Square D NW Insulated Case Breaker Operation Counter Trip Unit Closing Push Button Opening Push Button Cluster Spring-Charging Motor Charging Handle Shunt Close (XF) Auxiliary Contact Lifting Tab Cradle Rejection Kit Arc Chamber Trip Unit Connection to Overcurrent Trip Switch Shunt Trip (MX2) or Undervoltage Trip Device Shunt Trip (MX1) Auxiliary Control Connection Sensor Plug Push-to-reset on Fault Trip Open / Close Push Button Cover (Lockable with padlock) Charged / Discharged Indicator Open / Close Indicator Accessory Cover Mounting Plate for Fixed Circuit Breaker Trip Unit Battery Accessory Label Catalog Number 1.800.476.1486 www.southlandelectrical.com NW

Transcript of Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ......

Page 1: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Square DNW Insulated Case Breaker

Operation Counter

Trip Unit

Closing Push Button

Opening Push Button

Cluster

Spring-Charging Motor

Charging Handle

Shunt Close (XF)

Auxiliary Contact

Lifting Tab

Cradle Rejection Kit

Arc Chamber

Trip Unit Connection toOvercurrent Trip Switch

Shunt Trip (MX2) orUndervoltage Trip Device

Shunt Trip (MX1)

Auxiliary ControlConnection

Sensor Plug

Push-to-reseton Fault Trip

Open / Close PushButton Cover(Lockable with padlock)

Charged / DischargedIndicator

Open / CloseIndicator

Accessory Cover

Mounting Plate forFixed Circuit Breaker

Trip Unit Battery

Accessory Label

Catalog Number

1.800.476.1486www.southlandelectrical.com

NW

Page 2: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

3.0 S131A

5.0 S133A

Without A E P, H

Micrologic for Masterpact & Compact NS

Micrologic 5 . 0 E

Type of measurementVersionType of current protection

2. Distribution L, I

5. Distribution L, S, I

6. Selective and earth-fault protection L, S, I, G

7. Selective protection with earth-leakage protection L, S, I, V

Without A E P,H

2.0

5.0

6.0

2.0

5.0

6.0

2.0

5.0

6.0

7.0

5.0

6.0

7.0

No Measurement Power Measurement

Product Numbers

Without

2.0 S132R

A P H

2.0A S142R

3.0A S141A

5.0A S143A

6.0A S144A

7.0A N/A

5.0P S163A

6.0P S164A

7.0P N/A

3.0 S131A

5.0 S133A 5.0H S173A

6.0H S174A

7.0H N/A

P=H=

Without=A=E=

Square DNW Accessory Parts

NW

Current MeasurementEnergy Measurement

Harmonic Measurement

Page 3: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Square DNW Accessory Parts

1.800.476.1486www.southlandelectrical.com

S47361 48/60 VAC/DC

S47364 277 VAC

S47362 100/130 VAC/DC

S47365 380/480 VAC/DC

S47324 200/240 VAC/DC

S47325 277 VAC

S47326 380/480 VAC

S47320 12 VDC

S47322 48/60 VAC/DC

S47321 24/30 VAC/DC

S48493 100/130 VAC/DC

S48492 48/60 VAC/DC

S48457 12 VDC

S48459 48/60 VAC/DC

S48458 24/30 VAC/DC

S48495 277 VAC

S48496 380/480 VAC

S48461 200/240 VAC/DC

S48462 277 VAC

Shunt Trip Part Numbers - Standard Coil (MX1/MX2) Close XF

NW Fixed NW Drawout

Shunt Trip Part Numbers - (MX1) Close XF

S47323 100/130 VAC/DC S48460 100/130 VAC/DC

S48463 380/400 VDC

S33166

CRK2000A3P

CRK3000L3P

CRCLIP CRK3200A3P

CRK6000A3P

CRK2000A4P

CRK3200A4P

CRK6000A4P

Cluster Kit Part Numbers

S47363 200/240 VAC/DC

S47360 20/30 VAC/DC

S47359 12 VDC S48490 12 VDC S48494 200/240 VAC/DC

S48491 24/30 VAC/DC

Cust. Fact. Aux.

