Special Cables Catalogue

126
Special Cables

description

Cables

Transcript of Special Cables Catalogue

Page 1: Special Cables Catalogue

Special Cables

Page 2: Special Cables Catalogue

ELSEWEDY CABLES IN BRIEF

Elsewedy Cables was established in 1984 and is considered as one of the oldest and most successful industrial and trading business groups across the Middle East and Africa in the fields of energy, plastics and contracting. Elsewedy Cables is specialized mainly in Wires, Cables, Telecom Solutions, Electrical Products, Turnkey Projects, and recently Energy Generation. The group’s turnover has been rapidly rising during the past few years to reach $ 1.5 billion in 2007, also, the production capacity is the second highest one in the region, with 125000 tons/annum, expecting 212000 tons/annum in 2008.

Although the company began as an Egyptian local manufacturer, it has branched out regionally and internationally to include 23 production facilities for cables and electrical products that are located in 12 contries (Egypt, Sudan, Algeria, Zambia, Ghana, Syria, Saudi Arabia, Qatar, Slovenia, India and Malaysia), and it currently export its wide range of high quality and safe products to more than 110 countries worldwide. Additionally, the group’s outstanding human potential, which is more than 5000 employees, and its solid financial postioin, along with the strong geographical prsensce, have heavily contributed to the group’s success and prosperity.

To strengthen its position world wide, and following the corporate strategy, on the one hand, Elsewedy Cables fully acquired by the end of 2007 ISKRAEMECO, a leader manufacturer of electrometers and currently the third largest player in the European market and the seventh largest globally; on the other hand, Elsewedy Cables is involved with 74% ownership jointly with Glencore International in a 850 $US million project for the construction of a copper smelter to be located in Egypt.

Page 3: Special Cables Catalogue

ELSEWEDY CABLES IN BRIEF

Further more, Elsewedy Cables provides a complete portfolio of solutions and advanced technologies for sectors as diverse as the automotive and aerospace industries, railways, buildings, telecommunication and energy networks, oil and gas, submarine power systems, etc. Accordingly, Elsewedy Cables is divided in three segments in order to cover all those sectors: Wires & cables, electrical products, and turn-key projects. The group has obtained quality certificates from the most reputable laboratories, among them: ISO 90012000-, ISO 14001, QS 9000, KEMA.a

Quality and safety are so much considered. Elsewedy Cables adopted a policy that assures maximum effectiveness and efficiency through processes and systems ensuring that every aspect of each company’s activity is aligned to satisfy customer needs and all other objectives without wasting effort and with the use of the full potential of every person. Our organizational philosophy believes that customer satisfaction, health, safety, environmental considerations, and business objectives are mutually dependent.

In the industrial sector, we currently supply approximately 56% of Egypt’s global market share of power cables, telecommunication cables, and lighting industries. In the export sector, as part of a worldwide marketing plan, Elsewedy Cables has branches throughout Africa, Middle East, Gulf Area, Europe, and Asia, and consistently showing dramatic increases; Egypt enjoys an important number of trade agreements with most of those countries (EU Agreement, Arab Free Trade Agreement, COMESA Agreement). Nowadays, Elsewedy Cables is exporting approximately 60% of its total turnover (export value of 550 $US million in 2006, 1 $US billion in 2007). For that reason, the group is concentrating efforts and making investments to target market segments and countries world wide with strong growth potential, such as Europe, Asia, or Latin America, although strengthen its leadership in Africa and Middle East.

Elsewedy Cables’ mission is to become world expert in cables, with a strong financial basis and technical advanced product portfolio, making it an attractive partner for all its stakeholders: Shareholders, customers, suppliers, and employees.

Page 4: Special Cables Catalogue

GROUP HISTORy1938 Elsewedy family started its business as a trader in electrical equipment.

1960 The business was developed further by turning into a distributor for the only cables manufacturing at that time.

1984 Based on their experience in that field, the family decided to build Egypt’s first private sector cables factory “ARAB CABLES”.

1986 Arab Cables started production as Egypt’s and the Middle East’s private sector cables supplier.

1986-96 Arab Cables’ capacity quadruples from around 6.000 tons of copper cables in 1986 to 30.000 tons in 1996.

1996 Elsewedy family established their second factory, “EGyTECH CABLES”, which is the most advanced cables production facility in the Middle East with an annual capacity of 30.000 tons of copper cables and 15.000 tons of aluminum cables.

Elsewedy family established their first plant for producing PVC compounds and master batch for cables insulation “SEDPLAST” considered as major component for the production of cables.

1997 Elsewedy family established “UNITED INDUSTRIES”, the company consists of three different factories specialized in the production of special cables (first factory in Egypt), winding wires & fiber glass poles.

Elsewedy family established “ELASTIMOLD EGyPT”, as a joint venture with ELastimold, a unit of Thomas & Betts, one of the leading companies worldwide in the field of cables accessories, to produce power cable joints and Modular Terminators.

1998 Elsewedy family established “UNITED METALS CO.” Egypt’s first factory to produce High Grade Copper Rods, the main component in the production of cables conductors. The factory is considered as the largest copper rod factory in the Middle East region.

Elsewedy family established “Elsewedy SEDCO”, as the first and only factory in Africa and the Middle East producing cable accessories.

2002 Elsewedy Cables established their first cables factory outside Egypt “GIAD Elsewedy Cables” in partnership with the Sudanese company Giad for the production of power cables, over head conductors and telephone cables.

2003 Elsewedy Cables further enhances their facilities outside Egypt by establishing the “SUDANESE EGyPTAION ELECTRICAL INDUSTRIES CO.” in partnership with Sudanese electricity authority. SUDATRAF (specialized in manufacturing transformers, electrical panels & cables joint and terminators).

2004 Together Elsewedy Cables Group & Italsmea company (Italy) established a joint venture for the manufactory of explosion proof electrical equipment. Italsmea Elsewedy co.

2005 Elsewedy Cables established the Syria’s latest cables factory “Elsewedy Cables SyRIA” specialized in power cables manufacturing up to 400 kV, relying on the growth in the area of: Syria, Lebanon, Jordan, Iraq, Iran, Palestine and all Arab countries near by.

2006 Elsewedy Cables penetrated Ghana, by establishing “Elsewedy ELECTRIC-GHANA” the factory is specialized in Fiber Glass Road Lighting Poles manufacturing.

2007 Elsewedy Cables established two new factories:

Elsewedy Cables SAUDI ARABIA specialized in wires and cables.

Elsewedy ELECTRIC SyRIA specialized in transformers.

Acquisition of ISKRAEMECO specialized in energy measurement & management systems.

2008 Elsewedy Cables established two new factories:

Elsewedy Cables QATAR: specialized in power cables “Low & Medium”.

Elsewedy Cables ALGERIA: specialized in power cables “Low & Medium” in addition

to instrumentation cables.

Page 5: Special Cables Catalogue

GROUP STRUCTURE

Wires & Cables

Electrical Products

Turnkey Projects

PSPElsewedy

Power SystemsProjects

United Metals

SEDCO

Sedplast

Egyplast

UnitedWires

Red SeaCopper

Arab Cables

Egytech Cables

Giad Elsewedy Cables

Elsewedy Cables Syria

Elsewedy Cables

Saudi Arabia

Libya Cables

ElsewedyCables Egypt

ElsewedyCables Algeria

Elsewedy Electric

Transmission & Distribution

Elastimold Egypt

Elsewedy Transformers

Egypt

Elsewedy Electric Syria

ElsewedyElectric Zambia

United Industries

Sudanese Egyptian Electrical

Industries

Elsewedy Electric Ghana

ISKRAEMECO

Page 6: Special Cables Catalogue

index

A Instrumentation Cables

B Fire Resistant & Fire Alarm Cables

C Control Cables

D Lan and Telephone Cables

E Coaxial Cables

F Automotive Wires

G Appliance Cables and Cords

H Technical Information

I Glossary

J Certificates

Page 7: Special Cables Catalogue

High Resolution Pls

Page 8: Special Cables Catalogue

A. Instrumentation Cables

Page 9: Special Cables Catalogue

A. instrumentation Cables PVC Insulation, Multipairs, Twisted in Bundles, Collective Screen...............................................................

PVC Insulation, Single Pair or Triple, Collective Screen................................................................................

PVC Insulation, Multipairs, Layers, Collective Screen...................................................................................

PVC Insulation, Multipairs, Layers, Individual and Collective Screen............................................................

PVC Insulation, Multitriples, Layers, Collective Screen....................................................................................

PVC Insulation, Multitriples, Layers, Individual and Collective Screen...........................................................

PVC Insulation, Single Pair, Collective Screen, Galvanized Steel Wire Armour.............................................

PVC Insulation, Multipairs, Layers, Collective Screen, Galvanized Steel Wire Armour..................................

PVC Insulation, Individual and Collective screen, Galvanized Steel wire Armour...........................................

PVC Insulation, Multipairs, Layers, Individual and Collective Screen, Galvanized Steel Wire Armour..........

PE Insulation, Multipairs, Twisted in Bundles, Collective Screen......................................................................

PE Insulation, Single Pair or Triple, Collective Screen...................................................................................

PE Insulation, Multipairs, Layers, Collective Screen.........................................................................................

PE Insulation, Multipairs, Layers, Individual and Collective Screen................................................................

PE Insulation, Multitriples, Layers, Collective Screen....................................................................................... PE Insulation, Multitriples, Layers, Individual and Collective Screen.............................................................. PE Insulation, Single Pair, Collective Screen, Galvanized Steel Wire Armour..................................................

PE Insulation, Multipairs, Layers, Collective Screen, Galvanized Steel Wire Armour......................................

PE Insulation, Multipairs, Layers, Collective Screen Galvanized Steel Wire Armour.......................................

PE Insulation, Multipairs, Layers, Individual and Collective Screen, Galvanized Steel Wire Armour...........

PE Insulation, Multicores, Layers, Overall Screen of Tinned Copper Wire Braid.............................................

PE Insulation, Single Pair, Collective Screen of Tinned Copper Wire Braid.....................................................

PE Insulation, Multipairs, Layers, Overall Screen of Tinned Copper Wire Braid.........................................

PE Insulation, Multipairs, Layers, Overall Screen of Plain or Tinned Copper Wire Braid...........................

