SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1...

12
Motors | Automation | Energy | Transmission & Distribution | Coatings SSW7000 Medium Voltage Soft-Starter

Transcript of SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1...

Page 1: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

Motors | Automation | Energy | Transmission & Distribution | Coatings

SSW7000 Medium Voltage Soft-Starter

Page 2: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter2

Medium Voltage Soft-Starter

The SSW7000 uses state-of-the-art technology to provide start / stop control and protection for three-phase medium voltage induction motors. Developed to ensure excellent performance, it prevents mechanical shocks from the load, protects the motor against related burnouts or current surges in the power supply and thus, offers a complete solution for various applications.

The SSW7000 reduces the voltage applied to the motor at start. As a consequence, motor current and torque is reduced for a smooth start. The motor voltage control is performed with the firing angle control of the thyristors in antiparallel connection.

Power supply voltageU

t

Motor voltage

Certifications

Size A

pictures for illustrative purposes only

Falta

imag

em

Size N

Page 3: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter 3

Size N

Features

g Torque control The SSW7000 features FTC - Flexible Torque Control, technology developed by WEG which uses the vector control and control of direct torque concepts, based on technologies developed for the vector frequency inverters CFW. The FTC is flexible to select the desired torque control according to the type of load applied to the motor (constant loads, quadratic loads, or loads with lower or higher starting torque), providing a smooth start with a linear speed ramp

along the entire starting process.g Accessories can be easily and quickly installed by using the Plug and Play’ conceptg Motor voltage: 2.3kV, 4.16kV or 6.9kV g Power: 750 hp to 4500 hpg Output current: 180A, 300A and 360Ag Protection Degree: IP41 or Nema 12 g Operating interface (HMI) with graphic LCDg Real time clockg Main and bypass vacuum contactorsg Medium voltage fusesg Power and control insulated by fiber opticsg Flash memory module (accessory)g SoftPLC Functiong Licence-free software SuperDrive and WLPg USB connection to PC g Motor thermal protection - PT100 - 8 channels (optional accessory)g 5 start modesg Network communication boards (accessories): Devicenet, Profibus-DP, Ethernet and Modbus, RS-232 or RS-485

g The heatsinks are dimensioned for the heavy duty overload cycle.

g The power stacks are developed in independent modules with wheels, making installation and maintenance easy.

pictures for illustrative purposes only

Size A

Enables smooth starting of motors up to rated speed, by eliminating impacts of inrush current on the power supply and by eliminating impacts of mechanical shocks on the load and the coupling.This helps in reducing maintenance of bearings, couplings, gear boxes, pulleys, belts and chains, in addition to protecting the motor.

Page 4: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter4

The installation of the accessories is based on the plug-and-play philosophy, that is, they are automatically configured when connected to the SSW7000, ensuring a faster and easier process.

Plug and play philosophy

Characteristics

Slot 5 - Flash memory module (accessory)

Human Machine Interface – HMI (included in the standard product)

Slot 2 – Temperature sensor module PT100 (accessory)

Slot 3 – Communication (accessory)

Slot 4 – Communication (accessory)

pictures for illustrative purposes only

Page 5: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter 5

Human Machine Interface – HMI

Navigation is similar to the logic used in cell phones, with the option of sequential access to the parameters or through the groups (Menu) by means of the function access keys on the display (soft keys).

Characteristics

Left soft key: function defined by the display

Right soft key: function defined by the display

Key for scrolling through menus and parameters and for modifying

parameter content

FWD/REV Selection

Local / Remote Selection

Jog key

Start key

Stop key

pictures for illustrative purposes only

Page 6: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter6

Functions

g Power supply overvoltage and undervoltage programmable protections, voltage unbalance between phases of the power supply