COM

Vext

M6C

SDE2

Res

SDE1

MN

MX2

MX1

XF

PF

MCH

OF

EF

Communication ModuleExternal Voltage Sensing for the P or H

Programmable Contact Module

Overcurrent Trip Switch/ Electric ResetRemote Reset

Overcurrent Trip Switch

Undervoltage Trip Device

Shunt Trip

Shunt Trip

Shunt CloseReady to Close Contact

Spring Charging MotorAuxiliary ContactsCombined “Connected, Closed” Switches

Undervoltage Release Part Numbers - (MN)

S47383 440/480 VACS47380 24/30 VAC/DC

S47381 48/60 VAC/DC

S48501 24/30 VAC/DC

S48502 48/60 VAC/DC

S48504 200/240 VAC

S48505 380/400 VAC

S47382 100/130 VAC/DC

S47385 380/480 VAC

S48503 100/130 VAC

NW

Page 4: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Micrologic Trip Unit Adjustable Rating Plug Part Numbers UL/ANSI

S48818 “A”

S48820 “C”

S48836 “D”

S48838 “F”

S48839 “G”

S48819 “B” S48837 “E” S48840 “H”

S48842 “R”

S48843 “S”

S48844 “T”

S48845 “P”

S47051 100A

S47053 400A

S33093 1000A

S47052 250A S48824 1200A

S33094 1250A

S33095 1600A

S33982 2000A

S33983 2500A

Micrologic Trip Unit Sensor Plug Part Numbers

S48823 600A

S33092 800A

S33091 630A

S48825 3000A

S47820 4000A

S33984 3200A

S47821 2000A

S48826 3000A

S47822 2500A

S47823 3200A

S47825 5000A

S47824 4000A

S47827 6000A

S47826 6300A

Auxiliary Switch & Contacts Part Numbers (OF)

S48860S48859 S48198 S48468

S48207 48 VAC

S48212 200/240VAC

S48215 440/480 VAC

S48211 100/130 VAC S48206 24/30 VDC

S48208 100/130 VDC

S48209 200/250 VDCS48213 277 VAC

S48522 46 VAC

S48527 200/240 VAC

S48526 100/130 VAC

S48528 100/130 VDC

S48530 440/480 VAC

S48523 100/130 VDC

S48521 24/30 VDC

S47827 200/250 VDC

Spring Charging Motor Part Numbers (MCH)

NW Fixed NW Drawout

S48214 380/415 VAC

NW Fixed NW Drawout

Square DNW Accessory Parts

NW

S48529 380/415 VAC

Page 5: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Square DNW Dimensional Drawing

1.50[38,2]

.43[11,0]

.57[14,5]

Fixed 800-3000A, 3200A & 4000A (W-Frame) UL/ANSI Master Drawing

1.800.476.1486www.southlandelectrical.com

15.75[400,1]12.14[308,2]

TOP VIEW8.15[207,0]

6.40[162,5]

8.78[223,0]

4.35[115,0]

4.35[115,0]

.37[9,5]

.98[25,0]

Dimensions:in.[]mm

SIDE VIEW

5.25[133,4]

7.52[191,0]

5.16[131,1]

10.20[259,2]

.28[7,0]

1.20[30,5]

2.84[72,2]

.57[14,5]

