SPLN 7B_1978 Insulation Coordination,App

75
Publication 7i-2 snu.78 c0ir ilr Iss|0l{ EtrcTR0TEcH il|0 u E I1{T ER}tAT|01{ALE (affili6e i l'0rganisation Internationale deNormalisation - lS0) . ]II|RME DE L[ CEI I IITE R1{ATIll IIAL ELECTR(lTECHI{ICAt Cll MMI S S I l | l { (affiliated to theInternational 0rganization for Standardization - 180) I E G STAIIIlARI| Publication 7l-2 . Deuxidme 6dition - Second edition rF 1976' Coordination de I'isolemenl 0euxi0me partie: Guide d'applicalion Insulation co-ordination Parl 2: Application Guide 0roits de reproduction rdserv6s - Copyright - all rights reserved Bureau Central de laCommission Eiectrotechnique Internationale 1,rue de Varembd 0endve, S'risse

Transcript of SPLN 7B_1978 Insulation Coordination,App

Page 1: SPLN 7B_1978 Insulation Coordination,App

Publication 7i-2snu.78

c 0 i r i l r I s s | 0 l { E t r c T R 0 T E c H i l | 0 u E I 1 { T E R } t A T | 0 1 { A L E(affili6e i l'0rganisation Internationale de Normalisation - lS0)

. ] I I |RME DE L [ C E I

I I I T E R 1 { A T I l l I I A L E L E C T R ( l T E C H I { I C A t C l l M M I S S I l | l {(affiliated to the International 0rganization for Standardization - 180)

I E G STAII I lARI|

Publication 7l-2. Deuxidme 6dit ion - Second edit ion

r F 1 9 7 6 '

Coordination de I'isolemenl0euxi0me partie: Guide d'applicalion

Insulation co-ordinationParl 2: Application Guide

0roits de reproduction rdserv6s - Copyright - all rights reserved

Bureau Central de la Commission Eiectrotechnique Internationale1, rue de Varembd

0endve, S'risse

Page 2: SPLN 7B_1978 Insulation Coordination,App

R6vision de Ia pr6sente publication Revision of this publication

Le contenu technique des publ icat ions de la CEI est cons- The technical content of IEC publrcat ions is kept under

tamment revu par la Commission afin d'assurer qu'i l refldte constant revierr b) th.- I E C. thus ensuring that the content

bien l '6tat actuel de la technique. reflects current technolt'g1.

Les renseignements relatifs i ce travail de rdvision, d l '6ta- Information on the sork rrf rc'rtsitrfl. the issue of rerised

blissement des 6ditions r€visees et aux mises ir jour peuvent editions and amendn^*nt shc'eti !rla) bc obtained from IEC

€tre obtenus auprds des Cornit6s nationaux de la CEI et en National Committcc: anJ :rom 1l'1.' fq-rl lqruing IEC sources:

consultant les documents ci-dessous:

O Bulletin de la CEI O IEC Bulletin

O Rapport d'activit6 de la CEI O Report on I E C Actiritiex

Publi6 annuellement Published 1'earl1'

O Catalogue des publications de Ia CEI O Catalogue of IEC Publicatioos

Publi6 annuellement Published 1'earll '

Terminologie utilis6e dans la pr6sente publication Terminolog)' usd in this publication

Seuls sont d6finis ici les termes speciaux se rapportant d la Onll ' special terms required ft 'rr thc purposc of this publication

pr6sente publication. are defined herein.

En ce qui concerne la terminologie generale, le lecteur se For general terminologl', readers are referred to IEC Publi-

reportera d la Publication 50 de la CEI: Vocabulaire Electro- cation 50: International Electrotechnical Vocabulary (I.E.V.),

technique International (V.E.L), qui est dtablie sous forme de which is issued in the form of separate chapters each dealing

chapitres sdpar6s traitant chacun d'un sujet ddfini, l ' Index g6n6- with a specific field, the General Index being published as a

ral etant publi6 s6parement. Des ddtails complets sur le V.E.L separate booklet. Full details of the I.E.V. will be suppliedpeuvent €tre obtenus sur demande. on request.

Symboles graphiques et litt6raux Graphical and letter symbols

Seuls les symboles graphiquc-s et litteraux spdciaux sont Only special graphical and letter symbols are included ininclus dans la prdsente publication. this publication.

Le recueil complet des symboles graphiques approuv6s par The complete series of graphical symbols approved by thela CEI fait I 'objet de la Publication I l7 de la CEI. IEC is given in IEC Publication l17.

Les symboles littdraux et autres signes approuvds par la Letter symbols and other signs approved by the IEC areCEI font I 'objet de la Publication 27 de la CEL contained in IEC Publication 27.

Autre publication de la CEI 6tablie par le m6me Other IEC publication prepared by the sameComit6 d'Etudes Technical Committee

Publication no' '71-l : Coordination de l ' isc-r lement. Premiere Publication No. 7l- l : Insulat ion co-ordination, Part l :partie: Termes, d€finitions, principes et rdgles. Terms, definitions, principles and rules.

fi

Page 3: SPLN 7B_1978 Insulation Coordination,App

C.D.U./U.D.C.:621.315.61.01s.008.03 621.316.93.015.33::621.319.51.004.14(083.85)

c 0 i l t M I s s | 0 1 { E t r c T R 0 T E c H i l r 0 u E I l r T E R 1 { A T | 0 1 { A t E(affilide d l'Organisation Internationale de Normalisation - 180)

I I I IRME l lE tA C E I

I i l T E R i I A T I t l I I A L E L E C T R ( l T E C H N I C A L C t l M M I S S I ( | l {(affiliated to the lnternational Organization for Standardization - lS0)

I EC STA} I I lARl l

Publication 7l-2Deuxidme 6dit ion - Second edit ion

1 9 7 6

9PuN - PB.

Coordination de I'isolementl|euxiOme partie: Guide d'appllcalion

lnsulation ctl-tlrdinationParl 2: Applicalion Guide

P i : ' D I f i T 1 K A A NPUSTT PETIYEIIOI I \ i I MASAI.AH I(ELISTFIKA^!

9245s DF; 1e?7

Droits de reproduction rdservds - Copyright - all rights reserved

Aucune parlie de cette publication ne psut 6tre reproduite ni utilisGe sous No part ol this publication may be reproduced or utilizad in anyquelque forme que ce soit et par aucun proc0d6, 6lectronique ou mdca- form or by any means, electronic or mechanical, including photocopyingniqua, y compris la photocopie et les microfilms, sans I'accord €crit de l '6diteur. and microfilm, without permission in writing lrom the publisher.

Bureau Central de la Commission Electrotechnique Internationale1, rue de Varembd

6enive, Suise

;L, , : lm.-

Page 4: SPLN 7B_1978 Insulation Coordination,App

- 3 -

CONTENTS

Fonrwonp

Pnnrlce

SscrroN ONs - ScopB AND REFERENcE To EXrsrrNG IEC pusucATroNsClause

1. Scope2. Reference to existing I EC publications

SrcnoN Two - Vorrace srRESsEs rN sERVrcE

3. General .4. Power-frequency voltages5. Temporary overvoltages6. Switching and lightning overvoltages7. Determination of expected overvoltage levels

Page

5

5

77

91 ll ll 5l 9

SncnoN TnnBn - INsur.q,TroN wrrHsrAND

8. General .9. Insulation behaviour at power-frequency voltages and temporary overvoltages

10. Probability of disruptive discharge of insulation under impulse voltagesll. Apparatus with windings

. 2 3

. 2 5

. 2 5

. 3 1

3 l31333537

39

394l

4 l4 l

5 l

53536l

SncrroN Foun - PnorrcrrvE DEVrcEs

12. General .13. Non-linear resistor-type surge arresters14. Expulsion-type surge afresters15. Spark gaps16. Application of different protective devices

SecnoN FtvB - Co-onprN.q.TroN BETwEEN sTRESSES AND wrrHsrANDCoNsroBnmoNs coMMoN To RANGes A, B nwo C

17. Insulation design to power-frequency operating voltage and temporary overvoltages. Problems of pollution and ageing

18. Pollution19. Ageing

SncrroN Srx - Co-onorNarroN BETwEEN srREssEs AND wrrHsrAND IN voLTAcE naNcs A

20. Selection of the rated power-frequency withstand voltage21. Selection of the rated lightning-impulse withstand voltage

SecrroN SeveN - Co-onorNATIoN BETWEEN srREssEs AND wrErsrAND IN voLTAGE, uNcr B

22. Selection of the rated power-frequency withstand voltage and the rated lightning-impulse withstand voltage

SBcrroN Ercnr - Co-onorNATroN BETwEEN srREssEs AND wITHsTAND rN voLTAGE ruNcB C

23. Insulation design with respect to power-frequency voltage and temporary overvoltages24. Insulation design with respect to switching and lightning overvoltages .25. Block-diagram of the insulation design and co-ordination of an electrical installation

ApprNox A -

AppsNDrx B -

Appnwox C -

AppBNox D -

ApprNox E -

TlnrBs

Frcunrs

Surge transference through transformers . 67

Validity of the tests in Clauses 52, 53 and 54 of I EC Publication 7I-l . 77

Statistical evaluation of the protective effect of spark gaps 83

Examples of application . 89

Clearances in air between live conductive parts and earthed structures to secure a specified impulse withstandvoltage for dry conditions 93

. 9 5

. 106

Page 5: SPLN 7B_1978 Insulation Coordination,App

INTERNATIONAL

- 5 -

ELECTROTECHNICAL COMMISSION

INSULATION CO-ORDINATION

Part 2: Application Guide

FOREWORD

l) The fomal decisions or agreements of th€ IEC on technical matte$, prepared by Technical Committ!€s on which all the NationalComnittees having a spocial interest thercin are reprcsented, exprcss, as Dearly a.s possible, an internatioDal cons€trsus of opiniotr on thesubjects d€alt with.

2) They have the form ofrecomn€ndations for intemational us€ and they are accept€d by the National Committr€s itr that sense.

3) In order to promote i[temational unifcation, the I E C express€s th€ wisb that all National Cofunitte€s should adopt the t€xt ofthe I E Crecommetrdation for th€ir trational rul€s in so far as national conditions will permit. Aay divergence betweel the I EC r€comnrendationand ihe corr€sponding national rules should, as far as possible, be cl€arly indicat€d in the latter,

PREFACE

This publication has been prepared by IEC Technical Committee No. 28, Insulation Co-ordination.

It constitutes the second part of IEC Publication 71, Insulation Co-ordination, and supersedes IEC Publica-tion 71A (1962): Supplement to Publication 71, Recommendations for insulation co-ordination. ApplicationGuide.

Work relating to the Application Guide was f.rst begun during the meeting held in Milan in 1971; the draftsconcerning the various sections of the text were discussed during the meeting held in Athens in 1972. As a result ofthis meeting, the draft, Document 28(Central Ofrce)42, was submitted to the National Committees for approvalunder the Six Months' Rule in November 1973.

The following countries voted explicitly in favour of publication:

ArgentinaAustraliaAustriaBelgiumDenmarkFinlandFrance

GermanyIsraelItalyNetherlandsNorway

PolandRomaniaSouth Africa (Republic of)SpainSwedenSwitzerlandTurkey

Union of SovietSocialist Republics

. United Kingdom-

United States of AmericaYueoslavia

When the final text was being revised for publication, modifications stemming from changes in the text ofthe draftofIEC Publication 71-1 were included. Moreover, modifications in the wording suggested by the National Com-mittees were introduced, These do not affect the meaning of the original text.

Othet IEC publicationr quoted in this publicariot:

Publications Nos. 60: High-voltage T€st T€cbniqu€s.

7l-l'. InsulationCo.ordination,Part l: Terms, Definitions, Principles and Rul€s.

99-l: LightningAr.esters,Part l: Non-linear R€sistor Typ€ Arr€steN for A.C, SystefiE.

99-1Ar First Supplement to Publication 99-1.gg-2r Part 2: Expulsion-rype Lighhing Aresters.

28L1t High-voltageFuses,Part l: Currentlimiting Fuses.

Page 6: SPLN 7B_1978 Insulation Coordination,App

- 7 -

INSULATION CO.ORDINATION

Part 2: Application Guide

SECTION ONE SCOPE AND REFERENCE TO EXISTING IEC PUBLICATIONS

1. Scope

This publication provides some guidance on the selection of the electric strength of equipment, of surge arrestersor protective spark gaps, and on the extent to which it will be useful to control switching overvoltages.

The object of this publication is not to give strict rules for insulation co-ordination and design, but to provideguidance toward rational and ec6nomical solutions.

Therefore it is intended to consider only a few basic cases in this publication, it being evident that installationsconstituting exceptions to normal design, or included within systems having exceptional characteristics, will requirespecial study by experienced engineers.

This Application Guide is based on apparatus types and ratings in use at the time of publication. As new equip-ment and equipment characteristics are developed and proved, this guide should not be interpreted as a limit totheir adoption.

Like Publication 7l-I, PublicationTl-2 covers only phase-to-earth insulation.

Like Publication 7l-1, PublicationTl-2 deals separately with the three following ranges of the highest voltage forequipment:

- range A: above 1 kV and less than 52 kV;- range B: from 52 kV to less than 300 kV;- range C: 300 kV and above.

It covers installations of all kinds and in all situations involving voltages higher than I kV, whether or not thel'are exposed to lightning, with the exception of overhead lines. However, the test procedures apply also to the latter.

2. Reference to existing IE C publications

Several IEC publications give standards which deal respectively with the withstand and protective levels con-sidered separately. Thus:

a) IEC Publication 71-I, Insulation Co-ordination, Part 1: Terms, Def,nitions, Principles and Rules, containsthe definitions of terms to be found here; it gives the series of standard values of the rated lightning and switch-ing impulse withstand voltage, the rated withstand voltages of short duration at power frequency, as well asthe tables of the recommended combinations between the highest voltage for equipment and these rated withstandvoltages.

b) IEC Publicationgg-I, Lightning Arresters, Part 1: Non-linear Resistor Type Arresters for A.C. Systems,gives the protective characteristics under lightning impulses of non-linear resistor type surge arresters for ratingsup to 198 kV. Standard ratings above 198 kV are not included in IEC Publication 99-1. However, values forguidance are given up to 396 kV. Values for srvitching impulses are under consideration.

Page 7: SPLN 7B_1978 Insulation Coordination,App

- 9 -

The characteristics given in IEC Publication 99-l refer to surge arresters in general use. However, surge arresterswith better protective characteristics are available and their standardization is at present under consideration.IEC Publication 99-14, First Supplement to Publication 99-1, gives guidance on the selection of surge arresters.

c) IEC Publication 99-2, Lightning Arresters, Part 2: Expulsion-type Lightning Arresters, gives the impulsecharacteristics of expulsion-type surge arresters. No reference is made in IEC Publication 7l-1 to this type ofarrester, but it is still being used on some supply systems, particularly for voltages in range A.

d) IEC Publication2S2-1, High-voltage Fuses, Part 1: Current-limiting Fuses, lists the maximum overvoltagespermitted during the interruption of fault current by a high-voltage fuse.

e ) IEC Publication 60, High-voltage Test Techniques, describes the methods for generation and measurement oftest voltages and currents and the appropriate test procedures, and recommends methods for calibration andchecking of measuring devices.

There is no IEC publication for the protective characteristics of spark-gaps.

SECTION TWO VOLTAGE STRESSES IN SERVICE

3. General

Dielectric stresses on insulation may be classif.ed as follows:

- power-frequency voltages, under normal operating conditions;

- temporary overvoltages;

- switching overvoltages;

- lightning overvoltages.

In IEC Publication 71-1, overvoltages are classified with reference to the shape of the voltage wave uhich dc-termines their effect on insulation and on protective devices, without reference to the cause of the overvoltages.

The term "temporary overvoltages" refers to sustained overvoltages, or to oveNoltages having several successivepeaks, with a decrement of amplitude such as to be corrparable with a sustained overvoltage at power frequency orat harmonic frequency.

The terms "switching overvoltages" or "lightning overvoltages" refer to overvoltages for which only the highestpeak value has to be considered and which can be represented, with regard to their effects on insulation and protectivedevices, by the long-fronted standard switching impulses or short-fronted standard lightning impulses used for testpurposes. The foregoing names have been chosen because such overvoltages often-but not always---originate fromswitching operations or lightning discharges.

For example, the energization of a transformer-terminated line gives rise to an overvoltage that may be regardedas a "switching" or temporary overvoltage depending on the decrement ofthe successive peaks (i.e. depending onthe circuit parameters). As another example: a phase-to-earth fault, although actually a switching operation (thesame phenomenon would arise if a phase conductor was connected to earth by a circuit-breaker operation), may giverise to steep-front overvoltages, similar to those due to lightning; on the other hand, a lightning surge transferredthrough a transformer by inductive coupling between windings may produce on the secondary side of the trans-former long-fronted waves, similar to those due to switching operations.

Page 8: SPLN 7B_1978 Insulation Coordination,App

- 1 1 -

4. Power-frequencyYoltrg€s

In insulation co-ordination processes, since overvoltages and impulse voltages are defined in terms of their peakvalues to earth, it is also convenient to make use of the phase-to-earth peak value of the system voltage, which is

\/21 \/T :0.816 times the usual r.m.s. phase-to-phase voltage.

Under normal operating conditions, power-frequency voltage can be expected to vary somewhat in magnitudeand may be described by means of a probability distribution about the average oFrating value. The parameters ofthis distribution will differ from one point of the system to another. For purposes of insulation design and co-ordination, power-frequency voltage should however be considered as constant and equal to the highest voltage forequipment, which in voltage range C does not materially differ from the highest system voltage, with a phase-to-earth peak value ot V^,'r/21 1/T

In range A and in range B up to 72.5 kY, the highest voltage for equipment may be susbtantially higher than thehighest system voltage, as indicated in the note under Clause 5 ofIEC Publication 71-1. For the sake of standardiz-ation, it is however assumed that equipment insulation will always be able to operate satisfactorily at the highestvoltage for equiprnent immediately above, if not equal to, the highest system voltage.

5. Temporary oYerYoltages '

The severity of temporary overvoltages is mainly characterized both by their amplitude and duration.

The importance of temporary overvoltages in insulation co-ordination is twofold:

- on the one hand, the characteristics of temporary overvoltages at the surge arrester location are of great import-ance in surge arrester selection;

- on the other hand, the repetition of successive overvoltage peaks of opposite polarity, even if of lower amplitudethan some other overvoltages, may determine the design of both the internal insulation of equipment as well asthe external insulation (surfaces exposed to contamination).

Temporary overvoltages generally arise from:

a) earth faults;

D/ sudden changes of load;

c) resonance and ferro-resonance.

5.1 Earth faults

The overvoltage at power frequency on the sound phases when another phase is accidentally earthed depends, at agiven point of the system, on the treatment of the system neutral with respect to earth, as characterized by itsearth fault factor at that point.

Note. - In the evaluation of earth fault factors, the following remarks should be considered:- In general, in order to evaluate this factor at a given location it is assumed, for simplicity, that the fault is located at the point

for which the factor is desired; but, in some special cases, it may be desirable to investigate the effect of other fault locationson this factor.

- In principle, there are as many particular values of the earth fault factor at a given location as different possible configurationsof the system. The factor which characterizes the location considered is the highest of the values that correspond to the differ-ent system configurations which may occur in practice.

- The system configurations which have to be considered are those which exist during a fault; thus one should take into consider-ation those changes in the system which may be produced by the fault itself, for example, on account of the operation of circuit-breakers.

- For many systems, it will be sufficient to consider only one value of the earth fault factor which covers all possible fault lo-cations on the system.

- Attention is drawn to the fact that the highest voltage at power frequency which may appear on a sound phase during a par-ticular earth fault does not depend only on the value of the earth fault factor, but also on the value of the phase-to-phasevoltage at the time of the fault. This phase-to-phase voltage will generally be taken as the highest system voltage, as given in

Page 9: SPLN 7B_1978 Insulation Coordination,App

- 1 3 -

Defuitioa 4 of I EC Publication 71-1; but, in sorne cas€s, i[ order to predict the operation of Fot€ctive deeic€s and sperifytheir charapteri$tiG, it is n€cessary to take into account the incrqs€d value of the phas€-to-phas€ voltage that may appe{ atthe sel€cted locatioD utrder abnormal operating codditions not covered by the defnition referred to above.

Within range A and in some cases within range B, many systems or installations are operated with their neutralearthed through a high impedance, an arc-suppression coil or with their rieutral isolated. For the purpose of insul-ation co-ordination, particular attention must therefore be paid in these cases to the earth fault factor.

