Public Input No. 1-NFP A 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL and replace with UL. (3) API # and replace with API SPEC, STD, or RP #. Statement of Problem and Substantiation for Public Input Related Public Inputs for This Document Related Input Relationship Submitter Information Verification Submitter Full Name: Organization: Street Address: City: State: Zip: Submittal Date: Committee Statement Resolution: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 79 1/27/2016 2:09 PM

Transcript of Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with...

Page 1: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 1-NFPA 59-2015 [ Global Input ]

Throughout standard remove references to the following and replace with thefollowing:

(1) ANSI/API and replace with API.

(2) ANSI/UL and replace with UL.

(3) API # and replace with API SPEC, STD, or RP #.

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 79 1/27/2016 2:09 PM

Page 2: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 5-NFPA 59-2015 [ Section No. 1.1.2 ]

1.1.2

Liquefied Petroleum Gas Code

Additional Proposed Changes

File Name Description Approved

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 79 1/27/2016 2:09 PM

Page 3: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 2-NFPA 59-2015 [ Section No. 2.3 ]

SPEC Specifications for Fire Tests for Valves, 3rd edition, 1999, Reaffirmed 2011

STD Fire Test for Quarter-Turn Valves and ValvesEquipped with Nonmetallic Seats, 6th Edition, 2010

STD Design and Construction of Large, Welded, Low-Pressure Storage Tanks,2013, Amendment 1, 2014

10 Minimum Design Loads for Buildings and Other Structures,10th edition, 2010, Errata, 2011, and Revised Commentary 2013

ASME International Two

Boiler and Pressure Vessel Code, 2015

Process Piping, 2014

/A47M Standard Specification for Ferritic Malleable Iron Castings, 1999,Reapproved 2014

/A395M Specification for Ferritic Ductile Iron Pressure-Retaining Castings for Use atElevated Temperatures, 1999, Reapproved 2014

Specifications for Ductile Iron Castings, 1984, Reapproved 2014

Standard on Safety Relief Valves for Anhydrous Ammonia and LP-Gas Revised2010

Publishing

Merriam-Webster’s Collegiate Dictionary

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 79 1/27/2016 2:09 PM

Page 4: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 79 1/27/2016 2:09 PM

Page 5: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 10-NFPA 59-2015 [ New Section after 2.3.1 ]

2.3.1 ACI Publications. American Concrete Institute, P.O. Box 9094, Farmington Hills, MI48333.

Code requirements for Design and Construction of Concrete Structures for the Containment ofRefrigerated Gases

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 79 1/27/2016 2:09 PM

Page 6: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 11-NFPA 59-2015 [ Section No. 2.3.1 ]

Specifications for Fire Tests for Valves,

Fire Test for Soft-Seated Quarter-Turn Valves, Sixth Edition, September 2010

Design and Construction of Large, Welded, Low-Pressure Storage Tanks,Twelth Edition October 2013 with Addendum 1

November 2014 .

API 625, Tank Systems for Refrigerated Liquefied Gas Storage, First Edition, 2010, with addendum 1, July 1,2013

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 79 1/27/2016 2:09 PM

Page 7: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 12-NFPA 59-2015 [ Section No. 2.3.2 ]

Minimum Design Loads for Buildings and Other Structures,

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 79 1/27/2016 2:09 PM

Page 8: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 13-NFPA 59-2015 [ Section No. 2.3.3 ]

Boiler and Pressure Vessel Code,

Process Piping,

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 79 1/27/2016 2:09 PM

Page 9: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 14-NFPA 59-2015 [ Section No. 2.3.4 ]

Standard Specification for Ferritic Malleable Iron Castings,

Specification for Ferritic Ductile Iron Pressure-Retaining Castings for Use at ElevatedTemperatures,

Specifications for Ductile Iron Castings,

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 79 1/27/2016 2:09 PM

Page 10: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 15-NFPA 59-2015 [ Section No. 2.3.5 ]

Standard on Safety Relief Valves for Anhydrous Ammonia and LP-Gas

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 79 1/27/2016 2:09 PM

Page 11: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 9-NFPA 59-2015 [ Section No. 2.3.5 ]

Standard on Safety Relief Valves for Anhydrous Ammonia and LP-Gas

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 79 1/27/2016 2:09 PM

Page 12: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 19-NFPA 59-2015 [ New Section after 3.3.8 ]

3.XXX Component

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 79 1/27/2016 2:09 PM

Page 13: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 20-NFPA 59-2015 [ New Section after 3.3.11.2 ]

3.3.XXX Facility

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 79 1/27/2016 2:09 PM

Page 14: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 18-NFPA 59-2015 [ New Section after 3.3.25 ]

3.3.XX Plant

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 79 1/27/2016 2:09 PM

Page 15: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 16-NFPA 59-2015 [ New Section after 3.3.28 ]

