SS/264XG 4 2600T Series Pressure Transmitters...with sanitary, food and beverage direct mount seal...
Transcript of SS/264XG 4 2600T Series Pressure Transmitters...with sanitary, food and beverage direct mount seal...
Data SheetSS/264XG_4
ABB 2600T SeriesEngineered solutions
for all applications
Base accuracy : ±0.075%
Reliable sensing system coupled with very latestdigital technologies
Span limits– 0.54 to 8000kPa; 2.14inH2O to 1160psi– 1.1 to 8000kPa abs; 8mmHg to 1160psia
Comprehensive sensor choice– optimize in-use total performance and stability
5–year stability
Flexible configuration facilities– provided locally via local keys combined with LCD
indicator or via hand held terminal orPC configuration platform
Multiple protocol availability– provides integration with HART®, PROFIBUS PA
and FOUNDATION Fieldbus platforms offeringinterchangeability and transmitter upgradecapabilities
Application specific process interfaces completeof process spud
PED compliance to sound engineering practice (SEP)
FieldIT
2600T Series Pressure Transmitters
Model 264DG Differential/Gauge Model 264HG Gauge
Model 264NG Absolutewith sanitary, food and beverage direct mount seal
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
2
Functional SpecificationsRange and span limits
General DescriptionModel 264DG and 264HG/NG detailed in this data sheet apply for thosetransmitters which include on high pressure measuring side, a directmount seal which is integral to the transducer by a short capillaryconnection inside a protective rigid tube.This construction forms a standalone single assembly suitable to bemounted to the process by the seal mounting facilities.By properly selecting the high and low pressure side variant in the orderingcodes, model 264DG can be in the following versions :a) one direct mount seal and one flange for process connection, direct
1/4 – 18 NPT or 1/2 – 14 NPT through adapter; this allows also to connectthe other leg (wet or dry) for differential measurement.A proper filter is supplied as standard when 1/4 – 18 NPT connectionis selected, in order to plug the unused entry, leaving it vented for gaugemeasurement with reference to atmosphere.
b) one direct mount seal and one remote seal with capillary; the two sealsallow again a differential measurement and must be selected of sametype/size.
The combinations sensor code/seal type marked (•) modify the base accuracy rating and static pressure effect; refer to performance specifications.
ALL AVAILABLE SEALS FOR DIRECT MOUNT ARE SUITABLE FOR LISTED RANGES OF MODELS 264HG/NG WITHOUT LIMITATION.
Model 264HG and 264NG have the direct mount seal on the positive side,respectively with the reference at atmospheric or vacuum pressure, forgauge or absolute measurements. Allowed types of direct mount seal arethose mainly used for sanitary, food and beverage application:– union nut– Triclamp– Cherry Burrell– sanitary flush or extended– beverage boltedThese are suitable for food, beverage and sanitary applications, using FDAapproved filling, which are defined as food fills and are Generally RecognizedAs Safe (GRAS) by the US Food and Drug Administration (FDA).Refer to seal data sheet for all data and details relevant to seal element. Thefollowing table list the types of standard seal which can be mounted with264DG/HG/NG transmitters (the mnemonic is used as reference in thecompatibility table).
epytlaeS eziS cinomenM
detlobegareveB 1 1/2 ni 5.1K
,pmalcirT,tuNnoinUllerruByrrehC,yratinaS
05F/ni208F/ni3
ni4
2S3S3S
All following specification data apply for identical characteristics of the two seals when the transmitter has the remote seal in addition to the direct mount one.
rosneSedoC
egnaRreppU)LRU(timiL
)LRL(timiLegnaRrewoLmuminiM
naps
)GD462roflaesdewolla(ytilibitapmoCGD462
tnuomtceriDlaitnereffid
GD462tnuomtceriD
eguag
GN/GH462tnuomtceriDetulosba/eguag
tnuomtceriDylnolaes
dnatnuomtceriDlaesetomereno).mnihtgnelxam(
EaPk61
rabm061Hni46 2O
aPk61–rabm061–
Hni46– 2O
aPk61–rabm061–
Hni46– 2O
aPk45.0rabm4.5
Hni41.2 2O3S )•()3(3S
FaPk04
rabm004Hni061 2O
aPk04–rabm004–
Hni061– 2O
aPk04–rabm004–
Hni061– 2O
aPk76.0rabm7.6
Hni76.2 2O3S,)•(2S )4(3S
GaPk56
rabm056Hni062 2O
aPk56–rabm056–
Hni062– 2O
aPk56–rabm056–
Hni062– 2O
sbaaPk70.0/aPk56–sbarabm7.0/rabm056–
Hni062– 2 gHmm5.0/O
aPk1.1rabm11
Hni53.4 2O3S,)•(2S )4(3S
HaPk061
rabm0061Hni246 2O
aPk061–rabm0061–
Hni246– 2O
sbaaPk70.0sbarabm7.0
gHmm5.0
sbaaPk70.0sbarabm7.0
gHmm5.0
aPk76.2rabm7.62
Hni7.01 2O3S,2S )8(3S,)3(2S
MaPk006
rab6isp78
aPk006–rab6–isp78–
sbaaPk70.0sbarabm7.0
gHmm5.0
sbaaPk70.0sbarabm7.0
gHmm5.0
aPk01rab1.0isp54.1
3S,2S )8(3S,)6(2S
PaPk0042
rab42isp843
aPk0042–rab42–isp843–
sbaaPk70.0sbarabm7.0
gHmm5.0
sbaaPk70.0sbarabm7.0
gHmm5.0
aPk04rab4.0isp8.5
3S,2S )8(3S,)6(2S
QaPk0008
rab08isp0611
aPk0008–rab08–
isp0611–
sbaaPk70.0sbarabm7.0
gHmm5.0
sbaaPk70.0sbarabm7.0
gHmm5.0
aPk431rab43.1isp4.91
3S,2S )8(3S,)6(2S
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
3
Operative limits
Temperature limits °C (°F) :
Ambient (is the operating temperature)
Lower ambient limit for LCD indicators: –20°C (–4°F)
Upper ambient limit for LCD indicators: +70°C (+158°F)
Note : For Hazardous Atmosphere applications see the temperaturerange specified on the certificate/approval relevant to theaimed type of protection
Process
Lower limit (side without seal for 264DG only)
– refer to lower ambient limits; –20°C (–4°F) for Viton gasket
Upper limit (side without seal for 264DG only)
– Silicone oil : 121°C (250°F) (1)
(1) 100°C (212°F) for application below atmospheric pressure
The following table show characteristics of fill fluids when used intransmitters with direct mount seal on high pressure side.
Storage
Lower limit: –50°C (–58°F); –40°C (–40°F) for LCD indicators
Upper limit: +85°C (+185°F)
Span limits
Maximum span = URL(can be further adjusted up to ± URL (TD = 0.5) for differentialmodels, within the range limits)
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSORCODE PROVIDING THE TURNDOWN VALUE AS LOWEST ASPOSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS.
Zero suppression and elevation
Zero and span can be adjusted to any value within the range limitsdetailed in the table as long as:
– calibrated span ≥ minimum span
DampingSelectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s.This is in addition to sensor response time
Turn on time
Operation within specification in less than 1s with minimumdamping.