Independently of the earth fault factor, particularly high overvoltages may arise in range A and range B systemsin the case of:

aJ earth faults in a system the neutral of which is earthed tbrough an arc-suppression coil when the circuit isunder-compensated ;

b) arcing earth faults in a system the neutral of which is isolated and in some cases in a system the neutral ofwhich is earthed through an arc-suppression coil.

5,2 Swldm changes of load

In usual conditions of operation, the phase-to-phase voltage does not exceed the value of the highest voltage of thesystem as given by Clause 4 concerning definitions of IEC Publication 7I-I; but higher values may temporarily bereached in the case of sudden disconnection of large active and reactive loads; these values depend on the systemlayout after disconnection and on the characteristics of the sources (short-circuit power at the station, speed andvoltage regulation of the generators, etc.).

This voltage rise may be especially important in the case of load rejection at the remote end of a long line (Ferranti

effect). It affects mainly the apparatus at the station connected on the source side of the remote open circuit-breaker.

Note. - From the point of view of overvoltages, a distinction should be made between various types of system layouts. As extreme caseswe can consider: those with relatively short lines and high values of the short-circuit power at the terminal stations; and thosewith Iong lines and low values of the short-circuit power at the generating site. With the latter layouts, as are usual in an extra-high-voltage system in its initial stage, much higher overvoltages at power frequency may result when a large load is suddenlydisconnected.

Due to the characteristics of the systems, overvoltages of this kind are more severe in voltage range C than involtage range B; overvoltages of this kind, in voltage range A, occur in generator-transformer circuits.

5.3 Resonance and ferro-resonance

Temporary overvoltages due to these causes generally arise when circuits with large capacitive elements (lines,

cables, series-compensated lines) and inductive elements (transformers, shunt reactors) having non linear-magnetiz-ing characteristics are energi zed, or as a result of sudden changes of load.

These situations are generally found for systems in ranges B and C in the following cases:

a) A lightly loaded line, fed or terminated by a transformer, can show for example harmonic oscillations andpronounced overvoltages if the natural frequency of the linear part of the system corresponds to one of the har-monics of the transformer magnetizing current.

b/ Subharmonic oscillations and overvoltages can occur in systems compensated by series capacitors and termin-ated by lightly loaded power transformers or shunt reactors if the impressed voltage, the effective circuit resistance,

which is strongly influenced by synchronous machines, and the circuit capacitance fall between certain limits.

c ) If harmonic filters are connected to a system containing saturable elements, oscillations due to resonances

between these elements and the fllter capacitors can develop.

,f 7-

Page 10: SPLN 7B_1978 Insulation Coordination,App

- 1 5 -

These ferro-resonance effects following energization processes can either be sustained or last several cycles of thepower frequency depending on the time constant of transformer inrush currents.

Causes of resonance and ferro-resonance in systems of range A are:

d/ Resonance between inductive and capacitive components, e.g. when capacitors are used for power-factorcorrection

e ) Ferro-resonance which can occur in non-simultaneous closure or disconnection of the phases of a transformerthe secondary of which is loaded by a small capacitance only.

f) Ferro-resonance occurring on a transformer having on the secondary side an iron-cored inductive load suchas a voltage transformer, particularly when being switched in.

g/ Ferro-resonance which can occur when one phase of a circuit supplying an unearthed primary transformer isopened particularly if the circuit is a cable. At the highest end of range A, transformer bushing capacitance maybe sufficient to cause ferro-resonance under these conditions.

6. Switching and lightning overvoltages

For the purpose of this Guide, switching overvoltages are, as stated above, of a type which can be simulated by astandard switching impulse, i.e. an aperiodic wave with a front duration of the order of hundreds of microsecondsand a tail duration of the order of thousands of microseconds. They stress the various parts of an insulation in aboutthe same proportions as power-frequency voltages, but are not repetitive and only one peak of either polarity isnormally significant.

Lightning overvoltages are those which can be simulated by a standard lightning impulse, i.e. an aperiodic wavewith a front duration of the order of one microsecond and a tail duration of the order of several tens of microseconds.Due to the front steepness, they stress more than the former the longitudinal insulation of inductive windings, andbecause of their shorter duration, a generally somewhat higher stress at equal amplitude can be withstood by a giveninsulation. The magnitude of this effect depends on the type of insulation being considered.

These overvoltages generally arise from:

a) line energization and re-energization;

b/ faults and fault clearing;

c/ switching of capacitive currents and of small or moderate inductive currents;d) loadrejections;

e ) Iightning strokes (first or subsequent components of a lightning flash).

Note. - The overvoltages in cases a ) to d) depend on the characteristics of the equipment, especially of the circuit breakers, transformersand shunt reactors. They may generally be reduced by suitable choice of these characteristics, i.e. in case a) by using pre-insertionresistors or shunt reactors, and in case c) by using surge arresters connected between the circuit-breaker and the transformer.

6.I Switching overvoltages due to line energization and re-energization

Overvoltages due to closing and to single-phase and three-phase reclosing are of great importance in the selectionof system insulation in range C.

These overvoltages, except in special cases, are not of particular importance in the other ranges of voltages.

6.2 Switching overvoltages due to faults and fault clearing

In range A and in relatively few cases in range B under the conditions listed in Items a) and, b) of Sub-clause 5.1,high switching overvoltages can arise at the initiarion oi .:, rault.

,/-

Page 11: SPLN 7B_1978 Insulation Coordination,App

In all the voltage ranges, high overvoltages may arise due to faults to earth in composite circuits including over-head lines and cable-connected transformers.

At the highest voltages of range C, a high degree of control of overvoltages caused by line energization and re-energization is normally attempted. For this reason, switching overvoltages due to faults and fault clearing (singleand double phase-to-earth faults, and iheir clearance) need careful consideration.

6.3 Switching otervoltages due to switching of inductfue and capacitiye currents

In range A, the switching of inductive or capacitive currents can give rise to overvoltages, which may requireattention, both in high-voltage distribution systems and in industrial installations and power stations. In the case ofthe former, high overvoltages may arise ifthe circuit breaker deionizes so rapidly as to force the current prematurelyto zero, so-called current chopping.

In particular, the following switching operations should be taken into consideration:

a, interruption of the starting currents of motors;

bJ interruption of inductive currents, e.g. when interrupting the magnetizing current ofa transformer or reactor;

c) switching and operation ofarc furnaces and their transformers which may lead to current chopping;

dJ switching of unloaded cables and of capacitor banks;

e, interruption of cuments by high-voltage fuses.

In range B, overvoltages due to the interruption of capacitive currents (switching otr unloaded lines, cables orcapacitor banks) may be particularly dangerous since the use of restrike-free circuit-breakers cannot always beassumed.

6.4 Switching otervoltages due to sudden changes of load

Overvoltages due to sudden changes of load may start with a high switching surge followed by a temporaryovervoltage.

Overvoltages of this kind are particularly important at the highest voltages in range C where a high degree ofcontrol of reclosing surges is attempted.

6.5 Lightning ottervoltages

Lightning overvoltages are caused either by direct strokes to the phase co ductors, back-flashovers, or as a resultof strokes to earth very close to the line which produce induced lighlning surges. The overvoltages by which sub-station insulation is stressed are a function ofthe line construction and the system configuration. The configurationof the station itself has a great influence if the travelling time of surges within the station is not negligible in relationto the front time of the surge.

Depending on the system configuration, overvoltages with time parameters in the range of switching surges mayalso arise as a result of lightning strokes.

Lightning discharges which produce significant overvoltages in ranges B and C are confined to direct strokes tophase conductors or strokes to towers or earth wires with subsequent back-flashovers.

In range A, induced lightning surges must also be considered. Furthermore, in this range, surges transferredthrough transformers from a higher voltage slstem need care:ul "-onsideration.

Page 12: SPLN 7B_1978 Insulation Coordination,App

- 1 9 -

7. Determination of expected oYerYoltage Ievels

7 .l Range A

For voltages ofless than 52 kV, swirching overvoltages do not generally constitute a serious problem for overhead

supply systems and insulation co-ordination is based on lightning overvoltages'

Switching overvoltages transferred from an overhead line into a plant through transformers or lengths of cable

can, in general, be ignored for ttre same reason. An exception is the case of an installation connected to the lower-

voltage terminals of a high-voltage transformer feeder, particularly if resonance occurs between the two systems

during one- or two-phase energizing'

In industrial plants and power stations, the amplitudes and waveshapes ofswitching overvoltages generat€d within

the installation vary ov€r a very wide range. In the great majority of cases they are innocuous; in some cases,

serious overvoltage amplitudes and rates of change can occur. Thus sudden voltage swings can be caused when a

switching devic€ re-strikes; the resulting rate-of-change of voltage can equal that caused by a severe close lightning

strike.

A very large amount of practical operational experience is available from diferent industrial plants and power

stations, and tle most severe overvoltages or voltage swings can usually be avoided by eliminating resonance and

by correct choice of the switching device to be employed.

Detailed representation of the system under consideration on a digital computer or transient network analyser

can only be economically justified in particular cases at these voltage levels since accurate representation is needed to

obtain accurate results and a complex plant frequently consists of many pieces of equipment and electrical connec-

tions. Furthermore, the operation of some types of switching devices and arcing earths is difrcult to sirnulate with a

sufficient degtee of accuracy. Exlrrience is often the best guide and, in exceptional cases, deliberate switching te3ts

with simultaneous recording (both high-speed and low-speed) will produce the most valuable information so that

remedial measures can be taken as the result of subsequent calculations and confirmatory t€sts.

The amplitudes, waveshapes and frequency of occurrence of lightning overvoltages on systems in range A can be

estimated with a reasonable degree of accuraoy. As the impulse flashover voltage ofinsulators used on overhead lines

in this range is quite low as compared with the voltage imprdssed on such a line by a direct lightning stroke, the

stresses to which substation equipment is liable to be subjected are primarily determined by the type ofline construc-

tion. Thus careful protection of substation equipment is required if it is connected to a wood-pole line with un-

earthed cross-arms. Reduced protection is permissible where the lines are erected on steel masts, reinforced concrete

poles or where metal cross-arms are otherwise earthed.

Amplitudes and waveshapes are also affected by the following factors which characterize the constitution of the

system and arrangement of the station:

a) Surge impedance ofthose lines or cables which are connected to the station. For example, when only one line

is connected to a terminal transformer, the surge is reflected at the termination and is doubled in voltage amplitude;

when n lines ofthe same surge impedance are connected to the busbars of a station, and if the lightning stroke to

the line does not oc.cur close to the station, the voltage at the busbars bec omes 2 uf n, where z is the amplitude of

the surge voltage transmitted along the line on which the lightning surge originated; in the case of lightning in the

vicinity ofthe sub-station, wave reflection must be taken into account and calculation may prove to be necessary.

6) Cables with an earthed metallic sheath which are in series with the line or connected between the station bus-

bars and apparatus to be protected, Any cable tends to reduce the steepness of the waves entering the station, but

the cable length must be at least I or 2 km long before it has a significant effect on the surge amplitude. In the case

of a direct lightning stroke to the last span in front of a station, a cable section between overhead line and station

afiords practically no relief to the station equipment. More details arc given in Sub-clause 21.4.

c) Protective earth wires on the overhead lines extending up to a few kilometres from the station; these are efect-

ive against close lightning strikes to the line near the station uhich are the most dangerous. This pre-supposes

Page 13: SPLN 7B_1978 Insulation Coordination,App

- 2 1 -

that shielding by the earth wires is sufficiently well designed to prevent direct strokes reaching the phase conduc-tors, and that the earthing resistance of the tower is sufficiently low to reduce the risk of back flashover, as givenin Item e) below.

d) Prctective spark gaps or protective earth wires extending over one or two spans in front of the station; thesecan materially reduce the amplitudes of incoming surges on lines with high insulation to earth, e.g. on fully insul-ated wood-pole lines.

e,) Earthing resistances and inductances of the down leads of towers, particularly olose to the station. In the casesof high values of earthing resistance or the inductance of the down lead of the tower or pole, a lightning strike tosuch a tower or pole or to an earth wire may cause high overvoltages on the phase conductors by back flashoveracross the line insulators to one or more phase conductors.

In range A, lightning surges transferred through transformers are also important. Analytical expressions for theelectrostatic and electromagnetic terms of the transferfed voltages are derived in Appendix A.

7,2 Range B

In range B, as well as in range A, the insulation levels are generally such that switching overvoltages are seldom amajor problem and that insulation co-ordination is still mainly based upon lightning overvoltages occuning in over-head line systems.

Furthermore, also in this voltage range, there is usually no decisive economic incentive towards a detailed studyof oYervoltage stresses.

Thus the considerations in Sub-clause 7.1 continue to apply.

7.3 Range C

For this voltage range, the inportance of the switching overvoltages in insulation co-ordination becomes pre-dominant, all the more so as the voltage level increases. This is whatjustifles the substitution of a switching impulsetest, considered more representative, for the traditional 1-min power frequency test.

The high cost of equipment then compels consideration of more economical designs of insulation co-ordination.while, in turn, the serious consequences of a failure necessitate a more precise estimation of the overvoltages to beexpected. These have to be evaluated for each type of significant overvoltage in the particular system considered.

Because ofthe extensive computational requirements, virtually all practical overvoltage predictions must be madeusing transient network analisers or digital computers.

Experience with studies of a wide variety of systems has shown that development of generalized formulae for over-voltages is difficult because of the large number of parameters affecting the overvoltage value.

Both analogue and digital techniques of transient solution require a high level of skill in problern-solving. Theseskills are principally useful in the selection of significant cases (it being impractical to study all possibilities), in thereduction of the system to a reasonable number of busbars and tines (it is not practical to represent the entiresystem on either TNA or digital solutions) and in the description of system constants and apparatus characteristics.

Whenever possible, f.eld tests to check the validity of the parameters used are recommended.

In the sophisticated approaches to insulation co-ordination now becoming more and more usual for the highestvalues of voltage, the amplitudes of the overvoltages to be expected at a given location due to a given type of eventcannot be defined by a single value (see Figure 1, see page 106). It is only possible to state the probability f.(U) dU

Page 14: SPLN 7B_1978 Insulation Coordination,App

- 2 3 -

that an overvoltage value comprised between U and U + dU may occur, f"(tJ) being the overvoltage probabilitydensity. The probability F"(U') that the value U' may be exceeded is then given by:

Fo(U ' ) : I f " ( qdaU'

SECTION THREE INSULATION WITHSTAND

8. General

8.1 Self-restoring and non-sef-restoring insulation

Clauses 10 and 11, concerning definitions ofIEC Publication 71-1, subdivide insulation into self-restoring and non-self-restoring insulation according to its behaviour in the case of occurrence of a disruptive discharge during a di-electric test. On the former kind of insulation, it is possible to carry out tests under conditions that imply an appreci-able risk of such discharges, e.g. by applying a large number of impulses at the rated impulse withstand voltage, oreven in conditions with deliberately applied discharges as in a 50olo disruptive discharge test carried out at voltagesabove the rated impulse withstand level.

On non-self-restoring insulation, a disruptive discharge destroys the insulating property of the insulation and alarge number of impulses at rated withstand voltage may result in a gradual deterioration ofthe insulation. Non-self-restoring insulation is for these reasons tested by application of a limit€d number of impulses at rated withstandvoltage.

The degree of information on the dielectric strength ofthe equipment directly obtainable can thus be much higherfor self-restoring insulation. However, in the case of non-self-restoring insulation, the economic importance for themanufacturer of the risk of having the equipment rejected tends to compel him to design the equipment for a verylow probability of failure under test. Taking these two factors together, no difference is made in IEC Publi-cation 71-l between impulse withstand levels, in relation to the kind of insulation or the nature ofthe test.

While self-restoring insulation does not lose or rnodify its insulating ability following a disruptive discharge in adielectric test, it should not be inferred that damage may not occur in service ifthe disruptive discharge is followed b1an intense power arc.

Furthermore, possible damage to equipment is not the only consideration to be introduced in the selection of anacceptable risk of discharge in service, as the effect on continuity of supply also has to be considered. For example, anuch lower probability ofinsulation failure is required in the case ofbusbars than on individual lines.

It must be emphasized that the insulating structures of a piece of equipment are always made up of self-restoringand non-self-restoring parts. Generally it cannot therefore be stated that the insulation of an apparatus is self-restoring or non-self-restoring. But tlte probability that discharges may occur across or through non-self-restoringparts in the presence of self-restoring parts can, for diferent types ofequipment, be negligible or otherwise. Due to thediferent voltage-time sparkover characteristics of solid and air insulations, this probabitity tends to increase withincreasing impulse voltage amplitudes; thus it may be negligible at the rated withstand voltage, but may become ap-preciable around the 50% disruptive discharge voltage.

8.2 Selection of the type of test

For some types of apparatus, within the range of overvoltages that tests have to simulate, the probability of adischarge occurring across a non-self-restoring part is negligible. In this case, the discharge probability coincides

(1)

Page 15: SPLN 7B_1978 Insulation Coordination,App

- 2 5 -

with that of the self-restoring pats of th€ apparatus and its insulation may be called "essentially self-restoring"or, for the sake of simplicity, "self-restoring". Disconnecting switches may be considered an example of this type;in fact, €ven when applying impulses well above the 50% discharge voltage during a 507o discharge test, sparkovertakes place usually in air without any puncture of the porcelain. For this type of equipment, the test of Clause 52of IEC Publication 71-l is possible and recomnended.

For tl,p€s of apparatus with mainly or a large part of non-self-restoring insulation, the high cost of this part ofinsulation excludes tests ofthe complete apparatus at higher than rated withstand voltage. The test voltage is there-fore limited to the rated withstand voltage as this already implies an overinsulation of the non-self-restoring parts soas to give negligible probability of discharge up to rated withstand voltage.

Such t)?es of apparatus that also have a self-restoring part ofinsulation that cannot be tested separately from thenon-self-restoring part, e.g. bushings and some types of instrument transformers, would require a large number ofimpulses to prove the adequacy of the self-restoring insulation. The number of impulses must however be restrictedbecause of the possibility of gradual deterioration of the non-self-restoring parts of insulation. Insulation of thistype of equipment, that can be called combined, should be tested according to Clause 53 of IEC Publication 71-l,

For some types of equipment with mainly non-self-restoring insulation, e.g. power transformers, the self-restoringinsulation (e.g. bushings) can be tested separately according to Clause 52 of IEC Publication 71-1. This kind ofequipment is called "essentially non-self-restoring" or, for the sake of simplicity "non-self-restoring". Insulationof this kind is verifed by means ofthe test in Clause 54 of IEC Publication 71-1.

Considerations on the validity ofthe tests in Clauses 52, 53 and 54 of IEC Publication 71-1 are given in Appen-dix B.

9. Insulation behaviour rt power-frequency yoltages rnd temporary oyervoltag€s

In general, sparkover under power-frequency voltage in normal operating conditions and under temporaryovervoltages will be caused by progressive deterioration ofthe insulating properties ofthe equipment or by excep-tional reductions in insulation withstand due to severe ambient conditions.

In the latter case, the concept of probability is applicable to the degree ofcontamination (see Clause 4).

Because ofthe difrculties involved, no use of statistical concepts will be made in this Guide in respect of insulationbehaviour at power-frequency voltages and temporary overvoltages (see also Clauses 17 and 18).

10. Probability of di$uptive rlischrrge of insulation under impulse voltages

The ability of a given insulation to withstand the dielectric stresses caused by the application of an impulse ofgiven waveshape and peak value U is, in most cases, a random phenomenon, even if we consider a time interval sosmall (such as that needed to carry out a dielectric test on equipment) that the ambient and insulation conditions maybe considered constant, at least with respect to parameters such as pressure, temperature, humidity, etc., which canbe measured and which are used to define the ambient and insulation conditions during tests.

The disruptive discharge probability of insulation for an impulse of given waveshape and polarity, and for a peakvalue U in a short time interval as defined above (e.g. in a dielectric test) can be determined, if the insulation is self-restoring, by applying the impulse U N times successively within this time interval, and counting the number Nl of

. N ldischarges. From the fraction , a numerical value can be obtained for this probability which will be the more

accurate the greater is the valu; of N.

Page 16: SPLN 7B_1978 Insulation Coordination,App

- 2 7 -

The discharge voltages of a population of non-self-restoring insulation can be described statistically by means ofa distribution curve that gives the relation between the amplitude of the discharge voltage and the fraction of thepopulation that will break down at that voltage amplitude. For the determination of this distribution curve. testsmust be performed vrith Yoltage amplitudes increased up to breakdown on a sample of pieces from the population.The accuracy in the determination of the curve will be increased by increasing the number of pieces in the sample.Because a disruptive discharge normally results in the destruction ofthe test piece, the number ofpieces in the samplemust be limited for reasons of economy.