3.3 Process Pressure Vessel

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 79 1/27/2016 2:09 PM

Page 16: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 17-NFPA 59-2015 [ New Section after 3.3.30 ]

3.3.30 Refrigerated Storage Tank System.

3.3.30 Refrigerated Storage Tank System. Low pressure (less than 15 psi) equipment designed for the purposeof storing refrigerated LPG consisting of one or more containers, together with various accessories, appurtenances, andinsulation

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 79 1/27/2016 2:09 PM

Page 17: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 59-NFPA 59-2015 [ Section No. 3.3.36 ]

3.3.36*

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 79 1/27/2016 2:09 PM

Page 18: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 57-NFPA 59-2015 [ Section No. 4.5.2.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 79 1/27/2016 2:09 PM

Page 19: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 79 1/27/2016 2:09 PM

Page 20: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

NFPA 70 National Electrical Code

Part Location Extent of Classified Area a

Equipment Shallbe Approved for

NationalElectrical Code,

Class I a , Group

D b

(see FigureA.4.5.2.2)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 79 1/27/2016 2:09 PM

Page 21: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

(seeFigure A.4.5.2.2)

(see Figure A.4.5.2.2)

NFPA 70 National Electrical Code

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 79 1/27/2016 2:09 PM

Page 22: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 79 1/27/2016 2:09 PM

Page 23: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 21-NFPA 59-2015 [ Section No. 4.8.2 [Excluding any Sub-Sections] ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 79 1/27/2016 2:09 PM

Page 24: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 22-NFPA 59-2015 [ Section No. 4.8.2.2 ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 79 1/27/2016 2:09 PM

Page 25: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 6-NFPA 59-2015 [ New Section after 4.8.2.3 ]

4.9 Corrosion Protection

4.9.1

4.9.2

4.9.3

4.9.4

4.9.4.1

4.9.4.2

4.9.5

4.9.6

4.9.6.1

4.9.6.2

4.9.6.3

Additional Proposed Changes

File Name Description Approved

Statement of Problem and Substantiation for Public Input

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 79 1/27/2016 2:09 PM

Page 26: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 79 1/27/2016 2:09 PM

Page 27: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 23-NFPA 59-2015 [ Section No. 5.6.1 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 79 1/27/2016 2:09 PM

Page 28: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 61-NFPA 59-2015 [ Section No. 5.6.1 ]

5.6.1

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 79 1/27/2016 2:09 PM

Page 29: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 60-NFPA 59-2015 [ Section No. 5.8.1 ]

5.8.1

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 79 1/27/2016 2:09 PM

Page 30: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 58-NFPA 59-2015 [ Chapter 6 ]

58:

58:

Boiler and Pressure Vessel Code58:

Boiler and Pressure Vessel Code

Design and Construction of Large, Welded, Low-Pressure Storage Tanks,

58:

Design and Construction of Large, Welded, Low-Pressure Storage Tanks,58:

Design andConstruction of Large, Welded, Low-Pressure Storage Tanks,

58:

58:

58:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 79 1/27/2016 2:09 PM

Page 31: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Design and Construction of Large, Welded, Low-Pressure StorageTanks

58:

58:

58:

58:

Design and Construction of Large, Welded,Low-Pressure Storage Tanks, 58:

58:

58:

Minimum Design Loads for Buildingsand Other Structures 58:

58:

58:

Minimum Design Loads for Buildings and Other Structures 58:

58:

58:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 79 1/27/2016 2:09 PM

Page 32: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Process Piping 58:

58:

58:

58:

58:

58:

58:

58:

58:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 79 1/27/2016 2:09 PM

Page 33: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 79 1/27/2016 2:09 PM

Page 34: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

58:

58:

58:

58:

Design and Construction of Large, Welded, Low-Pressure Storage Tanks

58:

58:

58:

58:

58:

58:

58:

58:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 79 1/27/2016 2:09 PM

Page 35: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

58:

[Please see SUGGESTED Reorganization and re write of NFPA 59 Chapter 6 fromAmerican Gas Association, Supplemental Gas Committee, Attached]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 79 1/27/2016 2:09 PM

Page 36: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

58:

Water Capacity per Container Aboveground Containers

gal m 3 ft m

≤ ≤

58:

6.

58:

Water Capacity per Container Aboveground Containers

gal m 3 ft m

≤ ≤

58:

58:

58:

58:

58:

58:

Additional Proposed Changes

File Name Description Approved

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 79 1/27/2016 2:09 PM

Page 37: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 79 1/27/2016 2:09 PM

Page 38: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 24-NFPA 59-2015 [ Section No. 6.5.8.3 ]

58:

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 79 1/27/2016 2:09 PM

Page 39: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 25-NFPA 59-2015 [ Chapter 7 [Title Only] ]

Piping, Valves, Process Pressure Vessels and Equipment

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 79 1/27/2016 2:09 PM

Page 40: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 28-NFPA 59-2015 [ New Section after 7.1.1.4 ]

7.1.1.5 Buried flammable liquid or gas piping shall be installed with a minimum of 30 inches of cover in normal soiland a minimum of 18 inches in consolidated rock.