g Motor overload and underload programmable protectionsg Motor thermal protectionsg Actuation of the programmable protections between fault or alarm g Indication of: g motor current per phase, motor current as % of SSW rated current and as % of motor nominal current g power supply input voltages per phase g motor active and apparent power in kW and kVA g value of the analog inputs g status of the digital inputs and outputs g status of the thermal class protection g temperature of the SCRs g motor temperature using the accessory module for measuring temperature IOE g hours energized, hours in operation, hours fan use g ground fault current or voltage g Fault and alarm indication g Fault history: g saving of the 10 last faults g date and time of fault occurence g motor current in the fault event g power supply voltage in the fault event g SSW7000 operating status in the fault eventg Start and full duty diagnosis: g maximum starting current g average starting current g real starting time g maximum current at full duty g Power supply maximum and minimum voltage with the motor activated g Power supply maximum and minimum frequency with the motor activated g maximum number of starts per hour g total number of starts g maximum temperature of the SCRs g maximum temperatures of the motor (with the use of the IOE accessory) g Flexible selection of start and stop control type, enabling: Ramp Voltage, Constant or in Ramp Current Limitation, Pump

Control and -Constant Torque Control, Linear or Quadratic load startingg Flexible Torque Control with extremely high performanceg Possibility to monitor the measurements of power supply voltages via Serial or Fieldbus communicationg Monitoring and programming in graphical mode using SuperDriveG2 Softwareg Soft PLC allows implementation of PLC software or special operating versions of SSW7000 soft-starter.

Page 7: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter 7

Applications

Chemical, Petrochemical, Oil and Gas

Cement and Mining

Steel and Metallurgy

Sugar and Chemical

Pulp and Paper

Water & Waste Water Management

g Blowers

g Compressors

g Conveyors

g Chippers

g Fans

g Exhausters

g Pumps

pictures for illustrative purposes only

g Flexible Torque controlg Overload capacity of 450% for 30 s. (2x / hour duty cycle)g Management of Demand restrictions by the electric companyg Bumpless startingg Motor protectiong Mechanical wear reductiongHandles lower inrush current limitations of power supply

Advantages

Page 8: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter8

Specification

SSW7000 Medium Voltage Soft-Starter

Power Supply CodeOutput Rated

CurrentSize

Protection Degree

Single-Phase Auxiliary Power

Supply

Motor maximum power (*2)

HP kW

2300 Vac

Three-phase

SSW7000A180T22241180 A

A IP41

220 Vac 750 550

SSW7000A180T21141 110 Vac 750 550

SSW7000A300T22241300 A

220 Vac 1350 1000

SSW7000A300T21141 110 Vac 1350 1000

SSW7000A360T22241360 A

220 Vac 1500 1100

SSW7000A360T21141 110 Vac 1500 1100

4160 Vac

SSW7000A180T42241180 A

A IP41

220 Vac 1500 1100

SSW7000A180T41141 110 Vac 1500 1100

SSW7000A300T42241300 A

220 Vac 2500 1900

SSW7000A300T41141 110 Vac 2500 1900

SSW7000A360T42241360 A

220 Vac 3000 2250

SSW7000A360T41141 110 Vac 3000 2250

6900 Vac

SSW7000A180T62241180 A

A IP41

220 Vac 2500 1900

SSW7000A180T61141 110 Vac 2500 1900

SSW7000A300T62241300 A

220 Vac 3700 2800

SSW7000A300T61141 110 Vac 3700 2800

SSW7000A360T62241360 A

220 Vac 4500 3400

SSW7000A360T61141 110 Vac 4500 3400

Note: (2*) The motor power rates above are meant for loads with normal overload, e.g. centrifugal pumps and compressors, based on WEG 4-pole 60-Hz motors. For applications with heavy duty overloads or other more severe conditions, contact WEG’s sales force. The dimensioning of the SSW7000 must be calculated based on the information of the load curve, number of starts per hour and load type.