2346810121315161718192123252728293032333435

Page 10: Special Cables Catalogue

A 2

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 7.9 80 CPC-T1202-JU05GQ4 7 x 0.3 39.2 0.6 1.0 10.1 100 CPC-T1204-JU05GQ8 7 x 0.3 39.2 0.6 1.0 12.1 160 CPC-T1208-JU05GQ

12 7 x 0.3 39.2 0.6 1.2 14.4 230 CPC-T1212-JU05GQ16 7 x 0.3 39.2 0.6 1.2 16.1 300 CPC-T1216-JU05GQ

20 7 x 0.3 39.2 0.6 1.2 18.5 360 CPC-T1220-JU05GQ

24 7 x 0.3 39.2 0.6 1.4 20.3 450 CPC-T1224-JU05GQ

1.0

2 7 x 0.43 18.4 0.6 1.0 8.9 100 CPC-T1202-JU12GQ4 7 x 0.43 18.4 0.6 1.0 12 160 CPC-T1204-JU12GQ8 7 x 0.43 18.4 0.6 1.2 16 300 CPC-T1208-JU12GQ12 7 x 0.43 18.4 0.6 1.4 20 430 CPC-T1212-JU12GQ16 7 x 0.43 18.4 0.6 1.4 22 550 CPC-T1216-JU12GQ20 7 x 0.43 18.4 0.6 1.4 24.3 660 CPC-T1220-JU12GQ24 7 x 0.43 18.4 0.6 1.6 26.7 800 CPC-T1224-JU12GQ

TECHNICAL INFORMATION

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Twisted in Bundles, Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form pairs, 4 pairs twisted to form a bundle, bundles twisted in concentric layers, 2 pairs twisted as star quad

Colour code: One Pair : Blue / RedTwo Pairs : Grey / yellowThree Pairs : Green / BrownFour Pairs : White / BlackBundles are identified by coloured polyester tapes.

Wrapping: Polyester tapes

Collective Screen:Aluminum polyester tape with tinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or greyor blue

Minimum bending radius: 7.5*d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operaion

Packing: On non-returnable wooden drums

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

225

V

Page 11: Special Cables Catalogue

A 3

Cable Size

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At 20oC

mm2 No. x mm Ohm /Km mm mm mm Kg/Km -

1x 2 x 0.5 7 x 0.3 39.2 0.6 0.8 6.0 50 CPC-T1201-JU05B

1x 3 x 0.5 7 x 0.3 39.2 0.6 0.8 6.3 60 CPC-T1301-JU05B

1x 2 x 0.75 7 x 0.37 24.6 0.6 0.8 6.4 60 CPC-T1201-JU08B

1x 3 x 0.75 7 x 0.37 24.6 0.6 0.8 6.7 70 CPC-T1301-JU08B

1x 2 x 1.0 7 x 0.43 18.4 0.6 0.8 6.8 70 CPC-T1201-JU12B

1x 3 x 1.0 7 x 0.43 18.4 0.6 0.8 7.1 80 CPC-T1301-JU12B

1x 2 x 1.3 7 x 0.49 14.2 0.6 0.8 7.1 80 CPC-T1201-JU14B

1x 3 x 1.3 7 x 0.49 14.2 0.6 0.8 7.4 90 CPC-T1301-JU14B

1x 2 x 1.5 7 x 0.53 12.6 0.6 0.8 7.6 90 CPC-T1201-JU15B

1x 3 x 1.5 7x 0.53 12.6 0.6 0.8 8.0 110 CPC-T1301-JU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Single Pair or Triple, Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogueand digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: cores twisted to form a pair or triple and wrapped by polyester tapes

Colour code: Pair : White / BlackTriple : Black / White / Red

Screen:Collective screen aluminum polyester tape withtinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or greyor blue

Minimum bending radius: 7.5*d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operaion

Packing: On non-returnable wooden drums

TECHNICAL INFORMATION

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 12: Special Cables Catalogue

A 4

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 9.3 107 CPC-T1202-JU05B

4 7 x 0.3 39.2 0.6 1.0 10.0 117 CPC-T1204-JU05B

8 7 x 0.3 39.2 0.6 1.2 13.2 199 CPC-T1208-JU05B

12 7 x 0.3 39.2 0.6 1.2 15.0 265 CPC-T1212-JU05B

16 7 x 0.3 39.2 0.6 1.2 16.7 340 CPC-T1216-JU05B

20 7 x 0.3 39.2 0.6 1.3 18.7 410 CPC-T1220-JU05B

24 7 x 0.3 39.2 0.6 1.3 20.6 480 CPC-T1224-JU05B

30 7 x 0.3 39.2 0.6 1.5 23.3 685 CPC-T1230-JU05B

0.75

2 7 x 0.37 24.6 0.6 1.0 10.1 125 CPC-T1202-JU08B

4 7 x 0.37 24.6 0.6 1.0 10.8 140 CPC-T1204-JU08B

8 7 x 0.37 24.6 0.6 1.2 14.3 245 CPC-T1208-JU08B

12 7 x 0.37 24.6 0.6 1.2 16.3 330 CPC-T1212-JU08B

16 7 x 0.37 24.6 0.6 1.3 18.3 430 CPC-T1216-JU08B

20 7 x 0.37 24.6 0.6 1.3 20.3 520 CPC-T1220-JU08B

24 7 x 0.37 24.6 0.6 1.3 22.5 610 CPC-T1224-JU08B

30 7 x 0.37 24.6 0.6 1.5 23.3 720 CPC-T1230-JU08B

Multipairs, Layers, Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

TECHNICAL INFORMATION

PVC Insulation

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor:Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form pairs, twisted pairs in concentric layers and wrapped by polyester tapes

Colour code: Black / White, continuously numbered, or identification tapes numbered

Collective Screen:Aluminium polyster tape with tinned drainwire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colourblack or grey or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + +50oC during operation

Packing: On non-returnable wooden drums

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 13: Special Cables Catalogue

A 5

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm/Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.0 10.8 142 CPC-T1202-JU12B

4 7 x 0.43 18.4 0.6 1.0 11.6 166 CPC-T1204-JU12B

8 7 x 0.43 18.4 0.6 1.2 15.4 295 CPC-T1208-JU12B

12 7 x 0.43 18.4 0.6 1.3 17.8 415 CPC-T1212-JU12B

16 7 x 0.43 18.4 0.6 1.3 19.8 532 CPC-T1216-JU12B

20 7 x 0.43 18.4 0.6 1.3 22.0 641 CPC-T1220-JU12B

24 7 x 0.43 18.4 0.6 1.5 24.8 784 CPC-T1224-JU12B

30 7 x 0.43 18.4 0.6 1.7 27.5 1063 CPC-T1230-JU12B

1.3

2 7 x 0.49 14.2 0.6 1.0 11.7 160 CPC-T1202-JU14B

4 7 x 0.49 14.2 0.6 1.2 13.3 230 CPC-T1204-JU14B

8 7 x 0.49 14.2 0.6 1.3 16.5 375 CPC-T1208-JU14B

12 7 x 0.49 14.2 0.6 1.3 19.3 400 CPC-T1212-JU14B

16 7 x 0.49 14.2 0.6 1.3 21.7 590 CPC-T1216-JU14B

20 7 x 0.49 14.2 0.6 1.5 24.2 815 CPC-T1220-JU14B

24 7 x 0.49 14.2 0.6 1.7 26.3 950 CPC-T1224-JU14B

30 7 x 0.49 14.2 0.6 1.7 31.0 1300 CPC-T1230-JU14B

1.5

2 7 x 0.53 12.6 0.6 1.2 12.9 202 CPC-T1202-JU15B

4 7 x 0.53 12.6 0.6 1.2 14.1 243 CPC-T1204-JU15B

8 7 x 0.53 12.6 0.6 1.3 18.6 425 CPC-T1208-JU15B

12 7 x 0.53 12.6 0.6 1.3 21.3 594 CPC-T1212-JU15B

16 7 x 0.53 12.6 0.6 1.5 24.3 797 CPC-T1216-JU15B

20 7 x 0.53 12.6 0.6 1.5 27.1 963 CPC-T1220-JU15B

24 7 x 0.53 12.6 0.6 1.7 30.3 1164 CPC-T124-JU15B

30 7 x 0.53 12.6 0.6 2.0 33.7 1595 CPC-T1230-JU15B

TECHNICAL INFORMATION

PVC InsulationMultipairs, Layers, Collective Screen

Page 14: Special Cables Catalogue

A 6

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 10.3 122 CPC-T1202-SU05B

4 7 x 0.3 39.2 0.6 1.0 11.1 140 CPC-T1204-SU05B

8 7 x 0.3 39.2 0.6 1.2 14.7 240 CPC-T1208-SU05B

12 7 x 0.3 39.2 0.6 1.3 17.0 340 CPC-T1212-SU05B

16 7 x 0.3 39.2 0.6 1.3 18.9 433 CPC-T1216-SU05B

20 7 x 0. 3 39.2 0.6 1.3 21.0 518 CPC-T1220-SU05B

24 7 x 0. 3 39.2 0.6 1.5 23.7 636 CPC-T1224-SU05B

30 7 x 0. 3 39.2 0.6 1.5 26.3 867 CPC-T1230-SU05B

0.75

2 7 x 0.37 24.6 0.6 1.0 11.2 149 CPC-T1202-SU08B

4 7 x 0.37 24.6 0.6 1.0 11.9 165 CPC-T1204-SU08B

8 7 x 0.37 24.6 0.6 1.2 15.8 291 CPC-T1206-SU08B

12 7 x 0.37 24.6 0.6 1.3 18.3 409 CPC-T1208-SU08B

16 7 x 0.37 24.6 0.6 1.3 20.4 523 CPC-T1212-SU08B

20 7 x 0.37 24.6 0.6 1.3 22.8 631 CPC-T1216-SU08B

24 7 x 0.37 24.6 0.6 1.5 25.7 770 CPC-T1220-SU08B

30 7 x 0.37 24.6 0.6 1.7 26.4 902 CPC-T1230-SU08B

Multipairs, Layers, Individual and Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form pairs, pairs screened by aluminum polyester tape, screened pairs twisted in concentric layers, and wrapped by polyester tapes

Screen:Collective screen of aluminum polyester tape with tinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to +50oC during operaion

Packing: On non-returnable wooden drums

TECHNICAL INFORMATION

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 15: Special Cables Catalogue