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 79 1/27/2016 2:09 PM

Page 41: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 29-NFPA 59-2015 [ New Section after 7.1.1.4 ]

7.1.1.6 Buried flammable liquid or gas piping shall be installed with a minimum of 12 inches clearance between thepipe and any other structure not associated with the pipe to allow for proper maintenance

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 79 1/27/2016 2:09 PM

Page 42: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 30-NFPA 59-2015 [ Section No. 7.1.11 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 79 1/27/2016 2:09 PM

Page 43: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 27-NFPA 59-2015 [ Section No. 7.2.5 ]

Fire Test for Soft-Seated Quarter-Turn Valves Specifications for Fire Tests forValves

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 79 1/27/2016 2:09 PM

Page 44: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 31-NFPA 59-2015 [ Section No. 7.2.6 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 79 1/27/2016 2:09 PM

Page 45: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 32-NFPA 59-2015 [ Section No. 7.2.8 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 79 1/27/2016 2:09 PM

Page 46: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 33-NFPA 59-2015 [ Section No. 7.4.1 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 79 1/27/2016 2:09 PM

Page 47: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 34-NFPA 59-2015 [ Section No. 7.4.3 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 79 1/27/2016 2:09 PM

Page 48: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 35-NFPA 59-2015 [ Section No. 7.8.1 ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 79 1/27/2016 2:09 PM

Page 49: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 26-NFPA 59-2015 [ New Section after 7.8.5 ]

7.9 * Process pressure vessels shall be designed and fabricated in accordance with the ASME Boiler and PressureVessel Code, Section VIII, Division 1, or Division 2, or with the CSA B51, Boiler Pressure Vessel and Piping Code, andshall be code-stamped

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 79 1/27/2016 2:09 PM

Page 50: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 36-NFPA 59-2015 [ Section No. 7.10.4.3 ]

Exception: Such anchorage shall not be required for the tank car side.

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 79 1/27/2016 2:09 PM

Page 51: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 37-NFPA 59-2015 [ Section No. 7.10.4.4 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 79 1/27/2016 2:09 PM

Page 52: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 38-NFPA 59-2015 [ Section No. 9.4.3 [Excluding any Sub-Sections] ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 79 1/27/2016 2:09 PM

Page 53: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 39-NFPA 59-2015 [ Section No. 9.5.1.3 ]

101 Life Safety Code NationalFuel Gas Code

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 79 1/27/2016 2:09 PM

Page 54: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 62-NFPA 59-2015 [ Section No. 9.5.2.4 ]

9.5.2.4*

Exposure

Minimum Distance RequiredBetween Vaporizer and

Exposure

ft m

(see Section 9.5)

Additional Proposed Changes

File Name Description Approved

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 79 1/27/2016 2:09 PM

Page 55: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 63-NFPA 59-2015 [ Section No. 10.1.4 ]

10.1.4

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 79 1/27/2016 2:09 PM

Page 56: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 40-NFPA 59-2015 [ Section No. 11.2.1 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 79 1/27/2016 2:09 PM

Page 57: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 41-NFPA 59-2015 [ Section No. 12.3.6.1 ]

1⁄2

1⁄2

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 79 1/27/2016 2:09 PM

Page 58: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 79 1/27/2016 2:09 PM

Page 59: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 42-NFPA 59-2015 [ Section No. 12.3.8.1 ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 79 1/27/2016 2:09 PM

Page 60: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 43-NFPA 59-2015 [ New Section after 12.7 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 79 1/27/2016 2:09 PM

Page 61: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 48-NFPA 59-2015 [ Section No. 13.1.1 [Excluding any Sub-Sections] ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 79 1/27/2016 2:09 PM

Page 62: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 44-NFPA 59-2015 [ New Section after 13.1.1.3 ]

13.1.1.3

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 79 1/27/2016 2:09 PM

Page 63: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 45-NFPA 59-2015 [ Section No. 13.2 ]

13.2

NFPA 72 NationalFire Alarm and Signaling Code

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 79 1/27/2016 2:09 PM

Page 64: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 79 1/27/2016 2:09 PM

Page 65: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 46-NFPA 59-2015 [ New Section after 13.2.3 ]

13.2.2.1 *Where utilized, leak detection should be used to compliment fire and gas detection and is not intendedto replace fire and gas detection

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 79 1/27/2016 2:09 PM

Page 66: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 49-NFPA 59-2015 [ Section No. 13.4.4 ]

Standard for the Installation of Sprinkler Systems

Standard for the Installation of Standpipe and Hose Systems

Standard for Water Spray Fixed Systems for Fire Protection

Standard for the Installation of Stationary Pumps for Fire Protection

Standard for Water Tanks for Private Fire Protection

Standard for the Installation of Private Fire Service Mains and Their Appurtenances

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire ProtectionSystems

Standard on Fire Hose

Standard for the Care, Use, Inspection, Service Testing, and Replacement of Fire Hose,Coupling, Nozzles, and Fire Hose Appliances.