No method is at present known for the determination ofthe probability of disruptive discharge ofa single piece ofnon-self-restoring insulation.

If we consider either switching or lightning impulses of different peak values U, we shall be able to assoctate withevery possible value of U a discharge probability P,, thus establishing a relafionship pr(U) for a given insulation in ashort time interval At or, for the sake of simplicity, at a time t (see Figure 2a, page 107).

The values ofP,(LQ increase from near 0 to near 100% probability in a more or less narrow band ofvoltage values.In general, the resulting curve can be defined by a biparametric law, one paraneter being associated with the positionofthe voltage band and giving an indication of the withstand level, and the other associated with the bandwidth andgiving an indication of the scattering of the voltage values which give appreciable proportions of both dischareesand non-discharges.

Generally, in a laboratory, the parameter that defines the position of the probability curve is taken as the voltageUr uo which conesponds to the 50% discharge (or withstand) probability. The standard deviation of the distribution(o), defined by the square root of the sum of the squares ofthe deviations with respect to the mean is usualty takenas the parameter which expresses the scattering. For a Gaussian distribution, it corresponds to half the difierencebetween the voltages that give discharge probabilities of 16Vo and 84vo.

In service, the ambient and insulation conditions do not remain constant. Therefore the discharge probabilitycurve of insulation, as defi.ned above for the time t, is bound to change from one moment to another (.pr, pr.. . .)(see Figure 2a). The variations are determined, as regards external insulation, mainly by atmospheric conditions.

Taking the ambient and insulation conditions as random, it will be nec€ssary to consider for each insulation,inaddition to the discharge probability P,(t/), as defi.ned above, a discharge probability of insulation p1({/) to over-vdltages of amplitude U liable to occur at any instant of a long time interval z of operation. For the purpose ofinsulation design, it is this second distribution which is of interest (see Figu re zc, pageiol).

Similarly to Pt(U), P(Lf can be defined by the voltage (U1 50) which coruesponds to the 50% discharge (or $.irh-stand) probability and by the standard deviation of the distribution oa.

The variations of Pt( t/) within the time interval AZ may be conveniently defined by the probability density po([.'.,01where Ut 60 is considered as a random variable (Figure 2b, page 107). This latter function in turn may be charactcr-ized by the 50olo discharge voltage Ua 50 and by its standard deviatiou oo.

On the simplifying assumption that the standard deviation ar of Pr(U) is constant within the time interval A2.the following relation holds:

1l-=__---o, -- ll o? + o?

vIn IEC Publication 71-1, the parameter that defines the position of the probability curve p(Lf is taken as the

voltage which comesponds to a withstand probability of90% (see Clause 26 ofIEC pultication il-l), atthough the50% discharge voltage which was referred to above is a convenient measure for pieces of insulation that can be sub-mitted to a 50% disruptive dischaxge test.

The reason for this choice is that the 50% disruptive discharge test cannot be generally applied to all kinds of insu-lation. Thus, in order to have the same values of the rated impulse withstand voltages foi all tylrs of equipment,whatever its insulation, and to use these values directly in the definitions of statistical distributions, it has been!3em9d appropriate to refer to a higher value (90%) of the withstand probability, the rated impulse withstand voltageUav being identical with the lowest perrnissible value of the statistical impulse withstand voltage under specifedt€st conditions 4 eo.

(2)

Page 17: SPLN 7B_1978 Insulation Coordination,App

- 2 9 -

For risk-of-failure evaluations, it is however convenient to express the probability curves ofinsulation discharge interms of their 50% discharge voltages and standard deviations.

Assuming for Pr(U) a Gaussian distribution with standard deviation or, the difference between the 50"/o discharge(or withstand) voltage and the statistical (or 90%) withstand voltage is given by:

tr Ut sou t s o :

r - l - 3 o ,

o, depends upon numerous parameters (waveshape, polarity, confi.guration of the object, dielectric nature, etc.).However, on present info nation, and for equipment of range C in air, ot is taken as 0,03 or 0.06 depending on thetype of impulse, lightning or switching, unless another value has been specified by the relevant Apparaius Committee(see Clause 52 of IEC Publication 71-l).

The probability of discharge P,(Lf of a piece of equipment which during the test conforms to what is specifiedin IEC Publication 71-1 can then be defined in terms of its 50% discharge voltage and its standard deviation, asfollows:

(Jrro:*r-r r#a

The probability of discharge P,(U), defined by the above parameters, refers to the most severe test conditions forthe equipment, since Uis, is the rated switching or lightning impulse withstand voltage. Thercfore, if impulse testshave to be made in both wet and dry conditions, the probability P,(tr) refers generally to wet condifions.

The probability of discharge in service p1((/) of a given piece of equipment can only be deduced from field tests,depending on the site of insiallation.

However, as a broad indication, the probability Pa(Lf of a piece of equipment conforming to the specifications ofIEC Publication 7l'1 can be defined, recalling equation (2), in terms ofits 50% discharge voltage and its standarddeviation, as follows:

Un*Lhso > k------

l - 1 . 3 o ,-t /-o , - l l , ? + o lv

where /c is the ratio between the 50% discharge voltage of a given equipment in service during a time interral lIand the 50% discharge voltage under the most severe impulse test for the equipment (wet or dry, positive or negatrvepolarit .

For switching impulses U of positive polarity, the values of k and oo relevant to time intervals AT of fine dryweather or various bad weather conditions do not show appreciable differences. The same may be said concerningthe degree of atmospheric pollution, at least in the range from clean conditions to lightly polluted conditions.

.For switching impulses Lr of negative polarity, the values of /< and o,, are highly dependent on the type of weatherwithin the time interval A? under consideration. Concomitance ofbad weather (rain, snow, fog, misi, erc.; and notnegligible pollution leads to a low value of k ; bad weather also increases the value of oo.

Values of k : I and oo : 5olo are suggested in this Guide for normal conditions and a time interval AZ equal tothe seasonal cycle to cover the worse polarity impulse. This value ofoo results in a value ofar a little lower than g%.

The same values of ft and oo are also suggested for lightning impulses. This gives a value of aa equal to 6%approximately.

The information given above is to be considered merelyshould be made of more detailed data derived from field and

(3)

(4)

(s)

as broadly indicative and it is recommended that uselaboratory tests, if available.

Page 18: SPLN 7B_1978 Insulation Coordination,App

11. Apporetus with windings

An apparatus with high-voltage windings, such as a transformer or reactor, designed to withstand only full-wavetests, is vulnerable, to a certain extent, to a surge of high amplitude chopped in its vicinity because higher internalstresses than under full-wave conditions can be developed across adjacent turns and coils. All flashovers to earth ina substation result in chopped waves ofvarious degrees of amplitude and steepness. If because of the use of protec-tive spark gaps, flashovers are liable to occur frequently in service, the withstand strength of the windings againstsurges must be determined by testing with a suitable chopped wave. The provision for such a test is left to the relevantapparatus committee.

Where non'linear resistor-type surge arresters are used for the protection of transformers, chopped wave tlpesurges tend to be less severe and they are less likely to arise; in practice, chopped wave tests are not usually required.

For all types of apparatus having windings, such as rotating machines, transformers and reactors, rapidly changingvoltages due to the restriking ofswitching devices may also produce nonJinear voltage distributions similar to thosecaused by lightning overvoltages. For this reason, it is recommended that such equipment, irrespective of whetheror not it is to be used in installations subjected to lightning overvoltages, should be tested with a lightning-impulsevoltage to sheck the winding insulation for voltage withstand across turns and coils.

SECTION FOUR PROTECTIVE DEVICES

12. General

These devices fall under three classes:

- non-linear resistor-type surge arresters;- expulsion-type surge arresters (range A only);- spark gaps.

The choice between these three devices, which do not provide the same degree of protection, depends on variousfactors, e.g. the importance of the equipment to be protected, the consequences of an interruption of service, etc.

Their characteristics will be considered below from the point of view of insulation co-ordination.

13. Non-linear resistor-type surge anesters

These protective devices should be designed and installed to limit t}re magnitudes of overvoltages against whichthey protect equipment so that the total surge-arrester voltage during operation does not exceed an acceptable value.Surge arresters are deflned and their characteristics are given in IEC Publication 99-1. Their rating is defined as thespecified maxirnum permissible r.m.s. value of power-frequency voltage between their terminals at which they aredesigned to operate correctly; this voltage may be applied continuously to surge arresters without changing theiroperating characteristics. In addition to this defined capability, some types of surge arresters 1 can successfullywithstand either aJ higher than rated voltage for a specified short duration, or D) a specified number of successivedischarges.

In either case, a controlling factor in the selection of the surge arrester is its ability to interrupt follow current atits rated voltage or in the case of temporary overvoltages, exceeding its rated voltage.

I These types of surge arresters are currently available onl)' for range C.

Page 19: SPLN 7B_1978 Insulation Coordination,App

Aprimary point is that the voltage produced across the terminals ofthe arrester at any moment prior to and duringoperation must be considered in the determination of the switching impulse protective level and the lightning im-pulse protective level.

13.1 Lightning impulse protective level

The lightning impulse protective level of a surge arrester is characterized by the following voltages:

a) the sparkover voltage for a standard full lightning impulse (see Table VI of IEC Publication 99-1) 1;

6,) the residual (discharge) voltage at the selected standard nominal current (see Table YII of IEC Publi-cation 99-1);

c) the front-of-wave sparkover voltage (see Table VI of IEC Publication 99-1).

The protective level under lightning impulses is taken for insulation co-ordination purposes as the highest of thethree following values :

- maximum sparkover voltage with 1.2/50 impulse;- maxinum residual voltage at the specifled current;- maximum front-of-wave sparkover voltage divided by l.l5 (see Clause 33 of IEC Publication 71-1).

This evaluation of protective level gives a conventional value representing a generally acceptable approximation.For a better definition of wave-front prokction by a surge arrester, reference should be made to IEC Publi-cation 99-1.

13.2 Switching impulse prctective level

The swirching impulse protective level of a surge arrester is characterized by the following voltages:

a) the maximum sparkover voltage for the standard wave-shapes specifled in Sub-clause 61.4 of IEC Publica-tion 99-1;

,) the total surge-arrester voltage exhibited by the surge arrester when discharging switching surges.

The protective level for switching impulses is the higher value of a/ or 6). Until a standard test for D) has beenspecifled by IEC Technical Committee No. 37, Lightning Arresters, reference should be made to the surge-arrestermanufacturers,

14. Expulsion-type surge arresters

These protective devices operate to limit overvoltages and interrupt follow currents within their ratings. They havelow residual voltages. The characteristics of these devices are given in IEC Publication 99-2.

The impulse sparkover characteristics resemble those of protective spark gaps, but are in general lower and flatterfor the same sparkover distance.

These arresters may not appreciably limit the amplitude of the follow current before interrupting it and may havecurrent-interrupting ratings which must be compared with the prospective fault current and the prospective transientrecovery voltage at the point of installation.

I The tables mentioned here give for each surge arrester voltage rating the upper limit for each of the above voltag€s. If bettei character-istics than those specified in I EC Publication 99-1 are available, the actual voltages for the specific sulgp arester will be obtainable fromthe manufacturers. Thus, it is recommended that the actual voltages for the surge arrester prctectiv€ chaRcteristics be used foi co-ordi-lation studies.

Page 20: SPLN 7B_1978 Insulation Coordination,App

- 3 5 -

15. Spark glps

The spark gap is a surge-protective device which consists ofan open air gap between an energized electrode and anearth electrode.

On supply systems operating at voltages up to 245 kV, spark gaps have proved satisfactory in practice in somecountries with moderate lightning aotiyity. The adjustment of the gap settings is often a compromise between pro-tection and service continuity, but this difficulty can be largely overcome by the use of rapid automatic reclosing.

The sparkover voltage and the time-to-sparkover ofthe gap depend essentially on the distanc€ between the elec-trodes; they are influenced by the shape of the electrodes and also by their disposition and distsnce relafivd to theneighbourilg live and earthed parts.

In order to improve the operation of a spark gap under steep-fronted surges and to provide a flatter impulsesparkover-voltag€ time characteristic, the geometrical conf.guration ofthe simple rod-rod electrode arrangement canbe modified, for instance by appropriate shaping ofthe electrodes and by provision of a central auxiliary electrode.In range A, duplex-type spark gaps have also proved advantageous in regions where birds or small animals aretroublesome.

ls,L Prctective characteristics of a spark gap

Because of:

a) the dispersion of the sparkover voltage of an air gap,

,, the increase in the sparkover voltage with increasing amplitude ofthe applied wave when sparkover takes placeon the front of the wave,

the protection obtained by means of spark gaps is less precise and the protective level cannot be given as preciselyas the protective level of non-linear surge arresters.

The performance of a spark gap under impulse (switching or lightning) is characterized by the 50olo value and thestandard ddviation of its discharge voltage under standard laboratory conditions. Since spark gaps constitutetypical self-restoring insulation, the contents of Clause 10 apply also to them. Furthermore, because of the reasonsgiven in Iten b) above, knowledge of the times-to-sparkover of the spark gap for values of the applied impulseswell above the 50% sparkover value is often needed (see Appendix C).

15.2 Limitations of protective spark gaps

c) When the spark gap operates on a voltage surge and a power-arc results, this arc frequently persists until dis-connected by a fault-protective device of the system; this constitutes a phase-to-€arth fault in the case of a systemwith directly earthed neutral, entails mechanical stresses on the various parts of the system equipment and maycause disturbances to users. The location of the spark gap should therefore be considered in relation to its efect onthe system protection aud operation.

b) The spark gap is unacceptable from the point of view of service continuity if its presence noticeably increasesthe number of circuit outages, provided these flashovers are neither self-extinguishing nor interrupted by meansof high-speed tripping circuit-breakers followed by high-speed reclosing.

c) Spark-gap operation causes ohopping of the wave, thus increasing the probability of producing choppedwaves close to the terminals of protected apparatus, This has to be taken into consideration for insulation ofhigh-voltage windings (see also Clause 11).

d) Damage to the equipment may be caused by the power-arc across the spark gap if this is not installed in asuitable position. For instance, if a spark gap is fitted to the bushing of a transforrrer or circuit-breaker, its dis-tance from the bushing surface must be sufficiently large to prevent a power-arc being blown against the insulator.

e) The relative arrangement ofthe spark-gaps ofeach ofthe phases must be chosen so as to minimize the risk ofan arc spreading to neighbouring phases, which would transform a single-phase fault into a tfuee-phase fault.

Page 21: SPLN 7B_1978 Insulation Coordination,App

- 3 7 -

16. Application of different protective devices

l6.l Protection with non-linear resistor-type surge arresters

The distance separating the object to be protected from the surge arrester reduces the efficiency of the latter. Infact, when the surge arrester is separated from the object to be protected, the latter is subjected to an overvoltageexceeding the protective level of the arrester. This increase is due, in the first place, to the inductive voltage drop inthe arrester connections and in the link between arrester and apparatus to be protected; secondly, ifthe duration ofpropagation between arrester and apparatus is not negligible as compared to the duration ofthe incoming wave front,due to an increase of short duration of the voltage at the terminals of the apparatus with respect to the protectivelevel of the arrester. Thus, it is a general rule to locate the arrester as close as possible to the apparatus to be pro-tected. In particular, surge arresters should preferably either be installed on the transformer tank or its high-voltageand earth terminals should be connected to the transformer by the shortest possible connections.

Similarly, surge arresters should be fi.tted close to cable terminations if they need protection, with the shortestpossible connections between the terminals of the surge arrester and the phase conductor and the cablesheath respectively.

Note. - In rhe case ofsurge afieslers clo6e to theapparalus lo be protected, the followingsafety fadors are recommended.

a, Range A, - A safety factor of approximately 1.4 should be provided for Series I equipment between the rated lightningimpulse withstand level of the apparatus 10 be protected and the impulse protective level of the surge arrester (see Claus€s 4land 42 of I EC Publication 7lJ). For Series II equipment, factors down to 1.2 are acc€pted for sp€cific cases.

6., Ranges B and C. - Saf€ty factors ofat least 1.2 a.e normally provided for lightning overvoltag€s.

c, Range C. - Safety factors of at least l.l5 for switching overvoltagEs and 1.25 for lightning overvoltages are normallyadopted.

The considerations in I EC Publication 99-lA should also be taken into account.

The installation of surge arresters close to the apparatus to be protected can be achieved more easily in voltagerange A than in voltage ranges B and C.

The increase due to both these factors depends on a number of conditions: distance of the surge arrester and itslocation ahead of, or behind, the apparatus to be protected, characteristics of the line, capacitance of the apparatusto be protected, arrangement of the station and steepness of the incoming wave. This increase can be limited by allarrangements which limit the steepness of the surge arriving at the station (extension of shielding wires, localizedcapacitance, cable (even short), large number of connected lines).

16.2 Protection tuith expulsion4ype surge arrestefs

These arresters are sometimes used on high-voltage distribution circuits where shielding against lightning is norprovided (range A).

The impulse sparkover voltage-time characteristic of such an arrester is flatter than that of a rod gap of the samesparkover distance, but not quite as flat as that of some types of equipment, for example a transformer $ inding or acable.

For this reason, an adequate margin of safety is required, not only for the lightning-impulse sparkover voltage ofthe arrsster and of the equipment to be protected, but also for the corresponding front-of-wavd sparkover voltage.These conditions are assisted by the usual practice of installing these types of arrester close to the equipment to beprotected.

For further information concerning the applications of these devices, reference should be made to IEC Pub-lication 99-2.

16.3 Prctection tith spark gaps

The impulse sparkover voltage-time characteristic of a spark gap is usually much more curved than those of someof the types of apparatus to be protected, particularly those of transformsrs and cables.

Due to the curved shape of the voltage-time characteristic of a spark gap, the distance over which protection isensured for all surges is very small, usually not more than a few metres. If a spark gap is applied for protection

Page 22: SPLN 7B_1978 Insulation Coordination,App

- 3 9 -

against surges of a limited front steepness (considerably lower than the steepness of the standard lightning-impulsetest voltage wave), a distance of several tens of metres betwe€n the spa.rk gap and the object to be protected does notappreciably modify the conditions for the protection provided against such surges.

A spark gap is therefore liable to operate not infrequently when stressed by lightning surges, and occasionallywhen stressed by switching surges, the amplitudes of which are below the lightning-impulse withstand voltages ofthe apiaratus to be protected. In a large number of cases, the operation of the spark gap causes a circuit outage if thegap is on the supply side of the opening switch. If the supply can be restored quickly by high-speed automatic re-closing, the setting of the spark gap can be adjusted so as to provide an acceptable degree of protection to theapparatus without causing an excessive number of supply interruptions troublesome to consumers.

Note. - Safety fa.lors of tlre order of thos€ gived for su!8p arr€steE gcoerally ensure satisfactory prot€ction provided the occurren€ ofwry st€€p fro ed surg€s is excluded (s€e AppeDdix C).

SECTION FIVE _ CO-ORDINATION BETWEEN STRESSES AND WITHSTANDCONSIDERATIONS COMMON TO RANGES A. B AND C

17. Insulation design to F)wer-frequency operating yoltage anrl temtr orary oyeryoltrge, hoblems of pollutionand rgeing

Clauses 38 and 39 of IEC Publication 71-1 leave it to the relevant apparatus committees to prescribe the longduration power-frequency tests, intended to demonstrate the behaviour of equipment with respect to ageing of in-ternal insulation or to external pollution. General guidance only is given to the apparatus committees; it is indicatedthat as regards the voltage under normal operating conditions, the insulation shall withstand permanent operation atthe highest voltage for equipment.

18, Pollution

For insulation susceptible to contamination, the problem of specifying a suitable test method and pollution severitylevels is at present under consideration in various apparatus committees. When contamination tests are established,it is anticipated that the system engineer will specify a degree of pollution sevGrity in relaiion to the pollution of theenvironment in which the equipment is installed.

Table I, page 95, gives a provisional basis to the system engineer for establishing a classification of pollutionseverity levels.

A scale defined in quantitative terms with reference to a test method should be associated with each of thesequalificative levels of natural pollution severity for various tytrrs of insulator.

Besides being reproducible, the test method should, as far as possible, satisfy the requirements of validity, i.e. ofasaiisfactory simulation of the natural conditions in which the equipment is to be installed. Therefore, the mostsatisfactory tests, among those at present adopted, may vary from case to case.

