DPA 503 Three Phase Harmonics and Flicker Analyzer The DPA 503 is the heart of the Harmonics and Flicker Analyzing system. It meets all the requirements for the current and proposed IEC standards for har- monics and flicker measurement. The DPA 503 is a full-compliant analyzer for: Harmonic current measurement EN / IEC 61000-3-2: Ed.3 (2005) JIS C 61000-3-2 (2005) EN / IEC 61000-3-12 (2004) Flicker measurement EN / IEC 61000-3-3 A1 and A2 IEC 1000-3-3 (1994) EN / IEC 61000-3-11 (2000) The functional and design specifications are in accordance with EN / IEC 61000-4-7 (1991+2002) and EN / IEC 61000-4-15 (1997 & 2003) Specifications EN/IEC 61000-3-2 JIS C 61000-3-2 EN/IEC 61000-3-3 EN/IEC 61000-3-11 EN/IEC 61000-3-12 EN/IEC 61000-4-7 EN/IEC 61000-4-15 emc test equipment

Transcript of Specifications - EM Test · emc test equipment. ... the data are uploaded from the DPA to the...

Page 1: Specifications - EM Test · emc test equipment. ... the data are uploaded from the DPA to the computer where the software automatically performs harmonic analysis according to

DPA 503Three Phase Harmonics

and Flicker Analyzer

The DPA 503 is the heart of the Harmonics and Flicker Analyzing system. Itmeets all the requirements for the current and proposed IEC standards for har-monics and flicker measurement.

The DPA 503 is a full-compliant analyzer for:Harmonic current measurement

EN / IEC 61000-3-2: Ed.3 (2005)JIS C 61000-3-2 (2005)EN / IEC 61000-3-12 (2004)

Flicker measurementEN / IEC 61000-3-3 A1 and A2 IEC 1000-3-3 (1994) EN / IEC 61000-3-11 (2000)

The functional and design specifications are in accordance with EN / IEC 61000-4-7 (1991+2002) and EN / IEC 61000-4-15 (1997 & 2003)

S p e c i f i c a t i o n s

• EN/IEC 61000-3-2

• JIS C 61000-3-2

• EN/IEC 61000-3-3

• EN/IEC 61000-3-11

• EN/IEC 61000-3-12

• EN/IEC 61000-4-7

• EN/IEC 61000-4-15

emc test equipment

EM TEST AG Tel: +41 (0)61 717 91 91Sternenhofstr. 15 Fax: +41 (0)61 717 91 99CH-4153 Reinach emil: [email protected] RL http://www.emtest.com
Page 2: Specifications - EM Test · emc test equipment. ... the data are uploaded from the DPA to the computer where the software automatically performs harmonic analysis according to

EM TEST AG Tel: +41 (0)61 717 91 91Sternenhofstr. 15 Fax: +41 (0)61 717 91 99 data sheet DPA 503 V209.docCH-4153 Reinach emil: [email protected] 14.11.2007Switzerland RL http://www.emtest.com Page 2/4

General InformationHarmonic and Flicker measurement

Harmonic measurement

Main features

- Designed for measuring and analysis with - IEC 61000-4-7 :1991 & 2002- IEC 61000-4-15 :1997 & A1 (2003 New filter / Flickermeter 120V / 60 Hz)

- High resolution power analyzer for 1-or 3 phase application- Dual processor architecture for independent data acquisition- Windows based software with easy PASS / FAIL function- Simultaneously checks the AC power source output voltage- Real time multi-tasking data storage of voltage and current > 30 hours- Easy and simple handling with START / STOP button- Powerful documentation with direct export to Word- Data storage on computer for later analysis in the office- Class X library (create own limits for harmonic current)- Possibility to analyse a memorized data file with a different class at anytime- Self calibration function- Margin function (customized tolerance to selected limit)

Main characteristics for a full compliance requirement

- Dual processor architecture system based on a real time multi-tasking kernel to assure real time measurement

- Internal hard disk for long duration data storage- Wide input range (16 Bit A/D converter ) to avoid data lost by switching range

Accuracy of measurement

The signal conditioner uses a 16 bit A to D converter and a high perform-ance Motorola Digital Signal Processor to obtain highly accurate measure-ments.