A 7

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.2 12.2 172 CPC-T1202-SU12B

4 7 x 0.43 18.4 0.6 1.2 13.1 201 CPC-T1204-SU12B

8 7 x 0.43 18.4 0.6 1.3 17.2 351 CPC-T1208-SU12B

12 7 x 0.43 18.4 0.6 1.3 19.7 486 CPC-T1212-SU12B

16 7 x 0.43 18.4 0.6 1.3 21.9 626 CPC-T1216-SU12B

20 7 x 0.43 18.4 0.6 1.5 25.0 670 CPC-T1220-SU12B

24 7 x 0.43 18.4 0.6 1.5 27.6 923 CPC-T1224-SU12B

30 7 x 0.43 18.4 0.6 1.7 30.5 1253 CPC-T1230-SU14B

1.3

2 7 x 0.49 14.2 0.6 1.2 12.8 195 CPC-T1202-SU14B

4 7 x 0.49 14.2 0.6 1.3 14.0 245 CPC-T1204-SU14B

8 7 x 0.49 14.2 0.6 1.3 18.2 425 CPC-T1208-SU14B

12 7 x 0.49 14.2 0.6 1.3 20.3 615 CPC-T1212-SU14B

16 7 x 0.49 14.2 0.6 1.5 23.2 790 CPC-T1216-SU14B

20 7 x 0.49 14.2 0.6 1.5 27.0 880 CPC-T1220-SU14B

24 7 x 0.49 14.2 0.6 1.7 31.2 1100 CPC-T1224-SU14B

30 7 x 0.49 14.2 0.6 2.0 34.5 1450 CPC-T1230-SU14B

1.5

2 7 x 0.53 12.6 0.6 1.2 14.1 228 CPC-T1202-SU15B

4 7 x 0.53 12.6 0.6 1.2 15.4 273 CPC-T1204-SU15B

8 7 x 0.53 12.6 0.6 1.3 20.3 480 CPC-T1208-SU15B

12 7 x 0.53 12.6 0.6 1.5 24.0 700 CPC-T1212-SU15B

16 7 x 0.53 12.6 0.6 1.5 26.7 904 CPC-T1216-SU15B

20 7 x 0.53 12.6 0.6 1.7 30.2 1119 CPC-T1220-SU15B

24 7 x 0.53 12.6 0.6 2.0 34.0 1370 CPC-T1224-SU15B

30 7 x 0.53 12.6 0.6 2.2 37.4 1845 CPC-T1230-SU15B

TECHNICAL INFORMATION

PVC InsulationMultipairs, Layers, Individual and Collective Screen

Page 16: Special Cables Catalogue

A 8

Conductor size

Number of

triples

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - codeNo.x

dia.

Max. DC Res.

At 20oC

mm2 No. No. x mm

Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 10.1 125 CPC-T1302-JU05B

4 7 x 0.3 39.2 0.6 1.0 10.8 150 CPC-T1304-JU05B

8 7 x 0.3 39.2 0.6 1.2 14.6 245 CPC-T1308-JU05B

12 7 x 0.3 39.2 0.6 1.3 16.5 347 CPC-T1312-JU05B

16 7 x 0.3 39.2 0.6 1.3 18.7 450 CPC-T1316-JU05B

20 7 x 0.3 39.2 0.6 1.3 21.2 565 CPC-T1320-JU05B

24 7 x 0.3 39.2 0.6 1.5 24.0 670 CPC-T1324-JU05B

30 7 x 0.3 39.2 0.6 1.5 27.7 975 CPC-T1330-JU05B

0.75

2 7 x 0.37 24.6 0.6 1.0 10.9 145 CPC-T1302-JU08B

4 7 x 0.37 24.6 0.6 1.0 11.8 190 CPC-T1304-JU08B

8 7 x 0.37 24.6 0.6 1.3 15.9 375 CPC-T1308-JU08B

12 7 x 0.37 24.6 0.6 1.3 17.9 435 CPC-T1312-JU08B

16 7 x 0.37 24.6 0.6 1.3 20.2 535 CPC-T1316-JU08B

20 7 x 0.37 24.6 0.6 1.5 23.8 675 CPC-T1320-JU08B

24 7 x 0.37 24.6 0.6 1.5 26.0 970 CPC-T1324-JU08B

30 7 x 0.37 24.6 0.6 1.7 30.0 1175 CPC-T1330-JU08B

Multitriples, Layers, Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form triples, twisted triples in concentric layers, and wrapped by polyester tapes.

Colour code: Black / White / Red, continuously numbered, or identification tapes numbered

Wrapping: Polyester tapes

Collective ScreenAluminum polyester tape with tinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or greyor blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to +50oC during operation

Packing: On non-returnable wooden drums

TECHNICAL INFORMATION

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 17: Special Cables Catalogue

A 9

Conductor size

Number of

triples

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.2 12.1 170 CPC-T1302-JU12G4 7 x 0.43 18.4 0.6 1.2 13.6 2558 7 x 0.43 18.4 0.6 1.3 17.6 430 CPC-T1308-JU12G12 7 x 0.43 18.4 0.6 1.3 20.3 59016 7 x 0.43 18.4 0.6 1.3 22.8 750 CPC-T1316-JU12G20 7 x 0.43 18.4 0.6 1.5 25.6 93024 7 x 0.43 18.4 0.6 1.5 27.6 1090 CPC-T1324-JU12G30 7 x 0.43 18.4 0.6 1.7 33.2 1325

1.3

2 7 x 0.49 14.2 0.6 1.2 12.8 200 CPC-T1302-JU14G4 7 x 0.49 14.2 0.6 1.3 14.4 2958 7 x 0.49 14.2 0.6 1.3 18.8 510 CPC-T1308-JU14G12 7 x 0.49 14.2 0.6 1.3 21.7 71016 7 x 0.49 14.2 0.6 1.5 25.0 930 CPC-T1316-JU14G20 7 x 0.49 14.2 0.6 1.5 27.4 113024 7 x 0.49 14.2 0.6 1.7 29.6 1335 CPC-T1324-JU14G30 7 x 0.49 14.2 0.6 2.0 34.6 1630

1.5

2 7 x 0.53 12.6 0.6 1.2 14.0 230 CPC-T1302-JU15G4 7 x 0.53 12.6 0.6 1.3 15.9 3258 7 x 0.53 12.6 0.6 1.3 20.8 570 CPC-T1308-JU15G12 7 x 0.53 12.6 0.6 1.5 24.8 81016 7 x 0.53 12.6 0.6 1.5 27.9 1120 CPC-T1316-JU15G20 7 x 0.53 12.6 0.6 1.7 30.7 128024 7 x 0.53 12.6 0.6 2.0 33.1 1515 CPC-T1324-JU15G30 7 x 0.53 12.6 0.6 2.2 37.3 1960

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

PVC InsulationMultitriples, Layers, Collective Screen

Page 18: Special Cables Catalogue

A 10

Conductor size

Number of

triples

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 11.7 150 CPC-T1302-JU05B4 7 x 0.3 39.2 0.6 1.2 13.2 205 CPC-T1304-JU05B8 7 x 0.3 39.2 0.6 1.3 17.0 335 CPC-T1308-JU05B

12 7 x 0.3 39.2 0.6 1.3 19.6 450 CPC-T1312-JU05B16 7 x 0.3 39.2 0.6 1.3 22.0 575 CPC-T1316-JU05B20 7 x 0.3 39.2 0.6 1.5 24.7 710 CPC-T1320-JU05B24 7 x 0.3 39.2 0.6 1.5 26.6 835 CPC-T1324-JU05B30 7 x 0.3 39.2 0.6 1.7 29.2 1130 CPC-T1330-JU05B

0.75

2 7 x 0.37 24.6 0.6 1.0 12.5 165 CPC-T1302-JU08B4 7 x 0.37 24.6 0.6 1.2 14.1 235 CPC-T1304-JU08B8 7 x 0.37 24.6 0.6 1.3 18.3 395 CPC-T1308-JU08B

12 7 x 0.37 24.6 0.6 1.3 21.1 550 CPC-T1312-JU08B16 7 x 0.37 24.6 0.6 1.5 24.2 720 CPC-T1316-JU08B20 7 x 0.37 24.6 0.6 1.7 26.7 875 CPC-T1320-JU08B24 7 x 0.37 24.6 0.6 1.7 28.8 1030 CPC-T1324-JU08B30 7 x 0.37 24.6 0.6 2.0 32.4 1325 CPC-T1330-JU08B

Multitriples, Layers, Individual and Collective Screen

TECHNICAL INFORMATION

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form triples, triples screened by aluminum polyester tapes, screened triples twisted in concentric layers, and wrapped by polyester tapes

Colour code: Black / White / Red, continuously numbered, or identification tapes numbered

Wrapping: Polyester tapes

Collective ScreenAluminum polyester tape with tinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or grey or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 19: Special Cables Catalogue

A 11

Conductor size

Number of

Triples

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.2 13.7 195 CPC-T1302-SU12B

4 7 x 0.43 18.4 0.6 1.3 15.5 285 CPC-T1304-SU12B

8 7 x 0.43 18.4 0.6 1.3 20.3 480 CPC-T1308-SU12B

12 7 x 0.43 18.4 0.6 1.5 23.5 665 CPC-T1312-SU12B

16 7 x 0.43 18.4 0.6 1.5 27.1 880 CPC-T1316-SU12B

20 7 x 0.43 18.4 0.6 1.7 29.8 1060 CPC-T1320-SU12B

24 7 x 0.43 18.4 0.6 1.7 32.2 1250 CPC-T1324-SU12B

30 7 x 0.43 18.4 0.6 2.0 35.3 1530 CPC-T1330-SU14B

1.3

2 7 x 0.49 14.2 0.6 1.3 14.4 230 CPC-T1302-SU14B

4 7 x 0.49 14.2 0.6 1.3 16.4 330 CPC-T1304-SU14B

8 7 x 0.49 14.2 0.6 1.3 21.6 565 CPC-T1308-SU14B

12 7 x 0.49 14.2 0.6 1.5 25.6 810 CPC-T1312-SU14B

16 7 x 0.49 14.2 0.6 1.7 28.9 1050 CPC-T1316-SU14B

20 7 x 0.49 14.2 0.6 1.7 31.8 1270 CPC-T1320-SU14B

24 7 x 0.49 14.2 0.6 2.0 35.4 1525 CPC-T1324-SU14B

30 7 x 0.49 14.2 0.6 2.2 37.2 1730 CPC-T1330-SU14B

1.5

2 7 x 0.53 12.6 0.6 1.3 15.2 265 CPC-T1302-SU15B

4 7 x 0.53 12.6 0.6 1.3 17.3 365 CPC-T1304-SU15B

8 7 x 0.53 12.6 0.6 1.3 22.9 610 CPC-T1308-SU15B

12 7 x 0.53 12.6 0.6 1.5 27.2 935 CPC-T1312-SU15B

16 7 x 0.53 12.6 0.6 1.7 30.7 1180 CPC-T1316-SU15B

20 7 x 0.53 12.6 0.6 2.0 33.8 1430 CPC-T1320-SU15B

24 7 x 0.53 12.6 0.6 2.2 37.0 1710 CPC-T1324-SU15B

30 7 x 0.53 12.6 0.6 2.2 40.6 2200 CPC-T1330-SU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