Insulation resistance
> 100MΩ at 1000VDC (terminals to earth)
SDIULFLLIF)NOITACILPPA(
SNOITIDNOCGNITAREPO
xamTfo>sbaP@
nimPsbarabm
)aisp(
xamTnimP@
nimT
002CD-lioenociliS)esopruplareneG(
)093(002rabm53@
7.0)10.0(
061)023(
04–)04–(
02-MeeboeN-lioelbategeVADF)yratinaS-dooF(
)093(002rab1@
031)9.1(
051)003(
81-)0(
)%07(retaWnirecylGADF)yratinaS-dooF(
)002(39rab1@
0001)5.41(
39)002(
7–)02+(
28LOCRAM-liolareniMADF)yratinaS-dooF(
)093(002rabm002@
33)5.0(
04)401(
04–)04–(
gnilliFGD462sledoM GN/GH462sledoM
srosneSQotF
ErosneSsrosneS
QotGlioenociliS
002CD58+dna04–
)581+dna04–(58+dna52–
)581+dna31–(58+dna04–
)581+dna04–(
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
4
Pressure limits
Overpressure limits (without damage to the transmitter)
0.07kPa abs, 0.7mbar abs, 0.01psia to transmitter sensor limit or ratingof seal/fitting, whichever is less:
– 16MPa, 160bar, 2320psi for all sensor codes of model 264DG
– 21MPa, 210bar, 3045psi for all sensor codes of models 264HG/NG
– 3.8MPa, 38bar, 550psi for 2in Triclamp
– 2.4MPa, 24bar, 350psi for 3in Triclamp
– 1.7MPa, 17bar, 250psi for 4in Triclamp
– 2.5MPa, 25bar, 360psi for F50/F80 Union nut
– 1.9MPa, 19bar, 275psi for Cherry Burrell
– 1.9MPa, 19bar, 275psi for 4in Sanitary flush or extended
– 4MPa, 40bar, 580psi for 1 1/2in beverage bolted
– 1MPa, 10bar, 145psi for 4in V-band clamp option
– 0.7MPa, 7bar, 100psi @ 21°C for 4in schedule 5 V-band clamp option
Static pressure
Transmitters for differential pressure model 264DG operates withinspecifications between the following limits:
– 1.3kPa abs,13mbar abs, 0.2psia and 16MPa, 160bar, 2320psi orrating of seal/fitting as above, whichever is less
– 0.07kPa abs, 0.7mbar abs, 0.01psia and 16MPa,160bar, 2320psior rating of seal/fitting as above, whichever is less, using a secondseal remote on negative pressure side.
Proof pressure
The transmitter can be exposed without leaking to line pressure of up to:
– 28MPa, 280bar, 4000psi for model 264DG
– 40MPa, 400bar, 5900psi for model 264HG/NG
or two times the rating of seal/fitting whichever is less.
Meet ANSI/ISA–S 82.03 hydrostatic test requirements and SAMA PMC27.1.
Environmental limits
Electromagnetic compatibility (EMC)
Comply with EN 61000–6–3 for emission and EN 61000–6–2 forimmunity requirements and test;
Radiated electromagnetic immunity level: 30V/m(according to IEC 1000–4–3, EN61000–4–3)
Conducted electromagnetic immunity level : 30V(according to IEC 1000–4-6, EN 61000–4–6)
Surge immunity level (with surge protector): 4kV(according to IEC 1000-4–5 EN 61000–4–5)
Fast transient (Burst) immunity level: 4kV(according to IEC 1000–4–4 EN 61000–4–4)
Pressure equipment directive (PED)
Comply with 97/23/EEC following sound engineering practice (SEP)
Humidity
Relative humidity: up to 100% annual average
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2g at frequency up to 1000Hz(according to IEC 60068–2–26)
Shock resistance (according to IEC 60068-2-27)
Acceleration: 50g
Duration: 11ms
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected against immersioneffects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or byNEMA to 4X or by JIS to C0920. IP65 with Harting Han connector.
Hazardous atmospheres
With or without output meter/integral display– COMBINED INTRINSIC SAFETY and FLAMEPROOF/EUROPE:
ATEX/ZELM approvalII 1 GD T50°C, EEx ia IIC T6 (–40°C ≤ Ta ≤+40°C)T95°C, EEx ia IIC T4 (–40°C ≤ Ta ≤+85°C)II 1/2 GD T85°C, EEx d IIC T6 (–40°C ≤ Ta ≤ +75°C)
– INTRINSIC SAFETY/EUROPE:ATEX/ZELM approvalII 1 GD T50°C, EEx ia IIC T6 (–40°C ≤ Ta ≤+40°C)T95°C, EEx ia IIC T4 (–40°C ≤ Ta ≤+85°C)
– TYPE "N"/EUROPE:ATEX/ZELM type examination (for HART)II 3 GD T50°C, EEx nL IIC T6 (–40°C ≤ Ta ≤+40°C)
T95°C, EEx nL IIC T4 (–40°C ≤ Ta ≤+85°C)– FLAMEPROOF/EUROPE:
ATEX/CESI approvalII 1/2 GD T85°C, EEx d IIC T6 (–40°C ≤ Ta ≤ +75°C)
– CANADIAN STANDARDS ASSOCIATION and FACTORY MUTUAL:– Explosionproof: Class I, Div. 1, Groups A, B, C, D– Dust ignitionproof : Class II, Div. 1, Groups E, F, G– Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2– Nonincendive: Class I, Div. 2, Groups A, B, C, D– Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G
AEx ia IIC T6/T4, Zone 0 (FM)– STANDARDS AUSTRALIA (SAA): TS Approval
- Intrinsically safe Ex ia IIC T4/T5 (–20°C ≤ Ta ≤+80°C) only HART- No sparking Ex n IIC T4/T6 (–20°C ≤ Ta ≤+80°C) only HART- Flameproof Ex d IIC T4/T6 (–20°C ≤ Ta ≤+80°C)- Dust ignitionproof DIP A21 Ta T6 (–20°C ≤ Ta ≤+80°C)
– INTRINSIC SAFETY/CHINANEPSI approval Ex ia IIC T4-T6
– FLAMEPROOF/CHINANEPSI approval Ex d IIC T6
– GOST (Russia), GOST (Kazakistan), Inmetro (Brazil)based on ATEX
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
5
Optional surge protection
Up to 4kV
– voltage 1.2 µs rise time / 50 µs delay time to half value
– current 8 µs rise time / 20 µs delay time to half value
Output signal
Two–wire 4 to 20mA, user-selectable for linear or square root output,power of 3/2 or 5/2, 5th order or two 2nd order switching point selectableprogrammable polynomial output.
HART® communication provides digital process variable (%, mA orengineering units) superimposed on 4 to 20mA signal, with protocolbased on Bell 202 FSK standard.
Output current limits (to NAMUR standard)
Overload condition
- Lower limit: 3.8mA
- Upper limit: 20.5mA
Transmitter failure mode (to NAMUR standard)
The output signal can be user-selected to a value of 3.7 or 22mA ongross transmitter failure condition, detected by self-diagnostics.
In case of CPU failure the output is driven <3.7mA or >22mA.
Electrical Characteristics and Options
HART digital communication and 4 to 20mA output
Power Supply
The transmitter operates from 10.5 to 42VDC with no load and isprotected against reverse polarity connection (additional load allowsoperations over 42VDC).
For EEx ia and other intrinsically safe approval power supply mustnot exceed 30VDC.
Ripple
20mV max on a 250Ω load as per HART specifications
Load limitations
4 to 20mA and HART total loop resistance :
A minimum of 250Ω is required for HART communication.
Optional indicators
Output meter
CoMeter and Prometer LCD :
5-digit (±99999 counts) programmable with 7.6mm. high (3in),7-segment numeric characters plus sign and digital point for digitalindication of output value in percentage, current or engineer unit;
10-segment bargraph display (10% per segment) for analogindication of output in percentage;
7-digit with 6mm. high (2.3in), 14-segment alphanumericcharacters, for engineer units and configuration display
Analog : 36mm (1.4in) scale on 90°.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of analog outputin percentage.
User-definable matrix display mode with HART communication:
– process variable in pressure unit or
– output signal as percentage, current or engineering units
Display also indicates in/out transfer function, static pressure, sensortemperature and diagnostic messages and provides configurationfacilities.
R(kΩ) =Supply voltage – min. operating voltage (VDC)–––––––––––––––––––––––––––––––––––––––
22.5
(volts)
MINIMUM OPERATING VOLTAGES
10.5
with integral display
with optional output analog indicator
with optional surge protection
with ProMeter output indicator
10.7 12.3 12.5
no link on output indicator plugs
15.3
with CoMeter indicator and HART communication
13.3
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
6
PROFIBUS PA output
Device type
Pressure transmitter compliant to Profiles 3.0 Class A & B; ident.number 052B HEX.
Power supply
The transmitter operates from 9 to 32VDC , polarity independent.
For EEx ia approval power supply must not exceed 17.5VDC.Intrinsic safety installation according to FISCO model.
