START-UP PROCEDURE PROPEL PUMP
description
Transcript of START-UP PROCEDURE PROPEL PUMP
© Blue Graphics Concept Sauer-Danfoss
© Blue Graphics Concept Sauer-Danfoss
START-UP PROCEDURE PROPEL PUMP
InstructionSauer-Danfoss Belgium – T. Van Mossevelde
Know-How in Motion™ / Sauer-Danfoss 2
Example of propel setup
EXAMPLE:H1-pump + H1-variable motor• Reservoir screen 10 µm• Charge pressure filter
Know-How in Motion™ / Sauer-Danfoss 3
Start-up procedure
WARNINGUnintended movement of machine or mechanism may cause injury to
technician or bystanders. To protect against unintended movement, secure the machine or disable/disconnect the mechanism while servicing.
Prior to installing the units, check for shipping damage
Ensure that the hydraulic fluid and system components (reservoir,
hoses, valves and valve blocks, fittings, heat exchanger,... ) are
clean and free of contamination.
Install the different components
Add a measuring point (minimess) or 50-60 bar gauge on the
charge pressure port. (monitor charge pressure)
Check if line fittings are tightened properly
Do not connect input signal to servo control of pump
A) Preparation and installation
Know-How in Motion™ / Sauer-Danfoss 4
Start-up procedure
Mount connection for external filling pump on:• Integral charge pressure filtration: on point before filter (see schematic)• No charge pressure filtration: on measuring point M3 (pressure charge pump)
Hydraulic filling group (flow 1 to 20 l/min) must have a relief
valve that is set to 35-40 bar. This group must have a fine
pressure filtration !The charge pressure relief valve in the pump is set between 20 and 30 bar.
Filling of pumpcase will be ensured because oil will be directed to case when the pressure of filling pump exceeds
the charge pressure setting.
Start filling hydraulic circuit with clean and filtered oil untill oil is
visible through level glass in hydraulic tank.When high pressure system is filled, pressure from external pump will rise to level set at charge pressure relief
valve in propel pump. The pump case will be filled, followed by the drain line to cooler to tank...
If present, repeat this step for other propel circuits untill oil level
in tank is starting to rise.
B) Filling of hydraulic system with external pump (preferred method !!)
Know-How in Motion™ / Sauer-Danfoss 5
Start-up procedureB) Filling with external pump – charge pressure filter mounted
Charge pressure relief valve – filling oil to case and to tank when high pressure system is filled
Know-How in Motion™ / Sauer-Danfoss 6
Start-up procedure
Fill housings of pumps and motors by adding filtered oil in the
upper case drain ports.
Open the case plug on top of pump (or plug on highest position
of pump) to assist with air bleed.
continue filling untill oil is present Fill hydraulic reservoir completely with clean oil of
recommended type and viscosity. After some time, the oil level will lower due to gravity
Loosen suction line of charge pump to check if oil present.
if not, fill suction line completely or make sure that oil is
coming to avoid cavitation at inlet port of charge pump !
C) Filling of hydraulic system via hydraulic tank
Know-How in Motion™ / Sauer-Danfoss 7
Start-up procedure
Use a common method to disable the engine to prevent the engine from starting. Preferably: disconnect electrical connector (if present) from controller of
diesel engine. In some cases, it is possible to actuate the diesel engine start motor without starting the diesel engine. The pumps are rotated by start motor movement.
Crank the starter for several seconds
(do not exceed recommendation of engine manufacturer)
Wait for a minute (cool down start motor) and crank the engine
a second time
this operation helps remove air from system lines
Keep an eye on reservoir level refill untill recommended level
D) Starting diesel engine with start motor
Know-How in Motion™ / Sauer-Danfoss 8
Start-up procedure
Continue previous steps untill charge pressure on pump (or all propel pumps if present) reaches 3,5 bar.
Start diesel engine and let it run at idle speed for at least 30
seconds
work air out of system
When required charge pressure is reached at all pumps (20-30
bar), increase engine speed to normal operation rpm.
residual air out of system
Shut off the engine and connect control signal
E) Starting diesel engine
Know-How in Motion™ / Sauer-Danfoss 9
Start-up procedure
Start engine and check to be sure that the pumps remain in
neutral position
Increase engine speed to normal rpm and carefully check
forward and reverse control
Continue to cycle between forward and reverse for at least 5
minutes
purge air from system
Check if reservoir level is at required level
The system is now ready for operation
F) Initial movement of machine
Know-How in Motion™ / Sauer-Danfoss 10
Start-up procedure
Air entrapment in fluid under high pressure may damage
hydraulic components cavitation
Do not run at maximum pressure until system is completely free
of air and fluid has been filtered thorougly
Always ensure recommended fluid supply, as this may damage
hydraulic components when insufficient.