NW

*Other dimensionaldrawings available

upon request

Page 6: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Fram

e S

ize

1st Description

T NT(70MM) 3-Pole 800A ANSI/1200A UL489/1600A IEC

A NT(70MM) 4-Pole 800A ANSI/1200A UL489/1600A IEC

W NW(115MM) 3-Pole 3200A ANSI/3000A UL489/4000A IEC

E NW DC(115MM) 3/4-Pole 4000A ANSI/4000A UL489/4000A IEC

B NW(115MM) 4-Pole 3200A ANSI/3000A UL489/4000A IEC

Y NW(230MM) 3-Pole 6000A ANSI/6000A UL489/6300A IEC

C NW(230MM) 4-Pole 6000A ANSI/6000A UL489/6300A IEC

Inte

rrup

t Rat

ing

3rd Description

1 AIR Code N1/NA 42/42/42AIC(NW) @ 240/440/690V IEC

AIR Code N 25/50/35AIC(NT)/65/65/50AIC(NW) @ 240/480/600V UL/CSA/NOM

2 AIR Code N1 42/42/42AIC(NW) or (AIR Code N1/NA) 42/42/NA AIC(NT) @ 250/508/635V ANSI

AIR Code HA 42/42/42AIC(NT)/50/50/50AIC(NW)/65/85/85AIC(N-W(a)) @ 240/440/690V IEC

3 AIR Code HF 85/85/85AIC(NW) @ 240/440/690V IEC

AIR Code HHF 65/50/50AIC(NT)/100/100/85AIC(NW) @ 240/480/600V UL/CSA/NOM

4 AIR Code H1/HA 42/42/22AIC(NT)/65/65/35AIC(NW) @ 250/508/635V ANSI

AIR Code H1 42/42/42AIC(NT)/65/65/65AIC(NW)/100/100/100A-IC(NW(a)) @ 240/440/690V IEC

5 AIR Code H2 65/85/85AIC(NW) or (AIR Code HA) 85/85/85AIC(N-W(d)) @ 250/508/635V ANSI

AIR Code H2 50/50/42AIC(NT)/100/100/85AIC(N-W)/150/150/100AIC(NW(a)) @ 240/440/690V IEC

6 AIR Code H3/HF 100/100/85AIC(NW) @ 250/508/635V ANSI

AIR Code H3 150/150/100AIC(NW(b)) @ 240/440/690V IEC

7 AIR Code L1 150/130/25AIC(NT)/150/150/100AIC(NW) @ 240/440/690V IEC

AIR Code L/HB 200/100/NA AIC(NT)/200/150/100AIC(NW) @ 240/480/600V UL/CSA/NOM

8 AIR Code L1/H3 200/200/130AIC(NW) @ 250/508/635V ANSI

AIR Code H10 50AIC(1150V)(NW) @ 240/440/690V IEC

AIR Code L1 100/65/NA AIC(NT) @ 240/480/600V UL/CSA/NOM

9 AIR Code L1F 200/200/130AIC(NW) @ 250/508/635V ANSI

AIR Code HA10 50AIC(1150V)(NW) @ 240/440/690V IEC

AIR Code LF 200/100/NA AIC(NT)/200/150/100AIC(NW) @ 240/480/600V UL/CSA/NOM

Fram

e R

atin

g

4th Description

A 800A ANSI/UL/IEC(AC), ANSI/UL(DC)

B 1000A IEC(AC/DC)

C 1200A UL(AC/DC)

D 1250A IEC(AC)

E 1600A ANSI/UL/IEC(AC), ANSI/UL(DC)

F 2000A ANSI/UL/IEC(AC/DC)

G 2500A UL/IEC(AC), UL(DC)

H 3000A UL(AC), ANSI/UL(DC)

J 3200A ANSI/IEC(AC)

K 4000A ANSI/UL/IEC(AC/DC)

L 5000A ANSI/UL/IEC(AC)

M 6000A ANSI/UL(AC)

N 6300A IEC(AC)

P 800A(250A Sensor) ANSI/UL/IEC(AC)

Am

pera

ge

5th Description

A 800A

B 1000A

C 1200A

D 1200A(IEC) DC 1250-2500A

E 1600A

F 2000A

G 2500 DC 2500-5400A

H 3000A

J 3300A

K 4000A

L 5000A DC 5000-6400A

M 6000A

N 6000A(IEC)

P 250A

R 3600A

S 400A

T 600A

U 600A(IEC)

W 100A

W A 4 A T R1st 2nd 3rd 4th 5th 6th

Con

nect

ion

6th Description

A Fixed Mount 4 Pole Rear Connected “T” Vertical 6 Pole Top/ Bottom

B Fixed Mount 4 Pole Rear Connected “T” Vertical Top/ Bottom

C Fixed Mount 4 Pole Rear Connected “T” Vertical w/Heat Sinks 6000A RP Top/ Bottom

D Fixed Mount 2 Pole Front Connected Top/Rear Connected “T” Horizontal Bottom

E Fixed Mount 4 Pole Rear Connected “T” Vertical w/Heat Sinks 6 Pole Top/ Bottom

F Fixed Mount 2 Pole Front Connected Top/ Bottom

G Fixed Mount 9.7in Front Connected “T” Top/ Bottom

H Fixed Mount 2 Pole Rear Connected “T” Horizontal Top/ Bottom

J Fixed Mount 4 Pole Rear Connected “T” Horizontal Top/ Bottom

K Fixed Mount 2 Pole Front Connected Top/Rear Connected “T” Vertical Bottom

L Fixed Mount 2 Pole Rear Connected “T” Vertical Top/Front Connected Bottom

M Fixed Mount 4 Pole Rear Connected “T” Vertical 6 Pole Top/ Bottom

N Fixed Mount 4 Pole Rear Connected “T” Horizontal Top/Rear Connected “T” Vertical Bottom