Current consumptionoperating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 withtransmission to Manchester II modulation, at 31.25kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part 2/DIN 19245 part 1–3.
Output update time
25ms
Function blocks
2 analog input, 1 transducer, 1 physical
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for indication of output inpercentage of the analog input function block assigned to the primaryvariable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of analog input functionblocks
Display also indicates diagnostic messages and providesconfiguration facilities.Secondary variable, static pressure and sensor temperature can beread.
Transmitter failure mode
On gross transmitter failure condition, detected by self-diagnostics,the output signal can be driven to defined conditions, selectable by theuser as safe, last valid or calculated value. If electronic failure or shortcircuit occur the transmitter consumption is electronically limited at adefined value (20mA approx), for safety of the network.
FOUNDATION Fieldbus output
Device type
LINK MASTER DEVICE
Link Active Scheduler (LAS) capability implemented.
Power supply
The transmitter operates from 9 to 32VDC, polarity independent.
For EEx ia approval power supply must not exceed 24VDC (entitycertification) or 17.5VDC (FISCO certification), according to FF–816.
Current consumption
operating (quiescent): 10.5mA
fault current limiting: 20mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 withtransmission to Manchester II modulation, at 31.25kbit/sec.
Function blocks/execution period
2 enhanced Analog Input blocks/25ms max (each)1 enhanced PID block/40ms max.1 standard ARitmetic block/25ms1 standard Input Selector block/25ms1 standard Control Selector block/25ms1 standard Signal Characterization block/25ms1 standard Integrator/Totalizer block/25ms
Additional blocks
1 enhanced Resource block
1 custom Pressure with calibration transducer block
1 custom Advanced Diagnostics transducer block including Plugged Input Line Detection
1 custom Local Display transducer block
Number of link objects35
Number of VCRs
35
Output interface
FOUNDATION fieldbus digital communication protocol to standard H1,compliant to specification V. 1.6; FF registration in progress.
Integral display
LCD, 15 lines x 56 column dot matrix providing 2 lines indication as
– top: 5-digit (numeric) plus sign or 7-digit alphanumeric
– bottom: 7-digit alphanumeric
and additional 50-segment bargraph for percentage indication of theanalog input function block output, assigned to the primary variable.
User-definable matrix display mode:
– process variable in pressure units or
– primary variable in engineering units (output of transducer block) or
– output as percentage or engineering units of one or more selected function blocks
Display also indicates diagnostic messages. Secondary variable,static pressure and sensor temperature can be read.
Transmitter failure mode
The output signal is "frozen" to the last valid value on gross transmitterfailure condition, detected by self-diagnostics which also indicate aBAD conditions. If electronic failure or short circuit occur the transmitterconsumption is electronically limited at a defined value (20mA approx),for safety of the network.
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
7
Operating influences
Temperature effect
per 20K (36°F) ambient temperature change on transmitter sensorbetween the limits of –20°C to +65°C (–4 to +150°F)
Transmitter effect:
– ±(0.04% URL + 0.065% span)
Direct mount seal additional effect:
– 1 1/2in beverage seal (tx + seal effect): ± (0.15% URL + 0.15% span)
per 20K (36°F) process temperature change on seal diaphragmbetween the process operating temperature limits
per 20K (36°F) process temperature change on seal diaphragmbetween the process operating temperature limits of –25 to 120°C(–13 to 248°F)
– 1 1/2in beverage seal: 0.2kPa, 2mbar, 0.8inH2O
Multiply by 1.5 the above values for 20K (36°F) change between thelimits of –40 to –25°C (–40 to –13°F) and of +120 to +150°C (+248 to302°F).
Optional CoMeter and ProMeter ambient temperature
Total reading error per 20K (36°F) change between the ambient limitsof –20 and +70°C (-4 and +158°F) :
±0.15% of max span (16mA).
Static pressure (zero errors can be calibrated out at line pressure)
seal effect additional to transmitter sensor effect applicable fordifferential measurement per 2MPa, 20bar or 290psi.
Model 264DG direct mount seal only– zero error: ±0.15% of URL– span error: ±0.15% of readingModel 264DG direct mount plus remote seal– zero error: ±0.20% of URL– span error: ±0.20% of readingMultiply by 1.5 the errors for sensor seal combinations marked (•)
Supply voltage
Within voltage/load specified limits the total effect is less than0.005% of URL per volt.
Load
Within load/voltage specified limits the total effect is negligible.
Electromagnetic field
Total effect : less than 0.10% of span from 20 to 1000MHz and forfield strengths up to 30V/m when tested with shielded conduit andgrounding, with or without meter.
Common mode interference
No effect from 100Vrms @ 50Hz, or 50VDC
Vibration effect
±0.10% of URL (according to IEC 61298–3)
URLSpan
URLSpan
URLSpan
Performance specificationsStated at reference condition to IEC 60770 ambient temperature of 20°C(68°F), relative humidity of 65%, atmospheric pressure of 1013hPa(1013mbar), mounting position with vertical diaphragm and zero basedrange for transmitter with isolating diaphragms in AISI 316 L ss and siliconeoil fill and HART digital trim values equal to 4–20mA span end points, inlinear mode.
Unless otherwise specified, errors are quoted as % of span.
Some performance data are affected by the actual turndown (TD) as ratiobetween Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODEPROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TOOPTIMIZE PERFORMANCE CHARACTERISTICS.
Accuracy rating% of calibrated span, including combined effects of terminal basedlinearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function block outscalerange
Using direct mount seal sizes <F80/3in– ±0.075% for TD from 1:1 to 10:1
(±0.10% for sensor code F ±0.10% for sensor code E for TD from 1:1 to 5:1)
– ±0.0075% x for TD from 10:1 to 20:1
(±0.01% x for sensor code F
±0.02% x for sensor code E for TD from 5:1 to 10:1)
Using direct mount seal sizes ≥F80/3in– ±0.075% for TD from 1:1 to 10:1
(±0.10% for sensor code E for TD from 1:1 to 5:1)
– ±0.0075% x for TD from 10:1 to 20:1
(±0.02% x for sensor code E for TD from 5:1 to 10:1)
Multiply the values by 1.5 for sensor/seal combination marked (•) and fortransmitter with direct mount seal plus one remote seal.
URLSpan
URLSpan
ezisepytlaeSrorrE
aPk rabm Hni 20
05F/ni2yratinaS 9.0 9 6.3
08F/ni4–3yratinaS 60.0 6.0 42.0
ezisepytlaeSrorrE
aPk rabm Hni 20
05F/ni2yratinaS 9.0 9 6.3
08F/ni4–3yratinaS 20.0 2.0 80.0
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
8
Physical Specification(Refer to ordering information sheets for variant availability related tospecific model or versions code)
Materials
Model 264DG only
Low pressure side process isolating diaphragms (*)
AISI 316 L ss
A remote seal can be selected with required diaphragm (refer to highpressure side).
Low pressure side process flanges, adapters, plugs and drain/ventvalves (*)
AISI 316 L ss; Hastelloy C276™; Monel 400™.
Bolts and nuts
AISI 316 ss bolts and nuts Class A4–50 per UNI 7323 (ISO 3506), incompliance with NACE MR0175 Class II.
Gaskets (*)
Viton™; PTFE.
Model 264DG/HG/NG
High pressure side process diaphragm (direct mount seal) (*)
AISI 316 L ss.
High pressure side fill fluid (direct mount seal)
Silicone oil-DC200™, Vegetable oil-Neobee M-20™, GlycerinWater, Mineral oil-MARCOL 82™.
Sensor fill fluid
Silicone oil (DC200™).
Sensor housing
AISI 316 L ss.
Electronic housing and covers
Barrel version
– Copper-free content aluminium alloy with baked epoxy finish;
– Low-copper content aluminium alloy with baked epoxy finish;
– AISI 316 L ss.
DIN version
– Low-copper content aluminium alloy with baked epoxy finish.
Covers O-ring
Buna N.
Local zero and span adjustments:
Glass filled polycarbonate plastic (removable).
Tagging
AISI 316ss data plate attached to the electronics housing.