It should be emphasized that Table I does not cover some environmental situations, such as desert areas wherelong dry periods are followed by condensation or light rain.

As an example, Table II, page 97, gives the relationship between the levels ofnatural pollution and their simulationin laboratories according to two types of tests. The table also gives an indication of the requircd creepage distance,although it is recognized that the performance of surface insulation is greatly affect€d by insulator shape. Moreover,at the present stage of research, these indications are valid only for pin-and-cap type insulators.

\."..!

Page 23: SPLN 7B_1978 Insulation Coordination,App

- 4 1 -

The data in Table II are intended to cover the behaviour of equipment at the appropriate single-phase voltage,i.e. U^l t/l However, in the case of a system which may operate with a phase earthed for long durations, thesef.gures are valid for the phase-to-phase voltage U-.

If temporary overvoltages are frequent and severe, it may be necessary to take them into account in specifying thepollution test.

In the case of stations with a high degree of pollution, when it may be impossible or extremely expensive torequire the necessary performance of equipment under pollution conditions, the alternatives of greasing or washingthe insulating surfaces should be considered.

19. Ageing

For insulation susceptible to ageing, the problem of specifying suitable test methods is also at present under con-sideration in various apparatus committees.

SECTION SIX - CO.ORDINATION BETWEEN STRESSES AND WITHSTANDIN VOLTAGE RANGE A

20. Selection of the roted lnwer-frequency withstand voltage

The tables of standardized values for Series I and II in IEC Publication 71-1 indicate only one value of ratedpower-frequency withstatrd voltage for each system voltage (/-.

21. Selection ofthe rated lightning-impulse witlstand yoltage

Table I of standardized values for Series I in IEC Publication 71-l leaves the choic€ open between two rated light-ning-impulse withstand voltages, corresponding to list 1 and list 2. Table II for Series II indicates representatiye yalues

of rated lightning-impulse withstand voltage depending upon whether the power of the equipment is below or equalto 500 kvA, or above.

The reduced rated lightning-impulse withstand voltages of Series I, list l, were introduced with the avowed aim tomake these values acceptable to all apparatus committees. Reduced rated lightning-impulse withstand voltages havebeen used with good results in many countries and for a wide range of equipment over long periods of time. Com-prehensive tests have also been performed on different types of equipment for this voltage range to determine theirinpulso withstand voltages, both for standard lightning impulses and representative switching impulses. It has beenfound, in particular, that the breakdown voltage of insulation under typical switching impulses is always higher thanthe peak of the power-frequency test voltage. This is one reason why it was not found necessary to introduce a separateswitching-impulse withstand test in voltage range A.

The choice between list I and list 2 is to be made in accordance with Clause 42 of IEC Publication 71-1 and tbefollowing considerations relevant to the equipment installations:

a, equipment with no connection to an overhead line;

D,/ equipment connected to an overhead line through a transformer;

c, equipment connected to an overhead line either directly or through a cable, *:

i

;'il

Page 24: SPLN 7B_1978 Insulation Coordination,App

_ 4 3 _

21.1 Equipment with no corneclion to ot overhead line

A wide variety of installations is covered by this category, e.g. large underground cable networks in cities; manyindustrial installations; power stations and ship installations. Equipment in such locations is not subjected to anyexternal (lightning) overvoltages, but may be subjected to switching overvoltages (see Sub-clause 6,3).

Clause 42 of IEC Publication 71-1 specifies the conditions for the use of equipment according to list 1 in suchinstallations. In all other cases, equipment according to list 2 should be used and, with few exceptions, no surgeprotection is required. One such exception is an electric arc-furnace installation where high overvoltages are liable todevelop due to current chopping by a circuit-breaker. Protection by special surge arresters may be required in such acase both between phases and between phases and earth.

21.2 Equipment connected to an overhead line through a transformer

A) GENBRAL coNsrDERATroNs

Equipment connected to the lower-voltage side ofa transformer supplied on the higher-voltage side from an over-head line is not directly subjected to lightning or switching overvoltages originating on the overhead line. However,du€ to electrostatic and electromagnetic transference of such overvoltages from the higher-voltage winding to thelower-voltage winding of the transformer, such equipment can be subjected to overvoltages which, in certain cir-cumstances, can exceed its withstand voltage.

Analytical expressions for the electrostatic and electromagnetic terms of the transferred voltage are given inAppendix A.

For a given transformer, the magnitudes and waveshapes of these transferred overvoltages are mainly dependenton the nature of the lower-voltage circuit and, for this reason, it is convenient to consider the selection ofthe ratedlightning-impulse withstand voltage of the equipment and its protection separately for the two basic categories ofinstallation as follows :

Category 1. - Equipment connected through transformers to higher-voltage overhead lines, and incorporatingconnections of moderate length, say uP to 100 m, between the lower-voltage side of the transformer and the equilFment, such a8 the main supply switchgear of a cable distribution netlvork or an industrial installation.

Category 2, - Generator-transformer installation.

B) BAsrc cnrDANcB

a) Category 1 equipme t

Factors which tend to increase the magnitude of transferred overvoltages for such equipnent are:

i) a transformer having a high-voltage ratio and high capacitance between windings;i, a transformer disconnected from its load on the lower-voltage side;lr) low-capacitance connections between a transformer and its associated equipment;rv, a higher-voltage winding which is not earthed (e.g. delta or unearthed star) or having a star point which isearthed through a high reactance (e.g. arc-suppression coil);v) surges having steep wavefronts and surges having long durations;yt switching surges due to energizing a transformer from a remote point on an overheatlline system (i.e. ener-gizing a transformer-feeder).

See also note below.

Estimates of the magnitudes of transferred overvoltages can be made, and methods of calculation, with examples,are described in Appendix A.

Page 25: SPLN 7B_1978 Insulation Coordination,App

- 4 5 -

Category 1 equipment can usually be protected by surge arresters, and where such protection is provided asnormal practice, it is not necessary to make these calculations. For other cases, basic guidance is given below on thenature of the transferred voltages, the general influence of circuit conditions and the criteria which can be used todetermine whetler precautions are necessary'

Note, - Resorunt orerrolrage: A, c..ndition ofr€sonance between two systems coDn€cted by a traDsfornrer cant cause abtromally large volt-agEs to be tlansfer€d through thc traosformer. It is reaonunended that an examin4tioo of the clruits for possible lesonanceshould be ruade. atrd modifications should be made as n€cessary to avoid resonance.

The application ofshort duration, or steeply rising, voltage surges to the higher-voltage winding ofthe transformer,e.g. a lightning stroke to the transmission line very close to the transformer can, through capacitive coupling, give ashort duration voltage "spike" on the lower-voltage winding. This may exceed the impulse test voltages given inTable I, lists 1 and 2, or Table II of IEC Publication 7l-1. On the other hand, the shortest possible front time,determined by surge impedance of the line and transformer input capacitance, is often so long that the capacitivelytransferred voltage can be ignored.

For Category I equipment, the most severe condition arises when the load circuits are disconnected, i.e. on thetransformer side of the lower-voltage switchgear, sinc€ with the load connected its capacitance is usually sufficientto reduc€ the amplitude of the initial voltage "spike" to a safe value.

If the capacitance of the connections between the transformer and lower-voltage switchgear is not sumcient toreduce the amplitude ofthe initial voltage "spike", either additional capacitance can be connected between the trans-former terminals and earth, or equipment in accordance with Table I, list 2, or Table II of IEC Publication 7l-1,may be used.

It may also be desirable to consider adding surge arresters. Attention is also drawn to the possibility of increasinginductively transferred overvoltages by additional capacitance. This increase can be reduced by a series dampingresistor of carefully adjusted resistance valu€.

The application of a longer duration voltage surge to the higher-voltage winding of the transformer, e.g. a light-ning stroke to the transmission line some distance from the transformer or a switching surge, will, through inductivecoupling, give a voltage surge on the lower-voltage winding of the transformer having a longer duration and anamplitude similar to the peak value of the power-frequency test voltage given in Table I ofIEC Publication 71-1.

Dangerously high temporary overvoltages can be transferred to the lower-voltage winding ofa transformer throughcapacitive coupling from the higher-voltage winding when an earth fault exists on the higher-voltage system and whenthe neutral of the lower-voltage system is earthed through an arc-suppression coil or when it is isolated. In suchcases, the connection of additional capacitances between the low-voltage terminals of the transformer and earth is awidely-used protection method.

b) Category 2 equipment

Recommendations on the need for overvoltage protection of generator-transformer installations and on the choiceof suitable types of protective equipment need to be based on consideration of overvoltages of atmospheric originonly since studies haye not revealed more severe conditions likely to arise frorn transference of switching surges,Corresponding to the front of an incident lightning surge, or to the collapse of voltage due to wave chopping, therecan be a capacitively transferred voltage ofshort duration (initial voltage "spike"). This is independent ofthe longer-duration voltage surge which is usually transferred by the combined efect ofinductive and capacitive couplings.

The maximum amplitude of the initial voltage "spike" is highly dependent on details of the design of the instal-lation. Where these are such as to assist capacitive transference, there may be justif.cation for making a low-voltagesurge-injection test on the installation or on the generator-transformer connected to a circuit simulating the generatorand its external connections.

Factors which tend to increase the magnitude of transferred overvoltages for such equipment are:

l'J high capacitance between the transformer windings;

fi,) low-capacitance connections between transformer and generator;

Page 26: SPLN 7B_1978 Insulation Coordination,App

- 4't -

,rr, high-voltage ratio of transformer;

iy, lower-voltage transformer winding not connected to a generator;

vJ surges having steep wavefronts and surges having long duration.

Ifthere are indications that the amplitude ofthe initial voltage spike should be reduced, this can be done effectivelyby connecting non-inductive capacitors between each phase and earth, preferably at the transformer terminal, bymeans of low-inductance connections. Attention is drawn however to the possibility of increasing inductively-transferred overvoltages by additional capacitors.

The longer-duration transferenc€ generally takes the form of a unidirectional voltage with superimposed oscil-lations having a frequency of several kilohertz and if reduction of this is necessary, consideration should be givento the addition of surge arresters.

However, voltage division between the reactances of the generator transformer and the generator normallyensures that the amplitude of the longer-duration transference does not warrant the use of surge arresters. For largegenerator installations, surge arresters on the generator are not generally acceptable and check calculations shouldbe made. In so far as surge arresters can be readily applied to small installations, there is no necessity in these casesfor calculations of transference to be hade. If the generator transformer can be energized from the high-voltagesystem when the generator is disconnected, voltage division between generator and transformer does not occur andconsideration should be given to the higher amplitude of the longer-duration transference affecting that part of thelower-voltage circuit which remains connected to the transformer.

The etrects ofthe application of longer-duration voltage surges to the higher-voltage winding ofa transformer andtheir transference to the lower-voltage winding when an earth fault exists on the higher-voltage system and when theneutral ofthat system is earthed through an arc-suppression coil, or ifit is isolated, are subject to the same consider-ations as described for Category I equipment.

C) Srr,ecnor oF TNSTJLATToN LB\tsL

The choice of whether to use list I or 2 of Table I of IEC Publication 71-1 and whether additional overvoltageprotection is necessary should be based in the flrst place on service experience with similar installations. It may alsobe useful to make neasurements on a similar existing installation, using a low-voltage impulse-injection method.

For a large generator-transformer installation, for which the necessary data concerning the transformer and theprotective equipment are available, it will be useful to calculate the overvoltages liable to be transfered and tocompare the results with the appropriate withstand voltages of the equipment to be protected. This is normalll-advisable only for direct connections between generator and transformer and for low-voltage tertiary windings onlarge system transformers. If a circuit-breaker is installed between a generator-transformer and its associated gen-erator, consideration should be given to the two cases of when the breaker is closed and when it is open, although aload is usually connected to the lower-voltage winding of the transformer whereby transferred overvoltages may bcreduced even in the latter case.

Several methods of calculation have been published and, on the whole, these seem to give similar results. Althoughno absolute accuracy can be claimed for any method of calculation, comparison between calculation and exper-irrental results on a variety of installations has shown satisfactory agreement. It is therefore deemed appropriate toillustrate a nethod of calculation by reference to two numerical examples, covering Cat€gories I and 2 respectively.These examples are given in Clause A'2 of Appendix A.

21,3 Equipmmt connected directly to an overhead line

Equipment installed in a substation connected directly to an overhead line is subject to direct or indirect lightningovervoltages. Such equipment should, as a general rule, comply with the rated lightning-impulse withstand voltagesspecified in list 2 (Table I) or Series II (Table II) in IEC Publication ?l-1.

All equiprrent and, in particular, transformers in such locations require protection by surge arresters or sparkgaps' Taking into account the flat impulse sparkover voltage-time characteristic of a transformer winding, trans-

Page 27: SPLN 7B_1978 Insulation Coordination,App

- 4 9 -

formers should preferably be protected by non-linear resistor-type surge arresters in areas of intense lightningactivity. In areas of moderate lightning activity, expulsion-type lightning arresters can be used. Where lightningactivity is slight, protective spark gaps have proved adequate, particularly where the transformer is connected to aline with earthed cross-arms or where the transformer is designed to withstand steep-fronted chopped waves.

The bushings of circuit breakers, instrument transformers and substation insulators having curved impulsesparkover voltage-time characteristics, can be effectively protect€d by existing protective devices on the trans-formers. Considerations relative to the distance between protective device and protected apparatus developed inSubclause 16.1 are also valid here.

In areas of moderate or low lightning activity, equipment having rated lightning-impulse withstand voltages inacrordance with list I of Table I of IEC Publication 71-1 may be used but, in that case, careful attention must bepaid to adequate overvoltage protection. In a system the neutral of which is earthed through a low resistance, surgearresters or spark gaps can be used for this purpose. In a system the neutral of which is earthed through an arc-suppression coil, adequate overvoltage protection must be provided. If surge arresters are used, those which canwithstand repeated operations during the persistence of ficing earths are recommended.

ln the absence of any overvoltage-protective device, lightning surges impressed on an overhead line are limitedonly by sparkovers on the line at the weakest points which the surges meet during their propagation. If not correctlylocalized, such spa;kovers can cause damage to equipment as a result ofsurge reflections between the point of spark-over and a vulnerable apparatus, such as a transformer winding.

In the case of a substation with a number of lines normally connected to the busbars, the surge voltage arising atthe busbars is likely to be sufficiently reduced so as not to overstress apparatus in the station (see Sub-clause 7.1).

However, such a solution (no overvoltage-protective device) may be acceptable in practice on overhead supplysystems in regions of very low lightning activity, at least if equipment according to list 2 of Table I of IEC Publi-cation 71-1 is used.

2L.4 Equipmmt connected to an overhead line through a cable

Insulation co-ordination, in this case, is not only concerned with the protection of the substation equipment butalso with that of the cable.

When a lightning surge propagated along an overhead line impinges on a cable, it breaks up into a reflected waveand a transmitted wave. The amplitude U, ofthe surge flowing along tlle cable is given by:

. , 2 Z zu' : z, +z; u'

The amplitude Lrr, ofthe reflected wave is given by:

z"- z,a " : , n i u ,

where:

Ur : amplitude of surge voltage on overhead line

ZL : surge impedance of overhead line; in practice,400 O to 500 O

Zg : surge impedance of cable; in practice 25O to 50O, but for some types of cable it may be as low as 5 C)

This initial surge is reflected at the station end of the cable in accordance with the effective surge impedance atthe station busbar. Subsequent reflections at the cable terminals continue to be governed by the above equations withdue regard to the fact that 4 and Z, invariabll refer to the wave which impinges on a point of reflection while Utand Z, refer to the transmitted wave and UE refers to the reflected wave.

Page 28: SPLN 7B_1978 Insulation Coordination,App

- 5 l -

Provided at least one further cable of a few hundred metres in length is permanently connected to the busbar,the surge voltag€ to which the cable and the station equipment are subjected is notably lower than that on the lineon which the surge originated and this reduction is all the greater, the lower the surge impedance ofthe cable.

For a station to which at least two cables are connected, a decision on the adequacy of equipment according tolist 1 of Table I of I EC Publioation 71-l or the need for overvoltage protection can be determined from the aboveequation.

However, in the case of a terminal station, the ultimate surge-voltage amplitudes developed at the cable termin-ations as a result of successive reflections are a function of the amplitude and duration of the original lightning-surgevoltage on the line, the length of the cable and, if the stroke is fairly close to the cable, also the reflections fromthe point of strike. For lines with fully insulated cross-arms, the resulting voltage amplitudes are so high that, evenusing substation equipment and a oable with lightning-impulse withstand voltages according to list 2 of Table Iof IEC Publication 71-1, surge arresters ,nrrt be used at the line/cable junction. As an example, the maximumcable lengths are plotted in Figure 3, page 108, for which the cable and the substation equipment can be protectedby surge arresters at the line/cable junction only; the figure demonstrates the considerable benefit of the use of acable oflow surge impedance. The protection is fully eflective against direct and indirect lightning impulses and backflashovers provided these originate a few spans distant from the line/cable junction. If the cable length exceeds thevalu€s indicated in Figure 3, additional surge arresters are required at the substation end of the cable. If surge ar-resters with sparkover voltages lower than those specified in IEC Publication 99-1 are used, the cable lengthsindicated in Figure 3 can be increased in proportion to the differences indicated by comparing, for example, a 10.5 kYwith a 12 kY surge arrester.

However, ifthe cable supplies only a terminal transformer, the incident wave is doubled in amplitude at the trans-former. As a result of successive reflections at both cable terminations, this yoltage build-up increases towards twiceth€ amplitude until no further energy is supplied by the original surge.

For lines with earthed cross-arms feeding a cable with terminal transformer, the impulse flashover voltage toearth of the line insulation is only slightly higher than the corresponding value in list 2 of Table I of IEC Publi-cation 7l-1. ln such a case, surge arresters mdl be required at the line/cable junction and it may also be necessaryto use these at the station end of the cable.

The foregoing considerations apply to direct strokes a few spans distant from the cable termination. Full protec-tion against very close strokes is generally not possible.

In areas of moderate or low lightning activity, protective spark gaps can be used in place of surge arresters. How-ever, if the spark gaps at the line/cable junction are earthed through a low resistance (the usual case) and ifthe cableis terminated in a transformer, dangerous surge voltages can be developed across the transformer windings. Thespark gaps at the line/cable junction should therefore be earthed through a resistance of several tens of ohms.equalling ideally the surge imlxdance of the cable. Greatly improved protection can be achieved by installing ad-ditional spark gaps across the line insulators on the fust and second poles in front of the line/cable junction and,in this case, the e4rthing resistaoces of these additional spark gaps are immaterial.

SECTION SEYEN _ CO-ORDINATION BETWEEN STRESSES AND WITHSTANDIN VOLTAGE RANGE B

22. Selection of the rated power-frequency ysithstand yoltsge and the rated lighhing-impulse witlstand yoltrge

Many considerations concerning voltages in range A also apply to range B. However, the variety ofequipment andlocations is not as great as in range A.

Page 29: SPLN 7B_1978 Insulation Coordination,App

- 5 3 -

In Tablc III of IEC Publication 71-1, one to three values of the rated lightning-impulse withstand voltage areassociated with each value of U-. For each of these values, there is a corresponding single value ofthe rated power-frequency withstand voltage. Therefore there will be one choice for the rated power-frequency withstand voltage andthe rated lightning-impulse withstand voltage.

The choice between the possible alternatives for U- above 72.5 kV must take account of:

- the neutral earthing conditions;

- the existence of protective devices, their characteristics and their distance from the equipment considered.

The safety factors normally employed in the application of surge arresters in range B are to be foundin Subclause 16.1.

SECTION EIGHT - CO.ORDINATION BETWEEN STRESSES AND WITHSTANDIN VOLTAGE RANGE C

23. lrsulation design with r€sp€ct to power-ftequency voltage rnd temp,orary oyervoltrges

For this range of voltage, power-frequency tests are to be specified by the relevant apparatus committees, in ac-cordance with the considerations in Section Five, and taking into account that the temporary phas€-to-earth over-voltages will not usually exceed 1.5 p.u. for I s on each occasion.

24, Insulation d€sign with respect to switching rnrl lightning overvoltages

IEC Publication 7l-1 proposes two methods for co-ordination of insulation in respect of srvitching and lightningovervoltages: a conventional and a statistical method.

