4.1.025Arrange the cables in an orderly and good-looking way, the cables must be bundled with
evenly distributed space and proper tightness.MIN 0.2 000000L
5.1.003
Distribution of tail fibers:
1. When tail fibers are distributed at bending positions, they must not be too tight and cross
there. A pair of tail fibers must be tied neatly with moderate tightness.
2. Tail fibers can be drawn freely from the ring of cable
MAJ 2 000000G
5.1.004The protection tube must enter into the cabinet with a length of less than 10 cm, and be tied
firmly.MED 0.5 000000J
5.1.005The cut of protection tube for tail fiber must be smooth. Otherwise, the insulating tape must be
used to avoid hurting anyone.MED 0.5 000000J
5.1.006The flange of tail fiber must be fixed. If a fixing bracket exists, it must be installed on the fixing
bracket. MED 0.5 000000J
5.1.008The over long tail fiber inside a cabinet must be coiled in the box or coiled into a circle with
dia. more than 8 cm before it is fixed.MIN 0.2 000000L
7.1.005
The labels of cable are filled in and stuck correctly and reliably. They must be tidy position and
same direction. They must be stuck on a position 2 cm away from their connectors. They can
be made in a uniform way according to customer requirement.
MED 0.5 000000J
7.1.006
The labels of power cable and ground cable are filled in and stuck correctly and reliably. They
must be in a tidy position and the same direction. They must be stuck on a position about 2cm
away from their connectors. They can be made in a uniform way acc
MED 0.3 000000K
7.1.007 Labels must be stuck on the alarm box according to specifications, easy to maintenance. MED 0.3 000000K
7.1.008 On the DDF, trunk cable labels must be easily viewed for going to problem location. MED 0.3 000000K
7.1.009 Network cables, power cables, and SCSI cables must be properly labeled. MED 0.3 000000K
7.1.010 Labels of WS and network management system and so on must be placed neatly and firmly. MED 0.2 000000L
7.1.011 The labels of rack shall be placed neat and clean. MIN 0.2 000000L
7.1.012
The row and column labels of the cabinet must be stuck in a clear and tidy way. If there has a
dashed box on the cabinet,
labels must be stuck within it.
MIN 0.2 000000L
14.1.001 Check Antenna(s) Polarization according to the Plant documentation MAJ 2 000000G14.1.002 Check ODU(s) and pole mounting position according to the plant documentation MAJ 2 000000G
Microwave Installation
Fibers: Common
Labels
-
8/3/2019 SQMT Microwave
5/8
-
8/3/2019 SQMT Microwave
6/8
20.1.004The engineering supervisor must upload the completion photographs for the BTS along with
Hardware Self-Check Report to the EPMS system.MAJ 2 000000G
20.1.005 Lock rack door MED 1 000000I20.1.006 Lock site door MED 1 000000I
20.1.007 Equipment missing MED 1 000000I20.1.008 Equipment damaged MED 1 000000I
20.1.009
The items to be evaluated but not to be mentioned in this table:
1. According to the engineering design document
2. Referring to the installation manual
3. The re uirements to be ne otiated with customers before installation.
MED 0.5 000000J
20.1.010The alarm monitoring system is normal in test. It should not has any alarm when it runs
normally.MED 0.5 000000J
20.1.011 The power-on hardware test of equipment is normal. MED 0.5 000000J
20.1.012Fire safety system installation: Fire safety signs are clear, and hand extinguishers are firmly
fixed.MED 0.5 000000J
21.1.001Parameter of power in the equipment room can assure equipments running safety for long
time.MIN 0.2 000000L
21.1.002The cable distribution frame must be grounded firmly. The shielding layer of subscriber
external cable must be grounded.MIN 0.2 000000L
21.1.003Protection grounding cable must be connected firmly, grounding mode for equipment room
must be selected jointed gronding.
MIN 0.2 000000L
21.1.004The joint grounding resistance value must be satisfied the design requirements. Generally, it
must be less than 10 ohm,MIN 0.2 000000L
21.1.005
The radius and power supply mode of PGND cable, GND cable of primary power and -48V
power cable that connected to PDF or distribution power box are according to engineering
design document. They can assure equipment running safely and expansion request.
MIN 0.2 000000L
21.1.006 PDF and primary power output current-limiting fuse must be as specif ied. MIN 0.2 000000L
21.1.007Power cable arrangement outside must avoid impracticable into equipment room and must be
protected lightning.MIN 0.2 000000L
21.1.008 Condition of equipment room can assure equipments running safety for long time. MIN 0.2 000000L
21.1.009The ODF must be connected to the protection ground. The wire used to increase the strength
of an optical cable must also be connected to the protection ground.MIN 0.2 000000L
21.1.010 Fireproof measures must be adopted in the equipment room. MIN 0.2 000000L21.1.011 Corresponding antistatic measures must be adopted in the equipment room. MIN 0.2 000000L
21.1.012The earthquake-proof, lightning-proof protection and bearing measures of equipment room
must meet the requirements of construction and long-term safe operation.MIN 0.2 000000L
Equipment Working Enviorment
-
8/3/2019 SQMT Microwave
7/8
-
8/3/2019 SQMT Microwave
8/8
23.1.003QC of the partner must perform quality management regulation of partner ,and must inspect
sites quality;MAJ 2 000000G
23.1.004 The sites quality defects must be modified ,and quality report (after modified) must besubmitted. MAJ 2 000000G
23.1.005 The Engineer of partner must install Equipments by installation manual. MAJ 2 000000G
23.1.006Issue quality defects regular and implement correlative action according to award and
punishment rules.MAJ 1 000000I
23.1.007The supervisor of huawei must audit site quality,and must supervise defects to be modified by
the partner.MED 0.5 000000J
23.1.008 The QA of representative must audit site quality. MED 0.5 000000J