An internal calibration routine allows the calibration of each channel. Thefigures below show the accuracy of the current input of a typical measuringsystem in comparison to the recommended accuracy of a class I equipmentaccording EN / IEC 61000-4-7.

Harmonic tests

In a simple screen the operator selects the desired standard for testing. Thesoftware presents all standard possibilities and guides the user through thesetup. The dual processor architecture and the multi-tasking real time kernelassure full compliance to EN / IEC / JIS C 61000-3-2 ,EN / IEC 61000-3-12 and EN / IEC 61000-4-7.

- Simultaneous display of voltage and current in time and frequency domain- Dynamic calculation of the limits in class C and D- Different color for harmonics above the standard limits- Cursor sensed display of harmonic voltage, current, frequency, limits, power, and phase

- Real time monitoring of the AC power source- High accuracy measurement displays Vrms, Irms, Vpeak, Ipeak- Numeric display of THD(u), THD(i), True power, Reactive power, Apparent power, Power factor, Crest factor(u), Crest factor(i)

- Display of remaining test time during the test- Stop button to finish the test- Selection of the class A...D at every time- Data storage on the internal DPA hard disk- FFT calculation based on measurements with rectangular windows with no gaps

Harmonic Analysis

At the end of the test, the data are uploaded from the DPA to the computerwhere the software automatically performs harmonic analysis according tothe selected standard.

The software provides summaryoverviews for each inspection criteriaas per EN/IEC/JIS C 61000-3-2

Page 3: Specifications - EM Test · emc test equipment. ... the data are uploaded from the DPA to the computer where the software automatically performs harmonic analysis according to

EM TEST AG Tel: +41 (0)61 717 91 91Sternenhofstr. 15 Fax: +41 (0)61 717 91 99 data sheet DPA 503 V209.docCH-4153 Reinach emil: [email protected] 14.11.2007Switzerland RL http://www.emtest.com Page 3/4

Harmonic measurement Flicker measurement

Analyzing tools

- Standardized analysis tools provide complete test reports- Report generator for Word or other word processor- Graph with fluctuating harmonics for each harmonic- Easy jump to display frequency spectrum and time domain for each data set- Spectrum with maximum or average of harmonics for a fast overview- Tool to jump to an individual data set- Table with harmonic voltage and current values- Printing table of the selected data set- Printing & export (Word, Excel) functions for all graphics and tables

Report

The standard report can be modified and easy added with individual pic-tures of interests events.The program add on request the following information to the report- Harmonic table- Average harmonic table- Table of individual time window ( I, U or I & U )- Spectrum and time domain graph- Individual report header

Flicker tests

Flicker test uses defined standard impedance for measuring the voltagefluctuation.The start window offers a selection of different Basic and product standardsfor Flicker testing.The dual processor architecture and the multi-tasking real time kernel assurefull compliance to EN / IEC 61000-3-3 or 11 and EN / IEC 61000-4-15.

- User selectable flicker standards- User selectable parameters- Display of Vrms, Pst, Plt, dc, dmax, dt

- Automatic stop function when EUT fails

- Monitoring of the maximum values ofPst , dmax, dc, dt measurements

- Display of PASS / FAIL of every test parameter

Detailed graphic and table analysis inExcel format :

- d(t) Relative voltage change- dc Rel. steady state voltage change- PF5 Instantaneous flicker sensation- RMS Half period RMS measurements

Report

- A detailed report of every individual Pst measurement shows P50%S,P10%S, P3%S, P1%S, P0.1%, Pst, dc, dmax, dt.

