STRIDDE, CALLINS & ASSOCIATES INC. -...
Transcript of STRIDDE, CALLINS & ASSOCIATES INC. -...
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
INSTALL BRANCH DUCT AS HIGH AS POSSIBLE.
SUPPLY AIR DUCT CONNECTION SAME SIZE AS AIR DEVICE CONNECTION IN BOTTOM OFBRANCH DUCT. PROVIDE COMBINATION 45° TAKE-OFF AND BALANCING DAMPER(TYPICAL).
PROVIDE 90° ELBOW.
TRANSITION IN RISER TO UNIT DUCT CONNECTION SIZE.
TRANSITION IN RISER TO FAN DUCT CONNECTION SIZE.
COORDINATE SENSOR LOCATIONS WITH ARCHITECTURAL ELEVATIONS, ELECTRICALSWITCH LOCATIONS, ETC. PRIOR TO CONSTRUCTION (TYPICAL).
1
2
3
4
HVAC KEYED NOTES :(APPLICABLE TO THIS SHEET ONLY)
RE:M2.2 FORCONTINUATION
RE:M2.2 FORCONTINUATION
RE:M2.2 FORCONTINUATION
5
6
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
TRANSITION IN RISER TO UNIT DUCT CONNECTION SIZE.
COORDINATE SENSOR LOCATIONS WITH ARCHITECTURAL ELEVATIONS,ELECTRICAL SWITCH LOCATIONS, ETC. PRIOR TO CONSTRUCTION(TYPICAL).
1
2
HVAC KEYED NOTES :(APPLICABLE TO THIS SHEET ONLY)
MA
TCH
LIN
EM
ATC
HLI
NE
RE:M2-1 FOR CONTINUATION
RE:M2-1 FOR CONTINUATION
RE:M2-1 FOR CONTINUATION
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
TRANSFER AIR DUCT ABOVE CEILING WITH 1" THICK ACOUSTICAL DUCT LINER ANDFIRE/SMOKE DAMPER (TYPICAL).
1" INSULATE COPPER DRAIN PIPE. PROVIDE ROOF PENETRATION HOOD, COORDINATEWITH ARCHITECT / GENERAL CONTRACTOR PRIOR TO CONSTRUCTION.
1" INSULATED COPPER DRAIN PIPE AND P-TRAP.
CONDENSATE PIPE SUPPORT.
ROUTE CONDENSATE PIPE BETWEEN JOISTS WEBS AS HIGH AS POSSIBLE. COORDINATEROUTE WITH EXISTING CONDITIONS PRIOR TO CONSTRUCTION. MAINTAIN MINIMUM 1/8"PER SLOPE.
COORDINATE CEILING REMOVAL /REPLACEMENT REQUIREMENTS WITH GENERALCONTRACTOR PRIOR TO BIDDING.
CONDENSATE PIPE RISER SUPPORTED TO WALL WITH GALVANIZED CHANNELS ANDPIPE CLAMP. EXTEND AND TERMINATE OVER EXISTING FLOOR DRAIN.
1
2
3
4
HVAC KEYED NOTES :(APPLICABLE TO THIS SHEET ONLY)
5
6
7
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
INSULATED COPPER DRAIN PIPE AND P-TRAP EXTEND AND TERMINATE OVER ROOFRECEPTOR. PROVIDE ADJUSTABLE HEIGHT PIPE SUPPORTS (TYPICAL).
ROOF RECEPTOR BY PLUMBING CONTRACTOR. COORDINATE ROOFTOP UNIT DRAINPIPE CONNECTION LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO CONSTRUCTION(TYPICAL).
COORDINATE AIR ROOF MOUNTED EQUIPMENT ROOF PENETRATION DIMENSIONS ANDLOCATION PRIOR TO CONSTRUCTION (TYPICAL AIR EQUIPMENT).
1
2
3
HVAC KEYED NOTES :(APPLICABLE TO THIS SHEET ONLY)
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
PACKAGED ROOF TOP SCHEDULE
DESIG. EVAP.CFM O/A CFM
ESP IN(WC)
AIR ONCOND.
COOLING COIL ELECTRIC HEATING ELECTRICAL DATA
EER @AHRI
UNITWEIGHT
(LBS)
MANUFACTURER & MODEL NO.