Note: (*1) Under request

Product Code

1 2 3 4 5 6 7 8 9 10 11SSW7000 A 300 T 6 22 41 F - - -

T

246

1122

0041N2

F(blank)

(blank)

(blank)

(blank)

A size AN size N

SSW7000

1 - WEG medium voltage soft-starter 6 - Single-Phase Auxiliary Power Supply

7 - Protection Degree

8 - Forced Ventilation

9 - Special Hardware

10 - Special Hardware

11 - Market

Series 7000 110 Vac

IP00 (Kits) (*1)

Forced

220 Vac

IP41NEMA 12

Standard

Standard

Standard

Global

Three-phase

2.3 kV4.16 kV6.9 kV

2 - Frame Size

3 - Rated Output Current

4 - Power Supply

5 - Rated Voltage

2300 Vca 4160 Vca 6900 Vca180 = 180 A 180 = 180 A 180 = 180 A300 = 300 A 300 = 300 A 300 = 300 A360 = 360 A 360 = 360 A 360 = 360 A

Size A

Page 9: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter 9

M

3~

SSW7000 Medium Voltage Soft-Starter

Power Supply CodeOutput Rated

CurrentSize

Protection Degree

Single-Phase Auxiliary Power Supply

Motor maximum power (*2)

HP kW

2300 Vac

Three-phase

SSW7000A180T222N2180 A

N NEMA 12

220 Vac 750 550SSW7000A180T211N2 110 Vac 750 550SSW7000A300T222N2

300 A220 Vac 1350 1000

SSW7000A300T211N2 110 Vac 1350 1000SSW7000A360T222N2

360 A220 Vac 1500 1100

SSW7000A360T211N2 110 Vac 1500 1100

4160 Vac

SSW7000A180T422N2180 A

N NEMA 12

220 Vac 1500 1100SSW7000A180T411N2 110 Vac 1500 1100SSW7000A300T422N2

300 A220 Vac 2500 1900

SSW7000A300T411N2 110 Vac 2500 1900SSW7000A360T422N2

360 A220 Vac 3000 2250

SSW7000A360T411N2 110 Vac 3000 2250

Specification

Accessories

(1) Consulte manual de Comunicação Anybus-CC.

Reference Description Slot

Control accessories to install in Slots 1, 2 and 3IOE-04 Module for 8 temperature sensors PT100 1 e 2

RS485-01 RS-485 serial communication module (Modbus)3RS232-01 RS-232C serial communication module (Modbus)

RS232-02 RS-232C serial communication module with switch to program the microcontroller FLASH memoryAnybus-CA Accessories to install in Slots 4

PROFDP-05 ProfibusDP interface module

4DEVICENET-05 Devicenet interface module

ETHERNET/IP-05 EtherNet/IP interface moduleRS232-05 RS-232 interface module (passive) (Modbus)RS485-05 RS485 interface module (passive) (Modbus)

Flash Memory Module to install in Slot 5 – Included in Standard ModelsMMF-01 FLASH memory module 5

Other AccessoriesHMI-01 Man Machine Interface – MMI (sold separately) (1)

-RHMIF-01 Frame kit for MMI (protection rate IP56)TC FT Ground fault CT

Disconnecting Switchand Fuses

Medium Voltage Power Supply

Medium Voltage Motor

Power Stack

Main Contactor

Bypass Contactor

CTs

Block Diagram

Size N

Note: (2*) The motor power rates above are meant for loads with normal overload, e.g. centrifugal pumps and compressors, based on WEG 4-pole 60-Hz motors. For applications with heavy duty overloads or other more severe conditions,contact WEG’s sales force. The dimensioning of the SSW7000 must be calculated based on the information of the load curve, number of starts per hour and load type.

Page 10: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter10

pictures for illustrative purposes only

Dimensions

Standards

Power stacks

SizesWidth

mm (inch)Height

mm (inch)Depth

mm (inch)

Weight(w/ power

stacks)kg (lb)

A1200(47.2)

2365(93)

1007(39.6)

970(2140)

N1072(42.2)

2365(93)

845(33.3)

970 (2140)

Rated Voltage

Widthmm (inch)

Heightmm (inch)

Depthmm (inch)

Weightkg (lb)

2.3 kV262

(10.3)772

(28.4)430

(16.9)53,0(117)

4.16 kV262

(10.3)772

(28.4)546

(21.5)68.6(151)

6.9 kV262

(1.03)772

(28.4)664

(26.1)83.3(184)

1200(47.2)

1007(39.6)

2365 (93)

Size A Size N

1072(42.2)