PVC InsulationMultitriples, Layers, Individual and Collective Screen

Page 20: Special Cables Catalogue

A 12

Conductorsize

Number of

pairs

ConductorNominal insulation thickness

steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km

mm mm mm mm Kg/Km -

0.5 1 7 x 0.3 39.2 0.6 0.8 1.3 10.7 219 CPC-T1201-JM05B

0.75 1 7 x 0.37 24.6 0.6 0.8 1.3 11.0 240 CPC-T1201-JM08B

1.0 1 7 x 0.43 18.4 0.6 0.8 1.3 11.4 255 CPC-T1201-JM12B

1.3 1 7 x 0.49 14.2 0.6 0.8 1.4 11.8 275 CPC-T1201-JM14B

1.5 1 7 x 0.53 12.6 0.6 0.8 1.4 12.6 300 CPC-T1201-JM15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Single Pair, Collective Screen , Galvanized Steel Wire Armour

TECHNICAL INFORMATION

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: cores twisted to form a pair and screened by Aluminum Polyester tape with tinned drain wire and wrapped by polyester tapes

Colour code: Black / White

Screen:Collective screen of aluminium polyester tapes withtinned drain wire and wrapped by polyester tapes

Bedding:Polyvinylchloride

Armouring;Galvanized steel wire armour to BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 21: Special Cables Catalogue

A 13

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form a pairs, pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or identification tapes numbered

Screen:Collective screen of aluminium polyester tape with tinned drain wire and wrapped by polester tapes

Bedding:Polyvinylchloride

Armouring;Galvanized steel wire armour to BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

ConductorNominal insulation thickness

steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC

Res. At 20oC

mm2 No. No. x mm

Ohm /Km mm mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 0.8 1.4 13.5 344 CPC-T1202-JM05B4 7 x 0.3 39.2 0.6 0.8 1.4 14.6 395 CPC-T1204-JM05B8 7 x 0.3 39.2 0.6 1.25 1.5 18.7 665 CPC-T1208-JM05B12 7 x 0.3 39.2 0.6 1.25 1.6 20.7 800 CPC-T1212-JM05B16 7 x 0.3 39.2 0.6 1.25 1.6 22.4 920 CPC-T1216-JM05B20 7 x 0.3 39.2 0.6 1.6 1.7 25.3 1220 CPC-T1220-JM05B24 7 x 0.3 39.2 0.6 1.6 1.7 27.2 1370 CPC-T1224-JM05B30 7 x 0.3 39.2 0.6 1.6 1.9 30.1 1710 CPC-T1230-JM05B

0.75

2 7 x 0.37 24.6 0.6 0.8 1.5 15.6 395 CPC-T1202-JM08B4 7 x 0.37 24.6 0.6 0.8 1.5 16.7 440 CPC-T1204-JM08B8 7 x 0.37 24.6 0.6 1.25 1.6 21.5 760 CPC-T1208-JM08B12 7 x 0.37 24.6 0.6 1.25 1.7 24.9 905 CPC-T1212-JM08B16 7 x 0.37 24.6 0.6 1.6 1.7 27.0 1240 CPC-T1216-JM08B20 7 x 0.37 24.6 0.6 1.6 1.8 29.6 1390 CPC-T1220-JM08B24 7 x 0.37 24.6 0.6 1.6 1.9 32.7 1580 CPC-T1224-JM08B30 7 x 0.37 24.6 0.6 1.6 2.0 36.1 1800 CPC-T1230-JM08B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Layers, Collective Screen, Galvanized Steel Wire Armour

TECHNICAL INFORMATION

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 22: Special Cables Catalogue

A 14

Conductor size

Number of

pairs

ConductorNominal insulation thickness

steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC

Res. At 20oC

mm2 No.No. x mm

Ohm /Km

mm mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 0.8 1.5 15.2 440 CPC-T1202-JM12B

4 7 x 0.43 18.4 0.6 0.8 1.5 16.4 490 CPC-T1204-JM12B

8 7 x 0.43 18.4 0.6 1.25 1.6 21.1 840 CPC-T1208-JM12B

12 7 x 0.43 18.4 0.6 1.6 1.7 24.4 1200 CPC-T1212-JM12B

16 7 x 0.43 18.4 0.6 1.6 1.7 26.4 1380 CPC-T1216-JM12B

20 7 x 0.43 18.4 0.6 1.6 1.8 28.8 1580 CPC-T1220-JM12B

24 7 x 0.43 18.4 0.6 1.6 1.9 31.8 1850 CPC-T1224-JM12B

30 7 x 0.43 18.4 0.6 2.0 2.0 35.0 2470 CPC-T1230-JM12B

1.3

2 7 x 0.49 14.2 0.6 0.8 1.5 15.6 460 CPC-T1202-JM14B

4 7 x 0.49 14.2 0.6 1.25 1.5 18.1 630 CPC-T1204-JM14B

8 7 x 0.49 14.2 0.6 1.25 1.6 22.2 900 CPC-T1208-JM14B

12 7 x 0.49 14.2 0.6 1.6 1.7 25.3 1290 CPC-T1212-JM14B

16 7 x 0.49 14.2 0.6 1.6 1.8 28.1 1510 CPC-T1216-JM14B

20 7 x 0.49 14.2 0.6 1.6 1.8 30.4 1660 CPC-T1220-JM14B

24 7 x 0.49 14.2 0.6 1.6 1.9 32.5 1970 CPC-T1224-JM14B

30 7 x 0.49 14.2 0.6 2.0 2.0 35.9 2420 CPC-T1230-JM14B

1.5

2 7 x 0.53 12.6 0.6 1.25 1.6 18.2 620 CPC-T1202-JM15B

4 7 x 0.53 12.6 0.6 1.25 1.6 19.7 745 CPC-T1204-JM15B

8 7 x 0.53 12.6 0.6 1.6 1.7 25.2 1230 CPC-T1208-JM15B

12 7 x 0.53 12.6 0.6 1.6 1.8 28.1 1520 CPC-T1212-JM15B

16 7 x 0.53 12.6 0.6 1.6 1.9 31.3 1865 CPC-T1216-JM15B

20 7 x 0.53 12.6 0.6 1.6 1.9 34.1 2140 CPC-T1220-JM15B

24 7 x 0.53 12.6 0.6 2.0 2.0 38.3 2740 CPC-T1224-JM15B

30 7 x 0.53 12.6 0.6 2.0 2.0 41.6 3340 CPC-T1230-JM15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

PVC InsulationMultipairs, Layers, Collective Screen, Galvanized Steel Wire Armour

Page 23: Special Cables Catalogue

A 15

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride TI1 to BS 6746

Assembly: Cores twisted to form a pairs, pairs screened by aluminium polyester tapes, screened pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or identification tapes numbered

Screen:Collective screen of aluminum polyester tapes withtinned drain wire and wrapped by polyester tapes

Bedding:Polyvinylchloride

Armouring;Galvanized steel wire armour to BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

ConductorNominal insulation thickness

steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km

mm mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 0.8 1.4 14.7 390 CPC-T1202-SM05B

4 7 x 0.3 39.2 0.6 0.8 1.5 15.9 450 CPC-T1204-SM05B

8 7 x 0.3 39.2 0.6 1.25 1.6 20.4 760 CPC-T1208-SM05B

12 7 x 0.3 39.2 0.6 1.25 1.6 22.7 940 CPC-T1212-SM05B

16 7 x 0.3 39.2 0.6 1.6 1.7 25.5 1260 CPC-T1216-SM05B

20 7 x 0.3 39.2 0.6 1.6 1.8 27.8 1420 CPC-T1220-SM05B

24 7 x 0.3 39.2 0.6 1.6 1.9 30.7 1660 CPC-T1224-SM05B

30 7 x 0.3 39.2 0.6 1.6 1.9 33.0 2015 CPC-T1230-SM08B

0.75

2 7 x 0.37 24.6 0.6 0.8 1.5 15.6 440 CPC-T1202-SM08B

4 7 x 0.37 24.6 0.6 0.8 1.5 16.7 490 CPC-T1204-SM08B

8 7 x 0.37 24.6 0.6 1.25 1.6 21.5 850 CPC-T1208-SM08B

12 7 x 0.37 24.6 0.6 1.6 1.7 24.9 1210 CPC-T1212-SM08B

16 7 x 0.37 24.6 0.6 1.6 1.7 27.0 1390 CPC-T1216-SM08B

20 7 x 0.37 24.6 0.6 1.6 1.8 29.6 1620 CPC-T1220-SM08B

24 7 x 0.37 24.6 0.6 1.6 1.9 32.7 1880 CPC-T1224-SM08B

30 7 x 0.37 24.6 0.6 2.0 2.0 36.1 2590 CPC-T1230-SM08B

Individual and Collective Screen, Galvanized Steel Wire Armour

TECHNICAL INFORMATION

PVC Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 24: Special Cables Catalogue

A 16

Conductor size

Number of

pairs

ConductorNominal insulation thickness

steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.25 1.5 17.2 570 CPC-T1202-SM12B

