225 847 400 StecaGrid 10000 3ph, StecaGrid 8000 3ph similar StecaGrid 8000 3ph and StecaGrid 10000 3ph Always symmetrical The advantage of three-phase feeding is that the produced solar capacity is always symmetrically distributed on all three power con- ductors to the public power grid. This is the case across the whole output range offered by these inverters. When designing a sys- tem, the laborious avoidance of an asymmetry of more than 4.6 kW through the appropriate selection of separate inverters is thus dispensed with. Symmetrical feeding is greatly in the interests of energy supply companies. Lengthy discussions with such companies are therefore a thing of the past. Long service live While the voltage passes through zero on the grid-feeding phase, single-phase inverters must temporarily accommodate all energy supplied by the solar modules within the device. This is usually reali- sed by electrolytic capacitors. These components influence the ser- vice life of an electronic device, due to the possibility of drying out. With three-phase inverters, energy is fed into the grid on at least two phases at all times. Thus, the necessity of intermediate storage of energy in the device is greatly reduced, which is of benefit to the system operator with regard to a longer service life. Flexible connection Due to the wide input voltage range of 350 V to 845 V, and a maxi- mum input current of 27 A / 32 A, all commonly available crystalline solar modules can be connected to the inverters in various configu- rations. Beyond this, the system is also approved for use with CdTe and CIS / CIGS thin-film modules. Five plug/socket pairs are available for flexible, mechanical DC connection. Easy handling Despite their high output, the inverters are wall-mounted devices. Thanks to the high degree of protection, those inverters can be in- stalled indoors or outdoors.Due to the integrated DC circuit breaker, installation work is made easier, and the installation time is reduced. It is not necessary to open the inverter during installation. Flexible system design The combination of the StecaGrid 8000 3ph and the StecaGrid 10 000 3ph allows optimum design for almost any power class. A diverse range of combinations are possible but they all share the same goal: the effective use of solar irradiation. Product features High efficiency Wide input voltage range Three-phase, symmetrical grid feeding Low DC discharge currents due to special switching concept Integrated DC circuit breaker Robust metal casing Suitable for outdoor installation Wall-mounting with steel wall bracket for very easy installation Displays Multi-coloured LED shows operating states Options System monitoring with Solar-Log™and WEB’log Can be connected to the StecaGrid Vision display unit or a large-format display StecaGrid 8 000 3ph StecaGrid 10 000 3ph STECAGRID 8000+ 3PH / 10000+ 3PH / 8000 3PH / 10000 3PH

description

CHARGE CONTROLLER

Transcript of StecaGrid 8000 3ph 10000 3ph Specification 2012

Page 1: StecaGrid 8000 3ph 10000 3ph Specification 2012

225

847

400

StecaGrid 10000 3ph, StecaGrid 8000 3ph similar

StecaGrid 8000 3ph and StecaGrid 10000 3ph Always symmetricalThe advantage of three-phase feeding is that the produced solar capacity is always symmetrically distributed on all three power con-ductors to the public power grid. This is the case across the whole output range offered by these inverters. When designing a sys-tem, the laborious avoidance of an asymmetry of more than 4.6 kW through the appropriate selection of separate inverters is thus dispensed with. Symmetrical feeding is greatly in the interests of energy supply companies. Lengthy discussions with such companies are therefore a thing of the past.

Long service liveWhile the voltage passes through zero on the grid-feeding phase, single-phase inverters must temporarily accommodate all energy supplied by the solar modules within the device. This is usually reali-sed by electrolytic capacitors. These components influence the ser-vice life of an electronic device, due to the possibility of drying out.With three-phase inverters, energy is fed into the grid on at least two phases at all times. Thus, the necessity of intermediate storage of energy in the device is greatly reduced, which is of benefit to the system operator with regard to a longer service life.

Flexible connectionDue to the wide input voltage range of 350 V to 845 V, and a maxi-mum input current of 27 A / 32 A, all commonly available crystalline solar modules can be connected to the inverters in various configu-rations. Beyond this, the system is also approved for use with CdTe and CIS / CIGS thin-film modules. Five plug/socket pairs are available for flexible, mechanical DC connection.