ROWS /FPI
EDB/EWB(°F)
LDB/LWB(°F)
UNIT
GROSSTOTAL
CAPACITY(MBH)
GROSSSENSIBLECAPACITY
(MBH)
STAGES ENT DB LVG DB KW STAGES V/P/HCOMPRESSORS CONDENSER FAN EVAPORATOR FAN
MCA MOCPQTY. RLA TOTAL QTY. FLA QTY. MOTOR
HP FLA
RTU-1 3,000 200 0.7 104°F 76.7/63.5 56.3/53.88 88.08 67.58 2 67.8 87.0 18 2 480/3/60 [email protected]@4.7 1 2 1 3.6 4.3 32.5 35 12.5 1,220.0 TRANE THC 102
RTU-2 5,400 1,700 0.7 104°F 84/65.80 52.5/50.7 248.77 198.75 NOTE 13 57.5 87.0 50 4 480/3/60 2 19.1 EA. 2 3.6 1 3.0 4.3 67.97 70 11.0 4,603.0 TRANE SEHLF20
RTU-3 1,200 0 0.5 104°F 75.0/63.0 56.71/54.0 33.49 26.88 1 - - - - 480/3/60 1 5.8 1 0.6 1 .33 3.2 11 1515.0
(SEER) 775.0 TRANE THC036
RTVAV-1 7,900 1,700 4.05 104°F 81.1/64.9 54.73/52.38 317.46 255.72 NOTE 13 - - - - 480/3/60 2 22.2 EA. 3 5.4 1 10 12.6 68.95 90 10.2 4,982.2 TRANE SAHLF30
RTVAV-2 13,800 3,275 4.126 104°F 81.5/65 53.03/55.76 567.3 475.2 NOTE 14 - - - - 480/3/60 3 19.1/20.2/32.6 6 10.8 1 20 24.7 116.55 125 11.0 7,458.5 TRANE SAHLF-50
RTVAV-3 11,500 3,300 3.915 104°F 84.1/65.8 50.54/52.9 542.15 430.02 NOTE 14 - - - - 480/3/60 3 19.1/20.2/32.6 6 10.8 1 15 20.5 112.35 125 11.0 7,458.5 TRANE SAHLF50
RTVAV-4 5,130 1,435 3.827 104°F 81.9/65.1 54.41/51.78 217.63 168.55 NOTE 13 - - - - 208/3/60 2 41.4 EA. 2 8.2 1 7.5 22.2 124.5 150 10.3 4,492.7 TRANE SAHLF20
NOTES:1. SINGLE POINT WIRING CONNECTION.2. PROVIDE 2" COTTON MEDIA FILTER APPROX MERV 8 EFFICIENCY.3. PROVIDE MINIMUM 14" HIGH SOLID BOTTOM PLENUM CURB WITH R-8
INSULATION ON SIDES, AND 1" - 2 LB INSULATION ON BOTTOM. CURB HEIGHTAS REQUIRED TO MATCH ROOF INSULATION SLOPE AND BE A MINIMUM OF 8INCHES ABOVE ROOF. COORDINATE WITH ROOFING CONTRACTOR BEFORESETTING CURB.
4. FACTORY MOUNTED DISCONNECT SWITCH.5. PHENOLIC COATING ON CONDENSER COIL.6. PROVIDE HAIL GUARDS.
7. PROVIDE TYPE 304 STAINLESS STEEL DRAIN PAN.8. FURNISH GFI RECEPTACLE AND STEP DOWN TRANSFORMER, FACTORY
INSTALLED.9. FURNISH THRU-BOTTOM UTILITY CONNECTION FOR ELECTRICAL POWER AND
CONTROLS10. PROVIDE THERMAL EXPANSION VALVE AND R-410A REFRIGERANT.11. ATTACH CURB TO STRUCTURE AND RTU TO CURB (WITH STAINLESS STEEL
HARDWARE) PER LOCAL WINDSTORM REQUIREMENTS IF APPLICABLE.12. PROVIDE NETWORK INTEGRATION MODULE COMPATIBLE WITH OWNER'S
FACILITY MANAGEMENT SYSTEM (SCHNEIDER ELECTRIC TAC).13. RTU-2, RTVAV-1, RTVAV-4: PROVIDE DIGITAL SCROLL FIRST STAGE
COMPRESSOR
14. RTVAV-2, RTVAV-3: PROVIDE VARIABLE SPEED SCROLL.15. RTU-2: PROVIDE VARIABLE FREQUENCY DRIVE AND SINGLE ZONE VARIABLE
AIR VOLUME OPERATION. PROVIDE C02 SENSOR MOUNTED IN SPACE ANDDEMAND CONTROLLED VENTILATION CONTROLS AND SEQUENCE.
16. RTU-2: PROVIDE HOT GAS REHEAT, HUMIDISTAT CONTROLS ANDDEHUMIDIFICATION SEQUENCE.
17. RTVAV-1,2,3,4: PROVIDE DIRECT DRIVE PLENUM FAN, VARIABLE FREQUENCYDRIVE AND VARIABLE AIR VOLUME OPERATION. PROVIDE C02 SENSORMOUNTED IN RETURN AIR DUCT AND DEMAND CONTROLLED VENTILATIONCONTROLS AND SEQUENCE. PROVIDE HUMIDITY SENSOR MOUNTED IN SPACE.
EXHAUST FAN SCHEDULE
DESIG. CFME.S.P.
(IN. WG) MOTOR POWER V/P/H FAN RPMMANUFACTURER
&MODEL NO.
WEIGHT(LBS.)