- Report generator for Word or other word processor programs

Page 4: Specifications - EM Test · emc test equipment. ... the data are uploaded from the DPA to the computer where the software automatically performs harmonic analysis according to

EM TEST AG Tel: +41 (0)61 717 91 91Sternenhofstr. 15 Fax: +41 (0)61 717 91 99 data sheet DPA 503 V209.docCH-4153 Reinach emil: [email protected] 14.11.2007Switzerland RL http://www.emtest.com Page 4/4

Technical Data DPA 503

Measuring systemInput channels 6 ( 3 x current & voltage)Frequency range 15 ... 2500HzSampling rate 6400 HzA/D converter 16 BitController Embedded processor Pentium 200MHzSignal processor Motorola DSPMemory Internal hard diskClass of instrument Class I per EN / IEC 61000-4-7

Voltage InputInput range 10...530V rmsOverload 4000V peakAccuracy <30V 1.0% of reading

30V...100V 0.4% of reading 100V...200V 0.2% of reading 200V...530V 0.1% of reading

Current InputInput range Depends on used CT model.

Standard delivered model max. 140AAccuracy Universal CT(related to 16A)

2 turns 5 turns0...1 A 0.1 % 0.05 %1...5 A 0.4 % 0.25 %>5 A 0.8 % 0.6 %

Harmonic analysisAccording to EN / IEC / JIS C 61000-3-2 or

EN / IEC 61000-3-12Instrument design acc. EN / IEC 61000-4-7 (1991 & 2002)Harmonic range 1...50 th harmonicGrouping Interharmonics acc. EN / IEC 61000-4-7 (2002)Synchronization PLL; accuracy better than 0.005%Measurement window rectangular window ( 8,10,12,16 periods )Algorithm FFTSmoothing filter selectable 1st order 1,5 s digital low pass filter, (on/off)Anti-aliasing filter > 90 dBMeasuring duration up to more than 30hours limited by the

harddisk capability approx. 1MB/minDisplay Vrms, Irms, Ipeak, Vpeak

Harmonic 2...50 order V, I, Phase, P, Q, S,

Power information P,Q,S, Power factor, THD(U), THD(I),Crest factor(u), Crest factor(i)

Technical data subject to change without notice

Flicker analysisAccording to EN / IEC 61000-3-3 or 11Flickermeter design acc. EN / IEC 61000-4-15 (1997 & 2003)

230 V / 50 Hz and 120 V / 60 HzAccuracy Pst and Plt < 5%Accuracy dmax, dc, dt 0.15%Flicker data Pst and Plt, Vrms, dmax, dc, dt

P50%S, P10%S, P3%S, P1%S, P0.1%Maximum values Pst , dmax, dc, dtObservation period selectable min 1min

Environment and physicalTemperature 0...40°CHumidity 10%...90% non-condensingPower supply 85V...255V , 47Hz...63HzPower requirement 50W max.Dimension 19” 3HU: 133 x 449 x 400 mm,Weight 12kgInsulation Input to case / input 3kV rmsInterface RS 232, LPT ( ECP Mode )

Flicker impedance AIF 503 (optional, separate unit)According to EN/IEC 61000-3-3 and IEC 60725 for 3-phase applicationsPhase L1, L2, L3 0.24 + j 0.15ΩNeutral 0.16 + j 0.10ΩAccuracy < 3%Max. r.m.s. current 16A per phasePeak current 50A, 1s per phaseEach inductor is designed as a non-saturable air coil and is matchedmanually to the specified value.

Flicker impedance AIF 503S1 (optional, separate unit)According to EN/IEC 61000-3-3 and EN/IEC 61000-3-11and IEC 60725 for 3-phase applicationsZrefPhase l1, L2, L3 0.24 + j 0.15ΩNeutral 0.16 + j 0.10ΩZtestPhase l1, L2, L3 0.15 + j 0.15ΩNeutral 0.10 + j 0.10ΩAccuracy < 3%Max. r.m.s. current 32A per phaseEach inductor is designed as a non-saturable air coil and is matchedmanually to the specified value.

OptionsDPA503S1 This is a single phase analyzer which is best suited for thosecustomers who may wish to upgrade to a three-phase system at a laterdate