Specialty Ac Power Solutions
Transcript of Specialty Ac Power Solutions
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 1/1401900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
72A-264BAHEN-0272A-260BMHEN-02
Dual Input, 0/0 VAC
IEC C1 Outlets
With Circuit Protection
When properly installed into a standard EIA 19”
Rack, this power strip provides for the reliable
power distribution of up to 14.72 Kilowatts of power
via eight IEC C13 outlets available for power up to
230 VAC auxiliary appliances.
The Global unit features two IEC 309 - 32A input
connectors, and each input is protected with (2)16A UL-489 listed circuit breakers. The NEMA unit
features two L6-30P connectors, and each input is
protected with (2) 15A UL-489 listed circuit break-
ers. These circuit breakers are designed to prevent
accidental actuation to the OFF position while in
service, but can be turned OFF manually for equip-
ment maintenance or repair.
Input and OutputGlobal (72A-264BAHEN-02) NEMA (72A-260BMHEN-02)
Power Input Dual, Single Phase, AC Dual, Single Phase, AC
Voltage Range 230 VAC +5%/-15% 208 VAC +5%/-15%
Frequency 50-60 Hz 50-60 Hz
Line Current 2 x 32 Amps 2 x 30 Amps (2 x 24 Amps Derated)
Input Protection (2) 16A 2 Pole Circuit Breakers/Input (2) 15A 2 Pole Circuit Breakers/Input
Power Output 14.72 KVA - (High Power) 12.48 KVA - (High Power)
Output Receptacles 8 x IEC C13 4 x 2 IEC C13
Panel Indicators LED, Power-on LED, Power-on
Physical and Environmental
Global (72A-264BAHEN-02) NEMA (72A-260BMHEN-02)
Size (Overall) 29.13”W x 1.73”H x 4.50”D
Temp. Range 0°C to 50°C
Weight ≈ 16 lbs.
Electrical & Mechanical Specifcations
Applications
- Data Centers- Financial Centers
- Industrial ATE Cabinets
- Scientifc Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers- Defense ATE Equipment
- Portable Communications Equipment
IEC 60309, 32A
Global Power
Cord Connectors
L1
L2L3
N
S p
e c
i a l t
y A
C P
o w
e r
S o l u
t i o
n s
L6-30P
NEMA Power C
Connectors
Y
X
G
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 2/1411900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Mechanical Specifcations
Top View:
Front View:
Back View:
1 .
7 3
( 4 .
3 9 )
29.13
(73.99)
31.13
(79.07)
4 .
5 0
( 1 1
. 4 3 )
S
ilt
ACP
Sl
ti
Global (72A-264BAHEN-02)
NEMA (72A-260BMHEN-02)
Global (72A-264BAHEN-02)
NEMA (72A-260BMHEN-02)
1 .
7 3
( 4 .
3 9 )
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 3/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
72A-264BAXEN-0272A-260BMXEN-02
S p
e c
i a l t
y A
C P
o w
e r
S o l u
t i o
n s
Dual Input, 0/0 VAC
IEC C1 Outlets
With Circuit Protection
IEC 60309, 32A
Global Power
Cord Connectors
L1
L2L3
N
L6-30P
NEMA Power Cord
Connectors
Y
X
G
When properly installed into a standard EIA 19”
Rack, this power strip provides for the reliable
power distribution of up to 14.72 Kilowatts of power
via 24 IEC C13 outlets available for power up to 230
VAC auxiliary appliances.
The Global unit features two IEC 309 - 32A input
connectors, and each input is protected with (2)16A UL-489 listed circuit breakers. The NEMA unit
features two L6-30P connectors, and each input is
protected with (2) 15A UL-489 listed circuit break-
ers. These circuit breakers are designed to prevent
accidental actuation to the OFF position while in
service, but can be turned OFF manually for equip-
ment maintenance or repair.
