SubmittalPro® from clarkdietrich.com
CodeApprovals
15
CD-BlazeFrame 9/12 © ClarkDietrich Building Systems. The technical content of this literature is effective 9/10/12 and supersedes all previous information.
Turn to ClarkDietrich for a complete lineup of steel construction products and services nationwide:
Interior Framing∙Exterior Framing∙Interior Finishing∙Clips/Connectors∙Metal Lath/Accessories∙Engineering
9100 Centre Pointe Dr. Suite 210 West Chester, OH 45069
P 513.870.1100 F 513.870.1300
clarkdietrich.comClarkwestern Dietrich Building Systems LLC