845(33.3)

2365(93)

ANSI/IEEE C37.2 Function/Protection Feature Standard Option

19 Reduced Voltage Starting and Bypass

27 Undervoltage protection

37 Undercurrent protection

46 Phase-Balance Current protection

47 Phase Sequence

48 Incomplete Sequence

50 Instantaneous Overcurrent trip

51 Overcurrent trip

55 Power Factor check

59 Overvoltage

81 Frequency check

86 Lockout Relay - electronic

50N/51G Ground fault detection instantaneous and fault-current

49 & 38 Winding Temperature and Bearing Temperature

Page 11: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

www.weg.net

SSW7000 Medium Voltage Soft-Starter 11

Technical specifications

Power SupplyPower Voltage(R/1 L1, S/3L2,T/5L3)

Low voltage test:500Vac: (-60% to +10%) or (200 to 550Vac)Models:2300Vac: (-60% to +10%) or (920 to 2530Vac)4160Vac: (-60% to +10%) or (2760 to 4576Vac)6900Vac: (-60% to +10%) or (2760 to 7590Vac)

Frequency (50 to 60Hz): (±10%) or (45 to 66Hz)

CapacityMaximum number of starts 5 starts in 2 hours (One start every 30 minutes)Start cycle AC-53a; 4.5-30:50-2

Thyristors

Medium voltageSCRs per powerstack

2300Vac: 2 thyristors per per power stack4160Vac: 2 coupled pairs of thyristors6900Vca: 2 coupled trilplets of thyristors

Peak reversevoltage on thepower stack

2300Vac: 6.5kV4160Vac: 13kV6900Vac: 19.5kV

ProtectionsProtection byHardware

dv/dt filterActive overvoltage protection on the thyristors

Control Supply

Control voltage As per code of the SSW7000: 110Vac: (-15% to10%) or (93.5 to 121Vac) 230Vac: (-15% to 10%) or (195.6 to 253Vac)Frequency (50 to 60Hz): (±10%) or (45 to 66Hz)

ConsumptionContinuous: 900 mAPeak: 9.5 A (during the closing of the vacuum contactors)

Control Method

Voltage ramp. Current limitation.Pump control. Torque control. Current ramp.

InputsDigital 6 insulated digital inputs, 24 Vdc, programmable functions

Analog2 differential inputs insulated by differential amplifier; Al1 resolution: 12 bits, Al2 resolution: 11bits + signal, (0 to 10) V, (0 to 20) mA or (4 to 20) mA, Impedance: 400kQ for (0 to 10V), 500Q for (0 to 20mA) or (4 to 20mA), programmable functions

OutputsDigital 3 NO/NC contact relays, 240 Vac, 1A, programmable functions.

Analog2 insulated outputs, (0 to 10V) RL ± 10kQ (maximum load), 0 to 20mA or 4 to 20mA RL<500Q, 11-bitresolution, programmable functions

Man Machine Interface

Standard9 keys: Turn/Stop, Increase, Decrease, Rotation Direction, Jog, Local/Remote, right Soft key and leftSoft key. Graphic LCD.It enables access to/change of all parameters.

Safety Main protections

Under and Overcurrent and current unbalance. Under and Overvoltage andvoltage unbalance. Under and Overtorque and Active overpower Phaseloss.Reverse phase sequence Overtemperature in the power racks. Motoroverload. Motor overtemperature (optional). External defect.Ground fault by voltage or current.Fault in the power racks.Fault in the power contactors.Faults in the control boards.Communication faults of MMI and between controls.Faults in the communication networks.Programming errors.For further details and more protections implemented, refer to the programming manual.

Protection degree IP41 Standard panel

PC connection forprogramming

USB ConnectorUSB standard Rev. 2.0 (basic speed). USB plug type B “device”.Interconnecting Cable: standard host/device shielded USB cable

Environmental Conditions

Temperature -10° a 40°CAltitude Up to 1000 m above sea level. For higher altitudes, contact our sales force.Humidity Air relative humidity of 5 % to 90 % non-condensing.