24.1 Conventionalmethod

The conventional method is based upon the established concepts of maximum overvoltages stressing insulationand of minimum strength ofthe insulation (deflnitions in Clauses Z and 27 ofIEC Pubtication 7l-l). The notion ofrrinimum strength and that of maximum overvoltage are rather arbitrary since a rigorous rule can seldom be fol-lowed in the evaluation of the upper and lower limits of the insulation strength and overvoltage value, which areintrinsicaLly random variables.

Insulation is selected in such a way as to achieve a sufrcient margin between the maximum overvoltage and theminimum strength. This margin is intended to cover the uncertainties of the designer in the evaluation ofthe maximum overvoltage and of the minimum strength, and no endeavour is made to assess quantitatively the riskthat insulation may break down.

The safety factors normally employed in the application of surge arresters in range C are to be foundin Sub-clause 16.1.

2.4.2 Sratistical merhod

The statistical method attempts to quantify the risk of failure for use as a safety index in insulation design.

Page 30: SPLN 7B_1978 Insulation Coordination,App

- 5 5 -

Rational insulation design of a transmission system ought to be based on the minimum of the installation costplus the capitalized yearly operational cost and yearly cost of failure, the latter being calculated as the estimatedcost of failure of insulation rrultiplied by the average expected number of insulation failures per year.

In order to evaluate the aveiage expected number of failures per year of a piece of insulation located at a givenpoint ofthe system in consequenoe of overvoltages, all the events giving rise to overvoltages which may afect insu-lation design should be taken into consideration. Then for each type of event considered, the yearly frequencyof occurrence and a statistical distribution of the relevant overvoltage amplitudes are required.l

However, a process of insulation design and co-ordination, as outlined above, involves too many difrculties. Thestatistical approach considered here is therefore restricted to checking that the risk of insulation failure due to anyforeseeable type of event causing overvoltages in the system is within acceptable limits. These limits depend on thefrequenoy of occurrence of the type of event and on the consequences of the failure of the piece of insulation underconsideration.

Fortunately, the types of event which are signif.cant in insulation design are generally sumciently few in number asto allow an analytical approach. For instance, the insulation lvithstand to srvitching surges of many pieces of in-sulation of equipment in a system is, in general, determined primarily by reclosing overvoltages,

lf the frequency distribution of overvoltages caused by a given type of event and the corresponding insulationstrength are known, the risk of failure can be expressed numerically, as will be shown below.

L€t the withstand strength of a given piece of insulation within a given time interval AZbe defined by the prob-ability PT(LD of disruptive discharge of the insulation when it is subjected to an overvoltage of value U (Figure 4,page 109). Furthermore, let the distribution of the overvoltages stressing the same piece of insulation for the specifictype of event considered be defined by the probability density/o((D. Then the probabilitythat an overvoltage ofvaluecomprised between U' and U' f dUmay occur is/.(U') dU. The probability density of failure ofthe insulationdueto an overvoltage of value U' is therefore the product of the probability density that an overvoltage of value U'may occur and the probability that the insulation may fail under an overvoltage of value u'. Thus:

dR : f,(u,). Pr(U,) du (oThe probability of failure for a value of U taken at random, i.e. the risk of failure R for an event of the type

considered. will then be:

f,(u) . Pr(u) .du

This expression shows the general principle ofthe method by which the probability of failure may be assessed. Itassumes that/o(y) and P1(Lr) are uncorrelated.

lVole, - In principle, formula (7) applies to a siele-phase piece ofinsul,atiotr only. If several piec€s of equipmedt, coDn€cted itr parallelon the same phase, are subjected to the same overvoltage th€n it can be assu{red that the overall risk is equal to that of a singlepi€c. of equiplnett multiplied by the number of pieces io paralel. This is valid if we take hto consideration the fact that theacc€ptable risk offailure for substation iDsulatioD is lrually very low.

I It is evident that the amplitud€s ofall the overvoltages oc.uring in a system cainot b€ combined in ode distdbutior, but that ody ov€r-voltages identified by the same locatioD and cause can be considered as statisticslly homoggdeous. Actually, siDce the overvoltage s€veritydiffers for wavdhap€s which are companble resp€ctiv€ly with a lightding impulse and with a switching impuls€ (s€€ Note to Clauses 2l and22 ofl EC Publicatiou 7ll), tl€ overvolrage amplitude can be said to be homogpneous only ifidentifed by the sarF locatio!, cause andshape. However, ov€rvoltag€s due to the same cause at a given location have broadly a similar shape and, thercforc, those identified bythe same cause and location may, for the sake ofsimplicity, b€ r€garded as homoggneous. Ifproblefi$ ofstandardizatioo ofthe equipmcntof atr efltirc network are to be dealt with, an extensioo of the con@pt of a homogeneous group of overvoltag€s 4€eds to be considered.In this cas€, a group ofovervoltagps rnay be said to be homogen€ous if tie overvoltagps occur in similar locations of the system due to thesame cause. For exaErple, the reclosing overvoltages on the busbars (seoding.€Nrd) of say subBtation of the systEnr may be coNid€red as ahorDogeoeous group of overvoltagEs.

(7)u - |0

Page 31: SPLN 7B_1978 Insulation Coordination,App

Sonretifires it is trec€ssary to evaluate the risk of failure of at least on€ phas€ of a thr€e-pbas€ section of the system followitrga switchiqg op€ratioo (e.9. a closiDg operatioo), This risk may be obtained by multipllng by three the risk evaluat€d according toformula (7) ifthe probability deqsity/o(U) of the overvoltages rnay b€ assuned to be equal oo all three phas€s.

An altemative nrethod is to c€tablish the overvoltage probability density /o(Lr) by considering only the highest valu€ ofthe over-voltagEs caus€d otr the tfuee phases by a swirchi4 opemtion. Thed the dsk of failure is evaluated by makiog use of forrnula (7).

The form€r approaph gives risk valu€s higher than the aptual ones; the latter lowcr. Obviously the two approaches give resultJditreling by l€ss than 3: 1.

The mathematical model choset for deflning the severity of an overvoltage in formula (7) is based upon a fewsimplifications. In fact, the following assumptions are made:

a) Peaks other than the highest one in the waveshape of overvoltages are disregarded.

6/ The waveshapes of all of the lightning impulses and the switching impulses belonging to the distributiondefined byl.(Lf are assumed to be identical to the waveshape of the highest ovenoltage.

cJ The highest overvoltage peaks are assumed to be all of the same polarity, although, during switching, a balanceddistribution during the two polarities can be assumed in practice; this assumption, which leads to the calculationof greater risk than the actual risk, makes it possible to take all of the pieces of insulation into account, regardlessof the differenoes of performance between the two polarities. To be on the safe side, the more severe polarity willbe used.

As regards switching overvoltages, which are the transient overvoltages of predominant importance in the insu-lation design of EHV systems, assumption a, is. such as to give a calculated risk of failure lower than the actualrisk. Assumption c) results in a calculated risk higher than the actual one for the reason already indicated and sincethe standard waveshapes are so chosen as to establish the lowest withstand of apparatus (see Clause 5 1 of I E C Publi-cation 71-1).

In general, considering the opposite effects of the assumptions made, the risk of failure calculated by means offormula (7) grves risk values greater by about 0.5 to 1 decade (3 to 10 times) than the actual values. Norrrallyformula (7) is therefore conservative. As said above, fornula (7) can be applied for all the specific types of eventsigniflcant in insulation design.

Furthermore, it is clear that the accuracy in the calculation of the risk failure greatly depends on the accuracy inthe determination of the overvoltages and the disruptive discharge probability of insulation (see Appendices C andD). Since accuracy ofthese is seldom satisfactory, the accuracy ofthe calculated risk offailure can be correspondinglypoor.

However, the risk of failure has a precise physical meaning (contrary to the safety factor). By making use ofstatistical methods, it is therefore possible to co-ordinate the security levels of the various parts of the system accor-ding to the consequences ofa fault. Furthermore, it is possible to carry out sensitivity analyses (e.g. the effect of achange in the overvoltage severity or insulation withstand capability on the probability offaults). Statistical methodsdo therefore enable the engineer to take a decision on a rational basis.

According to the statistical method, insulation is selected in such a way as to obtain a calculated probability offailure lower than, or equal to, a pre determined value that characterizes the required safety level. Referring toFigure 4, page 109, a change in the insulation level shifts the curve representing the discharge probability of theinsulation Pr(t/) along the U axis with a consequent modification of the shaded area,{ which represents the pro-bability of failure R for a random value of U.

The statistical approach may require successive series of tentative designs and evaluations of risk, until a solutionis found that corresponds to the predeternined risk.

Formula (7) can also be applied to determine the probability of failure of an insulation protected by spark gapsor surge arresters, ifPl(Lf is taken as the discharge probability of the insulation in presence of the protecdive device.If the time-to-discharge of the protective device can be considered always shorter than that of the insulation to beprotected, an equally valid and simpler method is to use formula (7) and to take /,(t/) as the overvoltag€ probabilitydensity modified by the protective device (see Appendix C).

Page 32: SPLN 7B_1978 Insulation Coordination,App

- 5 9 -

The use of digital computers facilitates evaluation of the risk of failure, ard therefore the insulation design, oncethe statistical overvoltage distribution and the discharge probability curve of insulation are known.

24.3 Simplifed stqtistical melhod

Sensitivity aialyses and ready evaluations of the risk of failure can be made on the basis of simplified statisticalmethods in which the cirlculations are performed once and for all by making some generally acceptable assumptionsconcerning the mathematical laws by which the actual distributions ofthe overvoltages and the discharge probabilityof insulation are represented e.g. by assuming them to be Gaussian with known stardard deviations.

With these assumptions, the cornplete distribution of overvoltage and the discharge probability curve ofinsulationcan be defi:red by one point only corresponding to a given reference probability and called, in IEC Publication 71-1,"statistical overvoltage" (Clause 23) and "statistical impulse withstand voltage'' (Clause 26), respectively. The riskof failure can be correlated with the margin between these two values so that the approach becomes rather similar tothat of the conventional method.

Figure 5, page 111, gives a graphical explanation of the method. Figure 5a shows frequency distributions of over-voltage and insulation strength, where the statistical overvoltage is indicated by ys and the statistical withstand volt-age by Lr,p. In Figure 56, the overvoltage distribution and the electric strength distribution are superimposed forthree values 1.0, 1.2 and 1.4 of the statistical safety factor ), taken as equal to the runo Ualu,n. The correlation be-tween the statistical safety factor 7 and the risk of failure R is given in Figure 5c.

The reference probability of the overvoltages is chosen in this guide as equal to 20lo. The reasons for this choice aregiven below in this clause. As regards the reference probability of the withstand voltage, the 90% value was chosenin IEC Publication 71-1 for the reasons ouflined in Clause 10 of this guide.

As regards switching surges, Figves 6,7 and 8, pages 112, 113 and I14, illustrate the relationship between the riskof fai.lure and the statistical safety factor for air insulation in different cases.

The discharge probability curve of insulation is assumed to be Gaussian as stated in Clause 10 with /c (Formula (5)in Clause 10) equal to I and or (formula (2) in Clause 10) equalto 6%o,8Yo and 10% (Figures 6, 7 and 8 respectively).Ifft is taken as differing from 1, the statistical safety factor given for k : 1 shall be multiplied by l/k,

Figure 6 is applicable to laboratory conditions, while Figure 7 is generally applicable to service conditions.Figure 8 may be used for particularly severe conditions (high values ofon in formula (2)). In all three cases, the over-voltage distributions are assumed to be Gaussian truncated at three and four times the standard deviation 06, or nottruncated and with standard deviation o" equal to 10o/o, l5To znd 20Vo. Figur€s 6 to 8 give the average correlationbetween the statistical safety factor and risk of failure as well as the upper and lower envelopes of the correlationsobtained when considering the nine overvoltage distributions resulting frorr all the possible combinations of valuesof standard deviation and upper truncation point.

The choice of a Gaussian distribution to define the overvoltage severity does not mean that other disFibutions(e.g. extreme value distributions) may not give better approximations, but simply that Gaussian distributions matchactual distributions reasonably well over the range of interest.

The correlation between the statistical safety factor and risk of failure appears to be only slightly atrected bychanges in the shape of the overvoltage distribution. This is due to the fact that the zyo value chosen as a referenceprobability ofthe overvoltages falls in that part of the overvoltage distribution which gives the major contribution tothe risk offailure in the range ofrisk considered. If, on the contrary, a much lower or higher value were chosen, theinfluence ofthe shap ofthe overvoltage distribution would be very pronounced.

Figures 6 to 8 give the risk of failure of a piece of single-phase equipment (e.g. a post insulator). If the risk offailure of several pieces of equipment is required, reference should be made to the noie to Sub-clause 24.2 above.

For example, if the number of single-phase pieces ofequipment at a line entrance is equal to 2l (7 on each phase)and the risk of failure of each for a three-phase reclosing is 10a, then the risk of failure for the whole line entrance

Page 33: SPLN 7B_1978 Insulation Coordination,App

- 6 1 -

will be close to 2.1 ' 10-8. This simplifi.ed calculation is only valid under the condition of low risk (see note of Sub-clause 24.2) and if the number of parallel pieces of equipment is not too great.

Extension of this method to overhead lines is possible but presents problems particularly for long lines, with whichthis guide does not attempt to deal.

This method may be appliedlo IEhtnW szrges, keeping in mind the practical limitations indicated in Appndix D.In faot, it is not used at the present time. Analogous correlations between the statistical safety factor and the risk offailure are given in Figures 9, l0 and 11, pages 115, 116 and 117, for comparisons purposes only, for air insulationsubmitted to lightoing surges.

Assumptions similar to those of the previous sub-clauses have been made as regards the discharge probabilitycurve of insulation to lightning surges.

The lightning overvoltage distributions are assumed to be Gaussian and not truncated, with standard deviationsequal to 40% a'Jid 60V,.It is thought that such distributions approximate actual lightning overvoltage distributionsquite well around the 2% value.

Figures 9, 10 and I I give the correlation between the statistical safety factor and the risk of failure for borh over-voltage distributions and for standard deviations of insulation strength equ al to 3To , 5o/o and 7 o/o respectively.

lvore' - The corr€lations between tie statistical saf€ty factor ard the risk of failure givea above apply to self-rettoring insulation oDly.How€ver, they can be considered acceptable for th€ entirc equipmetrt io most cas€s for the following reasons:

The tests described in Clauses 52 and 53 of IEC Publication 7l-l are intended to ascertain the impulse withstand strength of self-restoring equipment and combined equipment respectively. Such tests do not altow any discharge on the non-self-restoring partsof the apparatus. Consequently, when both the self-restoring and non-self-restoring parts of insulation of the same apparatusare designed on the basis of the same risk of failing the test, the non-self-restoring parts will have an inherently lower dischargeprobability than the self-restoring parts in respect of overvoltages of the same amplitudes as those of the impulses applied duringthe tests.

Consequently, it can be stated that risk of failure of the non-self-restoring parts of self-restoring equipment (tested according toClause 53) is lower than that of the self-restoring parts if the major contribution to the overall risk of failure is given by over-voltages in the range of U56'tr t 2 o.

For combined insulation equipment, the non-self-restoring parts will be designed for a low risk of failure at test voltage. In thecases where the major contribution to the failure risk (calculated on the basis of the statistical withstand voltage) is given by over-voltages around the test voltage, the evaluation of the risk of failure can be carried out as for self-restoring insulation.

The foregoing considerations naturally presuppose that wave chopping during sparkover by a self-restoring piece of insulationdoes not cause serious stresses in the non-self-restoring insulation of equipment and does not accelerate ageing of insulation.

25. Block-diagran of the insulation design and co-orrlination of an elechical installation

Most predictions or analyses of system overvoltage levels assume that a piecc ofequipment (e.g. a circuit breaker,etc.) will operate as designed. In other cases, an arbitrary limit shall be ptaced on the "credible" severity ofsurges, asis often done in the case of lightning. It is obvious that surge levels based on such assumptions will sometimes beexceeded.

Whether or not it is necessary to take this into account depends largely on the consequence of failure resultingfrom such abnormally high overvoltages. For example, the consequences of transformer or reactor failure are soserious that their insulation co-ordination must usually provide for even extreme contingencies. This is achieved byapplying surge arresters at their terminals. There are other types of equipment such as post insulators, disconnectingswitches, etc., where the consequen@ offailure is not so serious as to warrant the application of surge affesters.

In developing a sequence of insulation design and co-ordination of an electrical system in the form of a block-diagram, it is convenient to differentiate between a case I (surge arrester protection) and a case II (no surge arresterot remote surge arrester protection). A block-diagram illustrating the method to be adopted is shown in Figure 12,page 119.

Page 34: SPLN 7B_1978 Insulation Coordination,App

- 6 3 -

The first step in insulation co-ordination (block 5), common to all tlpes ofequipment, has the purpose of ensuringthe ability of equipment to withstand power-frequency voltage under normal operating conditions and during tem-porary overvoltages. The system engineer shall specify an equivalent pollution severity test level for insulationsusceptible to contamination; howevgr, no special specif.cations will be given for insulation susceptible to ageing(see Clause 23).

If the expected phase-to-earth temporary overvoltages (block 3) are more severe than the overvoltages taken intoconsideration by the relevant Apparatus Technical Committee in specifying the power-frequency tests discussed inClause 39 of IEC Publication 71-1, it will be necessary to specify diferent voltage levels or durations of the test orto adopt suitable means or operational procedures to reduce temporary overvoltages in the system (feedback fromblock 5 to block 2, dashed line).

Insulation design as regards operating voltages and temporary overvoltages leads to a certain withstand of theequipment to both switching and lightning impulses. For instance, if a given withstand salinity is required for a postinsulator, a minimum distance in air is obtrined which varies according to the post insulator type. The equipmentwill therefore exhibit a certain withstand to switching surges due to requirements imposed by the operating voltagesand temporary overvoltages. These influences are indicated in Figure 12 by dotted lines (e.g. from block 5 to block 7and block 8).

Then it is necessary to consider case I and case II separately. Examples of selection of the rated switching andlightning impulse withstand voltage are given in Appendix D.

As regards apparatus of the first type (case I), choice of the rated switching and lightning impulse withstand volt-ages is usually made as follows:

1) Choose the rated voltage of the surge arresters on the basis of the temporary overvoltages (block 6); thus theprotective levels of the arresters under switching and lightning impulses will also be determined at least withinc€rtain limits.

2) Choose the rated switching and lightning impulse withstand voltages of the apparatus on the basis of safetyfactors dictated by experiences (see Sub-clauses 15.1 and 16.1).

3) Adopt suitable means in system design or suggest suitable operating procedures to reduce temporary over-voltages if an economical incentive exists to reduc€ insulation levels (start again from block 2).

This procedure of selecting the rated switching and lightning impulse withstand voltage of the apparatus dis-regards the severity of the actual switching and lightning overvoltages by which the apparatus connected in parallelwith the surge arresters may be stressed since it is based on the protective level ofthe surge arresters only.

The insulation levels of the apparatus of case II are usually chosen according to the following steps:

1) Choose the rated switching-impulse withstand voltage of the apparatus on the basis of an acceptable risk s hichcan be estimated directly on the basis ofthe expected distributions of the overvoltages and ofthe discharge lohages(statistical method), or by means of the correlations given in Sub-clause 24.3 between the risk of failure and thestatistical safety factor (simplified statistical method). Actually, these correlations apply to self-restoring insulationonly, but normally they can be considered acceptable for the entire equipment (see note in Sub-clause 24.3).

lvore. - ProtectioD against switching surges afforded by surge arresters installed close to €quipnrent in case I and spark gaps installed atthe line-€ntraoce can often be discounted as regards case II apparatus for the following r€asons:

a, Most of the types of €quipm€ot belooging to case II (especially lin€-ento4ce appantus) c4n at times be isolated ftom the

. surgp a$esters installed in the station to prot€ct case I appantus.

,, With the present technology ofsurge arresters, the protective level against switching impulses is often gre3ter than, or equalto the highest switching overvoltags which cad occur with corect behaviour of system apparatus. Insulation must thereforeb€ d€signed to withstaod these ov€rvoltages.

c) Spark gaps cannot provide a substantial degree of protection against switching surgps if undesircd spa.ko!€N are to beavoided, This point is given in Appendix C.

In Figu!€ 12, th€ block bet\reen block 4 and block 8 is therefore iodicated by dashed lioee.

Page 35: SPLN 7B_1978 Insulation Coordination,App

- 6 5 -

2) Adopt suitable means in system design to reduce switching overvoltages, if this is possible and if an economicalincentive exists in reducing the rated switching impulse withstand voltage of apparatus. No economical incentivemay exist in reducing insulation; for instance, if the withstand. to normal operating voltages and temporary over-voltages calls for "higher insulation" than switching surges (dotted line between block 5 and block 8).

