Status of PCC Panel & 11KV Switchgear

3
Sl. No. Panel Description Checks & Tests Remarks A PCC Panel has been checked with temporary Three Phase 415V supply and with 230V control supply for following checks and Observed as below: 1 PCC Panel: Trafo Incomer Manual & Electrical Spring Charging- OK Manual Breaker Closing-OK Manual Breaker Off-OK Electrical Closing -OK Electrical Switch Off-OK On & Off indication -OK 2 PCC Panel: GG1 Incomer(I/C- 1) Manual & Electrical Spring Charging- OK Manual Breaker Closing-OK Manual Breaker Off-OK Electrical Closing -OK Electrical Switch Off-OK On & Off indication -OK 3 PCC Panel: GG2 Incomer(I/C- 2) Manual & Electrical Spring Charging- Could not be done Manual Breaker Closing-Could not be done Manual Breaker Off-Could not be done Electrical Closing could not be checked Electrical Switch Off-N/A Only Off indication -OK 4 PCC Panel: EMDG Incomer Manual & Electrical Spring Charging- Could not be done Manual Breaker Closing-Could not be done Manual Breaker Off-Could not be done Electrical Closing could not be checked Electrical Switch Off-N/A Only Off indication -OK 5 PCC-Bus Coupler Manual & Electrical Spring Charging- OK Manual Breaker Closing-OK Manual Breaker Off-OK Electrical Closing -OK Electrical Switch Off-OK On & Off indication -OK PCC & HT Switchgear Status Needs Refurbishment & rectification and circuits for synchronisation to be made ready Circuits for synchronisation to be made ready Circuits for synchronisation to be made ready Needs Refurbishment & rectification and circuits for synchronisation to be made ready

description

vcvc

Transcript of Status of PCC Panel & 11KV Switchgear

Sl. No. Panel Description Checks & Tests Remarks

A

PCC Panel has been checked with temporary Three Phase 415V supply and with 230V control supply for following checks and Observed as below:

1 PCC Panel: Trafo Incomer Manual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

2 PCC Panel: GG1 Incomer(I/C-1) Manual & Electrical Spring Charging- OK

Manual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

3 PCC Panel: GG2 Incomer(I/C-2)

Manual & Electrical Spring Charging- Could not be doneManual Breaker Closing-Could not be doneManual Breaker Off-Could not be doneElectrical Closing could not be checkedElectrical Switch Off-N/AOnly Off indication -OK

4 PCC Panel: EMDG Incomer Manual & Electrical Spring Charging- Could not be doneManual Breaker Closing-Could not be doneManual Breaker Off-Could not be doneElectrical Closing could not be checkedElectrical Switch Off-N/AOnly Off indication -OK

5 PCC-Bus Coupler Manual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

PCC & HT Switchgear Status

Needs Refurbishment & rectification and

circuits for synchronisation to

be made ready

Circuits for synchronisation to

be made ready

Circuits for synchronisation to

be made ready

Needs Refurbishment & rectification and

circuits for synchronisation to

be made ready

6 PCC Panel: Outgoing to MCC-E Manual & Electrical Spring Charging- Could not be doneManual Breaker Closing-Could not be doneManual Breaker Off-Could not be doneElectrical Closing could not be checkedElectrical Switch Off-N/AOnly Off indication -OK

7 PCC Panel: Outgoing (Spare)Manual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

8 PCC Panel: Outgoing to MCC-1Manual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

9 PCC Panel: Outgoing to MCC-2Manual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

10 PCC-Capacitor Bank OutgoingManual & Electrical Spring Charging- OKManual Breaker Closing-OKManual Breaker Off-OKElectrical Closing -OKElectrical Switch Off-OKOn & Off indication -OK

11 PCC-Incoming Capacitor BankAll Panels of Capacitor Bank circuit-OKCapacitor conditions could not be checked on No Load

12 PCC Main Bus Bar Cleaned, Tightened and accepting Three Phase Power and reaching every panel

Needs Refurbishment &

rectfication

13 PCC Control & Auxiliary Bus Bar

Cleaned, Tightened and accepting control supply & Space Heater supply

B11KV Switchgear Panel Checked with control supply and observed :

Breaker spring charging-OKBreaker Electical closing & switch off operations- OKTrip circuit checked and found OK. However, tripping not OK at Oil Temperature Trip command.