EF-1 770 0.35 1/4 120/1/60 1,099 COOK 120C13D 87
EF-2 630 0.35 1/6 120/1/60 937 COOK 120C10D 87
KEF-1 4,800 1.0 2.0 460/3/60 1,183 COOK 195VCR 222
KSF-1 3,840 0.75 1.5 460/3/60 677 COOK 150KSP-B 421
NOTES:
1. PROVIDE INTEGRAL BACKDRAFT DAMPER.2. PROVIDE THERMAL PROTECTION.3. PROVIDE INTERNAL DISCONNECT SWITCH, FACTORY MOUNTED.4. EF-1, EF-2: DIRECT DRIVE, PROVIDE WITH SPEED CONTROL5. MAINTAIN MANUFACTURER'S RECOMMENDED DISTANCES FOR MAINTENANCE.6. PROVIDE VIBRATION ISOLATION7. PROVIDE MINIMUM 14" HIGH ROOF CURB. ADJUST AS REQUIRED TO MAINTAIN 8" TO TOP OF CURB
FROM FINISHED ROOF. SECURE FAN TO CURB (WITH STAINLESS STEEL HARDWARE) AND CURB TOROOF PER WINDSTORM REQUIREMENTS. COORDINATE WITH STRUCTURE ENGINEER.
9. KEF-1: PROVIDE HINGED SUB BASE, VENTED EXTENSION, AND GREASE TROUGH10. KSF-1: PROVIDE FACTORY FABRICATED INTAKE EXTENSION WITH FILTERS, BIRD SCREEN AND
INLET DAMPER.11. BELT DRIVE FANS: PROVIDE AUTOMATIC BELT TENSIONER.
CONTROLEF-1: TIME SCHEDULE THROUGH BMS.
KEF-1/KSF-1: INTERLOCK WITH KITCHENHOOD CONTROL PANEL/SWITCH ONHOOD.
A. THESE NOTES APPLY TO ALL DRAWINGS.B. DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.C. INSULATE DUCT IN ACCORDANCE WITH SPECIFICATIONS.
1. LINE ALL DUCT/PLENUMS/CONCENTRIC DEVICES.D. PROVIDE SHEET METAL SHOP DRAWINGS FOR DUCTWORK
PRIOR TO FABRICATION OF DUCTWORK. REFER TOARCHITECTURAL AND STRUCTURAL DRAWINGS FORDIMENSIONS AND MECHANICAL CLEARANCES ANDLOCATIONS OF AIR DEVICES.
E. PROVIDE FLEXIBLE DUCT CONNECTION AT DUCTATTACHMENTS TO AHU'S AND EXHAUST FANS.
F. HVAC EQUIPMENT SUBMITTED OTHER THAN SCHEDULEDMANUFACTURER'S SHALL NOT EXCEED PHYSICALDIMENSIONS.
G. ALL PIPING AND DUCTWORK PENETRATIONS OF FIRE-RATEDBARRIERS SHALL BE PROTECTED WITH FIRE BLOCKINGMATERIAL PER SPECIFICATIONS.
H. INSTALL ALL EXPOSED CONTROL WIRING IN RIGID CONDUIT.CONTROL WIRING ABOVE CEILINGS MAY BE EXPOSED.PROVIDE CONDUIT/WIRING SUPPORTS.
HVAC GENERAL NOTES
VARIABLE AIR VOLUME
ACCESS DOOR
COLD WATER (MAKE-UP) PIPING
CHILLED WATER RETURN PIPING
MANUAL MULTI-LEAF VOLUME DAMPER
INDICATES SIDE FACING VIEWER)DUCT SIZE, (FIRST OR TOP NO.