3) Verify that the rated lightning impulse withstand voltage, corresponding (in Table IV of IEC Publication 71-1)to the rated switching impulse withstand voltage determined above (Items I and 2), guarantees a satisfactoryperformance of the apparatus under lightning overvoltages. This should be done on the basis of the expecteddistribution of the lightning overvoltages and of the discharge voltages or by means of the correlation given inSub-clause 24.3, but for the sake of simplicity it is often done on a conventional basis (see Appendix D).

Consider that only the highest value of rated lightning impulse withstand voltage of each line should be used forapparatus not effectively protected by a surge arrester (see Clause 49 of IEC Publication 71-l).

4) Provide means to reduce the amplitude of lightning surges 1 (feed-back from 12 to 10 on the block-diagram ofFigure 12) or choose a rated lightning impulse withstand voltage higher than that determined on the basis ofTable IV of I E C Publicatio n 7 L-l if too high a risk of failure to lightning overvoltages results from Item 3. In thelatter case, the value of the rated lightning impulse voltage shall be selected from the series given in Item b ) ofClause 46 of IEC Publication 7l-1.

1 Consider possible changes in line design such as tower footing and shielding wires, install surge arresters other than those intended toprotect case I apparatus, make use of protective spark gaps. The actual degree of protection provided by spark gaps is discussed inAppendix C.

{

Page 36: SPLN 7B_1978 Insulation Coordination,App

- 6 7 -

APPENDX A

SURGE TRANSFERENCE THROUGH TRANSFORMERS

A1. Derivation of expressions

41.1 Initial mpacitive voltage spike

During the initial period ofabout I prs under the conditions of a lightning surge, thc transformer can be approxi-mately represented as shown in Figure 13a, page 120, as a capacitance voltage divider of ratio s where J < l. ff qis the sum of the capacitances of the higher-voltage and lower-voltage arms of this divider, the initial transferencecan be simulated as in Figures l3b, l3c and 13d, page 120, by a series circuit comprising a source [/o : rq, a ca-pacitance C, and the capacitance or resistance of the external lower-voltage system. Ur is the surge voltage on thehigher-voltage terminal during the initial period. The source voltage Uo is the open-circuit transferred voltage.

If tho extemal system can be represented by a capacitance C", as in Figure 13c, the equivalent circuit is a voltagedivider having the ratio:

C t * C "

If' during the initial period, the impedance ofthe external system is the surge impedanc€ ofa cable or the resistanceofthe load, this system can be represented by a resistance R as in Figure l3d. Typical values are from 10 O to a fewhundred ohms. The transferred surge voltage is then dependent on the steepness as well as on the amplitude of thesurge. For high values of R, the initial voltage is approximately Uo and for low values of R, it is given approximatelyby Ur" : s,9RC,, where ,S is the maximum steepness of the surge in volts/second.

The above expressions do not take into account the effect of superposition of the surge voltage on the power-frequency voltage. Allowance can be made for the power-frequenry voltage by substituting for 4 the actual peakvoltage y! and by introducing the factor p. For a star/delta or delta/star connected transformer the value ofp istypioally about 1.15. For a star/star or delta/delta connected transformer, the value ofp is truically about 1.05.However, slightly higher values than these may be encountered. For switching surges, the value ofp can be taken asunity. The amplitude Un will be limited to the front-of-wave sparkover value of the lightning arrester or spark gapon the higher-voltage side of the transformer (see IEC Publication 99-1).

The amplitude ofthe initial voltage "spike" on the open lower-voltage side is given by:

Uw : sPUo (9)

For a transformer without eiternal connections to the lower-voltage terminals, the value of factor s can range from0 to at least 0.4, depending on the winding arrangement. The value of J can be measured in a low-voltage impulseresponse test (e.9. with a recurrent-surge oscillograph). Values of C, generally lie in the range of l0-8 to l0-e F.

.iYole. - The values ofx and ct arc difrcult to cilculate for new d€sigds of transfomer, atrd the maDufacturer caE oDly be exp€cted togivc a rough €stimate without guarantee.

The value of Ur" should be compared with the appropriate impulse test voltage of Table I, list I or 2, or Table IIof IEC Publication 71-1.

The amplitude of the transferred surge may be reduced by:

l) using a surge arrester with a lower front-of-wave sparkover voltage on the higher-voltage side;

2) adding capacitance between each phase and earth on the lower-voltage side;

3) adding a surge arrester on the lower-voltage side between each phase and earth.

For numerical examples, see Clause A2.

Ct(8)

Page 37: SPLN 7B_1978 Insulation Coordination,App

- 6 9 -

A1.2 Inductively transferred voltage

The transferenc€ of e.m.f. by inductive couptng between windings in a three-phase transformer or bank of trans-formers can be evaluated for any winding connections by considering the surge voltage as a single-phase alternatingvoltage.

The efrect of delta windings on the z€ro-phase-sequence component of the single-phase voltage should be takeninto account.

Figure 14, page 121,.shows the results for eight different connections of the transformer, assuming the systemvoltage ratio is unity.

As in the analogous power-frequency considerations, the transferred voltages at the terminals are determined bythe e.m.f.'s and by voltage division between th€ internal impedance of the transformer and the extemal circuitimpedance. The e.m.f.'s can be assumed to have the same waveshayr as the surge on the higher-voltage system, ifthe effects of internal oscillations in the windings are neglected. The response of the lower-voltage system to thesee.m.f.'s is usually in the form ofa voltage of similar shape to the incident surge with a superimposed oscillation.

The. arnplitude of the inductively-transferred voltage depends also on the voltage ratio and three-phase connec-tions of the transformer and on the relative impedances of the lower-voltage system and the transformer.

The voltage on the lower-voltage side of the transformer which, as is shown in Figure 14, can be a phase-to-earthor phase-to-phase voltage, is given by:

Uz : pqrUnlN (10)

where:

4 : response factor ofthe lower-voltage circuit to the transferred surge e.m.f,

r : factor depending on the transformer connections (see Figure l4).

(,Ie : fpak voltage to earth on the higher-voltage side

if : system voltage (phase-to-phase) ratio of the transformer

The value of4 depends on the waveshape ofthe surge and on the electrical parameters ofthe lower-voltage circuit.

For lightning surges on a transformer having Category 1 equipment (see Sub-clause 21.2), without appreciableload connected to the lower-voltage side, the value of q is generally not greater than about 1.3 although this valuemay be exceeded. For switohing surges on a similar system without appreciable load, the value of 4 is not grealerthan about 1.8.

Generally, lower values of 4 apply if an appreciable load is connected due to voltage division between the loadimpedance and the leakage inductance of the transformer (see note below).

For Category 2 equipment (see Sub-olause 21.2), voltage division takes place between the leakage inductanccof the transformer and the subtransient inductance of the generator, and if these are about equal, 4 has the valueof about 0.9 for lightning and switching surges.

Values of r for a surge on one phase only (e.g. a lightning surge) and for equal surges of opposite polarity ontwo phases (one type of switching surge) are shown in Figure 14 for eight different three-phase connections of thetransformer.

The calculated value of U, is an estimate of the longer-duration transferred voltage, which in practice includeslonger-term effects of capacitive transference and transferred voltages corresponding to oscillations within thewindings. Its amplitude will be linited by the protective level of the surge arrester or protective spark gap. In thecase of the former, this will be the higher of the standard lightning impulse sparkover value and the residual voltagevalue for the lightning surges (see IEC Publication 99-l). For switching surges, except when the transformer isconnected to a highly-inductive load, such as an induction motor, overvoltages on the higher-voltage side maybe assumed not to generally provoke overvoltage exceeding 3 p.u. (see note).

Page 38: SPLN 7B_1978 Insulation Coordination,App

The value of Lr, should be compared with the peak values of the appropriate power-frequency test-voltages ofTable I or Table II of IEC Publication 71-1. Ii may be found necessary to reduce the value of the lightning orswitching surge on the higher-voltage side of the transformer. Adding extra capacitance to the lower-voltageside has little effect upon the amplitude of the inductively-transferred voltage, but it may be desirable to considerthe addition of surg€ arresters.

Numerical examples are to be found in Clause 42.

Nor?. - Wheo the circuit is switched off on thc higher-voltagc side of a traDsfomer which may be loaded on the lo!€r-voltage sidb byleactors or any other inductive load, then dangerous overvoltages may be attained under the most unfavourablc conditions ofoperatioo but, in gen€ral, U! does not exceed the peak value ofthe power-fr€quency t€st voltage since 4 is l€ss thao 1.0 on accountofvoltage division betw€en thc transformer and the load hductanoe.

A2. Numerical examples

A2.l Exatnple A: Category l installation

Transformer. 145 kY stax/l2 kV deltaLightning impulse withstand voltage 145 kV side : 550 kVImpulse test voltage 12 kY side 60 kV (assuming list I of Table I of IEC

Publication 71-l)Power-frequency test voltage 12 kV side : 28 kVSurge arrester on higher-voltage side of the transformer:

rated voltage : 120 kVfront-of-wave sparkover voltage : 463 kY1.2/50 impulse sparkover and residual voltage : 400 kV

a) Lightn@ surge on one phase

Initial voltage "spike" for transformer disconnected from load:

Uzo : spUo: 0,4 x 1.15 x 463 : 213 kV

Assuming a ratio of 1.25 beiween the impulse test voltage and the service overvoltage, i.e. for a value no1 ex-60

ceeding -II- : 48 kV, the cable connections from the transformer would have a capacitance of not less than C.- t-zi

such that :

c, 48c,+ c" < 213

: o'23

hence C, > 3,44 Ct,

Having obtained from the transformer manufacturer a value of Ct : 10{ F, the cable capacitanc€ per phaseshould be at least 3.42 x 10{ F.

If the load is connected, then this will reduce further the peak voltage od the lower-voltage side.

Due to inductive transference:

Uz : pqrUllN

_ 1.15 x 1.3 x 0.577 x 400 : 2g kVt2 . r

145w h e r e l r - _ : 1 2 . 1

t 2

Page 39: SPLN 7B_1978 Insulation Coordination,App

28 kV gives a ratio of 1.4 with the 39.6 kY peak test yoltage (28 {2j so that the insulation to list 1 of Table Iof IEC Publication 71-l is satisfactory.

b) Switching swges of opposite pohrities on two phases

Assuming a p.u. switching overvoltage on two phases of 2.5, and, p : l.O, lt : l.S and r : -] :1.15, then:\ / )

U z :1.0 x 1.8 x 1.15 x 145 x lT x2.5

1/l x I2.I

: 5 0 k V

In this case, the voltage peak exceeds the peak of the test voltage (39.6 kV) of Table I (IEC Publication 7l-l).To allow for this, either insulation oflist 2 of Table I (IEC Publication 71-1) should be used (i.e. having test voltagesof 75 kV lightning impulse withstand and 28 kV power frequency (r.m.s.) or 39.6 kY peak), or switching surgesbetween phases on the higher-voltage transmission system should be limited, in which case a surge arrester maybe selected on the higher-voltage side ofthe transformer having a lower protective level or alternatively consider-ation may be given to fitting a surge arrester on the lower-voltage side of the transformer.

422 Example B: Category 2 installation

Delta generator transformer 300 kV starlA kYLightning impulse withstand voltage 300 kV side : 1050 kVPower-frequency test voltage 24 kV side : 50 kYImpulse test voltage 24 kV side : 125 kV (assuming list 2 of Table I of IEC

Publication 7l-lSurge arrester on higher-voltage side of transformer:

rated voltage : 240 kVfront-of-wave sparkover voltage : 900 kV1,2/50 impulse sparkover and residual voltage 785 kV

a) Lightning surges on one phase

Initial voltage "spike" for transformer disconnected from Z kV system:

Uu : sPUo

. : O.2 x 1.15 x 900 : ZO7 kY (maximum)

(the value for s having been obtained from the transformer manufacturer).

This value would obviously be too great for insulation on the lower-voltage side.

Assuming a ratio of 1.25 between the impulse test voltage and the service overvoltage, i.e. a value not exceeding12511.25 : 100 kV, would require the addition of external capacitance. In this case:

c, 100c " + c , ( - : o ' 4 8

hence C" > 1.07 Cr,

The value of C, is obtained from the transformer manufacturer for a wave steepness ,S : I 200 kv/p.s (see IECPublication 99-l).

The other methods listed in this Appendix for reducing the capacitive peak (use of surge aresters) may also beconsidered.

Page 40: SPLN 7B_1978 Insulation Coordination,App

_ 75 _

The overvoltage due to inductive transference is:

U2 : pqrUllN

1 . 1 5 x 1 . 0 x 0 . 5 7 7 x 7 8 5: ---l2J : 41 kv

41 kY is less than the 70.7 kv (50 1/f) peak tests voltage, and this gives a ratio of 1.7, which can beconsidered adequate.

b) Switching surges of opposite pola ties on two phases

Assuming a p.u. switching ovenoltage on two phases of 2, then the inductive transference is :

f f 1 .0 x 1.0 x 1.15 x 300 x 1/T x2L't2 :

- 4 5 k V

w h e t e i p : 1 . 0 , q : 1 , 0 a n d r : + : 1 . 1 5 .\ / J

45 kV is about equal to the inductive transference of lightning surge (41 kV).

Page 41: SPLN 7B_1978 Insulation Coordination,App

- 7 7 _

APPENDIX B

VALIDITY OF THE TESTS IN CLAUSES 52, 53 AND 54 OF IEC PUBLICATION 7I-I

81. Confidence limits of the test

Tests can provide only estimates of varying accuracy of the true values of the withstand strength of equipment.An increase in accuracy can be obtained by an increase in the extent of the test. The extent of tests must however

be limited for reasons of cost, the diminishing return of gain in the accuracy and possible destructive eflects on theequipment. For these reasons, IEC Publication 7l-l prescribes three diferent test methods in Clauses 52,53 and54 according to the type of equipment.

Inrtem a) of Clause 52 dealing with the 50% disruptive discharge test, the note states that ,.There are a number ofprocedures available, and any of these may be used providing that the accuracy of the determination is within one-half of the standard deviation with a conf.dence level of 95 % . " It can be said that there should be a 95 % probabilitl.that the 50% discharge voltage of the equipment at the time of the test is within the boundaries given by the valueestimated from the test, plus or minus one-half of the standard deviatron.

A test procedure fulfilling this requirement is the "up and down" test with 30 impulses.

The accuracy of the 15 impulses withstand test is considerably less. The 95% confdence limits for the probabilityof discharge in this test are:

for 0 discharge approximately 0 to 0.213for I discharge approximately 0 to 0.32for 2 discharges approximately 0.015 to 0.40for 3 discharges approximately 0.045 to 0.4g.for 4 discharges approximately 0.0g to 0.54for 5 discharges approximately 0.12 to 0.61

Based on 957o confidence limits, it can be seen that from a test with 15 impulses only it is not possible to concludethat the discharge probability is less than 0.10, or than the probability of withstand is higher than 0.90, even for 0discharge. When the number of discharges exceeds 4, the test is significant to prove the hypothesis that the prob-ability of withstand is less than 0.90.

82. Examination of difrerent m€thods of t€st

Accepting the above basis limitations of tests with a small number ofimpulses, the following examines the validityof diferent methods of discharge testing and the balance between the risk to the manufacturer and the customer,bearing in mind the practical necessity for a limited number of impulses and, for the manufacturer, to design hisproducts to have an economically acceptable risk of failure on tests.

For the sake of simplicity, it is assumed in this appendix that the discharge probability p,(U) of the diferent piecesof equipment in a given population (same type of equipment on which an impulse test is to be carried out) followsa Gaussian law with a constant standard deviation o, equal for all the pieces of equipment. In this case, ono para-meter only, ( given in p.u. of or*see Figure 15, page 122) is sufrcient to determine the deviation of the insulationstrength ofone piece of equipment .,i,, at the time , (4 o0) from the specified value (Up111)

Tbe 90% withstand strength of a piece of equipment in a population varies from one specimen to another.Figure 16, page 123, shows how this can be described statistically in terms ofK. The value ofon is very small forthose types of equipment (e.g. disconnectors) which may be considered essentially air insulatin! structures, slncetolerances in dimensions are always very small.

To ensure the repeatability of tests, ambient and insulation conditions should be kept as constant as possibleduring tests (or correction factors should be used) and standardized testing techniques should be adopted. In prin-ciple, therefore, the discharge probability of a given piece of insulation under test conditions should not be exDected

Page 42: SPLN 7B_1978 Insulation Coordination,App

- 7 9 -

to change. In other words, the curve P'(Y) (see Figure 15) should be the same for diferent tests of pieces of equip-ment of the same type.

However, the value of the 90% withstand strength of insulation may show variations from the average value de-rived from several tests carried out by the same methods in the same laboratory at diferent times or in differentlaboratories, due to differences in the ambient and insulation conditions, or in the test circuits. Figure l6D, page 123,shows how laboratory inaccuracy can be described statistically considering the average value of the insulationstrength of one specimen as the "true value".

Assuming that the distributions of Figures 16a and 16b, page 123, are Gaussian with known standard devi-ations and that the design value of LIp has been chosen by the manufacturer, the probability density of thedeviation of the rreasured 90% withstand strengtl of the population of a piece of equipment can be calculated(see Figure l6c, page 123).

An ideal test should be such as to prevent equipment having, at the time of the test, either an insulation with-stand lower than that specifled to pass the test or a discharge voltage higher than that specified.

Self-restoring insulation having, at the rated impulse withstand voltage applied during the test, a probability ofwithstand equal to, or higher than, the reference probability (90%) should have a probability of passing the testequal to 1, while insulation having a probability of withstand lower than the reference probability should haveno chance of passing the test.

The probability of passing an ideal test, i.e. for which the selectivity would be perfect for an apparatus whosewithstand during the test ditrers by 1(o, frorr the specifred value, is represented in Figure l?, page 124, as a functionof K by the solid line.

Actual tests, however, depart from the ideal test and follow in the (Q, rK) plane curves similar to the dashed line.

Figure 17 shows the curves for the tests proposed in Clauses 52, 53 and 54 of IEC publication ?l-1 and for thetest recommended ]n Item d) of Clause 27 of IEC Publication 71 (fourth edition).l As far as the test of Clause 52is concerned, an "up and down" test based on 30 impulses was taken into consideration.

The probability density of the deviation of the measured withstand strength (Figure l6c) of a given populationis represented in Figure 18, page 125, by curve 1. By taking into account the probability of passing a given testprocedure as a function of K, along with the deviations between laboratories, curve 2 is obtained.r

The half-plane of positive ordinates of Figure 18 is thus divided into several sections for which the areas havethe following si gnif.cance :

1) Area (B + c) located to the left of the axis of the ordinates included between curve I and the two half-axesof co-ordinates, is equal to the proportion s of equipment of the population presenting a withstand probabilitylower than 90% (failure during tle ideal test).

2) Area (A + D) located to the right of the axis of the ordinates, included between curve 1 and the two half-axes of co-ordinates, is equal to the proportion of equipment of the population presenting a withstand prob-ability equal to or greater than 90% (successful ideal test).

Ivore. - Th€ sum ofthese two area.s, or I +, + C + D, is equal to udty.

3) Area C is equal to the proportion of equipment of the population which, although presenting a withstandprobability lower than 90olo, is satisfactory under actual testing; consequently, it is the customer's risk R.

r This latter test is defiDed as follows: a sed€'t of five impulses is applied. If Do discharg€ occurs, the €quipnFdt is coDsideled good. If t$odischa!8ps occur, th€ equipment is considered,bad, If a single discharge occu$, ten rew impulsas are applied. Duriag this new attempt,if !o discharg€ occuN, the equiprneot is considered good. If one dischargp occurs, th€ equiprneN is coDsiAerea UO.

-

I In the case where dr : O, thc combination would be reduced to th€ multiplicatio' of tbe ordiaates.s A rigorous fo.mulatiotl would irtoduce herc the probability that an apparatus of the populatiod would have a withstand probability

lower than 9O%.

Page 43: SPLN 7B_1978 Insulation Coordination,App

- 8 1 -

4) Area B is equal to the proportion of equipment of the population which presents a withstand probabilitylower than 90% and which is not satisfactory under actual testing.

5) Area D represents the proportion of equipment of the population which has a withstand probability equalto or greater than 90''/o and which is satisfactory under actual testing.

6) Area I represents the proportion of equipment of the population which has a withstand probability equalto or greater than 90o and which none the less is not satisfactory under actual testing; consequently, it is themanufacturer's risk R-.