Applications
- Data Centers- Financial Centers
- Industrial ATE Cabinets
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
- Defense ATE Equipment
- Portable Communications Equipment
Input and OutputGlobal (72A-264BAXEN-02) NEMA (72A-260BMXEN-02)
Power Input Dual, Single Phase, AC Dual, Single Phase, AC
Voltage Range 230 VAC +5%/-15% 208 VAC +5%/-15%
Frequency 50-60 Hz 50-60 Hz
Line Current 2 x 32 Amps 2 x 30 Amps (2 x 24 Amps Derated)
Input Protection (2) 16A 2 Pole Circuit Breakers/Input (2) 15A 2 Pole Circuit Breakers/Input
Power Output 14.72 KVA - (High Power) 12.48 KVA - (High Power)
Output Receptacles 24 x IEC C13 8 x 3 IEC C13
Panel Indicators LED, Power-on LED, Power-on
Physical and Environmental
Global (72A-264BAXEN-02) NEMA (72A-260BMXEN-02)
Size (Overall) 55.50”W x 1.73”H x 4.50”D
Temp. Range 0°C to 50°C
Weight ≈ 17 lbs.
Electrical & Mechanical Specifcations
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 4/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
S
ilt
AC
P
Sl
ti
Mechanical Specifcations
Top View:
Front View:
Side View:
58.324
(148.14)
56.324
(143.06)
2.981
(7.57)
1 .
7 2 0
( 4 .
3 7 )
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 5/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
When properly installed into a standard EIA 19” rack, this
power strip provides for the reliable power distribution of up
to 3.84 Kilowatts of power via eight IEC C13 outlets avail-
able for power up to 200 – 240 VAC auxiliary appliances.
The Power Strip’s AC inlet is ltered to reduce emissions
in Information Technology (IT) applications and provides
at least 30db of common mode noise reduction and even
greater differential noise reduction between the frequency
ranges of 1 to 10 Megahertz.
In addition, the Power Strip contains thermally protectedTransient Voltage Suppression (TVS) networks, which
clamp common mode and differential mode voltage tran-
sients with up to 170 Joules of energy content. The Power
Strip is also equipped with LED indicator lamps that show a
“green” status if the main power input is present, and if the
TVS networks are ready and functional. The built-in UL 489
circuit breaker is designed to prevent accidental actuation
to the OFF position while in service, but it can be turned
OFF manually for equipment maintenance or repair.
7200-A-39S1
0VAC, 1A,
IEC C1 Outlets
With Surge Protection
# Denotes Protective Earth Ground
µ Denotes a maximum continuous input current of 16A at 250Vac. Leakage current < 3.5mA @ 250Vac.
∆ The circuit breaker is UL 489 Listed, features a at rocker front surface with “Accidental Off” feature.
Ψ Output power is the combined power of the eight outlets, which averages 2 amps/outlet at 240Vac.
ε Power dissipation is the combination of heat losses due to wiring, input lter leakage, and LED indicators.
λ Overall size includes the width of the mounting anges. The PDU cabinet is sized for EIA 19” rack installation.
β LED’s are turned-off when TVS networks are disconnected from the circuitry because of overheating caused by abnormal transient voltage
conditions.
τ TVS network is thermally protected, and will absorb the specied energy of both common mode and differential mode transients for 2 msec
Input Specications
Power Input Single Phase, AC
Voltage Range 240 VAC+10%/-15%
Frequency 47-63 Hz.
Currentµ 16 Amps
Input Protection∆ 16A, Circuit Breaker
Power Dissipationε 10W nom. @ 240 VAC
Panel Indicatorsβ LED, Main & TVS
TVSτ 170 Joules
Output Specications
Power OutputΨ 3.84 KVA - (Basic Power)
Output Receptacle 8x-IEC 60320/C13
PE Ground# 1/4”-20 threaded Stud
Physical and
Environmental
Specications
Size (Overall)λ 19.0”W x1.72”H x6.50”D
Temp. Range 0°C to 55°C
Weight ≈ 5.7 lb (≈ 2.6 kg)
Electrical & Mechanical Specifcations
IEC C20Power Inlet Connect
Applications
- Financial Centers- Data Centers
- Industrial ATE Cabinets
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
- Defense ATE Equipment
- Portable Communications Equipment
L N
S p e c
i a l t y
A C
P o w
e r
S o l u t i
o n s
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 6/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Typical Insertion Loss (dB)
Frequency (Mhz) .15 .45 1 2 5 10 30
Common Mode 15 22 28 35 42 48 55Differential Mode 13 8 40 60 72 68 58
EMI/RFI Filtering
• Common Mode – Line to Ground
• Differential Mode – Line to Line
• High Frequency Ground Isolation
16 Amp Breaker
Green LED
100,000 Hour
Life, X3
Ground Stud
1/4-20 X .50”IEC 320-C13
Receptacles (8X)
IEC 320-C20
Inlet Plug (1X)
17.00
(43.18)
17.19
(43.66)
2 .
