Page 1: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator & Telemetry

Page 2: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

• Imagine a student measuring current on an electrical circuit

.59

With on meter, he measures .59 A. Being a cautious type, he measures again with a different meter, and reads 1.0 A. Which is correct?

1.0

Meter 1

Meter 2

Page 3: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

• Imagine a student measuring current on an electrical circuit

.59

1.0

On the back of Meter 1 it says the measurement is accurate to +/- 5% On the back of Meter 2 it says the measurement accuracy has a standard deviation of +/- 2%

What is the most probable actual current flow?

Page 4: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

What is the most probable actual current flow?

We cannot tell! All we know is that I have a bad meter! Each measurement is over 5 standard deviations from the other; making the probability of both being correct infinitesimal

The student assumed that the meaning of +/- 5% means that 99.9 % of measurements taken with that meter would be within 5%; or the STANDARD DEVIATION of the measurements would be 5%/3 = 1.666%

Probable Error of measurements

-0.05

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5 0.6 0.7 0.8 0.9 1 1.1

Page 5: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

But what if you do not know the accuracy of the instruments

• A state estimator is a minimization program, which minimizes the sum of weighted residuals. In this example, we assumed meter 1 had a measurement accuracy of +/- 1.666% standard deviation. (i.e. 99.9% of measurements would be within 5%), and meter 2 had a measurement accuracy of +/- 2 standard deviations.

Page 6: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

But what if you do not know the accuracy of the instruments

• If you have no idea of the expected accuracy of the instruments, then a “reasonable” approach is to average the two measurements. (.56 + 1)/2 = 0.78 A

• This is obviously not correct from our previous analysis: so a basic requirement is to know the expected accuracy of your measurements.

Page 7: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

Proposed Telemetry Requirement 1:

• TSP’s and QSE’s shall notify ERCOT of the expected accuracy of their analog measurements.

• Preferred format is expected accuracy of PT, CT, A/D converter and transducer in percentage.

• TSPs & QSE’s will identify how the accuracy was calculated: i.e.– Calculated from manufacturer specifications these

devices (high confidence)– MFG specs unavailable: estimated from typical

specifications historically installed by our company– A guess from our experience.

Page 8: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

Probable Error of measurements

-0.05

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0.5 0.6 0.7 0.8 0.9 1 1.1

But what do you do when you identify a problem?

Page 9: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

Proposed Telemetry Requirement 2

• When ERCOT identifies a measurement which is probably in Error, Participants shall recalibrate the device within 2 working days or provide ERCOT with data documenting reasons that the measurement is known to be correct.

• Each TSP and QSE shall have a telemetry calibration program which can be shown to maintain the probable number of devices outside of their specified accuracy range to < 1% OR alternatively shall be re-calibrated once every 2 years.

Page 10: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

• Imagine our student takes both meters to his Teaching Assistant, and asks him to check them. To his surprise, the instructor returns them 15 minutes later, telling him they both check out. What should he do?

• Logically he should ask how the meters were calibrated.

.59

1.0

Meter 1

Meter 2

Page 11: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

Proposed Telemetry Requirement 3

• If a TSP or QSE examines a measurement at the request of ERCOT, and no error is detected, the TSP or QSE shall provide ERCOT with details of how the calibration took place.

Page 12: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

• Below is a single-line diagram with scada measurements.• All measurements have equal weights (std=3%, w=1/(sd)^2=0.1111) in the uncertainty model.• Measurements shown are red are erroneous, they are 25Mw (~28Mw) and 20 MW ( ~23MW) in reality.

40Mw28Mw

15Mw15Mw

17Mw

20Mw

~

Page 13: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

SE solution 1 (SE values in black font and scada values in blue font)• Objective function is to minimize sum of weighted squares of residuals (PI)• KCL is loosened• Equal Weights on all measurements ( 0.1111)

40Mw28Mw

28Mw

15Mw15Mw

17Mw

20Mw

~

• PI = Σ weight(i) *residual(i)2 =0• Bus mismatches of 3 Mw at every bus

8Mw

8Mw

(15) (15)

(40)(28)

(17)

(20)

Page 14: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

SE solution 2 (SE values in black font and scada values in blue font)• Objective function is to minimize sum of weighted squares of residuals (PI)• KCL is tightened to 0• Equal Weights on all measurements ( 0.1111)

38.5Mw25.75Mw

25.75Mw

12.75Mw12.75Mw

17.75Mw

20.75Mw

~

• PI = 0.1111*23 = 2.56• Bus mismatches of 0 Mw at every bus • Note that error on 3 measurements is spread across all estimates

8Mw

8Mw

(15) (15)

(40)(28)

(28)

(17)

(20)

Page 15: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

SE solution 2 (SE values in black font and scada values in blue font)• Objective function is to minimize sum of weighted squares of residuals (PI)• 2 bad measurements have low weights ( std= 5%, w=0.04), all other measurements have normal weights (std=3%, w=0.111).• KCL is normal (i.e. relaxed)

40Mw25Mw

25Mw

15Mw15Mw

17Mw

23Mw

~

• PI = 0.1111*0+ 0.04* 27 = 1.08• Bus mismatches of 0 Mw at every bus

8Mw

8Mw

(15) (15)

(40)(28)

(17)

(20)

Page 16: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

Weighting Calculation

Stdv =(PTE+CTE+ADCE+TRE)*Base/(Probable Max stdv based on gaussian distribution=5)

Example: If PT error = 1% (.01); CT error = 1% (.01); transducer = 1% (.01) and AD converter accuracy = 1% (.01) on a 271 MVA line than the expected standard deviation of the measurement mapped to that line is: (.01+.01+.01+.01)*271/5 = 2.61 and the weighting is 1/SD2 = 0.14679

Now the Performance index = the sum of these weighting factors * residual or:

PI = Σ Weight Factor(i) * Residual(i)2

So what information do we need for each measurement?1. Accuracy of PT (maximum error)2. Accuracy of CT3. Accuracy of A/D converter4. Accuracy of transducer

Page 17: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

Page 18: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.

State Estimator

Default Weight Calculation

For a 1000Mva line belonging to MEAS class hasStdv = (.01+.01+.01+.01)*1000/5=8, w=1/64

For a load with parent fraction 10 has

Stdv = (.01+.01+.01+.01)*10/5= .08, w=1/.0064

Page 19: State Estimator & Telemetry. Imagine a student measuring current on an electrical circuit.59 With on meter, he measures.59 A. Being a cautious type, he.