4 7 x 0.43 18.4 0.6 1.25 1.5 18.6 660 CPC-T1204-SM12B

8 7 x 0.43 18.4 0.6 1.25 1.7 23.1 960 CPC-T1208-SM12B

12 7 x 0.43 18.4 0.6 1.6 1.7 26.3 1335 CPC-T1212-SM12B

16 7 x 0.43 18.4 0.6 1.6 1.8 28.7 1570 CPC-T1216-SM12B

20 7 x 0.43 18.4 0.6 1.6 1.9 32.0 1870 CPC-T1220-SM12B

24 7 x 0.43 18.4 0.6 1.6 1.9 34.6 2120 CPC-T1224-SM12B

30 7 x 0.43 18.4 0.6 2.0 2.1 38.3 2830 CPC-T1230-SM12B

1.3

2 7 x 0.49 14.2 0.6 1.25 1.5 18.2 680 CPC-T1202-SM14B

4 7 x 0.49 14.2 0.6 1.25 1.6 20.3 850 CPC-T1204-SM14B

8 7 x 0.49 14.2 0.6 1.6 1.7 26.4 1350 CPC-T1208-SM14B

12 7 x 0.49 14.2 0.6 1.6 1.8 29.5 1560 CPC-T1212-SM14B

16 7 x 0.49 14.2 0.6 1.6 1.9 32.0 1860 CPC-T1216-SM14B

20 7 x 0.49 14.2 0.6 2.0 2.0 36.6 2300 CPC-T1220-SM14B

24 7 x 0.49 14.2 0.6 2.0 2.1 39.3 3200 CPC-T1224-SM14B

30 7 x 0.49 14.2 0.6 2.0 2.2 44.2 3900 CPC-T1230-SM14B

1.5

2 7 x 0.53 12.6 0.6 1.25 1.7 22.8 1000 CPC-T1202-SM15B

4 7 x 0.53 12.6 0.6 1.25 1.7 24.1 1130 CPC-T1204-SM15B

8 7 x 0.53 12.6 0.6 1.6 1.8 30.4 1690 CPC-T1208-SM15B

12 7 x 0.53 12.6 0.6 1.6 1.9 34.1 2130 CPC-T1212-SM15B

16 7 x 0.53 12.6 0.6 1.6 2.0 38.7 2280 CPC-T1216-SM15B

20 7 x 0.53 12.6 0.6 2.0 2.2 43.3 3430 CPC-T1220-SM15B

24 7 x 0.53 12.6 0.6 2.0 2.3 48.5 4420 CPC-T1224-SM15B

30 7 x 0.53 12.6 0.6 2.5 2.5 52.8 5390 CPC-T1230-SM15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Layers, Individual and Collective Screen, Galvanized Steel Wire Armour

TECHNICAL INFORMATION

PVC Insulation

Page 25: Special Cables Catalogue

A 17

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Twisted in Bundles, Collective Screen

Conductor Size

Number of Pairs

ConductorNominal Insulation Thickness

Nominal Sheath

Thickness

Approximate Overall

Diameter

Approximate Net Weight

Cable CodeNo. x dia

Max. DC Res.

At 20º

mm2 No. No. x mm

Ohm/Km mm mm mm Kg/Km -

0.5

2 7 X 0.3 39.2 0.6 1.0 6.9 65 CGC-T1202-JU05BQ

4 7 X 0.3 39.2 0.6 1.0 9.1 85 CGC-T1204-JU05BQ

8 7 X 0.3 39.2 0.6 1.0 11.1 140 CGC-T1208-JU05BQ

12 7 X 0.3 39.2 0.6 1.2 13.4 195 CGC-T1212-JU05BQ

16 7 X 0.3 39.2 0.6 1.2 15.1 260 CGC-T1216-JU05BQ

20 7 X 0.3 39.2 0.6 1.2 16.5 340 CGC-T1220-JU05BQ

24 7 X 0.3 39.2 0.6 1.4 18.3 430 CGC-T1224-JU05BQ

2 7 X 0.43 18.4 0.6 1.0 8.9 85 CGC-T1202-JU12BQ

1.0

4 7 X 0.43 18.4 0.6 1.0 12.0 140 CGC-T1204-JU12BQ

8 7 X 0.43 18.4 0.6 1.2 16.0 165 CGC-T1208-JU12BQ

12 7 X 0.43 18.4 0.6 1.4 20.0 390 CGC-T1212-JU12BQ

16 7 X 0.43 18.4 0.6 1.4 22.0 500 CGC-T1216-JU12BQ

20 7 X 0.43 18.4 0.6 1.4 24.0 640 CGC-T1220-JU12BQ

24 7 X 0.43 18.4 0.6 1.6 26.0 780 CGC-T1224-JU12BQ

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene type 03 to BS 6234

Assembly: Cores twisted to form pairs, 4 pairstwisted to form a bundle , bundles twisted in concentric layers, 2 pairs twisted as star quad

Colour code: One Pair : Blue / RedTwo Pairs : Grey / yellowThree Pairs : Green / BrownFour Pairs : White / BlackBundles are identified by coloured polyester tapes

Wrapping: Polyester tapes

Collective Screen:Collective screen of aluminum polyester tapes withtinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colourblack or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

TECHNICAL INFORMATION

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

225

V

Page 26: Special Cables Catalogue

A 18

Cable SizeConductor Nominal

insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. x mm Ohm /Km mm mm mm Kg/Km -

1 x 2 x 0.5 7 x 0.3 39.2 0.6 0.8 5.3 40 CGC-T1201-JU05B

1 x 3 x 0.5 7 x 0.3 39.2 0.6 0.8 5.6 50 CGC-T1301- JU05B

1 x 2 x 0.75 7 x 0.37 24.6 0.6 0.8 6.4 56 CGC-T1201- JU08B

1 x 3 x 0.75 7 x 0.37 24.6 0.6 0.8 6.7 65 CGC-T1301- JU08B

1 x 2 x 1.0 7 x 0.43 18.4 0.6 0.8 6.8 66 CGC-T1201- JU12B

1 x 3 x 1.0 7 x 0.43 18.4 0.6 0.8 7.1 75 CGC-T1301- JU12B

1 x 2 x 1.3 7 x 0.49 14.2 0.6 0.8 7.1 75 CGC-T1201- JU14B

1 x 3 x 1.3 7 x 0.49 14.2 0.6 0.8 7.4 85 CGC-T1301- JU14B

1 x 2 x 1.5 7 x 0.53 12.6 0.6 0.8 7.6 85 CGC-T1201- JU15B

1 x 3 x 1.5 7 x 0.53 12.6 0.6 0.8 8.0 104 CGC-T1301- JU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Single Pair or Triple, Collective Screen

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-2

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene type 03 to BS 6234

Assembly: Cores twisted to form a pair or triple and wrapped by polyester tape

Colour code: Pair: Black / WhiteTriple: Black / White / Red

Wrapping: Polyester tapes

Collective Screen:Collective screen of aluminum polyester tapes withtinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colourblack or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to +50oC during operation

Packing: On non-returnable wooden drums

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 27: Special Cables Catalogue

A 19

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogueand digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene TI1 to BS 6746

Assembly: Cores twisted to form a pairs,pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes withtinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 9.3 98 CGC-T1202-JU05B

4 7 x 0.3 39.2 0.6 1.0 10.0 112 CGC-T1204-JU05B

8 7 x 0.3 39.2 0.6 1.2 13.2 189 CGC-T1208-JU05B

12 7 x 0.3 39.2 0.6 1.2 15.0 252 CGC-T1212-JU05B

16 7 x 0.3 39.2 0.6 1.2 16.7 318 CGC-T1216-JU05B

20 7 x 0.3 39.2 0.6 1.3 18.7 387 CGC-T1220-JU05B

24 7 x 0.3 39.2 0.6 1.3 20.6 452 CGC-T1224-JU05B

30 7 x 0.3 39.2 0.6 1.5 23.3 640 CGC-T1230-JU08B

0.75

2 7 x 0.37 24.6 0.6 1.0 10.1 120 CGC-T1202-JU08B

4 7 x 0.37 24.6 0.6 1.0 10.8 134 CGC-T1204-JU08B

8 7 x 0.37 24.6 0.6 1.2 14.3 232 CGC-T1208-JU08B

12 7 x 0.37 24.6 0.6 1.2 16.3 315 CGC-T1212-JU08B

16 7 x 0.37 24.6 0.6 1.3 18.3 410 CGC-T1216-JU08B

20 7 x 0.37 24.6 0.6 1.3 20.3 490 CGC-T1220-JU08B

24 7 x 0.37 24.6 0.6 1.3 22.5 575 CGC-T1224-JU08B

30 7 x 0.37 24.6 0.6 1.5 24.3 683 CGC-T1230-JU08B

Multipairs, Layers, Collective Screen

TECHNICAL INFORMATION

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 28: Special Cables Catalogue

A 20

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.0 10.8 138 CGC-T1202-JU12B

4 7 x 0.43 18.4 0.6 1.0 11.6 160 CGC-T1204-JU12B

8 7 x 0.43 18.4 0.6 1.2 15.4 282 CGC-T1208- JU12B

12 7 x 0.43 18.4 0.6 1.3 17.8 396 CGC-T1212-JU12B

16 7 x 0.43 18.4 0.6 1.3 19.8 504 CGC-T1216- JU12B

20 7 x 0.43 18.4 0.6 1.3 22.0 608 CGC-T1220-JU12B

24 7 x 0.43 18.4 0.6 1.5 24.8 745 CGC-T1224-JU12B

30 7 x 0.43 18.4 0.6 1.7 27.5 1005 CGC-T1230-JU12B

1.3

2 7 x 0.49 14.2 0.6 1.0 11.7 152 CGC-T1202-JU14B

4 7 x 0.49 14.2 0.6 1.2 13.3 215 CGC-T1204-JU14B

8 7 x 0.49 14.2 0.6 1.3 16.5 360 CGC-T1208- JU14B

12 7 x 0.49 14.2 0.6 1.3 19.3 385 CGC-T1212-JU14B

16 7 x 0.49 14.2 0.6 1.3 21.7 575 CGC-T1216-JU14B

20 7 x 0.49 14.2 0.6 1.5 24.2 780 CGC-T1220-JU14B

24 7 x 0.49 14.2 0.6 1.7 26.3 930 CGC-T1224-JU14B

30 7 x 0.49 14.2 0.6 1.7 31.0 1280 CGC-T1230-JU14B

1.5

2 7 x 0.53 12.6 0.6 1.2 12.9 194 CGC-T1202-JU15B

4 7 x 0.53 12.6 0.6 1.2 14.1 233 CGC-T1204-JU15B

8 7 x 0.53 12.6 0.6 1.3 18.6 405 CGC-T1208-JU15B

12 7 x 0.53 12.6 0.6 1.3 21.3 564 CGC-T1212-JU15B

16 7 x 0.53 12.6 0.6 1.5 24.3 797 CGC-T1216-JU15B

20 7 x 0.53 12.6 0.6 1.5 27.1 912 CGC-T1220-JU15B

24 7 x 0.53 12.6 0.6 1.7 30.3 1104 CGC-T1224-JU15B

30 7 x 0.53 12.6 0.6 2.0 33.7 1507 CGC-T1230-JU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

PE InsulationMultipairs, Layers, Collective Screen

Page 29: Special Cables Catalogue

A 21

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded plain annealed copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form a pairs, pairs screened by Aluminium Polyester tapes, Screened pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or identification tapes numbered

Screen: Collective screen of Aluminum Polyester tapeswith tinned drain wire and wrapped by polyestertapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 10.3 118 CGC-T1202-SU05B