1 0
( 5
. 3 3 )
6 .
5 0
( 1 6 .
5 1 )
1 .
7 2 0
( 4
. 3 7 )
18.31
(46.51)
Side View:
Back View:
Bottom View:
Front View:
Note: Remove screw prior to Hi Pot.
Install to perform Hi Pot.
Mechanical Specifcations
S
ilt
AC
P
S
lti
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 7/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
7200-A-39-3L5-30P
Power Cord Conne
When properly installed into a standard EIA 19” Rack, this
power strip provides for the reliable power distribution of up
to 3.84 Kilowatts of power via eight NEMA 5-20R outlets
available for power up to 120 VAC auxiliary appliances. The
power strip’s AC inlet is ltered to reduce emissions in In-
formation Technology (IT) applications and provides at least
30db of common mode noise reduction, and even greater
differential noise reduction between the frequency ranges
of 1 to 10 Megahertz.
In addition, the power strip contains thermally protected
Transient Voltage Suppression (TVS) networks, whichclamp common mode and differential mode voltage tran-
sients with up to 170 Joules of energy content. The Power
Strip is also equipped with LED indicator lamps that show a
“green” status if the main power input is present, and if the
TVS networks are ready and functional. The built-in UL 489
circuit breaker is designed to prevent accidental actuation
to the OFF position while in service, but it can be turned
OFF manually for equipment maintenance or repair.
Applications
- Industrial ATE Cabinets- Financial Centers
- Data Centers
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
- Defense ATE Equipment
- Portable Communications Equipment
# Denotes Protective Earth Ground
µ Denotes a maximum input line current of 30A at 120Vac (circuit derating = 24 Amps). Leakage current < 3.5mA @ 120Vac.
∆ The circuit breaker is UL 489 Listed, features a at rocker front surface with “Accidental Off” feature.
Ψ Output power is the combined power of the sixteen outlets, which approximates 1.9 Amps/outlet at 120Vac.
ε Power dissipation is the combination of heat losses due to wiring, input lter leakage, and LED indicators.
λ Overall size includes the width of the mounting anges. The PDU cabinet is sized for EIA 19” rack installation.
β LED’s are turned-off when TVS networks are disconnected from the circuitry because of overheating caused by abnormal transient volt
conditions.
τ TVS network is thermally protected, and will absorb the specied energy of both common mode and differential mode transients for 2 m
Input Specications
Power Input Single Phase, AC
Voltage Range 120 VAC+10%/-15%
Frequency 47-63 Hz.
Currentµ 30 Amps
Input Protection∆ 8 x 15A Circuit Breakers
Power Dissipationε 10W nom. @ 120 VAC
Panel Indicatorsβ LED, Main & TVS
TVSτ 170 Joules
Output Specications
Power OutputΨ 3.60 KVA - (Basic Power)
Output Receptacle 8 x 2 NEMA 5-20R
PE Ground# 1/4”-20 threaded Stud
Physical and Environmental Specications
Size (Overall)λ 19.0”W x 3.50”H x 6.50”D
Temp. Range 0°C to 50°C
Weight ≈ 11 lb (≈ 5 kg)
Electrical & Mechanical Specifcations
10VAC, 0A,
NEMA -0R Outlets
With Surge Protection
W
G
S p e c
i a l t y
A C P
o w e r
S o l u t i o
n s
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 8/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Mechanical Specifcations
Top View:
Side View:
Back View:
Front View:
S
ilt
AC P
S
lti
6 .
0 0
( 1
5 .