Standards

NBR IEC 62271-200High voltage controlgear and switchgear - part 200:High voltage controlgear and switchgear in metal enclosure for voltages over 1 kV up to and including 52 kV

IEC 62271-1High-voltage switchgear and controlgear - Part 1: Common specifications

IEC 60060-1High-voltage test techniques. Part 1: General definitions and test requirements

CISPR 11Industrial, scientific and medical (ISM) radio-frequency equipament - electromagnetic disturbance characteristics - limits and methods of measurement

IEC 61000-4-4Electromagnetic compatibility (EMC) - Part 4: testing and measurement techniques - section 4: electrical fast transient/burst immunity test. Basic EMB publication

IEC 61000-4-18 Electromagnetic compatibility (EMC) - Part 4-18: testing and measurement techniques - damped oscillatory wave immunity test NBR IEC 60529 Protection rates for electric equipment enclosures (ip code)UL 347 Medium Voltage AC Contactors, Controllers and Control CentersUL 347B Medium Voltage Motor Controllers

Page 12: SSW7000 - VFDs.com 2 SSW7000 Medium Voltage Soft-Starter ... Profibus-DP, Ethernet and Modbus ... 1 2 3 4 5 6 7 8 9 10 11 SSW7000 A 300 T 6 22 41 F - - - T 2 4 6 11 …

WEG Worldwide OperationsARGENTINAWEG EQUIPAMIENTOS ELECTRICOS S.A.(Headquarters San Francisco-Cordoba)Sgo. Pampiglione 4849Parque Industrial San Francisco2400 - San FranciscoPhone: +54 (3564) 421484Fax: +54 (3564) [email protected]/ar

AUSTRALIAWEG AUSTRALIA PTY. LTD.3 Dalmore DriveCarribean Park Industrial EstateScoresby VIC 3179 - MelbournePhone: 61 (3) 9765 4600Fax: 61 (3) 9753 [email protected]/au

BELGIUM WEG BENELUX S.A.Rue de l’Industrie 30 D, 1400 NivellesPhone: + 32 (67) 88-8420Fax: + 32 (67) 84-1748 [email protected]/be

CHILEWEG CHILE S.A.Los Canteros 8600 La Reina - SantiagoPhone: (56-2) 784 8900Fax: (56-2) 784 [email protected]/cl

CHINAWEG (NANTONG) ELECTRIC MOTOR MANUFACTURING CO., LTD.No. 128# - Xinkai South Road,Nantong Economic & Technical Development Zone, Nantong, Jiangsu Province. Phone: (86) 0513-85989333Fax: (86) [email protected]/cn

COLOMBIAWEG COLOMBIA LTDACalle 46A N82 - 54Portería II - Bodega 7 - San Cayetano II - BogotáPhone: (57 1) 416 0166Fax: (57 1) 416 [email protected]/co

DENMARKWEG SCANDINAVIA DENMARKSales Office of WEG Scandinavia ABAnelysparken 43BTrue8381 Tilst – DenmarkPhone: +45 86 24 22 00 Fax : +45 86 24 56 [email protected]/se

FRANCEWEG FRANCE SASZI de Chenes – Le Loup13 Rue du Morellon – BP 73838297 Saint Quentin FallavierPhone: +33 (0) 4 74 99 11 35Fax: +33 (0) 4 74 99 11 [email protected]/fr

GERMANYWEG GERMANY GmbHIndustriegebiet Türnich 3Geigerstraße 750169 Kerpen-TürnichPhone: +49 (0)2237/9291-0Fax: +49 (0)2237/[email protected]/de

GHANAZEST ELECTRIC GHANA LIMITED - WEG Group15, Third Close Street Airport Residential Area, Accra PMB CT 175, CantonmentsPhone: 233 30 27 664 90Fax: 233 30 27 664 [email protected]

INDIAWEG ELECTRIC (INDIA) PVT. LTD.#38, Ground Floor, 1st Main Road, Lower Palace Orchards,Bangalore – 560 003Phone(s): +91-80-4128 2007 +91-80-4128 2006 Fax: +91-80-2336 7624 [email protected]/in