P Fixed Mount 4 Pole Rear Connected “T” Horizontal 6 Pole Top/4 Pole Rear Connected “T” Vertical 6

Pole Bottom

Q Fixed Mount 4 Pole Rear Connected “T” Vertical Top/Rear Connected “T” Horizontal Bottom

R Draw-Out Mount

S Fixed Mount 4 Pole Rear Connected “T” Vertical 6 Pole Top/4 Pole Rear Connected “T” Horizontal 6

Pole Bottom

T Fixed Mount 11.76in Front Connected “T” Top/9.7in Bottom

U Fixed Mount 6in Rear Connected Ofset Vertical 3200A Top/ Bottom

V Fixed Mount 2 Pole Rear Connected “T” Vertical Top/ Bottom

W Fixed Mount 2 Pole Rear Connected “T” Horizontal Top/Rear Connected “T” Vertical Bottom

X Fixed Mount

Y Fixed Mount 2 Pole Rear Connected “T” Vertical Top/Rear Connected “T” Horizontal Bottom

Z Fixed Mount 3 Pole Rear Connected Ofset Vertical Top/ Bottom

Bra

nd/S

tand

ard

2nd Description

A SQD ANSI

C SQD IEC 947-2

L SQD UL/CSA/NOM

G Merlin Gerin UL/CSA/NOM

M Merlin Gerin IEC 947-2

N Merlin Gerin ANSI

B Federal Pioneer ANSI

R Federal Pioneer IEC 947-2

F Federal Pioneer UL/CSA/NOM

NW

Page 7: Square D - Southland · PDF file5.0A S143A 6.0A S144A 7.0A N/A 5.0P S163A 6.0P S164A 7.0P ... Micrologic Trip Unit Sensor Plug Part Numbers S48823 600A S33092 800A S33091 630A S48825