DUCT RISE IN DIRECTION OF AIR FLOW
SLOPED DUCT DROP IN DIRECTION OF AIR FLOW
DUCT ACCESS PANEL
WITH LOCKING QUADRANT
THERMOSTAT (SUBSCRIPT IDENTIFIES ZONE)
FLEXIBLE DUCT CONNECTION
RECTANGULAR DUCT ELBOW WITHTURNING VANES
TEMPERATURE SENSOR (SUBSCRIPT IDENTIFIES ZONE)
AIR DEVICE DESIGNATION AND AIR FLOW (CFM)
VENTURI FLOW TUBE
AUTOMATIC AIR VENTWEATHERPROOF
OUTSIDE AIR
PRESSURE GAUGE WITH COCK
THERMOMETER WITH WELL
GAUGE COCK ONLY
THERMOMETER WELL ONLY
STRAINER WITH BLOW-OFF
ELBOW UP, ELBOW DOWN
TEE UP, TEE DOWN
CONCENTRIC REDUCER
ECCENTRIC REDUCER
PRESSURE-RELIEF VALVE
UNION
CHECK VALVE
CONTROL VALVE, THREE WAY
CONTROL VALVE, TWO WAY
BUTTERFLY VALVE
GATE VALVE
ISOLATION VALVE
DRAIN PIPING
AUTOMATIC AIR VENT
BY-PASS VALVE
FD FIRE/ SMOKE DAMPER
M MOTORIZED DAMPER
FDX
CHILLED WATER SUPPLY PIPING
CONDENSER WATER RETURN PIPING
CONDENSER WATER SUPPLY PIPING
CO2 CARBON DIOXIDE SENSOR
12/10 1210
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN, EXHAUST, OR O/A DUCT UP
RETURN, EXHAUST, OR O/A DUCT DOWN
FM AIRFLOW METER
FIRE DAMPER WITH FUSIBLE LINK - REFERTO SCHEDULE FOR DESCRIPTION
000DEWPOINT SENSOR (SUBSCRIPT IDENTIFIES ZONE)
AIR HANDLING UNIT
EXISTING ROOFTOP AIR HANDLING UNIT
EXISTING FAN COIL
EXHAUST FAN
EXISTING SUPPLY FAN
UPBLAST FRONT
EXISTING EXHAUST FAN
ROOFTOP AIR HANDLING UNIT
ELECTRIC DUCT HEATER
COUNTER CLOCKWISE
CLOCKWISE
CONSTANT VOLUME
AIR FOIL
FAN COIL / FAN COIL UNIT
INDOOR AIR QUALITY
LEFT HAND FAN ORIENTATION
RIGHT HAND FAN ORIENTATION
UPBLAST REAR
SUPPLY FAN
VARIABLE FREQUENCY DRIVEVFD
UNIT VENTILATOR
HOT WATER SUPPLY
HOT WATER RETURN
BALL VALVE
SYMBOLS AND ABBREVIATIONS
STAINLESS STEEL
NOTES:
1. ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS OBTAINED FROM TABLES IN ARI STANDARD 885.2. SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-98.3. SIZE UNITS ARE GIVEN IN INCHES, FLOW UNITS ARE CUBIC FEET PER MINUTE, PRESSURE UNITS ARE INCHES OF WATER, AND
TEMPERATURE UNITS ARE DEGREES FAHRENHEIT.
VARIABLE AIR VOLUME BOX SCHEDULE
PRICEMODEL
NUMBERDESIG. UNIT SIZE
FANFLOW(CFM)
MAX (PRIMARY
CFM)
MIN (PRIMARY
CFM)
INLET PRESSURE (IN.WG)
DOWNSTREAM SP (IN.WG)
MIN OPER PD (IN.WG)
MAXDISCHARGE NC
MAXRADIATED
NC
CAPACITYKW EAT °F MINIMUM LAT
°F VOLTS STEPS CURRENTAMPS
DESV VB-01-01 6 300 300 90 0.5 .25 .07 10 16 4 40 82.1 277/1 2 18.10
DESV VB-01-02 6 300 300 90 0.5 .25 .07 10 16 4 40 82.1 277/1 2 18.10
DESV VB-01-03 6 250 250 75 0.5 .25 .05 10 14 3.5 40 84.2 277/1 2 15.80
DESV VB-01-04 6 200 200 60 0.5 .25 .03 - 11 1 40 82.1 277/1 1 4.50
DESV VB-02-01 6 200 200 60 0.5 .25 .03 - 11 2.5 40 79.5 277/1 1 11.30
DESV VB-02-02 6 300 300 90 0.5 .25 .07 10 16 4 40 82.1 277/1 2 18.10
DESV VB-03-01 6 150 150 45 0.5 .25 .02 - - 2 32 74.1 277/1 1 9.00
DESV VB-03-02 6 130 130 40 0.5 .25 .01 - - 1.5 32 68.5 277/1 1 6.80
FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE
MODELNUMBER DESIG. UNIT
SIZE
FANFLOW(CFM)
MAX(PRIMARY
CFM)
MIN(PRIMARY
CFM)
INLETPRESSURE (IN.WG)
DOWNSTREAMSP
(IN.WG)
MIN OPER PD (IN.WG)
MAXDISCHARG
E NC
MAXRADIATED
NC
MOTORHP
CAPACITYKW EAT °F MINIMUM
LAT °F VOLTS STEPS CURRENTAMPS
DTFS-F FPB-01-01 12 1300 1300 390 0.7 0.25 0.06 24 27 0.33 12 61 90 480/3 2 21.8
DTFS-F FPB-01-02 12 1350 1350 405 0.7 0.25 0.06 25 27 0.33 13 61 91 480/3 2 23.3