Standard for Fire Hose Connections

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 79 1/27/2016 2:09 PM

Page 67: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 79 1/27/2016 2:09 PM

Page 68: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 8-NFPA 59-2015 [ Section No. 13.5.1.1 ]

13.5.1.1

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Affilliation:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 79 1/27/2016 2:09 PM

Page 69: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 50-NFPA 59-2015 [ Section No. 13.5.3 ]

Standard for Portable Fire Extinguishers

Standard for Low-, Medium-, and High-Expansion Foam

Standard on Carbon Dioxide Extinguishing Systems

Standard on Halon 1301 Fire Extinguishing Systems

Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems

Standard for Dry Chemical Extinguishing Systems

Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems

Standard on Clean Agent Fire Extinguishing Systems

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 79 1/27/2016 2:09 PM

Page 70: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 51-NFPA 59-2015 [ Section No. 13.6 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 79 1/27/2016 2:09 PM

Page 71: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 52-NFPA 59-2015 [ Section No. 13.8.2.3 ]

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 79 1/27/2016 2:09 PM

Page 72: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 53-NFPA 59-2015 [ New Section after A.4.5.2.2 ]

A.4.5.2.2 When classifying the extent of an entire facility or a specific portion of the facility, considerationshould be given to increasing the extent of the hazardous area location above those stated in the NEC andNFPA 59 Table 4.5.2.2 based on higher flow rates and pressures utilized within larger facilities. Additionalguidance for extending electrical area classifications can be found in NFPA 497 Electrical Installations inChemical Atmospheres Involving Flammable Liquids, Gases, or Vapors.

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 79 1/27/2016 2:09 PM

Page 73: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 54-NFPA 59-2015 [ New Section after A.7.4.5 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 79 1/27/2016 2:09 PM

Page 74: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 55-NFPA 59-2015 [ Sections A.10.1, A.11.2.3 ]

Sections A.10.1, A.11.2.3

Guide for Pressure-Relieving and Depressuring Systems

Standard for the Safeguarding of Tanksand Containers for Entry, Cleaning, or Repair Purging Principles and Practice

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 79 1/27/2016 2:09 PM

Page 75: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 79 1/27/2016 2:09 PM

Page 76: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 47-NFPA 59-2015 [ New Section after A.13.2.4 ]

A13.2.2.1 Leak detection used to compliment gas detection systems, leak detection mayinclude but not limited to acoustic (ultrasonic)? which, detects small leak rates (mass/time), vaporcloud video surveillance cameras? which, detects gas cloud size, Low Temperature Detectors,including Resistant Temperature Detectors (RTD), and Linear Leak Detection (such as fiber opticleak detection technology).

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 79 1/27/2016 2:09 PM

Page 77: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 56-NFPA 59-2015 [ New Section after A.13.2.4 ]

Statement of Problem and Substantiation for Public Input

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

Statement:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 79 1/27/2016 2:09 PM

Page 78: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Public Input No. 3-NFPA 59-2015 [ Section No. F.1.2 ]

Interchangeability of Other Fuel Gases with Natural Gas,2002.

Interchangeability — What it Means,

Introduction to LPG Safety for Propane Air Plant Operators,

Purging Principles and Practice,

STD Guide for Pressure-Relieving and Depressuring Systems, 6th edition,2014

Protection Against Ignitions Arising out of Static, Lightning, and Stray Currents,

ASME Internationl Two

Boiler and Pressure Vessel Code, 2015

, 15835 Park Ten Place

NACE Control of External Corrosion of Underground or Submerged Metallic PipingSystems 2013

NACE Control of Corrosion Under Thermal Insulation and Fireproofing Materials ASystems Approach

NACE Corrosion Control of Underground Storage Tank Systems by CathodicProtection

Publishing

Statement of Problem and Substantiation for Public Input

Related Public Inputs for This Document

Related Input Relationship

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 79 1/27/2016 2:09 PM

Page 79: Statement of Problem and Substantiation for Public Input ... · Twe lth Edition October 2013 with Addendum 1 November 2014 . API 625, Tank Systems for Refrigerated Liquefied Gas Storage,

Submitter Information Verification

Submitter Full Name:

Organization:

Street Address:

City:

State:

Zip:

Submittal Date:

Committee Statement

Resolution:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...