Easy handlingDespite their high output, the inverters are wall-mounted devices. Thanks to the high degree of protection, those inverters can be in-stalled indoors or outdoors.Due to the integrated DC circuit breaker, installation work is made easier, and the installation time is reduced. It is not necessary to open the inverter during installation.

Flexible system designThe combination of the StecaGrid 8000 3ph and the Steca Grid 10 000 3ph allows optimum design for almost any power class. A diverse range of combinations are possible but they all share the same goal: the effective use of solar irradiation.

Product features ∙ High efficiency ∙ Wide input voltage range ∙ Three-phase, symmetrical grid feeding ∙ Low DC discharge currents due to special switching concept ∙ Integrated DC circuit breaker ∙ Robust metal casing ∙ Suitable for outdoor installation ∙ Wall-mounting with steel wall bracket for very easy installation

Displays ∙ Multi-coloured LED shows operating states

Options ∙ System monitoring with Solar-Log™and WEB’log ∙ Can be connected to the StecaGrid Vision display unit or a large-format display

StecaGrid 8000 3ph StecaGrid 10000 3ph

STECAGRID 8000+ 3PH / 10000+ 3PH / 8000 3PH / 10000 3PH

Page 2: StecaGrid 8000 3ph 10000 3ph Specification 2012

Meteocontrol WEB’log and Meteocontrol WEB’log ComfortData logger

StecaGrid VisionDisplay unit

Solar-Log 500/1000TM

Data loggerStecaGrid UserVisualisation software

www.steca.com

System monitoring and accessories

8000 3ph 10 000 3ph

DC input side (PV-generator)

Maximum start voltage 845 V

Maximum input voltage 845 V

Minimum input voltage 350 V

Minimum input voltage for rated output

350 V

MPP voltage 350 V … 700 V

Maximum input current 27 A 32 A

Maximum input power at maxi-mum active output power

9,250 W 10,800 W

Maximum recommended PV power 10,500 Wp 12,500 Wp

AC output side (Grid connection)

Grid voltage 320 V … 480 V(depending on regional settings)

Rated grid voltage 400 V

Maximum output current 15 A

Maximum active power (cos phi = 1)

8,800 W 10,300 W 1)

Rated power 8,000 W 9,500 W

Rated frequency 50 Hz

Frequency 47.5 Hz ... 52 Hz (depending on regional settings)

Night-time power loss < 1.6 W

Feeding phases three-phase

Distortion factor (cos phi = 1) < 3 % (max. power)

Power factor cos phi 1

Characterisation of the operating performance

Maximum efficiency 96.3 %

European efficiency 95.2 % 95.4 %

MPP efficiency > 99 %

Power derating at full power from 50 °C (Tamb)

Standby power 9 W

8000 3ph 10 000 3ph

Safety

Isolation principle no galvanic isolation, transformerless

Grid monitoring yes, integrated

Residual current monitoring yes, integrated 2)

Operating conditions

Area of application indoor rooms with or without air conditioning, outdoors with protection

Ambient temperature -20 °C … +60 °C

Relative humidity 0 % … 95 %

Noise emission < 60 dBA

Fitting and construction

Degree of protection IP 54

Overvoltage category III (AC), II (DC)

DC Input side connection Multicontact MC4 (5 pairs),Nennstrom 22 A je Eingang

AC output side connection Wieland RST25i5 plug, mating connector included

Dimensions (X x Y x Z) 400 x 847 x 225 mm

Weight 42 kg

Communication interface RS485 plug-in card (included in delivery); 2 x RJ45 sockets; connectable to StecaGrid Vision,

Meteocontrol WEB‘log or Solar-Log

Integrated DC circuit breaker yes, compliant with VDE 0100-712

Cooling principle temperature-controlled fan, variable speed

Test certificate certificate of compliance as per DIN VDE 0126-1-1, CE mark, DK5940, G83, AS4777

1) Belgium and Australia: 10,000 W2) The design of the inverter prevents it from causing DC leakage current

STECAGRID 8000+ 3PH / 10000+ 3PH / 8000 3PH / 10000 3PH