DTFS-F FPB-01-03 12 1575 1575 475 0.7 0.25 0.09 28 29 0.33 15 61 91 480/3 2 26.3
DTFS-F FPB-01-04 12 1500 1500 450 0.7 0.25 0.08 27 28 0.33 14 61 90 480/3 2 24.8
DTFS-F FPB-01-05 12 1500 1500 450 0.7 0.25 0.08 27 28 0.33 14 61 90 480/3 2 24.8
DTFS-F FPB-02-01 12 1330 1330 400 0.7 0.25 0.06 24 27 0.33 13 61 91 480/3 2 23.3
DTFS-F FPB-02-02 10 850 850 260 0.7 0.25 0.1 21 25 0.25 8 60 90 277/1 2 37.9
DTQP FPB-02-03 10 870 870 260 0.7 0.25 0.16 16 34 0.25 7.5 60 89 277/1 2 36.6
DTFS-F FPB-02-04 10 1180 1180 350 0.7 0.25 0.19 22 25 0.33 11 61 90 480/3 2 20.3
DTFS-F FPB-02-05 10 1240 1240 370 0.7 0.25 0.2 23 25 0.33 11.5 61 90 480/3 2 21.0
DTFS-F FPB-02-06 10 900 900 270 0.7 0.25 0.11 23 25 0.25 8.5 61 90 480/3 2 14.5
DTQP FPB-02-07 10 650 650 195 0.7 0.25 0.32 17 31 0.25 4 61 92 277/1 1 21.2
DTFS-F FPB-02-8 12 1680 1680 500 0.7 0.25 0.1 30 29 0.33 16 61 91 480/3 2 27.8
DTFS-F FPB-02-09 12 1380 1380 415 0.7 0.25 0.31 17 35 0.25 13 61 90 480/3 2 21.0
DTFS-F FPB-02-10 10 1150 1150 345 0.7 0.25 0.18 21 24 0.33 11 61 91 480/3 2 20.3
DTFS-F FPB-02-11 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9 61 90 480/3 2 15.3
DTFS-F FPB-02-12 10 1150 1150 345 0.7 0.25 0.18 21 24 0.33 11 61 91 480/3 2 20.3
DTFS-F FPB-03-01 12 1400 1400 420 0.7 0.25 0.07 26 27 0.33 14 58 90 480/3 2 24.8
DTQP FPB-03-02 10 1200 1200 360 0.7 0.25 0.31 17 35 0.25 10.5 55 90 480/3 2 18.5
DTQP FPB-03-03 08 785 785 235 0.7 0.25 0.3 16 34 0.25 7.5 57 91 277/1 2 36.6
DTFS-F FPB-03-04 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9.5 58 90 480/3 2 16.0
DTFS-F FPB-03-05 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9.5 58 90 480/3 2 16.0
DTFS-F FPB-03-06 10 1150 1150 345 0.7 0.25 0.18 21 24 0.33 11.5 58 90 480/3 2 21.0
DTFS-F FPB-03-07 10 1000 1000 300 0.7 0.25 0.13 25 25 0.25 10 58 90 480/3 2 16.8
DTFS-F FPB-03-08 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9.5 58 90 480/3 2 16.0
DTFS-F FPB-03-09 10 1150 1150 345 0.7 0.25 0.18 21 24 0.33 11.5 58 90 480/3 2 21.0
DTFS-F FPB-03-10 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9.5 58 90 480/3 2 16.0
DTFS-F FPB-03-11 10 950 950 285 0.7 0.25 0.12 24 25 0.25 9.5 58 90 480/3 2 16.0
DTQP FPB-03-12 10 785 785 235 0.7 0.25 0.12 15 33 0.33 7.5 57 91 277/1 2 36.6
DTFS-F FPB-4-01 10 1060 1060 315 0.7 .25 0.14 19 24 .33 8 65.5 90 208-1 2 51.80
DTFS-F FPB-4-02 12 1240 1240 370 0.7 .25 0.05 23 25 .33 9.5 65.5 90.4 208-3 2 37.50
DTFS-F FPB-4-03 12 1480 1480 440 0.7 .25 0.07 26 28 .33 11.5 65.5 90.7 208-3 2 44.40
DTFS-F FPB-4-04 10 1080 1080 320 0.7 .25 0.15 19 24 .33 8.5 65.6 91.1 208-1 2 54.80
DTQP FPB-4-05 8 600 600 180 0.7 .25 0.16 22 35 .17 4.5 65.5 89.8 208-1 2 28.70
DTQP FPB-4-06 8 540 540 160 0.7 .25 0.13 21 34 .17 4.5 65.6 92.6 208-1 2 28.70
NOTES:
1. ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS OBTAINED FROM TABLES IN ARI STANDARD 885.2. SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-98.3. SIZE UNITS ARE GIVEN IN INCHES, FLOW UNITS ARE CUBIC FEET PER MINUTE, PRESSURE UNITS ARE INCHES OF WATER, AND
TEMPERATURE UNITS ARE DEGREES FAHRENHEIT.4. TERMINAL UNIT CONFIGURATION:
a. DTQP - PARALLEL FANa. DTFS - SERIES FANb. DTFS-F - SERIES FAN WITH INTEGRAL INLET FACTORY SOUND ATTENUATOR.