Und

ervo

ltage

16th Description

A 24-30VAC/DC Instantaneous Undervoltage

B 48-60VAC/DC Instantaneous Undervoltage

C 100-130VAC/DC Instantaneous Under-voltage

D 200-240VAC/DC Instantaneous Under-voltage

E 380VAC Instantaneous Undervoltage

G 48-60VAC/DC Adjustable Time-Delayed Undervoltage

H 100-130VAC/DC Adjustable Time-Delayed Undervoltage

J 200-240VAC/DC Adjustable Time-Delayed Undervoltage

K 380VAC Adjustable Time-Delayed Under-voltage

L 100-130VAC/DC Fixed Time-Delay Undervoltage

M 200-240VAC/DC Fixed Time-Delay Undervoltage

N 12VDC Second Shunt Trip

P 24-30VAC/DC Second Shunt Trip

R 48-60VAC/DC Second Shunt Trip

S 100-130VAC/DC Second Shunt Trip

T 200-240VAC/DC Second Shunt Trip

U 277VAC Second Shunt Trip

W 380VAC Second Shunt Trip

X None

Oth

er O

ptio

ns

17th Description

A Ready To Close Switch

B Low Level Ready To Close Switch

C Padlockable Push Button Cover

D Mechanical Operation Counter

E Ready To Close Switch, Pad-lockable Push Button Cover

F Ready To Close Switch, Me-chanical Operation Counter

G Low Level Ready To Close Switch, Padlockable Push

Button Cover

H Low Level Ready To Close Switch, Mechanical Operation

Counter

J Padlockable Push Button Cover, Mechanical Operation

Counter

K Ready To Close Switch, Padlockable Push Button

Cover, Mechanical Operation Counter

L Low Level Ready To Close Switch, Padlockable Push Button Cover, Mechanical

Operation Counter

X None

Func

tion

7th/8th Description

31 ELS 3.0 LI Function

32 ELS 2.0 LSO Function

33 ELS 5.0 LSI Function

41 ELA 3.0A LI Function

42 ELA 2.0A LSO Function

43 ELA 5.0A LSI Function

44 ELA 6.0A LSIG Function

45 ELA 7.0A LSIV Function

63 ELU 5.0P LSI Function

64 ELU 6.0P LSIG Function

65 ELU 7.0P LSIV Function

73 ELH 5.0H LSI Function

74 ELH 6.0H LSIG Function

75 ELH 7.0H LSIV Function

NN Non-Automatic Switch No Function

SS Automatic Switch Instant Override Function

XX Without Trip Unit No Function

10 DC Trip Unit 1 Instanta-neous Only Function

PC

M

11th Description

A No PCM 4 Form C B1 Low Level

B 2 PCM 4 Form C B1 Low Level

C No PCM 8 Form C B2

D No PCM 12 Form C B2

E 6 PCM 4 Form C B1 Low Level

F 2 PCM 4 Form C B1 or B2

G 2 PCM 8 Form C B2

H 2 PCM 12 Form C B2

K 6 PCM 4 Form C B1 or B2

L 6 PCM 8 Form C B2

M 6 PCM 12 Form C B2

S No PCM 4 Form C B1 or B2

Spr

ing

Cha

rgin

g M

otor

12th Description

C 24-30VAC/DC Spring Charging Motor

D 48-60VAC/DC Spring Charging Motor

F/G 100-130VAC/DC Spring Charging Motor

H/J 200-240VAC/DC Spring Charging Motor

K 277VAC Spring Charging Motor

L 380-415VAC Spring Charging Motor

P 440-480VAC Spring Charging Motor

X None

Shu

nt T

rip

13th Description

A 12VDC Shunt Trip

B 24-30VAC/DC Shunt Trip

C 24-30VAC/DC Shunt Trip-Com

D 48-60VAC/DC Shunt Trip

E 48-60VAC/DC Shunt Trip-Com

F 100-130VAC/DC Shunt Trip

G 100-130VAC/DC Shunt Trip-Com

H 200-240VAC/DC Shunt Trip

J 200-240VAC/DC Shunt Trip-Com

K 277VAC Shunt Trip

M 380-480VAC Shunt Trip

R 277VAC Shunt Trip-Com

S 380-480VAC Shunt Trip-Com

V 12VDC Shunt Trip-Com

X None

Ele

ctro

nic

Res

et

15th Description

F 100-130VAC/DC Electronic Reset

H 200-240VAC/DC Electronic Reset

W 2ND OC Trip Switch SDE

X None

Y 2nd OC Trip Switch Low Level

Plu

g

9th Description

A UL Plug “A”

B UL Plug “B”

C UL Plug “C”

D UL Plug “D”

E UL Plug “E”

F UL Plug “F”

G UL Plug “G”

H UL Plug “H”

X No Rating Plug Required

P “OFF” Plug(IEC) Only

R IEC Standard Plug

S IEC Lower Range Plug

T IEC Upper Range Plug

Com

mun

icat

ions

10th Description

2 For Future Use

3 Modbus

4 Device Net

5 CAN

6 Profibus DP

7 Batibus

8 For future Use

9 None

Clo

sing

Coi

l

14th Description

A 12VDC Closing Coil

B 24-30VAC/DC Closing Coil

C 24-30VAC/DC Closing Coil-Com

D 48-60VAC/DC Closing Coil

E 48-60VAC/DC Closing Coil-Com

F 100-130VAC/DC Closing Coil

G 100-130VAC/DC Closing Coil-Com

H 200-240VAC/DC Closing Coil

J 200-240VAC/DC Closing Coil-Com

K 277VAC Closing Coil

M 380-480VAC Closing Coil

R 277VAC Closing Coil-Com

S 380-480VAC Closing Coil-Com

V 12VDC Closing Coil-Com

X None

Lock

s

18th Description

A B1/B2, Padlock

B B1, 1 Kirk Lock

C B1, 1 Ronis Lock

D B1, 1 Fed Pioneer Lock

E B1, 1 Profalux Lock

F B1, 1 Castell Lock

M B2, Padlock, 1 Kirk Lock

P B2, Padlock, 2 Kirk Locks

Q B2, Padlock, 1 Ronis Lock

R B2, Padlock, 2 Ronis Locks

S B2, Padlock, 1 Fed Pioneer Lock

T B2, Padlock, 2 Fed Pioneer Locks

U B2, Padlock, 1 Profalux Lock

V B2, Padlock, 2 Profalux Locks

W B2, Padlock, 1 Castell Lock

X B1/B2, None

Y B2, Padlock, 2 Castell Locks

44 A 9 S X X X X X X X7th/8th 9th 10th 11th 12th 13th 14th 15th 16th 17th 18th