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
9
CalibrationStandard: at maximum span, zero based range, ambient temperatureand pressure;
Optional: at specified range and ambient conditions.
Optional extras
Output indicator
plug-in rotatable type, LCD or analog.
Supplemental customer tag
AISI 316 ss tag screwed/fastened to the transmitter for customer's tagdata up to a maximum of 20 characters and spaces on one line for tagnumber and tag name, and up to a maximum of 3 spaced strings of 10characters each for calibration details (lower and upper values plusunit). Special typing evaluated on request for charges.
Surge protection (only as external unit for PROFIBUS PA and FF)
Process sealing gasket
V-band clamps and fittings (tank spud)
Test Certificates (test, design, calibration, material traceability)
Tag and manual language
Communication connectors
Process connectionson conventional flanges : 1/4 – 18 NPT on process axis
on adapters : 1/2 – 14 NPT on process axis
fixing threads: 7/16 – 20 UNF at 41.3mm centre distance
on seal side
Triclamp: 2in, 3in or 4in
Union nut: F50 or F80 to DIN 11851
Cherry Burrell: 2in, 3in or 4in
Sanitary: 4in flush diaphragm or 4in extended (2in, 4in or 6in) diaphragm
Beverage bolted: 1 1/2in flush diaphragm with integral 6 holesflanged connection
Electrical connectionsTwo 1/2 – 14 NPT or M20x1.5 or PG 13.5 or 1/2 GK threadedconduit entries, direct on housing.
Special communication connector (on request)
– HART : straight or angle Harting Han connector and one plug.
– FOUNDATION Fieldbus, PROFIBUS PA: M12x1 and 7/8.
Terminal block
HART version: three terminals for signal/external meter wiring up to2.5mm2 (14AWG) and three connection points for test andcommunication purposes.
Fieldbus versions: two terminals for signal wiring (bus connection)up to 2.5mm2 (14AWG)
Grounding
Internal and external 6mm2 (10AWG) ground termination points areprovided.
Mounting positionTransmitter can be mounted in any position.Electronics housing may be rotated to any position. A positive stopprevents over travel.
Mass (without options)5kg to 8kg approx (11 to 18lb) according to specified seal(s)options; add 1.5kg (3.4lb) for AISI housing.Add 650g (1.5lb) for packing.
PackingCarton
™ Hastelloy is a Cabot Corporation trademark
™ Monel is an International Nickel Co. trademark
™ Viton is a Dupont de Nemour trademark
™ DC200 is a Dow Corning Corporation trademark
™ Neobee M20 is a Stepan Company trademark
™ Marcol is a Esso Italiana trademark (*) Wetted parts of the transmitter.
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
10
ConfigurationTransmitter with HART communication and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's specified range.Calibrated range and tag number are stamped on the tag plate. If acalibration range and tag data are not specified, the transmitter will besupplied with the plate left blank and configured as follows:
Engineering Unit kPa4 mA Zero20 mA Upper Range Limit (URL)Output LinearDamping 1 sec.Transmitter failure mode UpscaleSoftware tag (8 characters max) BlankOptional LCD indicator/display 0 to 100.0% linear
Any or all the above configurable parameters, including Lower range–valueand Upper range-value which must be the same unit of measure, can beeasily changed using the HART hand–held communicator or by a PCrunning the configuration software SMART VISION with DTM for 2600T.The transmitter database is customized with specified flange type andmaterial, O–ring and drain/vent materials and meter code option.Custom configuration (option)The following data may be specified in addition to the standardconfiguration parameters:
Descriptor 16 alphanumeric charactersMessage 32 alphanumeric charactersDate Day, month, year
Transmitter with PROFIBUS PA communicationTransmitters are factory calibrated to customer's specified range.Calibrated range and tag number are stamped on the tag plate. If acalibration range and tag data are not specified, the transmitter will besupplied with the plate left blank and configured as follows:
Measure Profile PressureEngineering Unit kPaOutput scale 0% Lower Range Limit (LRL)Output scale 100% Upper Range Limit (URL)Output LinearHi-Hi Limit Upper Range Limit (URL)Hi Limit Upper Range Limit (URL)Low Limit Lower Range Limit (LRL)Low-Low Limit Lower Range Limit (LRL)Limits hysteresis 0.5% of output scalePV filter 0 sec.Address (settable by local key) 126Tag 32 alphanumeric characters
Any or all the above configurable parameters, including Lower range-valueand Upper range–value which must be the same unit of measure, can beeasily changed by a PC running the configuration software SMART VISIONwith DTM for 2600T.The transmitter database is customized with specified flange type andmaterial, O–ring and drain/vent materials and meter code option.Custom configuration (option)The following data may be specified in addition to the standardconfiguration parameters:
Descriptor 32 alphanumeric charactersMessage 32 alphanumeric charactersDate Day, month, year
Transmitter with FOUNDATION FieldbuscommunicationTransmitters are factory calibrated to customer's specified range.Calibrated range and tag number are stamped on the tag plate. If acalibration range and tag data are not specified, the transmitter will besupplied with the plate left blank and the analog input function block FB1is configured as follows:
Measure Profile PressureEngineering Unit kPaOutput scale 0% Lower Range Limit (LRL)Output scale 100% Upper Range Limit (URL)Output LinearHi-Hi Limit Upper Range Limit (URL)Hi Limit : Upper Range Limit (URL)Low Limit Lower Range Limit (LRL)Low-Low Limit Lower Range Limit (LRL)Limits hysteresis 0.5% of output scalePV filter time 0 sec.Tag 32 alphanumeric characters
The analog input function block FB2 is configured for the sensor tempe-rature measured in °C. Any or all the above configurable parameters,including the range values, can be changed using any host compliant toFOUNDATION fieldbus. The transmitter database is customized withspecified flange type and material, O–ring and drain/vent materials andmeter code option.
For any protocol available engineering units of pressure measure are :Pa, kPa, MPainH2O@4°C, mmH2O@4°C, psiinH2O@20°C, ftH2O@20°C, mmH2O@20°CinHg, mmHg, Torrg/cm2, kg/cm2, atmmbar, bar
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
11
MOUNTING DIMENSIONS (not for construction unless certified) – dimensions in mm (in)264DG with direct mount Triclamp seal
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Min. clearanceto removethe cover
Output meterhousing
264HG/NG with direct mount Triclamp seal
pmalcirT
ni2 ni3 ni4
)aid(A )2.2(3.65 )62.3(38 )43.4(3.011
)aid(B )5.2(46 )85.3(19 86.4(911
18 (0
.71)10
0 (3
.94)
BA
2.85
(0
.11)
16(0
.63)
25 (0
.98)
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
35(1
.38)
BA
71 (2.80) 113 (4.45)
2.85 (0.11)
25 (0.98)
135
(5.3
1)
+
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
Integral displayhousing
Drain/ventValve
Processconnection
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
12
264HG/NG with direct mount Union Nut seal
264DG with direct mount Union Nut seal
100
(3.9
4)
B
A
16(0
.63)
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
18 (0
.71)
35(1
.38)
C
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Min. clearanceto removethe cover
Output meterhousing
tuNnoinU
05F 08F
)aid(A )86.2(86 )39.3(001
)DR(B )70.3(87 )33.4(011
C )36.0(61 )47.0(91
71 (2.80) 113 (4.45) C
135
(5.3
1)
+
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
BA
Integral displayhousing
Drain/ventValve
Processconnection
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
13
71 (2.80) 113 (4.45)
135
(5.3
1)
+
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
B
AC D
E
FGH
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Integral displayhousing
Min. clearanceto removethe cover
Output meterhousing
Drain/ventValve
Processconnection
264DG with direct mount Cherry Burrell seal
18 (0
.71)10
0 (3
.94)
16(0
.63)
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
35(1
.38)
E
FH
G
B
A
C
D
264HG/NG with direct mount Cherry Burrell seal
eziS)ni(mmSNOISNEMID
)aid(A )aid(B )aid(C )aid(D E F G H
ni2 )46.2(76 )2.2(65 )56.1(24 )42.2(75 )31.0(2.3 )62.0(5.6 )94.0(5.21 )21.0(3
ni3 )78.3(4.89 )91.3(18 )58.2(24.27 )3.3(8.38 )90.0(4.2 )13.0(9.7 )95.0(51 )21.0(3
ni4 )88.4(421 )83.4(52.111 )58.2(24.27 )3.4(3.901 90.0(4.2 )13.0(9.7 )95.0(51 )21.0(3
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
14
71 (2.80) 113 (4.45)
135
(5.3
1)
+
127 (5.00)
dia
36(1
.41)
10 (0.39)
dia
72 (2
.83)
dia
100
(3.9
3)
dia
152
(5.9
8)
A5.6 (0.22)
dia
132.
