SPS Schemes for Grid Security (With Generation at Palatana) Case 1: When Palatana unit trips Case 2:...
-
Upload
alexandrea-nowell -
Category
Documents
-
view
215 -
download
2
Transcript of SPS Schemes for Grid Security (With Generation at Palatana) Case 1: When Palatana unit trips Case 2:...
SPS Schemes for Grid Security(With Generation at Palatana)
Case 1: When Palatana unit trips
Case 2: 400 kV Palatana-Silcher (D/C) lines trip
Case 3: 400 kV Silchar – Byrnihat line trips
Initial Conditions :Pre condition:
Following lines should be kept in open condition
132 kV Khliehriat – Lumshnong S/C
132 kV Pailapool – Jiribam line at Jiribam end
132 kV Khleihriat (PG) – Khliehriat (Me) D/C (Based on Leshka Generation and System Conditions)
Load (Drawal from Grid) in Southern Part of NER :
Peak
South Assam : 100 MW
Manipur : 115 MW
Mizoram : 75 MW
Tripura : 145 MW
Meghalaya : 15 MW
(Lumshnong load)
Total : 440 MW
ISGS Generation in Southern Part of NER :
Peak
AGTPP : 75 MW
Loktak : 105 MW
Palatana : 350 MW
Total : 530 MW
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow in Initial Conditions
System Requirement
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
90 MW
10 MW
6 MW
72 MW
Khandong Kopili
34 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
1 MW
19 MW
350 MW
Case 1: When Palatana unit trips (PEAK Case)
Scheme:
i. When generator at Palatana trips a signal will be generated from trip relay of the unit.
ii. This signal should trip the CB of 132 kV Silchar – Srikona D/C & 132 kV Silchar – Panchgram lines
at Silchar.
iii. Subsequently, tripping of 132 kV Silchar – Panchgram line a signal will be generated from trip relay of 132 kV Silchar –Panchgram line. This signal should trip the CB of 132 kV Badarpur – Panchgram line at Badarpur.
iv. After these trippings a instant load relief of 60 MW at off-peak & 105 MW in peak which will avert the system from cascade tripping
v. Then manual demand disconnection should be imposed.
Load Relief Off-Peak Peak
Srikona : 15 MW 25 MW
Pailapool : 10 MW 20 MW
Panchgram: 20 MW 35 MW
Lumsnong : 15 MW 25 MW
Total 60 MW 105 MW
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After Tripping of Palatana Module-1 (350 MW)
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
82 MW
53MW
50 MW
Khandong Kopili
59 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
27 MW
143 MW
System Requirement
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After SPS Operation
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
54 MW
Khandong Kopili
28 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
16 MW
CB shall trip
CB shall trip
CB shall trip
CB shall trip
A signal will be
generated from trip
relay of 132 kV Silchar
–Panchgram
line
When generator trips signal will be generated from trip
relay of the unit80 MW
System Requirement
Case 2: When 400 kV Palatana-Silchar (D/C) lines trip (PEAK Case)
Scheme:i. When both the ckts of 400 kV Palatana – Silchar lines trip, a signal will be generated from trip
relays at Silchar
ii. This signal should trip the CB of 132 kV Silchar – Srikona D/C & 132 kV Silchar – Panchgram
lines at Silchar.
iii. Subsequently, tripping of 132 kV Silchar – Panchgram line a signal will be generated from trip relay of 132 kV Silchar –Panchgram line. This signal should trip the CB of 132 kV Badarpur – Panchgram line at Badarpur.
iv. After these trippings a instant load relief of 60 MW at off-peak & 105 MW in peak which will avert the system from cascade tripping
v. Then manual demand disconnection should be imposed.
Load Relief Off-Peak Peak
Srikona : 15 MW 25 MW
Pailapool : 10 MW 20 MW
Panchgram: 20 MW 35 MW
Lumsnong : 15 MW 25 MW
Total 60 MW 105 MW
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After Tripping of 400kV Silchar-Palatana D/C
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
92 MW
38MW
54 MW
Khandong Kopili
86 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
43 MW
132 MW
350 MW
System Requirement
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After SPS Operation
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
56 MW
Khandong Kopili
35 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
20 MW
CB shall trip
CB shall trip
CB shall trip
CB shall trip
A signal will be
generated from trip
relay of 132 kV Silchar
–Panchgram
line
When both the ckts of 400 kV Palatana – Silchar lines trip, signal will be generated from trip relays
at Silchar
75 MW
350 MW
System Requirement
Case 3: When 400 kV Silchar – Byrnihat S/C line trips (OFFPEAK Case)
Load Relief Off-Peak Peak
Srikona : 15 MW 25 MW
Pailapool : 10 MW 20 MW
Panchgram: 20 MW 35 MW
Lumsnong : 15 MW 25 MW
Total 60 MW 105 MW
Scheme:i. When 400 kV Byrnihat – Silchar lines trip, signal will be generated from trip relays at
Silchar
ii. This signal should trip CB of GTG/STG of at Palatana. But unit will be running in FSNL
iii. A instant relief in line loading of 230/130 MW which will avert the system from cascade tripping.
v. Then manual demand disconnection should be imposed.
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After Tripping of Silchar - Brynihat
Shall be kept open
Byrnihat Shall be kept open
10 MW
15 MW
20 MW
15 MW
12 MW
Khandong Kopili
59 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
1 MW
34 MW
350 MW
System Requirement
177 MW
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
Palatana Nehu
NEIGRIHMS
Line Flow After Tripping of Silchar - Brynihat
Shall be kept open
Byrnihat Shall be kept open
10 MW
15 MW
20 MW
15 MW
101 MW
Khandong Kopili
174 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
32 MW
51 MW
350 MW
System Requirement
Badarpur (PG)
Dullavchera
Pailapool
Lumsnong
Khliehriat (Me)
Panchgram
Srikona
Khliehriat (PG)
Dharmanagar
P K Bari
Jiribam(PG)
UdaipurS. Nagar
Silchar
PalatanaNehu
NEIGRIHMS
Line Flow After SPS Operation
Shall be kept open
Byrnihat Shall be kept open
20 MW
25 MW
35 MW
15 MW
39 MW
Khandong Kopili
94 MW
Loktak(NH)
105 MW
Imphal(PG)
Dimapur(PG)
Kumarghat(PG)
AGTPP(NO)
75 MW
9 MW
43 MW
220 MW
When 400 kV Byrnihat
– Silchar lines trip,
signal will be generated from trip relays at Silchar
ST-1 shall trip
System Requirement