AIR DEVICE SCHEDULEDESIG. NECK SIZE TYPE SERVICE MOUNTING MANUFACTURER & REMARKS
10"Ø DIFFUSER SUPPLY LAY-INTITUS TMS 4-WAY FIXED DISCHARGE,STEEL CONSTRUCTION, 24" X 24"LAY-IN PANEL, WHITE FINISH
8"Ø DIFFUSER SUPPLY LAY-IN
TITUS TMS 4-WAY FIXED DISCHARGE,STEEL CONSTRUCTION, 24" X 24"LAY-IN PANEL, WHITE FINISH
6"Ø DIFFUSER SUPPLY LAY-IN
TITUS TMS 4-WAY FIXED DISCHARGE,STEEL CONSTRUCTION, 12" X 12"PANEL, WHITE FINISH
12"Ø DIFFUSER SUPPLY LAY-IN
TITUS TMS 4-WAY FIXED DISCHARGE,STEEL CONSTRUCTION, 24" X 24"LAY-IN PANEL, WHITE FINISH
8"Ø DIFFUSER SUPPLY LAY-IN
TITUS TMS, 4-WAY FIXED DISCHARGE,STEEL CONSTRUCTION, 12" X 12"PANEL, WHITE FINISH
18"x6" DIFFUSER SUPPLY SIDEWALL
TITUS 272 RS 3/4" AIRFOIL BLADESPACING, DOUBLE DEFLECTION,STEEL CONSTRUCTION, WHITE FINISH
22"x22" GRILLE SUPPLY LAY-IN
TITUS - PAR STEEL CONSTRUCTION,24" X 24" PANEL, WHITE FINISH
60"x8" DIFFUSER SUPPLY SURFACE
TITUS ML-38 LINEAR DIFFUSER, 5'-0'LONG, THREE 3/4" WIDE SLOTS,ADJUSTABLE PATTERNCONTROLLERS, PROVIDE PLENUM
14"Ø DIFFUSER SUPPLY LAY-IN
TITUS - PAR STEEL CONSTRUCTION,24" X 24" PANEL, WHITE FINISH
10"Ø DIFFUSER SUPPLY SURFACE
TITUS TDC, 4-WAY LOUVERDISCHARGE, STEEL CONSTRUCTION,15"X15" PANEL, WHITE FINISH.
8"X6" DIFFUSER SUPPLY SIDEWALL
TITUS 272 RS 3/4" AIRFOIL BLADESPACING, DOUBLE DEFLECTION,STEEL CONSTRUCTION, WHITE FINISH
24" x 12" GRILLE RETURN LAY-INTITUS 350 RL, 35° FIXED DEFLECTION,3/4" BLADE SPACING, STEELCONSTRUCTION, WHITE FINISH
24" x 24" GRILLE RETURN LAY-INTITUS 350 RL, 35° FIXED DEFLECTION,3/4" BLADE SPACING, STEELCONSTRUCTION, WHITE FINISH
18" x 10" GRILLE RETURN SIDEWALLTITUS 350 RL, 35° FIXED DEFLECTION,3/4" BLADE SPACING, STEELCONSTRUCTION, WHITE FINISH
12" x 12" GRILLE EXHAUST SURFACETITUS 350 RL, 35° FIXED DEFLECTION,3/4" BLADE SPACING, STEELCONSTRUCTION, WHITE FINISH
NOTES:
1. CONTRACTOR IS RESPONSIBLE TO PROVIDE THE AIR DEVICE FRAME AND MOUNTING SYSTEM TO MATCH THEARCHITECT CEILING TYPES. SEE ARCHITECTURAL DRAWINGS FOR COORDINATION.2. CONFIRM AIR DEVICE COLOR WITH ARCHITECT.ON ALL REGISTERS, PROVIDE CONCEALED FRAME MOUNTING. NO SCREWS SHALL BE IN FACE OF FRAME
A
B
C
D
E
F
G
H
I
J
K
R1
R2
R3
R4
Corpus Christi, TX 78405-3615342 S. Navigation Blvd.Fax (361) 883-9177(361) 883-9199
& ASSOCIATES INC.STRIDDE, CALLINS
MECHANICAL * ELECTRICAL
CONSULTING ENGINEERS
Registration # F-006328
KEYNOTES:
PRIMARY SUPPLY AIR DUCT. REFER TO FLOORPLAN FOR SIZE.
45° TAKE-OFF.
REFER TO MANUFACTURER'S INSTALLATIONINSTRUCTIONS FOR MINIMUM LENGTH ANDCONFIGURATION OF PRIMARY AIR SUPPLY TO VAVTERMINAL UNIT.
ACOUSTICAL FLEXIBLE DUCT, MAXIMUM LENGTHAPPROXIMATELY 18".
VAV TERMINAL UNIT PER SCHEDULE.
ELECTRIC HEATING COIL. EXTERNALLY INSULATEHEATER CASING.
RECTANGULAR FLEXIBLE CONNECTION.
SECONDARY SUPPLY AIR DUCT.
INDUCED AIR INLET.
SUSPEND TERMINAL FROM STRUCTURE ABOVEWITH GALVANIZED 5/16" ALL THREAD RODS,SPRING VIBRATION ISOLATORS AND GALVANIZEDUNISTRUT CHANNELS.