The sum of areas A I B is equal to the proportion of equipment of the population which does not prove satis-factory under actual testing, regardless of its withstand probability. As a rule, the manufacturer designs the insu-lation IZ of his product in such a way as to minimize the sum of ar€as I f B, which can also be interpreted as theprobability P, of failure under actual testing.

By repeated calculation of R" and Pr for different values of the intended value of the insulation strength ( I4l),curves can be constructed which show the relation between the risk of the customer of accepting a deflcient productand the manufacturer's probability Pr of his product failing the test.

Figure 19, page 126, shows such curves on the assumption that standard deviations ds, ol a'rrd ol are those statedin the legends of the figures.

Figure 20, page 127, gives the correlation between X- (manufacturer's risk) and Ro (customer's risk) for thecases considered in Figure 19.

It should be noted that if on and o, are equal to zero (homogeneous population and no laboratory inaccuracy),one ofthe two risks is annulled. In fact, if the equipment conforms to the specifications, it is R" (customer's risk)which is equal to zero; if the equipment does not conform, it is R- (manufacturer's risk) which is equal to zero.

In other words, there is only one risk either for the customer or for th€ manufacturer. This risk, as well as thevalue of P,, can be obtained directly from Figure 17, page 124.

Page 44: SPLN 7B_1978 Insulation Coordination,App

- 8 3 -

APPENDTX C

STATISTICAL EVALUATION OF THE PROTECTIVE EFFECT OF SPARK GAPS

For a given waveshape of the applied impulses, let us call:

- Pt(A) and Po(U) the disruptive discharge probabilities of the insulation and of the spark gap as a function ofthe crest value U of tle impulse 1;

- ProI(D the probability that the insulation may discharge before the protective gap sparkover, as a functionof the crest value U of the impulse.

The discharge probability curves of insulation rit4 a"a of the spark gue P:Q) connected in parallel arcexpressed by:

r l lP,(u): P,(u)11 - P"(u)l + Pt(u). pe(u). piry,(u) 01)

r l l t lpo(a): p!(u)11-p,(u)l + pDQ).p{u)l I - B'(u)l (. l ,2)L l t l

Notes 1, - OD the assumption that times-to-discharge of the iuulation and of thc spark gap follow a BaussiaD law, whate\€r may be thecrest valu€ U of tho applied impulsc, thc probability Pr"(y) is given by thc formula:

niru>:P{u) ft-p"tolL I

* u q o f lR, : Jo P,(u)

Ll - P"(u)l . f,(u) du

(13)

wh€f,€:

Tr@) - T"@)r,ng,):Tffi6

Te(a) - fi7"veJrc of the tin€-to-sparkover ofthe spark gap, as a fudction ofthe cr€6t value U ofthe applicd impu.lseTr\U) : So%valw ofthe tidFto-discharge of th€ insulatio4 as a functiotr ofthe crest value {,rof the applied impuls€drly) : stsndird deviation of the time-to-sparkover of the spark gap, as a fuDctioo of the clest valu€ U of the applied

rmpusedtr(U) : statrda.rd deviatio! of thc tfun€-todischargE of the insulation, as a fuoctioo of the oest value of appli€d impuls€

2. - To writ€ equatiods (t 1) arrd (12), it was assurned that th€ idsulatiod and the spark gap caDlot strike simultaqeously.

If, for a particular combination of the insulation to be protected and of the spark gap, there is a negligible prob-ability that the time-to-discharge of equipment may be lower than the time-to-sparkover of the spark gap in theentire range 0 < U < U^ *, Prn((D becomes zero and formula (11) may be written:

(14)

In the case of combinations of insulation and protective spark gaps behaving thus, we shall consider the be-haviour of the protective spark gap as being ..ideal".

By making use of yforrrula (7), the risk of failure of a protected piece of insulation can be evaluated by meansof the following formula:

-r ay | .l a4o

x , : J p , ( u ) . l l - p , ( u ) | . 1 " ( u )du+ I & (u ) . pD (u ) . p r y , ( a ) . f ' ( u )du ( 15 )' " o l - l " o

Under the conditions of validity of formula (13), it is possible to express the fault risk by the formula:

r The formulae given here are generally valid for two pieces of insulation in parallel.

(16)

Page 45: SPLN 7B_1978 Insulation Coordination,App

- 8 5 -

The ratio of the 50% lightning impulse sparkover voltage to the 50% switching impulse sparkover voltageof a spark gap can be chosen from a wide range (l-1.5) by changing the electrode configuration. It is thereforepossible to select the discharge probability curve qf the gap Pr(U) to switching impulse almosi irrespective of thedischarge probability curve to lightning impulses.

Design of a spark gap with a view to switching impulses will make the average expected nurnber of flashoversof the spark gap per year, due to switching surges, equal to a value l{" such as not to make system performanceunder switching surges significantly worse. Therefore, the probability of sparkover of the spark gap when switchingovervoltages reach the level evaluated on the assumption that equipment operates as designed (see Clause 25)must be made very low.

Consequently, even if the spark gap behaves like an "ideal" protective device, the spark gap will provide noprotection against switching overvoltages and insulation must be designed to withstand this type of switchingovervoltage. This is evident if we recall formula (14), (case of "ideal" spark gap).

P: : P,(u) [t

- P"(4] ! Pi(r/) (17)

As regards switching overvoltages exceeding the values based on the assumption of correct behaviour of equipment,we can assume that the overvoltage value is such that a gap sparkover will almost certainly be oaused. Formula (1)then becomes:

P t ( U ) : P { U ) ' P t n ( U )

and formula (15)

Pr(U) . Prn(U) .f,(U) . dU

The protective effect is, in this case, due only to Prn(U), i.e. to the relationship between the time-to-discharge ofthe insulation and that ofthe spark gap. It is therefore necessary to make Pb([/) as close as possible to zero over theentire range of interest of U.

Design of a spark gap with a view to lightning impulses will be such as to limit the average expected number offlashovers per year ofthe spark gap to lightning surges to an acc€ptable valu6 Nr,

In this connection, it must be remembered that in many cases the sparkover of the spark gap does not lead to anysupply interruption.

Let us consider the example of a spark gap installed on the line side of a circuit-breaker. If the l.ightning strokecauses the line to flashover, a coincidental sparkover of the spark gap is ofno significance. On the other hand, if theovervoltage amplitude does not reach the sparkover level of the line at the point struck, it is unlikely to cause asparkover of the spark gap, even if the spark gap withstard level is lower than that of the line. This is due to thereduction in surge amplitude at the point of installation of the spark gaps because of attenuation during wavepropagation as well as the possible presence of other lines and surge arresters at the station.

Thus, in contrast to the case of switching surges, it is possible to accept in certain cases spark gaps with a 50%discharge voltage to lightning impulses lower than that obtained basing the design of the apparatus on switchingsurges and using the combinations ofthe rated impulse withstand voltages given in Table IV ofIEC Publication 71-1.

Therefore, it can be concluded from formulae (11) and (14) that spark gaps may ofer a limited degree of protec-tion in the case of lightning overvoltages of the order of the rated switching impuls€ withstand voltageof the apparatus.

As regards lightning overvoltages much higher than the rated lightning impulse withstand voltage ofthe apparatus,gap sparkover will almost certainly be caused. In this case, forrrula (18) and the same considerations as regards.Prr(t/.) previously made in respect of switching surges apply.

(1 8)

( le)* U^ro

R , : J0

Page 46: SPLN 7B_1978 Insulation Coordination,App

- 8 7 -

For air insulation of equipment, the condition Pre(U) - 0 may be fulfilled both for lightning and switchingimpulses by making use of gaps having a high critical sparkover voltage to switching surges (kv/crn), i.e. spark gapsmuch shorter than the air distances of the insulation of the apparatus, for instance by making use of spark gapshaving a conductor-rod confuuration for the electrodes.

For non-self-restoring insulation ofequipment, the check that factor Pb((/) is reasonably small should be made bymeans of chopped wave withstand tesb carried out at a voltage level based on the highest overvoltage which can beexpected in the system and with a cut-of time chosen on the basis of the time-to-sparkover of the spark gap.

These tests are not laid down in IEC Publication 71-1 and, if necessary, should be agreed upon between user andsupplier.

Page 47: SPLN 7B_1978 Insulation Coordination,App

- 8 9 -

APPENDX D

EXAMPLES OF APPLICATION

Table III, page 98, illustrates the choice of the insulation level ofa piece of equipment for case I (see Clause 25),protected against both switching and lightning overvoltages by surge anesters mounted at its terminals. Examole 1refers to a 420 kV transformer and example 2 to a 765 kY hansformer.

The insulation levels of the transformers depend on the protective levels of surge arresters against both swirchingand lightning impulses (block 7 of Figure 12, page 119). The protective level of a particular surge arrester depends,in its turn, on its characteristics and rating. The rating of surge arresters in both examples I and 2 is chosen as theavailable rating immediately above the temporary overvoltages anticipated on the system (block 6). Temporaryovervoltages include voltage rise during faults, overvoltages due to inrush currents, sudden load rejection and othercauses. The overvoltage to be expected is influenced by the earth fault factor, system configuration, the characteristicsof system equipment and operating practices (see Clause 5).

' Table lV, page 101, shows the choice of the insulation level of a piece of equipment for case II with no surgeanester protection or with remote surge arrester protection. Example 1 refers to the line-to-earth insulation of a420 kV disconnecting switch on the line-side of the circuit-breaker, no surge arresters being installed at the lineentrance. Example 2 refers to a 765 kV disconnecting switch at the same location.

The rated switching impulse withstand voltage is selected frorn Table IV of IEC Publication 71-l on the basis ofthe statistical switching overvoltage level at the equipment location and on the basis of an acceptable risk of failure(blocks 4 and 8 of Figure 12).

For both examples, it is assumed that the only critical switching overvoltages are those due to line ie-energization(i.e. it is necessary to check the risk of failure due to reclosing op€rations only).

By making use of the sirnplified statistical approach (see Sub-clause 24.3) and choosing an appropriate standarddeviation, it is possible to determine the statistical safety factor y corresponding to the maximum admissible risk offailure; from factor Z, it is possible to derive the rninimum statistical switching impulse withstand yoltage and thento select the rated switching impulse withstand voltage immediately above,

In the example, the correlation between risk of failure and the statistical safety factor given in Figurc 7, page I 1 3(or : 8%) is used.

Once the rated switching impulse withstand voltage has been obtained, a corresponding rated lightning impulsewithstand voltage is selected from the same line of Table IV of IEC Publication 71-1, considering that only thehighest value ofrated lightning impulse withstand voltage should be used for apparatus not effectively protected bysurge arresters (see Clause 49 of IEC Publication 71-1).

It is then necessary to verify that this value guarantees satisfactory performance under atmospheric overvoltages,i.e. a risk of failure not higher than the permissible one. This can be done in a similar way as previously for switchingimpulses @locks 9 to 12 in Figure 12),

In the case under consideration, an approximate distribution of the lightning overvoltages, at least for the case ofdisconnecting switches in the open position, may be evaluated quite sirrply on the basis of the line characteristicsand of errpirical or semi-errpirical laws for wave attenuation.

However, lightning overvoltage stresses vary from point to point in a substation. In general, it is therefore extremelydifficult and time-consuming to achieve the knowledge of stresses necessary to make use of the statistical or sim-plified statistical approach.

Only the highest overvoltage stresses in the most common contingencies (most common position of circuit-breakers and disconnectors) are therefore evaluated. It is then verified that the rated lightning impulse withstandvoltage selected as stated above, starting from the rated switching impulse withstand voltage, exceeds the maximum

Page 48: SPLN 7B_1978 Insulation Coordination,App

- 9 1 -

credible atmospheric overvoltages by a suitable margin (: l0%). If a rated lightning impulse withstand voltage

higher than that determined on the basis of Table IV of IEC Publication 7l-1 is desirable, the new value shall be

selected from the series in Item b) of Clause 46 of IEC Publication 7l-1.

In Table V, page 103, there is an evaluation of the increase of the risk of failure for a rated switching impulsewithstand voltage lower than the selected value given in Table IV of IEC Publication 7l-1.

Page 49: SPLN 7B_1978 Insulation Coordination,App

- 9 3 -

APPENDIX E

CLEARANCES IN AIR I BETWEEN LIVE CONDUCTTVE PARTSAND EARTHED STRUCTURES TO SECURE A SPECIFIED IMPULSE WITHSTAND VOLTAGE

FOR DRY CONDITIONS

In installations which, for various reasons, cannot be impulse tested, it is advisable to take steps to avoid flash-over occurring below the impulse withstand level which has been specified for the equipment under test.

The condition to be fulfilled is that the statistical switching and lightning impulse withstand voltages in air betweenlive parts and earth should be equal to the rated switching and lightning impulse withstand vjtage as specifledin IEC Publication 71-1. This results in a minimum clearance to be observed which depends on the-configurationof the live parts and the nearby structures (electrode configuration).

No distance is indicated for an equipment which has an impulse test included in its specifcation since computsoryclearances might hamper the design of the equipment, increase its cost and impede progress. The impulse test,even when only a type test, is sufrcient to prove that the impulse withstand condition is fulfilled.

Tables YI A and YI B, page 105, are suitable for general application, providing as a first approximation a clear-anc€ to be specified in relation to the insulation level.

In Table VI A, reference in made in the first column to the rated lightning impulse withstand voltage and inthe second column to the air clearances for unfavourable confi.gurations of live and earthed parts. In Table vI B,reference is made in the first two columns to the values defining the insulation levels and i; the third and fourthcolumns to the air clearances for electrode configurations of the "conductor-structure" type and .,rod-structure,,typc.

The "rod-structure" conf.guration is the worst eleotrode configuration normally encountered in practice; the"conductor-structure" configuration covers a large range of normally used configurations. In Tabie vI B. ref-erence is made to the electrode configuration because of its notable influence for u- > 245 kv.

The values of air clearances given in Tables YI are the minimum values dictated by electrical considerations,and do not include any addition for construction tolerances, effect of short circuits, wind effects and safetv ofp€rsonnel, etc.

These values are valid for altitudes not exceeding I 000 m (3 300 ft).

r Thcse indications refer to a simple distance tbrough an air spac€, without consid€f,atio! of the surfaoc sparkover voltage alo1g a le{kagcpath of th€ idsulator relat€d to the contarniEatioD Droblem.

Page 50: SPLN 7B_1978 Insulation Coordination,App

- 9 5 -

T.q'Bu I

Provisional scale of natural pollution levels

r Refereocc is made to norm4l-type insul4tors with the folowiDg charactedstics: spacing; 146 mm; diametgr, 255 rnm; arcepage diltaDce,300 mtrL

r TheJefer€o@ to adtipollution-tyP itrsulatoN is sorDewhat vague, due to the great variety of antipollution-typ€ insulators which ar€ iDs€rvice at the pres€nt tirne on H,V. liocs.

s Areas of moderal€ extersiod very clos€ to highways, wh€Ie a mixture ofsalt atrd bitumeo car! cause s€vcle depqsits on the insulatorsmay b€ subject€d to a high pollutiotr lcwl.

Pollution level

No significantpollution

Environment Performance of existing lines

Areas without industries and with low densityof houses equipped with heating plants;areas with low density of industries orhouses but subjected to frequent winds and/or rainfalls. All areas must be situated farfrom the sea or at a high altitude, and mustnot in any case be exposed to winds fromthe sea

No faults are observed in high humidity con-ditions (fog, mist, etc.) on 145 kV lines evenwhen equipped with less than 9-10 insulatorsof the normal type 1, nor on 245 kV lineseven when equipped with less than 15 suchinsulators

Light I Areas with industries not producing particu- Faults occur in fog conditions on 145 kV lini:swith less than 9-10 insulators of the normaltype t and on 245 kV lines equipped withIess than 15 such insulators

larly polluting smokes and/or with averagedensity of houses equipped with heatingplants; areas with high density of housesand/or industries but subjected to frequentclean winds and/or rainfalls; areas exposedto winds from the sea but not too close to thecoast (at least about I km)

Heavy Areas with high density of industries and sub-urbs of large cities with high density ofheating plants producing pollution; areasclose to the sea or in any case exposed torelativety strong winds from the sea

Faults occur in fog conditions, or when thewind blows from the sea, on H.V. Iinesequipped with normal-type insulatorsl, unlessthe number of units per string is exception-ally high: more than 11-12 units on 145 kVlines and more than 18 units on 245 kVIines

Very heavy 3I

Areas gbnerally of moderate extension, sub-jected to industrial smokes producing par-ticularly thick conductive deposits; areasgenerally of moderate extension, very closeto the coast and exposed to very strong andpolluting winds from the sea

Faults occur in fog conditions or during salt-storms on H.V. Iines, even when equippedwith antipollution-type insulators 2, unlessthe number of units per string is exception-ally high: more than 11-12 antipollutionunits on 145 kV lines and more than 18 anti-pollution units on 245 kV lines '

Page 51: SPLN 7B_1978 Insulation Coordination,App

- 9 7 -

Lc.nI,r II

Provisional relation between pollution levels, test levels and creepage distances

Notes 1. - The values reported in the table were established on the basis of normal cap-and-pin insulators. For other types of insulatorand particularly for very large insulators in substations, the correlation with these test methods, between testlivels and creep-age distances and service experience, is not yet sufficient to give more deflnite indications.

2. - The creepage distances given in the table are those recommended for the various pollution levels and do not necessarily agreewith the creepage distances derived from the third column of Table I, which refer to existing overhead lines whose behaviourunder power frequency voltage may or may not be satisfactory.

Type of test

Pollution levelSalt fog method Solid layer method Creepage distance/phase-

to-earth voltage(cm/kV r.m.s.)

Withstand salinity(ke/m3)

Layer conductivity(ps)

No significant pollution < 5

to-20

5-10 2.0-2.s

3.0-3.5Light pollution r0-20

20-40Heavy pollution 40-80

> 160

4.0-5.0

Very heavy pollution > 5 0 > 6

Page 52: SPLN 7B_1978 Insulation Coordination,App

Basic data

Highest voltage for equipment U^(r.m.s.)Corresponding phase-to-earth voltage- r.m.s. value- peak vatue tJ^ft lvtDetermining temporary overvoltage (derived from system studies)- r.m.s. value- peak value

Minimum safety factor- for switching overvoltages- for lightning overvoltages

Characteristics of surge arrester

Rated voltage (r.m.s.)Maximum switching impulse sparkover voltageMaximum lightning impulse sparkover voltageMaximum front-of-wave sparkover voltageMaximum residual voltage at rated discharge current

Protection level

to switching impulsesto lightning impulses 1

Insulation level ( phase-to-earth )

Switching impulses:

Minimum conventional switching impulse withstand voltageRated switching impulse voltageRatio of the rated switching impulse withstand voltage to the switch-

ing impulse protection level

Lightning impulses:

Minimum conventional lightning impulse withstand voltageRated lightning impulse withstand voltageRatio of the rated lightning impulse withstand voltage to the light-

ning impulse protective level

I Maximum front'of-wave sparkover voltage divided by l.l5 (see Sub-clause l3.l).

1)

- 9 9 -

T,c,Br,n III

Choice of the insulation level of case I equipment(e.g. transformer protected by surge qrresters)

KV

kvkV (p.u.)

KVkV (p.u.)

KVkvKVKVkv

kv (p.u.)kV (p.u.)

kV (p.u.)kV (p.u.)

Example I Example 2

2)

3)

4)

420

243343 (1.00)

3204s2 (r.32)

1 . 1 51.25

324765805

1 0 1 0735

765 Q.23)878 (2.s6)

765

442625 (1.00)

60s855 (1.37).

1 . 1 5t.25

I 230 (1.96)| 440 Q.30)

| 4rs (2.26)| 42s (2.28)

t . 1 6

I 800 (2.76)I 800 (2.87)

t .25

612230400660400

880950

Q.66)(2.77)

r.24

100 (3.20)r1s (3.42)

1.33

kV (p.u.)kV (p.u.)

