Sprinklers Evolvedby Allan Macpherson, FM Global
IFE Scotland and BAFSA : Technical Sprinkler Seminar 2010National Library of Scotland
20 January 2010
![Page 2: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/2.jpg)
It started simply…
Summer, 1891
![Page 3: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/3.jpg)
Then in the 1950’s…
Standard Spray Sprinkler
![Page 4: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/4.jpg)
Then came…
A bunch of Control Mode Density Area (CMDA) sprinklers…
- Large Orifice Sprinkler
- Extra Large Orifice (ELO) Sprinkler
- Very Extra Large Orifice (VELO) Sprinkler
![Page 5: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/5.jpg)
Other Milestones
1970 ----> Residential Sprinkler 1970 ----> Large Orifice Sprinkler (CMSA)
1980 ----> ESFR (SM)
![Page 6: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/6.jpg)
Leading to…
more Control Mode Density
Area (CMDA) sprinklers…
and a bunch of Control Mode Specific Application (CMSA) sprinklers…
…and a bunch of Suppression Mode (SM) sprinklers
![Page 7: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/7.jpg)
Where we are in 2009? Three different sprinkler categories
Three sets of installation guidelines (461 pages of guidance!)
Terminology indicates intended performance
Two different design formats
![Page 8: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/8.jpg)
Stepping back…
Existing terminology misleading
Actual performance can be otherwise
> Control mode sprinklers - fire suppression
> Suppression mode sprinklers - fire control
![Page 9: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/9.jpg)
Change in sprinkler terminology
New terminology based on intended use:
> Storage sprinkler
> Non-storage sprinkler
> Special protection sprinkler
![Page 10: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/10.jpg)
True or False?
Two different FM Approved control mode sprinklers discharging the exact same amount of water will provide equivalent protection
Quiz
![Page 11: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/11.jpg)
K 80
K 360
![Page 12: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/12.jpg)
K factor video
![Page 13: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/13.jpg)
K 80250 l/min @ 10 bars
K 360250l/min @ .5 bar
Light fog - Minimal penetration - Easily pushed aside - Prone to skipping
Heavy downpour - Better penetration - Difficult to push aside - Skipping less likely
![Page 14: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/14.jpg)
Test 1 – 32 mm/min density / upright
![Page 15: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/15.jpg)
Test 2 –24 mm/min density / pendent
![Page 16: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/16.jpg)
Test 2 – K 360 EC sprinkler Lower water demand
> 10.7 m. building 6 sprinklers at 2.75 bars 3600 l/min
More cost effective > Spacing up to 18 m2 per head means less pipe, fewer
sprinklers> Much less fire, smoke and goods damage
![Page 17: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/17.jpg)
What’s really most important?
Sprinkler K factor (~ nozzle size) Orientation (upright or pendent) RTI (standard or quick response)
… and not so much
Ceiling discharge density
![Page 18: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/18.jpg)
What does this mean for Data Sheets?
Need to update sprinkler terminology
Need to replace density in design criteria
Opportunity to simplify and improve
![Page 19: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/19.jpg)
New Data Sheet 2-0
Replaces 2-2, 2-7, 2-8N
Installation rules – sprinkler type
Acceptance tests
![Page 20: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/20.jpg)
![Page 21: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/21.jpg)
New Data Sheet 8-9 & Protection Tables
Needed to update terminology
Transition design format away from density
Easier to identify the best protection options
Paves the way for future improvements
![Page 22: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/22.jpg)
Protection tables based on> Ceiling height> RTI (standard or quick response)> Orientation (upright or pendent)> Sprinkler K factor (~ nozzle size)
![Page 23: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/23.jpg)
Ceiling Height, ft
K11.2 K16.8 K11.2 K14.0 K25.2 K14.0 K16.8 K25.2EC K14.0 K16.8 K22.4 K25.2 K25.2EC
2015 @ 25psi
15 @ 15psi
15 @ 25psi
15 @ 20psi
12 @ 7psi12 @ 20psi
12 @ 15psi
6 @ 7psi12 @ 20psi
12 @ 15psi
12 @ 10psi
12 @ 7psi 6 @ 7psi
2520 @ 30psi
20 @ 20psi
15 @ 30psi
15 @ 25psi
12 @ 10psi
15 @ 25psi
12 @ 20psi
6 @ 15psi12 @ 25psi
12 @ 20psi
12 @ 15psi
12 @ 10psi
6 @ 15psi
3030 @ 50psi
25 @ 35psi
25 @ 50psi
25 @ 40psi
12 @ 15psi
15 @ 50psi
15 @ 30psi
8 @ 30psi12 @ 50psi
12 @ 35psi
12 @ 20psi
12 @ 15psi
8 @ 30psi
35 -30 @ 40psi
30 @ 75psi
30 @ 60psi
15 @ 25psi
20 @ 60psi
20 @ 40psi
10 @ 40psi
12 @ 60psi
12 @ 40psi
12 @ 30psi
12 @ 25psi
10 @ 40psi
40 - - - -15 @ 40psi
- -14 @ 50psi
12 @ 75psi
12 @ 50psi
12 @ 40psi
12 @ 35psi
14 @ 50psi
45 - - - -20 @ 50psi
- - - -15 @ 75psi
12 @ 60psi
12 @ 50psi
-
Protection for Class 4 and Cartoned Unexpanded Plastics on Wet-Pipe System;
160°F Standard Response AS 160°F Quick Response AS
Ceiling Storage Sprinklers: Numper of sprinklers @ psi
Upright Pendent Upright Pendent
Sample protection table
![Page 24: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/24.jpg)
Many of these new designs mean:
Less Sprinklers
Less Piping
Less Labour
Less Water
Lower Pressures
Less Resources
Greater Sustainability
More Sprinklers Installed !
![Page 25: Sprinklers Evolved by Allan Macpherson, FM Global · Then in the 1950’s ... 30 30 @ 50psi 25 @ 35psi 25 @ 50psi 25 @ 40psi 12 @ 15psi ... Sprinklers Evolved by Allan Macpherson,](https://reader030.fdocuments.us/reader030/viewer/2022021505/5ade236e7f8b9a8b6d8dd787/html5/thumbnails/25.jpg)
What is the bottom line?
Through these Data Sheet changes, FM Global is poised to provide our clients, with the most effective protection options, which are not only simpler and cheaper to install, but a more sustainable choice.