2 4 )
19.00
(48.26)
18.316
(46.52)
17.00
(43.18)
8x2 NEMA 5-20R
6.00
(15.24)
3 .
4 7
( 8
. 8 1 )
3 .
0 0
( 7
. 6 2 )
1 .
7 4 9
( 4
. 4 4 )
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 9/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Dual Input, Phase
IEC C1 Outlets
With Surge Protection
72RA2A8BWFFN-0072RA296BXFFN-00
Applications
- Data Centers- Financial Centers
- Industrial ATE Cabinets
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
When properly installed into a standard EIA 19” Rack, this
dual input 3 Phase supplied power strip provides for up
to 22 Kilowatts of reliable power from six IEC C19 outlets.
It supports auxiliary appliances operation from 200 - 240
VAC. The six individual outlets, one per phase, are each
protected with a 16 Amp UL489 listed circuit breaker.
These circuit breakers are designed to prevent accidental
actuation to the OFF position while in service, but can be
turned OFF manually for equipment maintenance or repair.
The Power Strip provides a simple AC Power Distribution
solution for the new WS-CAC-8700W-E (8700 Watt AC in-
put power supply) of the advanced Catalyst 6509E Switch,
and is also an ideal solution for all 20 Amp 200-240 VAC
appliances.
Electrical & Mechanical Specifcations
Input and Output
Global (72RA296BXFFN-00) NEMA (72RA2A8BWFFN-00)
Input Conguration Dual 3 Phase, Y Dual 3 Phase, ∆
Voltage Input 400 VAC+10%/-15% 208 VAC+10%/-15%
Voltage Output 230 VAC 208 VAC
Line Current* 16A Max./Input 30A Max./Input
Output Power Ψ 22.08 KVA - (Enforcer Power) 17.29 KVA - (Enforcer Power)
PE Ground# (2) 1/4”-20 Studs (2) 1/4”-20 Studs
Output Connector (6) IEC 320 C19 (6) IEC 320 C19
Input Protection∆ 16A 1 Pole Circuit Breaker/Outlet 16A 2 Pole Circuit Breaker/Outlet
Panel Indicators Power-on, LED Power-on, LED
Physical and Environmental
Global (72RA296BXFFN-00) NEMA (72RA2A8BWFFN-00)Size (Overall)λ 19.0”W x1.72”H x6.50”D 19.0”W x1.72”H x6.50”D
Temp. Range -5°C to 70°C -5°C to 70°C
Weight 20 lbs 20 lbs
# Denotes Protective Earth Ground
∆ The circuit breaker is UL 489 Listed, features a at rocker front surface with “Accidental Off” feature.
Ψ Output power is the combined power of six outlets at nominal output voltage (at derated current).
λ Overall size includes the width of the mounting anges. The PDU cabinet is sized for EIA 19” rack installation.
* Derated current is 80% of maximum line current for NEMA version PDU.
L15-3
NEMA P
Cord Con
IEC 60309, 32A/Phase
Global Power
Cord Connectors
L1
L2L3
N
S p e c
i a l t y
A C
P o w
e r
S o
l u t i
o n s
Great for use with20A blade servers
and switches.
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 10/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Mechanical Specifcations
Top View:
Side View:
Back View:
Front View:
S
ilt
AC
P
S
lti
19.00
(48.26)
6 .
5 0
( 1 6
. 5 1 )
17.00
(43.18)
LED Power-on Indicator (6X)
1 .
7 2
6.50
(16.51)
IEC C19 (6X)
Global (72RA296BXFFN-00)
NEMA (72RA2A8BWFFN-00)
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 11/1401900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
72A-120BUHEM-71IEC C20
Power Inlet Connec
L N
0VAC, 0A,
IEC C1 Outlets
With Circuit Protection
and Current Meter
Input and Output
Voltage Input 200 - 240 VAC
Voltage Output 200 - 240 VAC
Inlet Current 20A maximum
Output Power 4.60 KVA - (Basic Power)
Output Connector (8) IEC C13
Input Protection 20A Single Pole Circuit Breaker
Panel Indicators Power-on, LED
Physical and Environmental
Size (Overall) 29.13”W x 1.69”H x 2.97”D
Temp. Range 0°C to 40°C
Weight 7 lbs.