6 (5
.22)
264DG with direct mount Sanitary Extended seal
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Min. clearanceto removethe cover
Drain/ventValve
Processconnection
264HG/NG with direct mount Sanitary Extended seal
eziS)ni(mmsnoisnemiD
A
ni2 )1.2(3.35
ni4 )1.4(1.401
ni6 )1.6(9.451
18 (0
.71)10
0 (3
.94)
16(0
.63)
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
35(1
.38)
dia 72 (2.83)
dia 100 (3.93)
dia 152 (5.98)
A
10 (0
.39)
5.6(
0.22
)
dia 132.6 (5.22)
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
15
71 (2.80) 113 (4.45)
135
(5.3
1)
+
127 (5.00)
dia
72 (2
.83)
dia
110
(4.3
3)
dia
152.
4 (6
)
18.5
(0.72)
dia
119
(4.6
8)
dia
85.5
(3.3
6)
8 (0.31) for thin wall13 (0.51) for thick wall
19.3(0.75)
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Min. clearanceto removethe cover
Drain/ventValve
Processconnection
264HG/NG with direct mount Sanitary Flush seal
264DG with direct mount Sanitary Flush seal
18 (0
.71)10
0 (3
.94)
16(0
.63)
127 (5.00)
17 (0.67)26 (1.02)
17 (0.67)36 (1.42)
35(1
.38)
dia 72 (2.83)
dia 110 (4.33)
dia 152.4 (6)
19.3
(0.7
5)
18.5
(0.7
2)8
(0.3
1) fo
r thi
n w
all
13 (0
.51)
for t
hick
wal
l
dia 119 (4.68)
dia 85.5 (3.36)
dia 36 (1.41)
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
16
264HG/NG with direct mount Beverage seal
18 (0
.71)
100
(3.9
4)
16(0
.63)
45.1
(1
.78)
dia 44.5(1.75)
dia 52.2(2.06)
dia 63.5 (2.50)
5.1
(0.2
0)
N° 6 holes M6(at 60° equally spaced)
dia 64 (2.52)
dia 39.8(1.57)
36 (1
.42)
dia 52.2 (2.06)
dia 44.7(1.76)
N° 6 holesdia 6.5
12 (0
.47)
4 (0
.16)
dia 39 (1.54)
dia 34 (1.34)
1.3
(0.0
6)
127 (5.00)
17 (0.67)
26 (1.02) 36 (1.42)17 (0.67)
Certificationlabel
Identification tagAdjustments
Terminalside
Electronicside
Integraldisplayhousing
Min. clearanceto removethe cover
Output meterhousing Flanged tank
spud
Gasket seatdetail
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
17
Electrical connectionsHART Version
FIELDBUS Versions
+
+
-
-
++
--691HT
A B C
1
D E F
2
G H I
3
J K L
4
M N O
5
P Q R
6
S T U
7
V W X
8
Y Z #
9
@ % & /
0
+-
PV
REVIEW SERIALLINK
TRIM
F1 F2 F3 F4
CONF
M
Kent-Taylor
0
43
56 7 8
9
1020
40
0
60
100%
2 80
M+
-
- 1
54 6
23 8
7
+
TEST COMM
Internal groundtermination point
Fieldbus line(polarity independent)
External groundtermination point
Test points4 to 20mA
Hartingpin (male)
identification
Internal groundtermination point
External groundtermination point
Hand-heldcommunicator
GND
Line load
Remoteindicator
Powersource
250 ohm min
Receiver
HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistanceis 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications
Optional
BUS CONNECTIONS
2
1
4
3
1 3
42
7/8” connector
M12 x 1 connector
NOITACIFITNEDI)elam(NIPNOITADNUOF
subdleiFSUBIFORP
AP11111222223333344444
-FF+FF
DLEIHSDNUORG
+APDNUORG
–APDLEIHS
CONNECTOR IS SUPPLIED LOOSE WITHOUT MATING FEMALE PLUG
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
18
BASIC ORDERING INFORMATION model 264DG Differential /Gauge Pressure Transmitter withSanitary and Food direct mount sealSelect one character or set of characters from each category and specify complete catalog number.Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1– ts 5ot ht sretcarahc2 6 4 D G X X X X X X d'tnoC
%570.0YCARUCCAESAB–laestnuomtceriddoofdnayratinashtiwrettimsnarTerusserPeguaGlaitnereffiD
–stimilnapS-ROSNES 6 ht retcarahcaPk61dna45.0
aPk04dna76.0aPk56dna1.1
aPk061dna76.2aPk006dna01
aPk0042dna04aPk0008dna431
rabm061dna4.5rabm004dna7.6rabm056dna11
rabm0061dna7.62rab6dna1.0
rab42dna4.0rab08dna43.1
Hni46dna41.2 2OHni061dna76.2 2OHni062dna53.4 2OHni246dna7.01 2Oisp78dna54.1isp843dna8.5
isp0611dna4.91
EFGHMPQ
noitcennocgnitnuoM/eziS-EDISERUSSERPHGIH 7– ht retcarahc
05F–15811NIDtunnoinU08F–15811NIDtunnoinU
pmalcirTni2pmalcirTni3pmalcirTni4
llerruByrrehCni2llerruByrrehCni3llerruByrrehCni4
mgarhpaidhsulfyratinaSni4mgarhpaid)ni2(dednetxeyratinaSni4mgarhpaid)ni4(dednetxeyratinaSni4mgarhpaid)ni6(dednetxeyratinaSni4
ABFGHLMNPQRS
diulflliF–EDISERUSSERPHGIH 8– ht retcarahc
lioenociliS)devorppaADF(liolareniM
)devorppaADF(lioelbategeV)devorppaADF(retaW-nirecylG
SWAB
)strapdettew(diulflliF/lairetammgarhpaidediserusserpwoL 9– ht retcarahc
ssL613ISIA)dettewton(ssL613ISIA
lioenociliSlioenociliS )yletarapesdetouqebotlaesetomereno(
SR
)strapdettew(noitcennocdnalairetamsretpada/segnalfssecorpediswoL – 01 ht retcarahc
)noitcennoclatnoziroH(ssL613ISIA)noitcennoclatnoziroH(ssL613ISIA
)noitcennoclatnoziroH(™672CyolletsaH)noitcennoclatnoziroH(™672CyolletsaH
)noitcennoclatnoziroH(™004lenoM)noitcennoclatnoziroH(™004lenoM
noitcurtsnocslaesowtrofegnalfgnisolc613ISIA
1/4 (tceridf-TPN81– 7/ 61 )gnillird.S.UFNU02–1/2 (retpadahguorhtf-TPN41– 7/ 61 )gnillird.S.UFNU02–1/4 (tceridf-TPN81– 7/ 61 )gnillird.S.UFNU02–1/2 (retpadahguorhtf-TPN41– 7/ 61 )gnillird.S.UFNU02–1/4 (tceridf-TPN81– 7/ 61 )gnillird.S.UFNU02–1/2 (retpadahguorhtf-TPN41– 7/ 61 )gnillird.S.UFNU02–
)1etoN()1etoN()1etoN()1etoN()1etoN()1etoN()2etoN(
ECANECANECANECANECANECANECAN
ABDEGHR
)strapdettew(teksagediswoL/stloB 11– ht retcarahc
)aPM61=PWM(–)ECAN(ss613ISIA)aPM61=PWM(–)ECAN(ss613ISIA
noitcurtsnocslaesowtrofteksagtuohtiw)aPM61=PWM(–)ECAN(ss613ISIA
™notiVEFTP
)1etoN()1etoN()2etoN(
ECANECANECAN
34R
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
19
GD462ledomNOITAMROFNIGNIREDROCISAB X X
noitcennoclacirtcelednalairetamgnisuoH 21– ht retcarahc
)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevNID(yollamuinimulA)noisrevNID(yollamuinimulA)noisrevNID(yollamuinimulA
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocsubdleiF)02MC(5.1x02M
5.31gProtcennocnaHgnitraH
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg()ylnoesopruplareneg()ylnoesopruplareneg()ylnoesopruplareneg(
)3etoN()3etoN(
)3etoN()3etoN(
)3etoN(
)3etoN(
ABDCEGHLNMPRSTVUZJYK
snoitpolanoitiddA/tuptuO 31– ht retcarahc
Am02ot4dnanoitacinummoclatigidTRAHAm02ot4dnanoitacinummoclatigidTRAH
APSUBIFORPAPSUBIFORP
subdleiFNOITADNUOFsubdleiFNOITADNUOF
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)5,4setoN()4etoN(
)5,4setoN()5etoN(
)5,4setoN()5etoN(