FILTER RACK WITH 1" FILTER.
PROVIDE ADAPTOR TO MATCH INLET DUCT SIZETO VAV TERMINAL CONNECTION SIZE.
TRANSITION TO TERMINAL UNIT DUCTCONNECTION SIZE.
PROVIDE HANGER BRACKETS INTEGRAL TO UNIT.
CONNECT WITH STAINLESS STEEL CLAMPINGBANDS. (TYPICAL)
MIN 36"CLEARANCE
MIN 30"CLEARANCE
VAV TERMINAL UNIT LEGEND
CFMDESIGNATION
200A
REFER TOFLOOR PLAN
NOTES
HEATERRACKACCESSDOOR
2
1
3
154
1512
5
119
8
13
76
14
10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DRAIN PANTOP OF UNIT
SLOPE
CONSTRUCT TRAP PERMANUFACTURER'SINSTRUCTION
TURN PIPING DOWN OVER DRAIN
AIR BREAK MINIMUM 1" ABOVETHE TOP OF UNIT DRAIN PAN
PACKAGED ROOF TOP UNIT
EXTEND ANDTERMINATE OVERROOF DRAIN.PROVIDE AIR GAP.
CONDENSATE ADJUSTABLE ROLLERPIPE SUPPORT, MIRO INDUSTRIESOR EQUAL. COORDINATE WITHROOFING CONTRACTOR.
ROOF DECK
MIN. 1" LARGERTHAN UNIT TOTALSTATIC PRESSURE
ROOF DRAIN BYPLUMBINGCONTRACTOR.
"ROLLER-BEARING" PIPE SUPPORT SHALL BEUSED TO SUPPORT CONDENSATE PIPES.PIPES SHALL REST ON A SELF-LUBRICATINGROLLER SYSTEM WHICH SHALL BE MADE OFA STAINLESS STEEL OR GLASS-FILLED NYLONROD AND A STURDY POLYCARBONATE RESINROLLER. THE PIPE STAND SHALL CONSIST OFTWO MAJOR COMPONENTS: (1) A ONE-PIECEPOLYCARBONATE BASE, PIPE SUPPORT, ANDADJUSTABLE ROLLER HOUSING, (2) A ROLLERMADE OF POLYCARBONATE RESIN AND ASTAINLESS STEEL OR GLASS-FILLED NYLONROD WHICH RESTS IN AN ADJUSTABLEHEIGHT ROLLER HOUSING. CARBON BLACKSHALL BE ADDED TO THE POLYCARBONATEFOR UV RESISTANCE AND PROTECTION. PIPESTAND SHALL ACCOMMODATE UP TO 4" PIPE(INSIDE DIAMETER) OR UP TO 5" OUTSIDEDIAMETER PIPES. PIPE STANDS SHALL BEMIRO 4-RAH-7P OR APPROVED EQUAL.
KEYNOTES:
GALVANIZED HANGER STRAP.
SECURE GALVANIZED STEELSTRAP TO STRUCTURE ABOVE.
GALVANIZED BOLT.
DOUBLE NUT.
1/8" THICK x 1 1/2" WIDEGALVANIZED STEEL STRAP.
EXTERNAL INSULATION WITHVAPOR BARRIER.
VAPOR SEAL AT LOCATIONHANGER STRAP PENETRATESTHE INSULATION.
1
2
3
4
5
6
7
5
6
7
2
4
2
7
6
5
3
1
FIRE RESISTANT RUBBERIMPREGNATED FABRIC.
1-1/2" POCKETSLIP
DUCT
20 U.S.GAUGESTEEL
3"-4" (10" MAX)
20 U.S.GAUGESTEEL
1" X 1/8"BAND IRON
SHEET METAL SCREWSON 4" CENTERS
EQUIPMENTOUTLET/INLET
2" RAD.
1" R
AD.
1/4" 3/4" TURNING VANES, TYP ALL ELLS
CLIP ANGLE
KEYNOTES:
TRUNK DUCTMANUAL OPPOSED BLADE DAMPER(RUSKIN MD35 WITH "VENTLOC"LOCKING DEVICE. LOCATE MINIMUMOF THREE EQUIVALENT DUCTDIAMETERS FROM TRUNK DUCT.BRANCH DUCT
6"
AIR FLOW
45°
1
2
3
MINIMUM3 DUCTDIAMETERS
1
2
3
INSULATE REAR OF DIFFUSER.REFER TO SPECIFICATIONS.
SUPPLY AIR DIFFUSER.
CEILING. REFER TO ARCHITECTURAL FORTYPE AND HEIGHT.
BORDER PER CEILING TYPE. REFER TO HVACSCHEDULES AND ARCHITECTURAL DIVISION.
INSULATE PER SPECS.
SUPPLY TRUNK DUCT. REFER HVAC PLANSFOR SIZE.
2" WIDE FLEXIBLE STRAP. SUPPORT FROMSTRUCTURE ABOVE.