4 7 x 0.3 39.2 0.6 1.0 11.1 136 CGC-T1204-SU05B

8 7 x 0.3 39.2 0.6 1.2 14.7 234 CGC-T1208-SU05B

12 7 x 0.3 39.2 0.6 1.3 17.0 325 CGC-T1212-SU05B

16 7 x 0.3 39.2 0.6 1.3 18.9 413 CGC-T1216-SU05B

20 7 x 0.3 39.2 0.6 1.3 21.0 495 CGC-T1220-SU05B

24 7 x 0.3 39.2 0.6 1.5 23.7 606 CGC-T1224-SU05B

30 7 x 0.3 39.2 0.6 1.5 26.3 822 CGC-T1230-SU08B

0.75

2 7 x 0.37 24.6 0.6 1.0 11.2 145 CGC-T1202-SU08B

4 7 x 0.37 24.6 0.6 1.0 11.9 159 CGC-T1204-SU08B

8 7 x 0.37 24.6 0.6 1.2 15.8 280 CGC-T1208-SU08B

12 7 x 0.37 24.6 0.6 1.3 18.3 390 CGC-T1212-SU08B

16 7 x 0.37 24.6 0.6 1.3 20.4 500 CGC-T1216-SU08B

20 7 x 0.37 24.6 0.6 1.3 22.8 602 CGC-T1220-SU08B

24 7 x 0.37 24.6 0.6 1.5 25.7 736 CGC-T1224-SU08B

30 7 x 0.37 24.6 0.6 1.7 26.4 864 CGC-T1230-SU08B

Multipairs, Layers, Individual and Collective Screen

TECHNICAL INFORMATION

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 30: Special Cables Catalogue

A 22

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.2 12.2 170 CGC-T1202-SU12B4 7 x 0.43 18.4 0.6 1.2 13.1 195 CGC-T1204- SU12B8 7 x 0.43 18.4 0.6 1.3 17.2 340 CGC-T1208- SU12B

12 7 x 0.43 18.4 0.6 1.3 19.7 465 CGC-T1212- SU12B16 7 x 0.43 18.4 0.6 1.3 21.9 600 CGC-T1216- SU12B20 7 x 0.43 18.4 0.6 1.5 25.0 645 CGC-T1220- SU12B24 7 x 0.43 18.4 0.6 1.5 27.6 880 CGC-T1224- SU12B30 7 x 0.43 18.4 0.6 1.7 30.5 1195 CGC-T1230- SU12B

1.3

2 7 x 0.49 14.2 0.6 1.2 12.8 180 CGC-T1202- SU14B4 7 x 0.49 14.2 0.6 1.3 14.0 230 CGC-T1204- SU14B8 7 x 0.49 14.2 0.6 1.3 18.2 410 CGC-T1208- SU14B

12 7 x 0.49 14.2 0.6 1.3 20.3 590 CGC-T1212- SU14B16 7 x 0.49 14.2 0.6 1.5 23.3 760 CGC-T1216- SU14B20 7 x 0.49 14.2 0.6 1.5 27.0 850 CGC-T1220- SU14B24 7 x 0.49 14.2 0.6 1.7 31.2 1065 CGC-T1224- SU14B30 7 x 0.49 14.2 0.6 2.0 34.5 1400 CGC-T1230- SU14B

1.5

2 7 x 0.53 12.6 0.6 1.2 14.1 220 CGC-T1202- SU15B4 7 x 0.53 12.6 0.6 1.2 15.4 263 CGC-T1204- SU15B8 7 x 0.53 12.6 0.6 1.3 20.3 460 CGC-T1208- SU15B

12 7 x 0.53 12.6 0.6 1.5 24.0 670 CGC-T1212- SU15B

16 7 x 0.53 12.6 0.6 1.5 26.7 865 CGC-T1216- SU15B

20 7 x 0.53 12.6 0.6 1.7 30.2 1070 CGC-T1220- SU15B24 7 x 0.53 12.6 0.6 2.0 34.0 1300 CGC-T1224- SU15B30 7 x 0.53 12.6 0.6 2.2 37.4 1750 CGC-T1230- SU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Layers, Individual and Collective Screen

TECHNICAL INFORMATION

PE Insulation

Page 31: Special Cables Catalogue

A 23

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded plain annealed copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form a triples, triples twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White/ Red continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrappedby polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

Triples

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.Max. DC Res.

At 20oC

mm2 No.No. x mm

Ohm/Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 10.1 115 CGC-T1302-JU05B

4 7 x 0.3 39.2 0.6 1.0 10.8 135 CGC-T1304-JU05B

8 7 x 0.3 39.2 0.6 1.2 14.6 230 CGC-T1308-JU05B

12 7 x 0.3 39.2 0.6 1.3 16.5 330 CGC-T1312-JU05B

16 7 x 0.3 39.2 0.6 1.3 18.7 420 CGC-T1316-JU05B

20 7 x 0.3 39.2 0.6 1.3 21.2 535 CGC-T1320-JU05B

24 7 x 0.3 39.2 0.6 1.5 24.0 635 CGC-T1324-JU05B

30 7 x 0.3 39.2 0.6 1.5 27.7 960 CGC-T1330-JU08B

0.75

2 7 x 0.37 24.6 0.6 1.0 10.9 130 CGC-T1302-JU08B

4 7 x 0.37 24.6 0.6 1.0 11.8 175 CGC-T1304-JU08B

8 7 x 0.37 24.6 0.6 1.3 15.9 355 CGC-T1308-JU08B

12 7 x 0.37 24.6 0.6 1.3 17.9 415 CGC-T1312-JU08B

16 7 x 0.37 24.6 0.6 1.3 20.2 515 CGC-T1316-JU08B

20 7 x 0.37 24.6 0.6 1.5 23.8 645 CGC-T1320-JU08B

24 7 x 0.37 24.6 0.6 1.5 26.0 955 CGC-T1324-JU08B

30 7 x 0.37 24.6 0.6 1.7 30.0 1150 CGC-T1330-JU08B

Multitriples, Layers, Collective Screen

TECHNICAL INFORMATION

PE Insulation

UiC

Els

ew

ed

y in

stru

me

nta

tion

Ca

ble

s 30

0 V

Page 32: Special Cables Catalogue

A 24

Conductor size

Number of

Triples

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.4 0.6 1.2 12.1 160 CGC-T1302-JU12B

4 7 x 0.43 18.4 0.6 1.2 13.6 240 CGC-T1304- JU12B

8 7 x 0.43 18.4 0.6 1.3 17.6 420 CGC-T1308- JU12B

12 7 x 0.43 18.4 0.6 1.3 20.3 570 CGC-T1312- JU12B

16 7 x 0.43 18.4 0.6 1.3 22.8 730 CGC-T1316- JU12B

20 7 x 0.43 18.4 0.6 1.5 25.6 900 CGC-T1320- JU12B

24 7 x 0.43 18.4 0.6 1.5 27.6 1050 CGC-T1324- JU12B

30 7 x 0.43 18.4 0.6 1.7 33.2 1295 CGC-T1330- JU12B

1.3

2 7 x 0.49 14.2 0.6 1.2 12.8 190 CGC-T1302- JU14B

4 7 x 0.49 14.2 0.6 1.3 14.4 275 CGC-T1304- JU14B

8 7 x 0.49 14.2 0.6 1.3 18.8 485 CGC-T1308- JU14B

12 7 x 0.49 14.2 0.6 1.3 21.7 685 CGC-T1312- JU14B

16 7 x 0.49 14.2 0.6 1.5 25.0 910 CGC-T1316- JU14B

20 7 x 0.49 14.2 0.6 1.5 27.4 1100 CGC-T1320- JU14B

24 7 x 0.49 14.2 0.6 1.7 29.6 1300 CGC-T1324- JU14B

30 7 x 0.49 14.2 0.6 2.0 35.6 1590 CGC-T1330- JU14B

1.5

2 7 x 0.53 12.6 0.6 1.2 14.0 220 CGC-T1302- JU15B

4 7 x 0.53 12.6 0.6 1.3 15.9 300 CGC-T1304- JU15B

8 7 x 0.53 12.6 0.6 1.3 20.8 545 CGC-T1308- JU15B

12 7 x 0.53 12.6 0.6 1.5 24.8 785 CGC-T1312- JU15B

16 7 x 0.53 12.6 0.6 1.5 27.9 1100 CGC-T1316- JU15B

20 7 x 0.53 12.6 0.6 1.7 30.7 1250 CGC-T1320- JU15B

24 7 x 0.53 12.6 0.6 2.0 33.1 1460 CGC-T1324- JU15B

30 7 x 0.53 12.6 0.6 2.2 37.3 1920 CGC-T1330- JU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

PE InsulationMultitriples, Layers, Collective Screen

Page 33: Special Cables Catalogue

A 25

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form triples, triples screened by aluminium by polyester tapes, screened triples Twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White/ Red, continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

triples

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 11.7 145 CGC-T1302-SU05B

4 7 x 0.3 39.2 0.6 1.2 13.2 195 CGC-T1304-SU05B

8 7 x 0.3 39.2 0.6 1.3 17.0 320 CGC-T1308-SU05B

12 7 x 0.3 39.2 0.6 1.3 19.6 430 CGC-T1312-SU05B

16 7 x 0.3 39.2 0.6 1.3 22.0 560 CGC-T1316-SU05B

20 7 x 0.3 39.2 0.6 1.5 24.7 680 CGC-T1320-SU05B

24 7 x 0.3 39.2 0.6 1.5 26.6 800 CGC-T1324-SU05B

30 7 x 0.3 39.2 0.6 1.7 29.2 1100 CGC-T1330-SU08B

0.75

2 7 x 0.37 24.6 0.6 1.0 12.5 160 CGC-T1302-SU08B

4 7 x 0.37 24.6 0.6 1.2 14.1 220 CGC-T1304-SU08B

8 7 x 0.37 24.6 0.6 1.3 18.3 380 CGC-T1308-SU08B

12 7 x 0.37 24.6 0.6 1.3 21.1 530 CGC-T1312-SU08B

16 7 x 0.37 24.6 0.6 1.5 24.2 690 CGC-T1316-SU08B

20 7 x 0.37 24.6 0.6 1.7 26.7 845 CGC-T1320-SU08B

24 7 x 0.37 24.6 0.6 1.7 28.8 1000 CGC-T1324-SU08B

30 7 x 0.37 24.6 0.6 2.0 32.4 1300 CGC-T1330-SU08B

Multitriples, Layers, Individual and Collective Screen

TECHNICAL INFORMATION

PE Insulation

UiC

Els

ew

ed

y in

stru

me

nta

tion

Ca

ble

s 30

0 V

Page 34: Special Cables Catalogue

A 26

TECHNICAL INFORMATION

Conductor Size

Number of Triples

ConductorNominal Insulation Thickness

Nominal Sheath

Thickness

Approximate Overall

Diameter

Approximate Net Weight

Cable CodeNo. x dia

Max. DC Res.