H1P2F3
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
20
ADDITIONAL ORDERING INFORMATION for model 264DGAdd one or more 2-digit code(s) after the basic ordering information to select all required options
XX XX XX XX XX XX XX XX XX XX XX d'tnoC
)strapdettew()noitisopdnalairetam(evlavtnev/niarDssL613ISIAssL613ISIAssL613ISIA
™672CyolletsaH™672CyolletsaH™672CyolletsaH
™004lenoM™004lenoM™004lenoM
sixassecorpnopotedisegnalfno
mottobedisegnalfnosixassecorpno
potedisegnalfnomottobedisegnalfno
sixassecorpnopotedisegnalfno
mottobedisegnalfno
)6etoN()6etoN()6etoN()7etoN()7etoN()7etoN()8etoN()8etoN()8etoN(
ECANECANECANECANECANECANECANECANECAN
1V2V3V4V5V6V7V8V9V
noitacifitreclacirtcelEaixEEytefaScisnirtnI–DG1yrogetaCIIpuorGXETA
dxEEfoorpemalF–DG2/1yrogetaCIIpuorGXETA)9etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyT–DG3yrogetaCIIpuorGXETA
ylno()ASC(noitaicossAdradnatSnaidanaC 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–)subdleiFNOITADNUOFdnaAPSUBIFORProfnxEdnaaixEtoN(AASailartsuAsdradnatS
htiwylno(lavorppa)MF(lautuMyrotcaF 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–foorpemalFdnaytefaScisnirtnI-XETAdenibmoC
)3edoctuptuOFFrofelbaliavatoN(aixEytefaScisnirtnI-)anihC(ISPENdxEfoorpemalF-)anihC(ISPEN
aixEE)aissuR(TSOGdxEE)aissuR(TSOG
aixEE)natsikazaK(TSOGdxEE)natsikazaK(TSOG
)9etoN(aixEE)lizarB(ortemnI)9etoN(dxEE)lizarB(ortemnI)9etoN(LnxEE)lizarB(ortemnI
1E2E3E4E5E6E7EYEZE1W2W3W4W5W6W7W
retemtuptuO
noitarbilacdradnatS,reteMorPnoitarbilaclaicepS,reteMorP
elacs%001–0raenilrotacidnituptuogolanAelacs01–0toorerauqsrotacidnituptuogolanA
)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA)elacstoorerauqsrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP)noitarugifnocremotsuc–reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)9etoN()9etoN()9etoN()9etoN()9etoN()9etoN()9etoN()9etoN(
1D2D3D4D5D6D7D8D
DCLlargetnIyalpsidlargetniDCLlatigiD 1L
egruS)Am02-4/TRAHroflanretnI(rotcetorPtneisnarT/egruS
ylnosubdleiFNOITADNUOFdnaAPSUBIFORProfesooldeilppuslanretxE(rotcetorPtneisnarT/egruShtiwelbatius 1/2 )TSUDon,snoitacifitrecASCdnaMF,XETAhtiwdnanoitcennoclacirtcele02MdnaTPN41–
1S
launamgnitarepOnamreG
nailatIhcnerF
1M2M4M
egaugnalgat&slebaLnamreG
nailatIhcnerF
1T2T4T
etalpgatlanoitiddAetalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoCHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°4taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°4taisp/O
motsuC
2N3N4N5N6N
setacifitreC
)tniop-9(noitarbilacfoB.1.3–40201NEetacifitrecnoitcepsnIngisedtnemurtsnifo1.2–40201NEredroehthtiwecnailpmocfoetacifitreC
1C6C
ytilibaecartlairetaM
strapdettewssecorpfo1.2–40201NEredroehthtiwecnailpmocfoetacifitreCstrapdettewssecorpfoB.1.3–40201NEetacifitrecnoitcepsnI
1H3H
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
21
Note 1: Not available with low side diaphragm code R
Note 2: Not available with low side diaphragm code S
Note 3: Select type in additional ordering code
Note 4: Not available with Electronic Housing code Z, R, G
Note 5: Not available with Electronic Housing code P, E, K
Note 6: Not available with Process flanges/adapters code D, E, G, H, R
Note 7: Not available with Process flanges/adapters code A, B, G, H, R
Note 8: Not available with Process flanges/adapters code A, B, D, E, R
Note 9: Not available with PROFIBUS PA and FF output code 2 or 3
Note 10: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B, J, Y
™ Hastelloy is a Cabot Corporation trademark
™ Monel is an International Nickel Co. trademark
™ Viton is a Dupont de Nemour trademark
Standard delivery items (can be differently specified by additional ordering code)– Adapters supplied loose
– Plug on axis (no drain/vent valves)
– General purpose (no electrical certification)
– No meter/display, no mounting bracket, no surge protection
– English manual and labels
– Configuration with kPa and deg. C units
– No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'SRESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
GD462ledomgniredrolanoitiddA XX XX XX
rotcennoC
)gulpelamefgnitamtuohtiwesooldeilppus(-)subdleiFNOITADNUOFrofdednemmoceR(8/7subdleiF)gulpelamefgnitamtuohtiwesooldeilppus(-)APSUBIFORProfdednemmoceR(1x21MsubdleiF
yrtnethgiarts–naHgnitraHyrtneelgna–naHgnitraH
)01,5setoN()01,5setoN()01,4setoN()01,4setoN(
1U2U3U4U
sgnittiF/pmalC
)pmalcirTni2rof(pmalCdnab-Vni2)pmalcirTni3rof(pmalCdnab-Vni3
)hsulfyratinaSni4dnallerruByrrehCni4,pmalcirTni4rof(pmalCdnab-Vni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)81.0(mm7.4otpullawknat,dupsknaTni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)73.0(mm5.9otpullawknat,dupsknaTni4
)laesdednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4)laesni2dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni2rofdupsknaT)laesni4dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni4rofdupsknaT)laesni6dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni6rofdupsknaT
1J2J3J4J5J6J7J8J9J
teksaG
)laesdednetxeyratinaSni4rof(001NDteksagenelyporpenelyhtE)laestunnoinU05Frof(05NDteksagenelyporpenelyhtE)laestunnoinU08Frof(08NDteksagenelyporpenelyhtE
)hsulfyratinasni4rof(teksag™notiV)hsulfyratinasni4rof(teksaganuB
1K3K4K6K7K
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
22
BASIC ORDERING INFORMATION model 264HG Gauge Pressure Transmitter with sanitary, foodand beverage direct mount sealSelect one character or set of characters from each category and specify complete catalog number.Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1– ts 5ot ht sretcarahc 2 6 4 H G X X X X X X
%570.0YCARUCCAESAB–laestnuomtceridegarevebdnadoof,yratinashtiwrettimsnarTerusserPeguaG
–stimilnapS-ROSNES 6 ht retcarahcaPk56dna1.1
aPk061dna76.2aPk006dna01
aPk0042dna04aPk0008dna431
rabm056dna11rabm0061dna7.62
rab6dna1.0rab42dna4.0
rab08dna43.1
Hni062dna53.4 2OHni246dna7.01 2Oisp78dna54.1isp843dna8.5
isp0611dna4.91
GHMPQ
)dettewton(diulFlliF/lairetammgarhpaiD 7– ht retcarahcssL613ISIA lioenociliS R
noitcennocgnitnuoM/eziS-EDISERUSSERPHGIH 8– ht retcarahc
05F–15811NIDtunnoinU08F–15811NIDtunnoinU