Electrical & Mechanical Specifcations
Applications
- Data Centers- Financial Centers
- Industrial ATE Cabinets
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
- Defense ATE Equipment
- Portable Communications Equipment
- Rapid Deployment Rack
This Spectrum Power Management Systems power
strip is specially designed for reliable power distri-
bution up to 4.60 KVA to eight AC loads. To avoid
the possibility of system faults, the unit features
a UL 489-listed circuit breaker and LCD current
metering.
The advanced power strip allows the user to moni-
tor the total load drawn at the PDU source. This
enables the user to quickly identify current draw onan individual appliance basis.
The unit also features an IEC C20 power inlet con-
nector for an economical solution to power distribu-
tion needs. The 72A-120BUHEM-71 is a simple so-
lution for all 20 Amp 200-240 VAC VAC appliances.
S p
e c
i a l t y
A C
P o w e
r S o
l u t i o n
s
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 12/1411900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
Mechanical Specifcations
Side View:
Back View:
Front View:
S
ilt
AC
P
S
lti
1 .
6 9
( 4
. 2 9 )
29.134
(73.99)
31.496
(80.00)
30.512
(77.50)
2.972
(7.55)
Bulk Current
Meter
20A Circuit Breaker
with Finger Guard
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 13/141900 West College Avenue, State College, PA 16801 • 814-272-SPMS • [email protected]
72A-196BAREMS0172A-190BQREMS01
L21-30P
NEMA Pow
Cord Conne
Input and Output
Global (72A-196BAREMS01) NEMA (72A-190BQREMS01)
Input Conguration 3 Phase-Y, AC 3 Phase-∆, AC
Voltage Input 3 ∅ 400/230VAC ±10% 3 ∅ 208/208VAC ±10%
Voltage Output 200/230 VAC 208 VAC
Phase Current 72A maximum, combined 41.6A maximum, combined
Output Power 16.56 KVA - (High Power) 8.65 KVA - (Intermediate Power)
Output Connector (18) IEC C13
Input Protection (6) 16A 2 Pole Circuit Breakers
Panel Indicators LED
Physical and Environmental
Global (72A-196BAREMS01) NEMA (72A-190BQREMS01)
Size (Overall) 55.5”W x1.75”H x5.2”D
Temp. Range 0°C to 55°C
Weight 32.5 lbs
Electrical & Mechanical Specifcations
1 IEC C1 Outlets
Phase Power Monitoring
and Distribution Unit
IEC 60309, 32A
Global Power
Cord Connector
This Spectrum Power Management Systems PDU is an
AC power distribution unit designed to distribute power
for up to eighteen (18) AC loads. The PDU distributes
3 phase power to six individual, over current protected,
output banks. The unit has multiple alarm capabilities and
includes an audible alarm circuit. Voltage and current are
monitored and displayed locally on a liquid crystal display
and remotely through a LAN connection. The LAN mod-ule consists of integrated hardware and a network agent
software program. These components provide the ability
to congure, control, and monitor aspects of multiple units
using a standard web browser. The network interface can
operate using the Web, Telnet, and SNMP. Operation/con-
trol is accomplished by use of six 16A breaker actuators.
This product complies with FCC, CE, TUV, UL60950-1 and
IEC60950 requirements.
Applications
- Data Centers- Financial Centers- Industrial ATE Cabinets
- Scientic Instrumentation Cabinets
- Communications Base Stations
- Network Operating Centers
- Defense ATE Equipment- Portable Communications Equipment
L1
L2L3
N
S p
e c
i a l t
y A
C P
o w
e r S
o l u
t i o
n s
8/14/2019 Specialty Ac Power Solutions
http://slidepdf.com/reader/full/specialty-ac-power-solutions 14/14
Mechanical Specifcations
Top View:
Side View:
Front View:
S
ilt
AC P
S
lt i
3.75
(9.53)
( 6 .
3 5 )
55.50
(140.97)
LAN Connector Current Meter
1 .
7 5
( 4 .
4 4 )