ITALYWEG ITALIA S.R.L.V.le Brianza 20 - 20092 - Cinisello Balsamo - MilanoPhone: (39) 02 6129-3535Fax: (39) 02 [email protected]/it

JAPANWEG ELECTRIC MOTORSJAPAN CO., LTD.Yokohama Sky Building 20F, 2-19-12 Takashima, Nishi-ku, Yokohama City,Kanagawa, Japan 220-001Phone: (81) 45 440 [email protected]/jp

MEXICOWEG MEXICO, S.A. DE C.V.Carretera Jorobas-Tula Km. 3.5, Manzana 5, Lote 1 Fraccionamiento Parque Industrial - Huehuetoca, Estado de México - C.P. 54680Phone: + 52 (55) 5321 4275Fax: + 52 (55) 5321 [email protected]/mx

NETHERLANDSWEG NETHERLANDS Sales Office of WEG Benelux S.A.Hanzepoort 23C 7575 DB OldenzaalPhone: +31 (0) 541-571080Fax: +31 (0) [email protected]/nl

PORTUGALWEG EURO - INDÚSTRIA ELÉCTRICA, S.A.Rua Eng. Frederico UlrichApartado 6074 4476-908 - MaiaPhone: +351 229 477 705Fax: +351 229 477 [email protected]/pt

RUSSIAWEG RUSSIA Russia, 194292, St. Petersburg, Prospekt Kultury 44, Office 419 Phone: +7(812)363-21-72 Fax: +7(812)[email protected] www.weg.net/ru

SOUTH AFRICAZEST ELECTRIC MOTORS (PTY) LTD. WEG Group47 Galaxy Avenue, Linbro Business Park - Gauteng Private Bag X10011 - Sandton, 2146 JohannesburgPhone: (27-11) 723-6000Fax: (27-11) [email protected]

SPAINWEG IBERIA S.L. Avenida de la Industria,2528823 Coslada - MadridPhone: (34) 916 553 008Fax : (34) 916 553 [email protected]/es

SINGAPOREWEG SINGAPORE PTE LTD159, Kampong Ampat, #06-02A KA PLACE. Singapore 368328.Phone: +65 6858 9081Fax: +65 6858 [email protected]/sg

SWEDENWEG SCANDINAVIA ABBox 10196Verkstadgatan 9434 22 KungsbackaPhone: (46) 300 73400Fax: (46) 300 [email protected]/se

UKWEG ELECTRIC MOTORS (U.K.) LTD.28/29 Walkers RoadManorside Industrial EstateNorth Moons Moat - RedditchWorcestershire B98 9HEPhone: 44 (0)1527 596-748Fax: 44 (0)1527 [email protected]/uk

UNITED ARAB EMIRATESWEG MIDDLE EAST FZEJAFZA – JEBEL ALI FREE ZONETower 18, 19th Floor, Office LB 18 1905P.O. Box 262508 - DubaiPhone: +971 (4) 8130800 Fax: +971 (4) [email protected]/ae

USAWEG ELECTRIC CORP. 6655 Sugarloaf Parkway, Duluth, GA 30097 Phone: 1-678-249-2000Fax: [email protected] www.weg.net/us

VENEZUELAWEG INDUSTRIAS VENEZUELA C.A.Avenida 138-AEdificio Torre Banco Occidental de Descuento, Piso 6 Oficina 6-12Urbanizacion San Jose de TarbesZona Postal 2001Valencia, Edo. CaraboboPhone(s): (58) 241 8210582 (58) 241 8210799 (58) 241 8211457Fax: (58) 241 [email protected]/ve

Cod

: 50

0310

14 |

Rev

: 00

| Dat

e (m

/y):

05/2

011

The

valu

es s

how

n ar

e su

bje

ct to

cha

nge

with

out p

rior

notic

e.

WEG Equipamentos Elétricos S.A.International Division Av. Prefeito Waldemar Grubba, 3000 89256-900 - Jaraguá do Sul - SC - Brazil Phone: 55 (47) 3276-4002 Fax: 55 (47) 3276-4060 www.weg.net