KEYNOTES:
SEAL CONNECTION WITH DUCT JOINTSEALANT.
45° TAKE-OFF AND DAMPER COMBINATION.FLEXMASTER TYPE STOD-B03 ORAPPROVED EQUAL.
BUILD-OUT WITH LOCKING QUADRANT.SEAL INSULATION WITH CANVAS CLOTHMASTIC.
ROUND METAL DUCT.
STAINLESS STEEL SCREW CLAMP. (TYPICAL)
INSULATED FLEXIBLE DUCT. WITH RADIUS INACCORDANCE WITH MANUFACTURERSDIRECTIONS. (MAX. LENGTH 6'-0")
1
2
3
4
5
6
7
8
9
10
11
12
13
9
11
12
8 10
7
13
1 2 3 4 5 6
KEYNOTES:
FACTORY FABRICATED INSULATED ROOF CURB TO MATCH SLOPE AND CONSTRUCTION OF ROOF.
CENTRIFUGAL FAN.
REMOVABLE WEATHERPROOF HOUSING.
FAN MOTOR WITH VIBRATION ISOLATORS.
CONTINUOUS BIRD SCREEN.
ROOF DECK. REFER TO ARCHITECTURAL FOR CONSTRUCTION AND TYPE.
BACKDRAFT DAMPER.
DUCTWORK.
CANT STRIP, FLASHING AND COUNTER- FLASHING.
MOTOR WIRING CONNECTION.
ELECTRICAL DISCONNECT SWITCH.
CONDUIT.
FIELD WIRING COMPARTMENT WITH TWIST LOCK RECEPTACLE.
DECK ADAPTER.
SECURE FAN TO CURB WITH MINIMUM EIGHT (8) STAINLESS STEEL SCREWS.
SECURE CURB TO ROOF DECK STRUCTURE WITH BOLTS OR WELDS IN ACCORDANCE WITH LOCAL WINDSTORM CODE REQUIREMENTS.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
614
1713
8
1216
15
9
5
2
4
3
11
10
RETURN AIR SUPPLY AIR
KEYNOTES:
OUTSIDE AIR INTAKE HOOD WITH AIR FILTER.
FACTORY FABRICATED, SOLID BOTTOM, VIBRATIONISOLATION, SOUND ATTENUATING PLENUM ROOF CURB,VIBRO ACOUSTICS OR EQUAL, TO MATCH SLOPE ANDCONSTRUCTION OF ROOF.
CANT STRIP, FLASHING, AND COUNTER- FLASHING.
MINIMUM 1" COPPER CONDENSATE DRAIN LINE. TRAP WITHOPEN TEE AND ROUTE FULL SIZE TO NEAREST DRAIN LINESYSTEM.
SUPPLY AND RETURN DUCTWORK.
TRANSITION RISER TO UNIT DUCT CONNECTION SIZE.INTERNAL DUCT INSULATION PER SPECS.
FLEXIBLE CONNECTOR ON DUCTWORK AT CONNECTIONTO UNIT.
SMOKE DETECTOR FURNISHED AND WIRED BY DIVISION 16,INSTALLED BY DIVISION 15.
SECURE EQUIPMENT TO CURB AND CURB TO ROOFSTRUCTURE WITH BOLTS OR WELDS IN ACCORDANCEWITH LOCAL WINDSTORM CODE REQUIREMENTS.
CEILING
ROOFTOPUNIT
D
ROOF
) ) ) ) ) )
)))))))
1
2
3
4
5
6
7
8
9
24
97
8
5
6
1
3
S S
OPENING10" X 10"
NOTES:
KEYNOTES:
24 GA. G.I. SHEET METAL HOOD SOLDER ALL SEAMSWATERTIGHT.
WATER STOP ON PIPE.
SCREEN OPENING WITH 1/4" MESH HARDWARE CLOTH.
SEAL AROUND ALL SEAMS AND PIPE WITH SILICONECAULK.
REFRIGERANT PIPING, NUMBER TO MATCH EXISTING.
MOUNTING BASE WITH 1.5" RIGID INSULATION.
2" X 8" WOOD BLOCK.
4" CANT STRIP.
(2) LAYERS 1" THICK ELASTOMERIC INSULATION WITH(2) COATS ULTRAVIOLET RESISTANT PAINTPROTECTION.
SLOPE FOR DRAIN.
1" X 1" WATER BAR.
24 GA. G.I. FLASHING ALL AROUND OPENING.
BASE FLASHING UP AND OVER CURB.
WOOD BLOCKING.
ROOF. COORDINATE WITH ARCHITECTURAL.
1
2
3
4
5
6
2
1
3
4
5
6
7
8
15
9
10
11
12
13
14
7
8
10
11
12
13
14
15
9
1. PATE MODEL PHA OR EQUAL.2. COORDINATE ROOF FLASHING WITH ARCHITECT.3. COORDINATE PENETRATION WITH GENERAL CONTRACTOR
AND STRUCTURAL.