In case of contamination, immediatly stop working and build off
all affected components to check internal damage.
Flushing of complete system is necessary, oil samples need to
be checked when same oil is used after flushing the system.
Warnings
© Blue Graphics Concept Sauer-Danfoss
© Blue Graphics Concept Sauer-Danfoss
START-UP PROCEDURE OPEN CIRCUIT PUMP
Instruction LS/PC pumps Series 45Sauer-Danfoss Belgium – T. Van Mossevelde
Know-How in Motion™ / Sauer-Danfoss 12
Start-up procedure Series 45-pump
WARNINGUnintended movement of machine or mechanism may cause injury to
technician or bystanders. To protect against unintended movement, secure the machine or disable/disconnect the mechanism while servicing.
Prior to installing the units, check for shipping damage
Ensure that the hydraulic fluid and system components (reservoir,
hoses, valves and valve blocks, fittings, heat exchanger,... ) are
clean and free of contamination.
Install the components
Add a measuring point (minimess) in suction line (as close as
possible to pump inlet) and on case of pump (see schematic)
Check if line fittings are tightened properly
A) Preparation and installation
Know-How in Motion™ / Sauer-Danfoss 13
Start-up procedure Series 45-pumpB) Schematic example
S45 LS pump + PVG32 valve• Reservoir screen 125 µm• Return line filter + cooler• Reservoir: Minimum oil level should
be higher than the suction inlet port of the open circuit pump
• Drain line of pump case directly to tank, mounted on top of reservoir submerged under oil level
Know-How in Motion™ / Sauer-Danfoss 14
Start-up procedure Series 45-pump
Pump installation position recommended under minimum oil level maintain low inlet pressure at all times
Suction line: short distance without corners if possible. Check fluid line speed for dimensioning diameter of suction line
Filtration
Suction filtration: 125 µm (150 mesh) screen
Do not use a suction filter element ! high pump inlet pressure
Return line of open circuit must be filtered: β10 = 10
See manual with id 520L0467 for more info about filtration
Oil fluid cleanliness: ISO 4406-1999 class 22/18/13 or better
Case drain line of pump case must be connected directly to tank, whitout a
filter, under the minimum oil level. Position must be as far away as
possible from pump suction line !
Use highest case drain connection (L1 or L2) of pump
Oil capacity of reservoir for open circuit: 1x to 3x pump volume
C) Installation guidelines
Know-How in Motion™ / Sauer-Danfoss 15
Start-up procedure Series 45-pump
Inlet pressure Minimum continuous working: 0,8 bar absolute / - 0,2 bar Minimum at cold start: 0,5 bar absolute / - 0,5 bar
Case pressure Maximum continuous working: 0,5 bar above inlet Intermittent (cold start): 2 bar above inlet
D) Operation parameters
Difference between case pressure and suction pressure must be within specification at all times
Damage of pump when this condition is not fulfilled !
See catalogue: TI Series 45
Know-How in Motion™ / Sauer-Danfoss 16
Start-up procedure Series 45-pump
Fill pump housing with clean oil at highest case drain port
Fill suction line completely with oil
Fill oil tank to suffient level
Check if suction line is bleeding to make sure that the oil is
present at the inlet port when loosening the inlet connection.
Loosen plug at highest point to purge air from system Use a common method to disable the engine to prevent the
engine from starting.
Keep an eye on reservoir level refill untill recommended level
The oil level will lower due to the filling of the open circuit functions (valve
blocks,...)
E) Start-up guidelines
Know-How in Motion™ / Sauer-Danfoss 17
Start-up procedure Series 45-pump
Start diesel engine and let the diesel engine run at idle speed for a couple of minutes whitout actuating open circuit functions purge air from system
Check difference between pump case pressure and suction pressure (See section D)
In case of LS-system: purge air from LS-signal line by actuating one work function that is not building up pressure untill LS-signal line is filled completely with oil.
If pressures are correct at cold start, increase engine speed to normal rpm and carefully check all open circuit functions: Check for abnormal noise when high flow is delivered (avoid cavitation,...) Check case pressure and suction pressure
Suction pressure will drop when higher flow is requested ! specification
When these tests are ok, the pump is ready for operation
E) Start-up guidelines