Step & Touch Voltage Calculation for Tunnel Ieee-80-2000
description
Transcript of Step & Touch Voltage Calculation for Tunnel Ieee-80-2000
Document number
CONTRACTOR : SAMSUNG C&T CLIENT QATARI DIAR
Revision NODate of Issue
1. INPUT DATA
SYSTEM VOLTAGE = 0.415 kV
SYSTEM GROUNDING = NEUTRAL
GRID CURRENT Ig = 44 kA
Duration of Shock Current ts = 1 Second
CALCULATION FOR MAXIMUM PERMISSIIBLE TOUCH AND STEP VOLTAGE
LUSAIL DEVELOPMENT PRIMARY INFRASTRUCTURE CP5B UTILITY TUNNEL ALONG ROAD A2
08-Jan-2013
Area of Substation Grid A = 24,363.72 Sq. Metre
Conductor Size for Main Grid d = 150 Sq. mm
Depth of Burial W.R.T Ground level h = 7.5 Metre
Length of burried Conductor L = 4,780.53 Metre( Periphery conductor + Grid conductors)Total Ground Rod Length Lr = 159 Metre
Soil Resistivity ρ = 101.53 Ohm -Metre
Resistity if Concrete ρs = 5,000.00 Ohm -Metre
Spacing for Earth Mat for Basement D = 15 Metre
Thickness of Basement Slab hs = 2.5 MetreThickness of Basement Slab hs = 2.5 Metre
Weighing Term Kii = 1
No of Conductors along the Length of Tunnel na = 206 Nos
No of Conductors along the width of Tunnel nb = 2 Nos
Calculation of Tolerable Etouch & E step voltage
The Maximum Allowable Toucgh Voltage From Eq .33 of IEEE 80-2000 for a person with 70 Kg body Weight]
Where Cs = Reduction factor for derating nominal value or surface layer resistivity
ts
sCsEtouch 157.05.11000
Where Cs = Reduction factor for derating nominal value or surface layer resistivityAs given in IEEE 80-2000 Eqn No 27
09.02
109.01
hs
sCs
Document number
CONTRACTOR : SAMSUNG C&T CLIENT QATARI DIAR
LUSAIL DEVELOPMENT PRIMARY INFRASTRUCTURE CP5B UTILITY TUNNEL ALONG ROAD A2
Substituting
Cs = 0.09 X(1- (101.53/ 5000))( 2 x 2.5 + 0.09)
Cs = 0.983
Substituting the above values
Tolerable E touch at basement = 0.157√1
= 1314.4825 volts
Tolerable E touch at basement = 1314.483 Volts
[1000+1.5x 0.983x 5000 ] x
1-
Tolerable E touch at basement = 1314.483 Volts
Tolerable E stepFrom Eq 30 of IEEE 80-2000, Step voltage for a person with a body weight of 70 Kg is given by
Substituting the derived Values
Tolerable E step=
√ 1
Tolerable E step at Basement 4786.93 Volts
[1000+6x 0.983x 5000 ] x 0.157 ]
ts
IskhsCsEStep 157.0)(61000
Document number
CONTRACTOR : SAMSUNG C&T CLIENT QATARI DIAR
LUSAIL DEVELOPMENT PRIMARY INFRASTRUCTURE CP5B UTILITY TUNNEL ALONG ROAD A2
3. Calculation of Grounding Resistance/Grid ResistnaceAs per Eq 40 of IEEE 80-86 for Grid Depths between 0.25 M & 2.5 M
ρ is the soil resistivityLt is is the total length of the buried conductorA is the total area occupied by the earthing grid
CALCULATION OF MAXIMUM ATTAINABLE TOUCH AND STEP VOLTAGE
(Refer Definitions for Detail)
AhALtRg
201
112011
Substituting the ValuesRg = 0.306 Ohms
4. Calculation of Maximum Ground Potential Rise
Maximum ground potential above remote earth GPR = Ig x Rg Volts
Where Ig = Grid Current
therefore Ig = 44 kA
substituting the Values Ground potential Rise GPR = 13469.49 Volts
Now the GPR is Greater than the tolerable touch voltage
5. Calculation of E Mesh VoltageAs per the IEEE 80-2000 Eqn no 80
(Refer Definitions for Detail)
IgKiKm
whereKm, the spacing factor of Mesh VoltageAs per the IEEE 80-2000 Eqn no 80
Where D is the spacing between the parellal Grid Conductorsh is the depth of the buried conductors
Kh is the weighting factor of depth of burial.
Kh = 2.915475947
No of Parellal Paths(n) = na x nb x nc x nd
LrLeIgKiKmEmesh
15.1
hKh 1(
12
8ln48
)2(16
ln21 22
nKhKii
dh
dDhD
dhDKm
Where p
c
LLna 2
A
Ln pb
42
Document number
CONTRACTOR : SAMSUNG C&T CLIENT QATARI DIAR
LUSAIL DEVELOPMENT PRIMARY INFRASTRUCTURE CP5B UTILITY TUNNEL ALONG ROAD A2
Lc is total length of horrizontal Grid conductors in Mtr = 5247+270+1283 Mtr(Incudes Tunnel Main Grid + Horrizontal connections) = 6800 Mtr
Lp is the length of Grid conductors on the perimeter in Mtr = 5103 Mtrsubstituting the Values
na = 2.67nb = 0.32
nc=nd=1 ( see Note Below)n = 2.67 x 0.32 x 1 x 1 n = 0.86
The irregularity factor Ki( Eqn 89 IEEE80-2000) = 0.644+(0.148 x n)== 0.771644184
Note : Considering the tunnel as Rectangular shape neglecting the Access Chambers, Susbtation & Ventillation Chamber. However the conductors within these structures are considered.
0.644+ ( 0.148 x 0.86)
The average spacing between the Grid conductors D
Wg & Lg is the width and length of the grid conductorsnr & nc are the no of rows and columns respectively
nc = 82nr = 2
Substituting these values D = 132.5
So Assigning the Values in the Equation for Km Km = 0.447
The effective Burried Length Lm =
Lm = 11461.727
Substituting the above values in the equation, the maximum attainable
1121
c
g
r
g
nL
nWD
RLLyLx
LrLcLm
2222.155.1
5. Calculation of attainable E Step
The Geometric spacing factor Ks is given by
Since the Maximum Attained voltage is less than the permissible voltage Calculated the system is considered SAFE
Substituting the above values in the equation, the maximum attainable Touch Voltage is
= 134.44 volts
LrLcIgkiksEstep
15.1
25.0111
211 n
DhDhKs
Document number
CONTRACTOR : SAMSUNG C&T CLIENT QATARI DIAR
LUSAIL DEVELOPMENT PRIMARY INFRASTRUCTURE CP5B UTILITY TUNNEL ALONG ROAD A2
Substituting the values on the above equation, Ks = 0.026
The Effective burried Length Ls = 0.75Lc+0.85Lr
= 5259 Meter
Finally the maximum allowable Step voltage Es is = 17.043 Volt
Since the Maximum Attained voltage is less than the permissible voltage Calculated the system is considered SAFE