Page 53: SPLN 7B_1978 Insulation Coordination,App

- 1 0 1 -

Tenlr IV

Choice of the insulation level of case II equipment( e.g. unprotected disconnecting switch )

Example I Example 2

420

245343 (1.00)

er0 (2.6s)l0-3

1 . 1 3

765

442625 (1.00)

I 255 (2.0)10-4

1.24

I 550

I 550Rated switching impulse withstand voltage selected

Risk of flashover corresponding to the rated switching impulse with-stand voltage selected 4.lo'4

Recommended ratedassociated with the

lightning impulse withstand voltage to berated switching impulse withstand voltage

Basic data II

Highest voltage for equipment U^ (r.m.s.) | wCorresponding phase-toearth voltage I- r.m.s. value I kV- peak varue u^lfr l\t I kv 0.u.)Statistical overvoltage at the equipment location (value exceeded in I

2l of cases only) due to reclosing operations I kV (p.u.)Maximum accepted risk of flashover to earth for reclosing operation

Statistical safety factor 7 corresponding to the maximum acceptedrisk of failure (derived from Figure 7, page 113)

Minimum statistical switching impulse withstand voltage

kV (p.u.) 1 42s (4.1s) | 2 400 (3.84)

Page 54: SPLN 7B_1978 Insulation Coordination,App

- 1 0 3 -

TAsrr V

Risk of failureof inwlation as a function of the rated switching impulse withstand voltage

of the equipment of Table IV

Alternative a)

Rated switching impulse withstand voltage (selected value)Statistical safety factorRisk of failure corresponding to the above statistical safety factor

kV (p.u.)

Example I Example 2

I 050 (3.06)1 . 1 6

4.10'4

l 550 (2.48)t.2410-4

Alternative b)

Rated switching impulse withstand voltageStatistical safety factorRisk of failure

kV (p.u.) eso (2.76)1.05

5.10-3

| 42s (2.28)1 . 1 4

9.10-{

Alternative c)

Rated switching impulse withstand voltageStatistical safety factorRisk of failure

l 300 (2.08)1.04

6.10'8

Page 55: SPLN 7B_1978 Insulation Coordination,App

- 1 0 5 -

T.q.Brr VI A

Correlations between insulation levelsand minimum phase-to-earth air clearances

T.q.Br,n VI B

Correlations between insulation levelsand minimum phase-to-earth air clearances

Rated lightning impulse withstand I Minimum phase-to-earth airvoltage I clearance

(kv) | (-tn)

4 o l o o6 0 l s o7s I tzoe5 | too

rzs I zzor4s I ztot7o I EZO2so I +eo32s | 0ro4s0 | q00550 | r roo650 | r roo7so I r soo

Impulse withstand voltages

(kv)

Minimum phase-to-earth air clearance

(m)

Rated switching impulsewithstand voltage

Rated lightning impulse withstandvoltage

(650)(650)750750850850950050t7530042s550

750850850950950

I 050I 050; I 175

1.41 .51.61.71 .81 .92.22.63 .13.64.24.9

1.51.71.91.92.42.42.93.44.14.85.66.4

175; l300:1425300; 1 425;1 550425;1 550; 1 800550; 1 800;2 100

Conductor-structure

800; 1 95O;2400

Page 56: SPLN 7B_1978 Insulation Coordination,App

1

0,75

0,50

Fo(U'l0,25

1

0,75

0,50

0,25

Fo(U)

0

Fo (Ul

- 1 0 6 -

Fo(U'\

u (p.u.)

2t9176

Ftc. la. - Surtensions de mise sous tension de ligne.

Line energi zation overvoltages.

Fo(U)

Fo (U'l

Flc. lb. - Surtensions apparaissant sur une chalne d'isola-teurs suite d des coups de foudre sur Ie pyl6ne.

Overvoltages across an insulator string due tolightning strokes to the tower.

r (rt\ _ densit6 de la probabilitd de surtensiont o\v ) -

overvoltage probability density

F (rA _ probabilitd (cumul6e) de surtension' o\v'' - overvoltage (cumulative) probability

Ftc. 1. - Surtensions.Overvoltages.

Page 57: SPLN 7B_1978 Insulation Coordination,App

- 1 0 7 -

dPr(U)dtJ

Ur io

Frcuns 2c

Flc. 2. - Probabilit6 de ddcharge disruptive d'une isolation soumise i des tensions de choc.Probability of disruptive discharge of insulation under impulse voltage.

t / .Py"(U) ,f Py,(lJ) ./

'Pt(J')- f - - - - f - - - - /

- f ff l

t tl t

l lt l

t t- I - ' - -T--T--

1 lt l

l lt l ,

t t FI t l t

t ! l /- - - r - - - - r t - - - / -

ri

I

- - r -2 o t

Page 58: SPLN 7B_1978 Insulation Coordination,App

- 1 0 8 -

t (m)

I

II

ilII

\\I

lrt

\

\t\ |'

,\

\\ \ 10,5 kV '

Tension nominale du parafoudreSurge arrester rating

7), I I\\ N\

v= l \12 kV

\-.._36 kV

\\ \ , _ .__

I

I{.=.r - - _ _

I*

I

60

40

0 10 20 30 40 50 z(0)

, _ imp€dance d'onde du cAble en ohms- -

cable surge impedance in ohms

, _ longueur du cAble en mdtresL -

cable length in metres

Ftc. 3. - Longueur de cAble maximale admissible dans le cas d'un parafoudre i la jonction a6rosouterraine.Maximum permissible cable length with surge arrester of line/cable junction only.

Page 59: SPLN 7B_1978 Insulation Coordination,App

- 1 0 9 -

:f: Pr(r') 'ro(r')

F = .[ PrQ) .fou) du0

o _ aire hachuree"

- shaded area

Ftc. 4. - Evaluation du risque de d6faut d'une isolation.

Evaluation of the risk of failure of a piece of insulation.

f f i A

Page 60: SPLN 7B_1978 Insulation Coordination,App

foU)

Pr(Ul140%

- 1 1 1 -

[1 - Pr(U)]0%

Frc. 5c. - Relation between the statistical safety factor yand the risk of failure R (measured by area A).

Us- Uw

Ua UwUw = 1,2 Ug

PrUl100%

U8 UwUw:1 ,4 U8

227176

Three attempts at determining the risk of failure(arca A) for statistical safety factors.

U*i : T : l . o , 1 . 2 a n d l . 4

t-z g

fo(U)

fo(U\

Frc. 5b. -

U

226176

Frc. 5a. - Us : statistical overvoltage placed on theprobability density curve (the shadedarea (2%) represents the referenceprobability).

Uw : statistical withstand voltage placed onthe discharge probability curve OO%represents the reference probability).

Rz

F3

y1 y2

method.

v228176

- - - t - - -If lt l

- - - b - - l

Ftc. 5. - Simplified statistical

Ys

Page 61: SPLN 7B_1978 Insulation Coordination,App

- t t z -

1r7 Y

229 I 76

Ecart type de la distribution des surtensions d, : 10, 15 et20/"Ecart type de I'isolation or : 6Y

Standard deviation of overvoltage distribution o, : 10, 15 and 2OY"Standard deviation of insulation oT : 6y

Flc. 6. - Corr6lations entre le risque de d6faut (R) et le coefficient de s6curite statistique (y) pour diverses distri-

butions de surtensions de manceuvre.

Correlations between risk of failure (R) and statistical safety factor (7) for various switching surge

distributions.

R

I

5

2

10- l

5

2

10'2

5

2

10-3

5

2

10-4

5

2

10-s

5

2

10-6

5

2

10 '7

5

2

10-8

5

2

10-e1 '61,51'41 ,31121110,90,7

Dist r ibut ion t ronqu6e i ^- Distr ibution truncated at

o 6"

Dis t r ibut ion t ronqu6e i oDistr ibution truncated at

* 6s

Dis t r ibut ion non t ronqu6eDistr ibution not truncated

\

\ s$i..NN\*'\.

N EnveloUpper

ppe sup6envelope

neure'\ ./

-- Envelc

- Lowerppe in f6r ienve lope

arrr)\.\

N\.'i',\N\\\\N,tl'- 6 s : 2 0 %

\\\ \\x"\\ d \ r\' .N...tlo" : 1 5 %

\ \i\ ? \ \

N \ \.\- \d s : 1 0 % tNt \ t t

\\'l t \tt \

I

\ \\ \ \ \

\ t \ \ tI ''\ r

\\\r\r

Page 62: SPLN 7B_1978 Insulation Coordination,App

10-1

10-2

10-3

- 1 1 3 _ _

\

\

\

- E n

-Iurv l

velopprrp8l el|

l sup6ruelope

teure

NEnvrLow

l loppe ier enve

nf6rieuiope

. ) \\ \\ \ \

\ ' \\ \ \

\ \ \

\ \ \\ \ \

\

10-4

10-5

10-6

10-7

10-8

5

2

10-e0,7 0,9 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 y

23t176

Ecart type de I'isolation or : 87o

Standard deviation of insulation 6T : 8y

FIc. 7. - Corr6lations entre le risque de ddfaut (.R) et le coefrcient de sdcuritd statistique (y) pour diverses distri-butions de surtensions de maneuvre.

Correlations between risk of failure (.R) and statistical safety factor (y) for various switching surgedistributions.

Page 63: SPLN 7B_1978 Insulation Coordination,App

- I r 4 -

10-2

10-3

1,5 1 ,6 y

232176

Ecart type de I'isolation 6r : lOYo

Standard deviation of insulation 6r : l0y

Frc. 8. - Corr6lations entre le risque de d€faut (.R) et le coefrcient de s6curit6 statistique (7) pour diverses distri-butions de surlensions de mancuvre.

Correlations between risk of failure (R) and statistical safety factor (7) for various switching surge

distributions.

R

1

10-1

10'4

10-5

10{

10-7

10-8

5

2

10-e1141,31,21'10,7

\

\

Ent

fuo,'eloppe sup6rieureper envelope

\.

EnvelLowe

oppe inr envel l

f6rieurr)pe

N \.\

\ \\\

\ \

\

Page 64: SPLN 7B_1978 Insulation Coordination,App

- 1 1 5 -

10'2

5

10'3

5

10-4

5

10'50,5 0,6 0F 0,9 0,9 1,0 1,1 1r2 1,3 .y

2t3 176

Ecart type de I'isolation oT : 3oAEcart type de la distribution des surtensions d, : {Q et 60%

Standard deviation of insulation or : 3yStandard deviation of overvoltage distribution o" : 4O and ffiY"

FIc. 9. - Correlations entre le risque de d€faut (X) et le coefrcient de sdcurit6 statistique (/) pour diverses distri-butions de surtensions de foudre.

Correlations between risk of failure (R) and statistical safety factor (y) for various lightning surgedistributions.

R1

5

10-1

5

l -

\\

\\

\\

o" :60%7

\

\ 1\\

o a : 4 0 % A

Page 65: SPLN 7B_1978 Insulation Coordination,App

- 1 1 6 -

10-2

5

10-3

5

10-4

5

10-5

0,5 0,6 0,7 0,9 0,9 1,0 1,1 1,2 1,3 y

234176

Ecart type de I'isolation 6r : 57oEcart type de la distribution des surtensions 6" : {Q et 60%

Standard deviation of insulation 6T : 5yoStandard deviation of overvoltage distribution o" : 40 and 607"

FIc. 10. - Corrdlations entre le risque de d6faut (R) et le coefrcient de s6curit6 statistique (7) pour diverses distri-butions de suriensions de foudre.

Conelations between risk of failure (R) and statistical safety factor (7) for various lightning surgedistributions.

R1

5

10'1

5

\\

\\

\\

o " : U O % 7

\

\ .{

\ \

6 e : 4 0 % /\

Page 66: SPLN 7B_1978 Insulation Coordination,App

- t t 7 -

10-2

5

10-3

5

10-4

5

10-5

0,5 .0,6 0,7 0,g 0,9 1,0 1r1 7r2 1,3 y

Ecart type de I'isolation or : 7 7oEcart type de Ia distribution des surtensions o, - 40 et 600/"Standard deviation of insulation oT : 7 yStandard deviation of overvoltage distribution o, : 4O and @7.

FIc. 11. - Corrdlations entre le risque de difaut (.R) et le coefrcient de s6curit6 statistique (7) pour diverses dis-tributions de surtensions de foudre.

Correlations between risk of failure (R) and statistical safety factor (y) for various lightning surgedistributions.

R1

5

10-1

5

\\

\

\\

.d8 = 60%_7

/\ \ /

\(

No s : 4 0 % t \

-='{*b

Page 67: SPLN 7B_1978 Insulation Coordination,App

- 1 1 9 -

Introduction of means tored uce llghtning overvoltages

@

Operating voltageunder normal

conditlons

Characteristlcsof the system

Introduction of means@ to reduce temporary or

switchin g overvoltages

Calculatlonof temporaryovervoltages

Calculationof switchingovervoltages

Selectionof surgearresterg

rated-voltage

Insulat ion designas regards operating

voltages and temporaryovervoltages

Selectlonof rated lightnlng

and switchlng withstandimpulse voltage

of case I apparatus

Selectlonof rated

and switching withstandimpulse voltage

of case ll apparatus

Lightningovervoltage

characteristics

Line insulationlevel,

numberof earth wiresspark gaps

at the line-entrance

Calculatlonof l ightning

overvoltages

Selectlonof rated

l ightning withstandimpulse voltage

of case ll apparatus

Flc. 12. - Block-diagram of insulation co-ordination and design.

Page 68: SPLN 7B_1978 Insulation Coordination,App

Frc.

Frc.

237176

l3a, - Transformateur repr6sent6 par un diviseur detension capacitif.

Transformer as a capacitive voltage divider.

t l-ll-l

c t l

:sul + cgUo: sUl

239176

l3c. - R6seau extdrieur de capacit6 C".

External system having capacitance C..

- r 2 0 -

initiale de tension capacitive.

capacitive voltage spike.

"--ll---Ct

Uo - sUl

Frc. 13b. - Circuit dquivalent pour la transmissioncapacitive.

Equivalent circuit of capacitance transmission.

U o =

Frc. l3d. - Rdseau extdrieur de rdsistance R.

External system having resistanceR.

Pointe

Initial

Frc. 13. -

Page 69: SPLN 7B_1978 Insulation Coordination,App

- t 2 t -

Ftc. 14. - Valeurs du facteur r.

Values of factor r.

21r 176

CasCase

Couplagc du ttansformcteurTransformer connecuorul

Choc sur une phase sculementSurge on one phase onlyU s : l , U " : g r " : g

Chocs dc polarit6s oppos6cs sur 2 phascsSurgcs ofopposite polarity on 2 phases

U s : l , U s : - 1 , U c : 0

NoNo.

Enroulementhaute tension

Higher.voltagewinding

Enroulemcntbasse tension

Lower-voltagcwinding

TertiaireTcrtiary

Enroulementhaute tension

Higher-voltagewinding

Enroulementbasse tensionLower-voltagc

winding

Enroulemonthautc tensionHigher-voltage

winding

Enroulemcntbasse tensionLower-voltagc

winding

I Y(e) y (e) (- t v) ,'tla ,'f-,2 Y(e) v (i) (-, y) x, -(

-1ls -1/3 )[- l-0 -l

3 Y(e) d (-, y, O )1, '<? tr2

.v.2

4 r(t) y (e, i) (-, Y, d)\-tr

I.4.

0 0.,'/rr-+1"/, A

o + - 1

5 v(r) d (-' Y, d)$r t

,4.0 0

'(i "uru

,lvr<'_l;5 Y(f) z (e, i) (-, y, O

)(,

( '' lve-)-,tvi

, lv'-, lv'

7 D y (e, i) (-, Y, d) x'u_s * - 1 l V s

I lVar l / ;$-nl r '

8 D d (-, y, O <' -''<:; .<:,

Page 70: SPLN 7B_1978 Insulation Coordination,App

- t 2 2 -

1 - P t(%,0

URw : tension de tenue nominale aux chocsrated impulse withstand voltage

K en p.u. de o1K in p.u. of o1

212176

Ftc. 15. - D6f,nition de la tenue di6lectrique d'un appareil d I'instant t a I'aide du paramdtre K.

Definition of the insulation strength of a piece of equipment at the time I as function of the parameter K.

Pt(%,100

90

100

o,(,, , d" I 'apparei l de r6f6rence' r\v ' for the reference piece of equipment

Probabilit6 de r6f6rence.Reference probabllity

Ut n- Unw

Page 71: SPLN 7B_1978 Insulation Coordination,App

- r 2 3 -

Distribution de la tenue didlectrique (90%) des appareils deIa population p.

Distribution des diff6ren@s entre Ia tenue di6lectrique 90%d'un appareil donn6 mesur6e dans diff6rents laboratoires etla tenue di6lectrique reelle.

Distribution de la tenue di€lectrique 901l d'un appareilquelconque de la population p dans divers laboratoires.

Frc. 16. -

nominale au chocwithEtand voltage

243 176

aJ Distribution of the 90[withstand voltage of the apparatusof population p.

D/ Distribution of the difference between the 90Yo withstandvoltage of a given apparatus measured in various laboratoriesand the actual one.

c/ Distribution of the90% withstand voltage of any apparatusof population p in various laboratories.

mesur6e d'une population d'appareils.

strength of a population of apparatus.

0I

a)

b)

c)

Densit6 de frdquence

Frequency density of

de la tenue didlectrique (90%)

the measured 90oh withstand

Tension tenueRated impulse

dpl : [A;+4

Page 72: SPLN 7B_1978 Insulation Coordination,App

- 1 2 4 -

0,8I

I

,f 0,,

i/ t'/ .m,u

i/ t'ilt

o'5

aa

,a

at

Ta

a

/'

, , /

Essai id6alldeal test

at t '

/a 2

l -

2 -

3 -

4 -

-0'8 -O'6 {'4' 4'2 0,2

essai par mont6es et descentes 30 chocs (article 52 de laPublication 71-1 de la CEI)

essai 15/2 (article 53 de la Publication 71-1 de la CEI)

essai 3/0 (article 54 de la Publication 7l'l de la CEI)

. { 5lO (article 27d) de la Publication 71 de Iaessar

I 5/l + 10/0 cEI, quatridme 6dition)

1 -

, , _

3 -

4 -

0,4 0,6 0,8 1

K en p.u. de o1

K in p.u. of o1

241176

up and down test 30 impulses (Clause 52 of IEC Publica-tion 7l-l)

15/2 test (Clause 53 of IEC Publication 71-1)

3/0 test (Clause 54 of IEC Publication 71-1)

I SIO test (Clause 27d) of IEC Publication 71,

I 5/1 + 10i0 fourth edition)

fonction de ses caractdristiquesFrc. 17. - Probabilitd pour un mat6rield'isolation.

Probability of an equipmentcharacteristics.

de r6ussir d diff6rents types d'essai en

to pass the different types of tests

,r'ift=:'=

as a function of its insulating

Page 73: SPLN 7B_1978 Insulation Coordination,App

Courbe oCurve

K en p.u. de o1

K in p.u. of o1

24s 176

FIc. 18. - Probabili6 Pt d'dchouer d I'essai (aire A + B).Risque du constructeur R* (aire ,,4).Risque du client Ro (aire C).

Probability Pt of test failure (area A + B).Manufacturer's risk R- (arca A).Customer's risk R" (area C).

Page 74: SPLN 7B_1978 Insulation Coordination,App

Rc

- t 2 6 -

10-4

: essai de d€charge disruptive 50f: essai 15/2: essai 3/0

| : 507. discharge testZ : l5l2 test3 : 3/0 test

F-'z

10-1

10-2

10'7'

10{

10€

10-4

10-5

10€

t0-110€10-5 10{ 1 P g

26176

f\

F

ia

It

I23

Frc. 19. - Risque du client en fonction de la probabilit6 d'6chec i I'essai (Pt).

Customer's risk as a function of probability Pt to fail the test.

( o P : t %

1 o t : 5 %

\ o t - a %

( o P : + %

1 o t : o %

( o t : 6 %

ut.li

fI

/ / I I)2/ /

. , J

I tI

I

t I

/ 1 t/ I, r

/ /

3 I

, I

t I I

2 ,I

II I I

,,

,1 i a

I

/ I ! a

t

F 4 * 'qf

Page 75: SPLN 7B_1978 Insulation Coordination,App

____ t d P : 4 %

d t : 5 o l

t- - -

{

o t : 6 %

6 P : 4 %

C r t : 0 %

o t : 6 %

/f I

t

.tr t

21 / II

,

/ f

l /Ia

1 , t

//

a Il

, J

tll

/

/ t3 l

at

.L/

/

/ 2 I

II

I t

1 lt

II

!s

I

1""I

Fc

10-l

10€

10-4

10-7

10-8

- 1 2 7 -

10-2

10-5

10€

10-5 104 1O-3 lo-2 10.1 1 tr?m

247176

I : essai de decharge disruptive 50f | : 507, discharge test2 : e s s a i l 5 / 2 2 : l l l 2 t a s t3 : essai 3/0 3 : 3/0 test

Ftc. 20. - Risque du client R" en fonction du risque du constructeur Rm.

Customer's risk R" as a function of manufacturer's risk Ro,.