At 20º

mm2 .No No. xmm

Ohm/Km

mm mm mm Kg/Km -

1.0

2 7 X 0.43 18.4 0.6 1.2 13.7 185 CGC-T1302-SU12B

4 7 X 0.43 18.4 0.6 1.3 15.5 270 CGC-T1304-SU12B

8 7 X 0.43 18.4 0.6 1.3 20.3 465 CGC-T1308-SU12B

12 7 X 0.43 18.4 0.6 1.3 23.5 650 CGC-T1312-SU12B

16 7 X 0.43 18.4 0.6 1.5 27.1 850 CGC-T1316-SU12B

20 7 X 0.43 18.4 0.6 1.7 29.8 1030 CGC-T1320-SU12B

24 7 X 0.43 18.4 0.6 1.7 32.2 1220 CGC-T1324-SU12B

30 7 X 0.43 18.4 0.6 2.0 35.3 1480 CGC-T1330-SU12B

1.3

2 7 X 0.49 14.2 0.6 1.3 14.4 220 CGC-T1302-SU14B

4 7 X 0.49 14.2 0.6 1.3 16.4 310 CGC-T1304-SU14B

8 7 X 0.49 14.2 0.6 1.3 21.6 540 CGC-T1308-SU14B

12 7 X 0.49 14.2 0.6 1.5 25.6 780 CGC-T1312-SU14B

16 7 X 0.49 14.2 0.6 1.7 28.9 1010 CGC-T1316-SU14B

20 7 X 0.49 14.2 0.6 1.7 31.8 1190 CGC-T1320-SU14B

24 7 X 0.49 14.2 0.6 2.0 35.4 1475 CGC-T1324-SU14B

30 7 X 0.49 14.2 0.6 2.0 37.2 1680 CGC-T1330-SU14B

1.5

2 7 X 0.53 12.6 0.6 1.3 15.2 255 CGC-T1302-SU15B

4 7 X 0.53 12.6 0.6 1.3 17.3 340 CGC-T1304-SU15B

8 7 X 0.53 12.6 0.6 1.3 22.9 570 CGC-T1308-SU15B

12 7 X 0.53 12.6 0.6 1.5 27.2 900 CGC-T1312-SU15B

16 7 X 0.53 12.6 0.6 1.7 30.7 1150 CGC-T1316-SU15B

20 7 X 0.53 12.6 0.6 2.0 33.8 1400 CGC-T1320-SU15B

24 7 X 0.53 12.6 0.6 2.2 37.0 1660 CGC-T1324-SU15B

30 7 X 0.53 12.6 0.6 2.2 40.6 2100 CGC-T1330-SU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

PE InsulationMultitriples, Layers, Individual and Collective Screen

Page 35: Special Cables Catalogue

A 27

Application: These cables are used in the chemical and petrochemical industries for the transmissionof analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form a pair or triple and screened by aluminium polyester tape with tinned drain wire and wrapped by polyester tapes

Colour code: Black / White

Bedding: Polyvinylchloride

Armouring: Galvanized steel wire armour to BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Single Pair, Collective Screen, Galvanized Steel Wire Armour

TECHNICAL INFORMATION

ConductorSize

Number of

Pairs

Conductor Nominal

InsulationThickness

Steel wirediameter

Nominal Sheaththickness

Approximate Overalldiameter

Approximate Net

WeightUIC- Code No. x

dia

Max. DC Res.At 20º

mm2 No. No. xmm

Ohm/Km

mm mm mm mm Kg/Km -

0.5 1 7 x 0.3 39.2 0.6 0.8 1.3 10.3 210 CGC-T1201-JM05B

0.75 1 7 x 0.37 24.6 0.6 0.8 1.3 11.0 230 CGC-T1201-JM08B

1.0 1 7 x 0.43 18.4 0.6 0.8 1.3 11.4 240 CGC-T1201-JM12B

1.3 1 7 x 0.49 14.2 0.6 0.8 1.4 11.8 260 CGC-T1201-JM14B

1.5 1 7 x 0.53 12.6 0.6 0.8 1.4 12.6 290 CGC-T1201-JM15B

PE Insulation

UiC

Els

ew

ed

y in

stru

me

nta

tion

Ca

ble

s 30

0 V

Page 36: Special Cables Catalogue

A 28

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damagesare expected to occur.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form pairs, pairs twistedin concentric layers and wrapped by polyester tapes

Colour code: Black / White, continuously numbered,or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes

Bedding:Polyvinylchloride

Armouring:Galvanized steel wire armour BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Steel wire

diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 0.8 1.4 13.5 330 CGC-T1202-JM05B

4 7 x 0.3 39.2 0.6 0.8 1.4 14.6 370 CGC-T1204-JM05B

8 7 x 0.3 39.2 0.6 1.25 1.5 18.7 630 CGC-T1208- JM05B

12 7 x 0.3 39.2 0.6 1.25 1.6 20.7 770 CGC-T1212- JM05B

16 7 x 0.3 39.2 0.6 1.25 1.6 22.4 880 CGC-T1216- JM05B

20 7 x 0.3 39.2 0.6 1.6 1.7 25.3 1170 CGC-T1220- JM05B

24 7 x 0.3 39.2 0.6 1.6 1.7 27.2 1340 CGC-T1224- JM05B

30 7 x 0.3 39.2 0.6 1.6 1.9 30.1 1660 CGC-T1230- JM05B

0.75

2 7 x 0.37 24.6 0.6 0.8 1.5 15.6 370 CGC-T1202- JM08B

4 7 x 0.37 24.6 0.6 0.8 1.5 16.7 410 CGC-T1204- JM08B

8 7 x 0.37 24.6 0.6 1.25 1.6 21.5 720 CGC-T1208- JM08B

12 7 x 0.37 24.6 0.6 1.25 1.7 24.9 880 CGC-T1212- JM08B

16 7 x 0.37 24.6 0.6 1.6 1.7 27.0 1200 CGC-T1216- JM08B

20 7 x 0.37 24.6 0.6 1.6 1.8 29.6 1350 CGC-T1220- JM08B

24 7 x 0.37 24.6 0.6 1.6 1.9 32.7 1530 CGC-T1224- JM08B

30 7 x 0.37 24.6 0.6 1.6 2.0 36.1 1730 CGC-T1230- JM08B

Multipairs, Layers, Collective Screen, Galvanized Steel Wire Armour

TECHNICAL INFORMATION

PE Insulation

UiC

Els

ew

ed

y in

stru

me

nta

tion

Ca

ble

s 30

0 V

Page 37: Special Cables Catalogue

A 29

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Layers, Collective Screen Galvanized Steel Wire Armour

TECHNICAL INFORMATION

ConductorSize

Numberof

Pairs

Conductor Nominal

InsulationThickness

Steel wirediameter

Nominal Sheaththickness

Approximate Overalldiameter

ApproximateNet

WeightUIC- Code No. x

dia

Max. DC Res.At 20º

mm2 No. No. xmm

Ohm/Km

mm mm mm mm Kg/Km -

1.0

2 7 X 0.43 18.4 0.6 0.8 1.5 15.2 420 CGC-T1202-JM12B

4 7 X 0.43 18.4 0.6 0.8 1.5 16.4 470 CGC-T1204-JM12B

8 7 X 0.43 18.4 0.6 1.25 1.6 21.1 820 CGC-T1208-JM12B

12 7 X 0.43 18.4 0.6 1.6 1.7 24.4 1170 CGC-T1212-JM12B

16 7 X 0.43 18.4 0.6 1.6 1.7 26.4 1350 CGC-T1216-JM12B

20 7 X 0.43 18.4 0.6 1.6 1.8 28.8 1530 CGC-T1220-JM12B

24 7 X 0.43 18.4 0.6 1.6 1.9 31.8 1760 CGC-T1224-JM12B

30 7 X 0.43 18.4 0.6 2.0 2.0 35.0 2390 CGC-T1230-JM12B

1.3

2 7 X 0.49 14.2 0.6 0.8 1.5 15.6 430 CGC-T1202-JM14B4 7 X 0.49 14.2 0.6 1.25 1.5 18.1 600 CGC-T1204-JM14B

8 7 X 0.49 14.2 0.6 1.25 1.6 22.2 860 CGC-T1208-JM14B

12 7 X 0.49 14.2 0.6 1.6 1.7 25.3 1240 CGC-T1212-JM14B

16 7 X 0.49 14.2 0.6 1.6 1.8 28.1 1460 CGC-T1216-JM14B

20 7 X 0.49 14.2 0.6 1.6 1.8 30.4 1600 CGC-T1220-JM14B

24 7 X 0.49 14.2 0.6 1.6 1.9 32.5 1900 CGC-T1224-JM14B

30 7 X 0.49 14.2 0.6 2.0 2.0 35.9 2850 CGC-T1230-JM14B

1.5

2 7 X 0.53 12.6 0.6 1.25 1.6 18.2 600 CGC-T1202-JM15B

4 7 X 0.53 12.6 0.6 1.25 1.6 19.7 705 CGC-T1204-JM15B

8 7 X 0.53 12.6 0.6 1.6 1.7 25.2 1190 CGC-T1208-JM15B

12 7 X 0.53 12.6 0.6 1.6 1.8 28.1 1460 CGC-T1212-JM15B

16 7 X 0.53 12.6 0.6 1.6 1.9 31.3 1800 CGC-T1216-JM15B

20 7 X 0.53 12.6 0.6 1.6 1.9 34.1 2090 CGC-T1220-JM15B

24 7 X 0.53 12.6 0.6 2.0 2.0 38.3 2680 CGC-T1224-JM15B

30 7 X 0.53 12.6 0.6 2.0 2.2 41.6 3220 CGC-T1230-JM15B

PE Insulation

Page 38: Special Cables Catalogue

A 30

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form pairs, pairs screened by aluminium polyester tapes, screened pairs twisted in concentric layer and wrapped by polyester tapes

Colour code: Black / White, continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes.