pmalcirTni2pmalcirTni3pmalcirTni4
llerruByrrehCni2llerruByrrehCni3llerruByrrehCni4
mgarhpaidhsulfyratinaSni4mgarhpaid)ni2(dednetxeyratinaSni4mgarhpaid)ni4(dednetxeyratinaSni4mgarhpaid)ni6(dednetxeyratinaSni4
laesdetlobnoitacilppaegareveB
ABFGHLMNPQRST
diulflliF–EDISERUSSERPHGIH 9– ht retcarahc
lioenociliS)devorppaADF(liolareniM
)devorppaADF(lioelbategeV)devorppaADF(retaW-nirecylG
SWAB
noitcennoclacirtcelednalairetamgnisuoH 01– ht retcarahc
)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocsubdleiF
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg(
)1etoN()1etoN(
)1etoN()1etoN(
)1etoN(
ABDCEGHLNMPRSTVUZ
snoitpolanoitiddA/tuptuO 11– ht retcarahc
Am02ot4dnanoitacinummoclatigidTRAHAm02ot4dnanoitacinummoclatigidTRAH
APSUBIFORPAPSUBIFORP
subdleiFNOITADNUOFsubdleiFNOITADNUOF
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)3,2setoN()2etoN(
)3,2setoN()3etoN(
)3,2setoN()3etoN(
H1P2F3
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
23
ADDITIONAL ORDERING INFORMATION for model 264HGAdd one or more 2-digit code(s) after the basic ordering information to select all required options
XX XX XX XX XX XX XX XX XX XX XX d'tnoCnoitacifitreclacirtcelE
aixEEytefaScisnirtnI–DG1yrogetaCIIpuorGXETAdxEEfoorpemalF–DG2/1yrogetaCIIpuorGXETA
)4etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyT–DG3yrogetaCIIpuorGXETAylno()ASC(noitaicossAdradnatSnaidanaC 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–
)subdleiFNOITADNUOFdnaAPSUBIFORProfnxEdnaaixEtoN(AASailartsuAsdradnatShtiwylno(lavorppa)MF(lautuMyrotcaF 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–
foorpemalFdnaytefaScisnirtnI-XETAdenibmoC)3edoctuptuOFFrofelbaliavatoN(aixEytefaScisnirtnI-)anihC(ISPEN
dxEfoorpemalF-)anihC(ISPENaixEE)aissuR(TSOGdxEE)aissuR(TSOG
aixEE)natsikazaK(TSOGdxEE)natsikazaK(TSOG
)4etoN(aixEE)lizarB(ortemnI)4etoN(dxEE)lizarB(ortemnI)4etoN(LnxEE)lizarB(ortemnI
1E2E3E4E5E6E7EYEZE1W2W3W4W5W6W7W
retemtuptuO
noitarbilacdradnatS,reteMorPnoitarbilaclaicepS,reteMorP
elacs%001–0raenilrotacidnituptuogolanA)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP)noitarugifnocremotsuc–reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)4etoN()4etoN()4etoN()4etoN()4etoN()4etoN(
1D2D3D5D7D8D
DCLlargetnIyalpsidlargetniDCLlatigiD 1L
egruS)Am02-4/TRAHroflanretnI(rotcetorPtneisnarT/egruS
ylnosubdleiFNOITADNUOFdnaAPSUBIFORProfesooldeilppuslanretxE(rotcetorPtneisnarT/egruShtiwelbatius 1/2 )TSUDon,snoitacifitrecASCdnaMF,XETAhtiwdnanoitcennoclacirtcele02MdnaTPN41–
1S
launamgnitarepOnamreG
nailatIhcnerF
1M2M4M
egaugnalgat&slebaLnamreG
nailatIhcnerF
1T2T4T
etalpgatlanoitiddAetalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoCHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°4taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°4taisp/O
motsuC
2N3N4N5N6N
setacifitreC
)tniop-9(noitarbilacfoB.1.3–40201NEetacifitrecnoitcepsnIngisedtnemurtsnifo1.2–40201NEredroehthtiwecnailpmocfoetacifitreC
1C6C
ytilibaecartlairetaM
strapdettewssecorpfo1.2–40201NEredroehthtiwecnailpmocfoetacifitreCstrapdettewssecorpfoB.1.3–40201NEetacifitrecnoitcepsnI
1H3H
rotcennoC
)gulpelamefgnitamtuohtiwesooldeilppus(-)subdleiFNOITADNUOFrofdednemmoceR(8/7subdleiF)gulpelamefgnitamtuohtiwesooldeilppus(-)APSUBIFORProfdednemmoceR(1x21MsubdleiF
yrtnethgiarts–naHgnitraHyrtneelgna–naHgnitraH
)5,3setoN()5,3setoN()5,2setoN()5,2setoN(
1U2U3U4U
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
24
Note 1: Select type in additional ordering code
Note 2: Not available with Electronic Housing code Z, R, G
Note 3: Not available with Electronic Housing code P, E
Note 4: Not available with PROFIBUS PA and FF output code 2 or 3
Note 5: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B
™ Viton is a Dupont de Nemour trademark
Standard delivery items (can be differently specified by additional ordering code)– General purpose (no electrical certification)
– No meter/display, no mounting bracket, no surge protection
– English manual and labels
– Configuration with kPa and deg. C units
– No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'SRESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
XX XX
sgnittiF/pmalC
)pmalcirTni2rof(pmalCdnab-Vni2)pmalcirTni3rof(pmalCdnab-Vni3
)hsulfyratinaSni4dnallerruByrrehCni4,pmalcirTni4rof(pmalCdnab-Vni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)81.0(mm7.4otpullawknat,dupsknaTni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)73.0(mm5.9otpullawknat,dupsknaTni4
)laesdednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4)laesni2dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni2rofdupsknaT)laesni4dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni4rofdupsknaT)laesni6dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni6rofdupsknaT
1rof(seloh6htiwdupsknatdegnalF 1/2 )laesegarevebni
1J2J3J4J5J6J7J8J9JAJ
teksaG
)laesdednetxeyratinaSni4rof(001NDteksagenelyporpenelyhtE1rof(teksagenelyporpenelyhtE 1/2 )laesegarevebni
)laestunnoinU05Frof(05NDteksagenelyporpenelyhtE)laestunnoinU08Frof(08NDteksagenelyporpenelyhtE
)hsulfyratinasni4rof(teksag™notiV)hsulfyratinasni4rof(teksaganuB
1K2K3K4K6K7K
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
25
BASIC ORDERING INFORMATION model 264NG Absolute Pressure Transmitter with sanitary, foodand beverage direct mount sealSelect one character or set of characters from each category and specify complete catalog number.Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1– ts 5ot ht sretcarahc 2 6 4 N G X X X X X X
%570.0YCARUCCAESAB–laestnuomtceridegarevebdnadoof,yratinashtiwrettimsnarTerusserPetulosbA
–stimilnapS-ROSNES 6 ht retcarahcaPk56dna1.1
aPk061dna76.2aPk006dna01
aPk0042dna04aPk0008dna431
rabm056dna11rabm0061dna7.62
rab6dna1.0rab42dna4.0
rab08dna43.1
gHmm084dna8gHmm0021dna02
isp78dna54.1isp843dna8.5
isp0611dna4.91
GHMPQ
)dettewton(diulFlliF/lairetammgarhpaiD 7– ht retcarahcssL613ISIA lioenociliS R
noitcennocgnitnuoM/eziS-EDISERUSSERPHGIH 8– ht retcarahc
05F–15811NIDtunnoinU08F–15811NIDtunnoinU
pmalcirTni2pmalcirTni3pmalcirTni4
llerruByrrehCni2llerruByrrehCni3llerruByrrehCni4
mgarhpaidhsulfyratinaSni4mgarhpaid)ni2(dednetxeyratinaSni4mgarhpaid)ni4(dednetxeyratinaSni4mgarhpaid)ni6(dednetxeyratinaSni4
laesdetlobnoitacilppaegareveB
ABFGHLMNPQRST
diulflliF–EDISERUSSERPHGIH 9– ht retcarahc
lioenociliS)devorppaADF(liolareniM
)devorppaADF(lioelbategeV)devorppaADF(retaW-nirecylG
SWAB
noitcennoclacirtcelednalairetamgnisuoH 01– ht retcarahc
)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA)noisrevlerraB(yollamuinimulA
)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA)noisrevlerraB(eerf-reppocyollamuinimulA
)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA)noisrevlerraB(ssL613ISIA
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocnaHgnitraHrotcennocsubdleiF
1/2 TPN41–)02MC(5.1x02M
5.31gP1/2 KG
rotcennocsubdleiF
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg()ylnoesopruplareneg(
)ylnoesopruplareneg(
)1etoN()1etoN(
)1etoN()1etoN(
)1etoN(
ABDCEGHLNMPRSTVUZ
snoitpolanoitiddA/tuptuO 11– ht retcarahc
Am02ot4dnanoitacinummoclatigidTRAHAm02ot4dnanoitacinummoclatigidTRAH
APSUBIFORPAPSUBIFORP
subdleiFNOITADNUOFsubdleiFNOITADNUOF
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)3,2setoN()2etoN(
)3,2setoN()3etoN(
)3,2setoN()3etoN(
H1P2F3
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
26
ADDITIONAL ORDERING INFORMATION for model 264NGAdd one or more 2-digit code(s) after the basic ordering information to select all required options
XX XX XX XX XX XX XX XX XX XX XX d'tnoCnoitacifitreclacirtcelE
aixEEytefaScisnirtnI–DG1yrogetaCIIpuorGXETAdxEEfoorpemalF–DG2/1yrogetaCIIpuorGXETA
)4etoN(ecnailpmocngisedLnxEE"N"noitcetorpfoepyT–DG3yrogetaCIIpuorGXETAylno()ASC(noitaicossAdradnatSnaidanaC 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–
)subdleiFNOITADNUOFdnaAPSUBIFORProfnxEdnaaixEtoN(AASailartsuAsdradnatShtiwylno(lavorppa)MF(lautuMyrotcaF 1/2 )noitcennoclacirtcele5.31gPdna02M,TPN41–
foorpemalFdnaytefaScisnirtnI-XETAdenibmoC)3edoctuptuOFFrofelbaliavatoN(aixEytefaScisnirtnI-)anihC(ISPEN
dxEfoorpemalF-)anihC(ISPENaixEE)aissuR(TSOGdxEE)aissuR(TSOG
aixEE)natsikazaK(TSOGdxEE)natsikazaK(TSOG
)4etoN(aixEE)lizarB(ortemnI)4etoN(dxEE)lizarB(ortemnI)4etoN(LnxEE)lizarB(ortemnI
1E2E3E4E5E6E7EYEZE1W2W3W4W5W6W7W
retemtuptuO
noitarbilacdradnatS,reteMorPnoitarbilaclaicepS,reteMorP
elacs%001–0raenilrotacidnituptuogolanA)elacsraenilrofdeificepsebot(noitaudarglaiceps,rotacidnituptuogolanA
)reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP)noitarugifnocremotsuc–reteMoC(rotarugifnocTRAHdnaretemlangiselbammargorP
)4etoN()4etoN()4etoN()4etoN()4etoN()4etoN(
1D2D3D5D7D8D
DCLlargetnIyalpsidlargetniDCLlatigiD 1L
egruS)Am02-4/TRAHroflanretnI(rotcetorPtneisnarT/egruS
ylnosubdleiFNOITADNUOFdnaAPSUBIFORProfesooldeilppuslanretxE(rotcetorPtneisnarT/egruShtiwelbatius 1/2 )TSUDon,snoitacifitrecASCdnaMF,XETAhtiwdnanoitcennoclacirtcele02MdnaTPN41–
1S
launamgnitarepOnamreG
nailatIhcnerF
1M2M4M
egaugnalgat&slebaLnamreG
nailatIhcnerF
1T2T4T
etalpgatlanoitiddAetalpleetssselniatsnogatfognitnirpresaL 2I
noitarugifnoCHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 F.ged=erutarepmeT;C°4taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°02taisp/OHni=erusserP–dradnatS 2 C.ged=erutarepmeT;C°4taisp/O
motsuC
2N3N4N5N6N
setacifitreC
)tniop-9(noitarbilacfoB.1.3–40201NEetacifitrecnoitcepsnIngisedtnemurtsnifo1.2–40201NEredroehthtiwecnailpmocfoetacifitreC
1C6C
ytilibaecartlairetaM
strapdettewssecorpfo1.2–40201NEredroehthtiwecnailpmocfoetacifitreCstrapdettewssecorpfoB.1.3–40201NEetacifitrecnoitcepsnI
1H3H
rotcennoC
)gulpelamefgnitamtuohtiwesooldeilppus(-)subdleiFNOITADNUOFrofdednemmoceR(8/7subdleiF)gulpelamefgnitamtuohtiwesooldeilppus(-)APSUBIFORProfdednemmoceR(1x21MsubdleiF
yrtnethgiarts–naHgnitraHyrtneelgna–naHgnitraH
)5,3setoN()5,3setoN()5,2setoN()5,2setoN(
1U2U3U4U
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
27
Note 1: Select type in additional ordering code
Note 2: Not available with Electronic Housing code Z, R, G
Note 3: Not available with Electronic Housing code P, E
Note 4: Not available with PROFIBUS PA and FF output code 2 or 3
Note 5: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B
™ Viton is a Dupont de Nemour trademark
Standard delivery items (can be differently specified by additional ordering code)– General purpose (no electrical certification)
– No meter/display, no mounting bracket, no surge protection
– English manual and labels
– Configuration with kPa and deg. C units
– No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'SRESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
XX XX
sgnittiF/pmalC
)pmalcirTni2rof(pmalCdnab-Vni2)pmalcirTni3rof(pmalCdnab-Vni3
)hsulfyratinaSni4dnallerruByrrehCni4,pmalcirTni4rof(pmalCdnab-Vni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)81.0(mm7.4otpullawknat,dupsknaTni4)laeshsulfyratinaSni4rof(pmalCdnab-Vni4dna)73.0(mm5.9otpullawknat,dupsknaTni4
)laesdednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4)laesni2dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni2rofdupsknaT)laesni4dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni4rofdupsknaT)laesni6dednetxeyratinaSni4rof(pmalcdnab-V5eludehcsni4dnanoisnetxeni6rofdupsknaT
1rof(seloh6htiwdupsknatdegnalF 1/2 )laesegarevebni
1J2J3J4J5J6J7J8J9JAJ
teksaG
)laesdednetxeyratinaSni4rof(001NDteksagenelyporpenelyhtE1rof(teksagenelyporpenelyhtE 1/2 )laesegarevebni
)laestunnoinU05Frof(05NDteksagenelyporpenelyhtE)laestunnoinU08Frof(08NDteksagenelyporpenelyhtE
)hsulfyratinasni4rof(teksag™notiV)hsulfyratinasni4rof(teksaganuB
1K2K3K4K6K7K
2600T Pressure TransmittersModel 264DG, 264HG, 264NG SS/264XG_4
ABB LtdHoward Road, St. NeotsCambridgeshire, PE19 8EUUKTel: +44(0)1480 475321Fax: +44(0)1480 217948
ABB Inc.125 E. County Line RoadWarminster, PA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB SACE spaBusiness Unit InstrumentationVia Statale 11322016 Lenno (CO) ItalyTel: +39 0344 58111Fax: +39 0344 56278
SS
/264
XG_4
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide
www.abb.com/instrumentation
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in Italy (02.06)
© ABB 2006