Bedding:Polyvinylchloride

Armouring:Galvanized steel wire armour to BS 1442

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 10x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Steel wire diameter

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC

Res. At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 0.8 1.4 14.7 315 CGC-T1202-JM05B

4 7 x 0.3 39.2 0.6 0.8 1.5 15.9 410 CGC-T1204-JM05B

8 7 x 0.3 39.2 0.6 1.25 1.6 20.4 690 CGC-T1208- JM05B

12 7 x 0.3 39.2 0.6 1.25 1.6 22.7 820 CGC-T1212- JM05B

16 7 x 0.3 39.2 0.6 1.6 1.7 25.5 1160 CGC-T1216- JM05B

20 7 x 0.3 39.2 0.6 1.6 1.8 27.8 1320 CGC-T1220- JM05B

24 7 x 0.3 39.2 0.6 1.6 1.9 30.7 1580 CGC-T1224- JM05B

30 7 x 0.3 39.2 0.6 1.6 1.9 33.0 1930 CGC-T1230- JM05B

0.75

2 7 x 0.37 24.6 0.6 0.8 1.5 15.6 355 CGC-T1202- JM08B

4 7 x 0.37 24.6 0.6 0.8 1.5 16.7 450 CGC-T1204- JM08B

8 7 x 0.37 24.6 0.6 1.25 1.6 21.5 755 CGC-T1208- JM08B

12 7 x 0.37 24.6 0.6 1.6 1.7 24.9 1110 CGC-T1212- JM08B

16 7 x 0.37 24.6 0.6 1.6 1.7 27.0 1260 CGC-T1216- JM08B

20 7 x 0.37 24.6 0.6 1.6 1.8 29.6 1540 CGC-T1220- JM08B

24 7 x 0.37 24.6 0.6 1.6 1.9 32.7 1760 CGC-T1224- JM08B

30 7 x 0.37 24.6 0.6 2.0 2.0 36.1 2470 CGC-T1230- JM08B

TECHNICAL INFORMATION

Multipairs, Layers, Individual and Collective Screen, Galvanized Steel Wire ArmourPE Insulation

UiC

Els

ew

ed

y in

stru

me

nta

tion

Ca

ble

s 30

0 V

Page 39: Special Cables Catalogue

A 31

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor Size

Number of

Pairs

ConductorNominal Insulation Thickness

Steel wire diameter

Nominal Sheath

thickness

Approximate Overall

diameter

Approximate Net

WeightUIC- CodeNo. x

dia

Max. DC Res. At

20º

mm2 No.No. x mm

Ohm/Km mm mm mm mm Kg/Km -

1.0

2 7 X 0.43 18.4 0.6 1.25 1.5 17.2 500 CGC-T1202-SM12B

4 7 X 0.43 18.4 0.6 1.25 1.5 18.6 610 CGC-T1204-SM12B

8 7 X 0.43 18.4 0.6 1.25 1.7 23.1 920 CGC-T1208-SM12B

12 7 X 0.43 18.4 0.6 1.6 1.7 26.3 1290 CGC-T1212-SM12B

16 7 X 0.43 18.4 0.6 1.6 1.8 28.7 1500 CGC-T1216-SM12B

20 7 X 0.43 18.4 0.6 1.6 1.9 32.0 1810 CGC-T1220-SM12B

24 7 X 0.43 18.4 0.6 1.6 1.9 34.6 2130 CGC-T1224-SM12B

30 7 X 0.43 18.4 0.6 2.0 2.1 38.3 2760 CGC-T1230-SM12B

1.3

2 7 X 0.49 14.2 0.6 1.25 1.5 18.2 620 CGC-T1202-SM14B

4 7 X 0.49 14.2 0.6 1.25 1.6 20.3 800 CGC-T1204-SM14B

8 7 X 0.49 14.2 0.6 1.6 1.7 26.4 1290 CGC-T1208-SM14B

12 7 X 0.49 14.2 0.6 1.6 1.8 29.5 1480 CGC-T1212-SM14B

16 7 X 0.49 14.2 0.6 1.6 1.9 32.0 1800 CGC-T1216-SM14B

20 7 X 0.49 14.2 0.6 2.0 2.0 36.6 2220 CGC-T1220-SM14B

24 7 X 0.49 14.2 0.6 2.0 2.1 39.3 3130 CGC-T1224-SM14B

30 7 X 0.49 14.2 0.6 2.0 2.2 44.2 3810 CGC-T1230-SM14B

1.5

2 7 X 0.53 12.6 0.6 1.25 1.7 22.8 930 CGC-T1202-SM15B

4 7 X 0.53 12.6 0.6 1.25 1.7 24.1 1070 CGC-T1204-SM15B

8 7 X 0.53 12.6 0.6 1.6 1.8 30.4 1600 CGC-T1208-SM15B

12 7 X 0.53 12.6 0.6 1.6 1.9 34.1 2030 CGC-T1212-SM15B

16 7 X 0.53 12.6 0.6 1.6 2.0 38.7 2190 CGC-T1216-SM15B

20 7 X 0.53 12.6 0.6 2.0 2.2 43.3 3320 CGC-T1220-SM15B

24 7 X 0.53 12.6 0.6 2.0 2.3 48.5 4310 CGC-T1224-SM15B

30 7 X 0.53 12.6 0.6 2.5 2.5 52.8 5280 CGC-T1230-SM15B

TECHNICAL INFORMATION

PE InsulationMultipairs, Layers, Individual and Collective Screen, Galvanized Steel Wire Armour

Page 40: Special Cables Catalogue

A 32

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted in concentric layers and wrapped by polyester tapes

Colour code: Black continuously numbered

Screen: Collective screen of tinned copper wire braid with coverage from 60% up to 80% and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No. x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.0

2 7 x 0.43 18.1 0.6 1.2 7.2 95 CGC-T1202-OU12B

3 7 x 0.43 18.1 0.6 1.2 7.6 110 CGC-T1103- OU12B

5 7 x 0.43 18.1 0.6 1.3 10.3 150 CGC-T1105- OU12B

7 7 x 0.43 18.1 0.6 1.3 11.1 180 CGC-T1107- OU12B

12 7 x 0.43 18.1 0.6 1.4 14.2 270 CGC-T1112- OU12B

19 7 x 0.43 18.1 0.6 1.4 16.3 380 CGC-T1119- OU12B

24 7 x 0.43 18.1 0.6 1.6 19.2 465 CGC-T1124- OU12B

1.5

2 7 x 0.53 12.1 0.6 1.2 9.0 125 CGC-T1102- OU15B

3 7 x 0.53 12.1 0.6 1.2 9.4 145 CGC-T1103- OU15B

5 7 x 0.53 12.1 0.6 1.3 11.2 200 CGC-T1105- OU15B

7 7 x 0.53 12.1 0.6 1.3 12.0 240 CGC-T1107- OU15B

12 7 x 0.53 12.1 0.6 1.4 15.4 375 CGC-T1112- OU15B

19 7 x 0.53 12.1 0.6 1.5 18.0 545 CGC-T1119- OU15B

24 7 x 0.53 12.1 0.6 1.6 21.0 670 CGC-T1124- OU15B

Multicores, Layers, Overall Screen of Tinned Copper Wire Braid

TECHNICAL INFORMATION

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 41: Special Cables Catalogue

A 33

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form a pair wrapped by polyester tapes

Colour code: Black / White

Screen: Collective screen of aluminium polyester tapes and tinned copper wire braid with coverage from 60% up to 80% and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Single Pair, Collective Screen of Tinned Copper Wire Braid

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

ConductorSize

Conductor Nominal

InsulationThickness

Nominal SheathThickness

Approximate OverallDiameter

ApproximateNet Weight

Cable CodeNo. x dia

Max. DC Res. At

20º

mm2 No. xmm

Ohm/Km mm mm mm Kg/Km -

1 X 2 X 0.5 7 X 0.3 39.2 0.6 0.8 6.3 40 CGC-T120-OU05B

1 X 2 X 0.75 7 X 0.37 24.6 0.6 0.8 6.6 46 CGC-T120-OU08B

1 X 2 X 1.0 7 X 0.43 18.4 0.6 0.8 7.0 53 CGC-T120-OU12B

1 X 2 X 1.3 7 X 0.49 14.2 0.6 0.9 7.6 65 CGC-T120-OU14B

1 X 2 X 1.5 7 X 0.53 12.6 0.6 0.9 8.2 73 CGC-T120-OU15B

PE Insulation

UIC

Els

ewed

y F

ire

Inst

rum

enta

tio

n C

able

s 30

0 V

Page 42: Special Cables Catalogue

A 34

Application: These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.

Engineering Specification:

Standard: BS 5308-1

Rated Voltage: 300/500 V

Conductor: Stranded annealed plain copper

insulation: Polyethelene 03 to BS 6234

Assembly: Cores twisted to form pairs, twisted pairs in concentric layers and wrapped by polyester tapes

Colour code: Black / White, continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes and tinned copper wire braid with coverage from 60% up to 80% and wrapped by polyester tapes

Sheath: Polyvinylchloride TM1 to BS 6746 colour black or blue

Minimum bending radius: 7.5 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Multipairs, Layers, Overall Screen of Tinned Copper Wire Braid

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.0 9.3 95 CGC-T1202-OU05B

4 7 x 0.3 39.2 0.6 1.0 10.0 115 CGC-T1204-OU05B

6 7 x 0.3 39.2 0.6 1.2 12.3 175 CGC-T1206- OU05B

8 7 x 0.3 39.2 0.6 1.2 13.2 190 CGC-T1208- OU05B

10 7 x 0.3 39.2 0.6 1.2 14.5 220 CGC-T1210- OU05B

12 7 x 0.3 39.2 0.6 1.2 15.0 250 CGC-T1212- OU05B

0.75

2 7 x 0.37 24.6 0.6 1.0 10.1 120 CGC-T1202- OU08B

4 7 x 0.37 24.6 0.6 1.0 10.8 134 CGC-T1204- OU08B

6 7 x 0.37 24.6 0.6 1.2 13.8 220 CGC-T1206- OU08B

8 7 x 0.37 24.6 0.6 1.2 14.3 230 CGC-T1208- OU08B

10 7 x 0.37 24.6 0.6 1.2 15.8 275 CGC-T1210- OU08B

12 7 x 0.37 24.6 0.6 1.2 16.3 320 CGC-T1212- OU08B

TECHNICAL INFORMATION

PE Insulation

UIC

Els

ewed

y In

stru

men

tati

on

Cab

les

300

V

Page 43: Special Cables Catalogue

A 35

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/km -

1.0

2 7 x 0.43 18.4 0.6 1.0 10.8 135 CGC-T1202-OU12B

4 7 x 0.43 18.4 0.6 1.0 11.6 160 CGC-T1204-OU12B

6 7 x 0.43 18.4 0.6 1.2 12.8 255 CGC-T1206-OU12B

8 7 x 0.43 18.4 0.6 1.2 15.4 280 CGC-T1208-OU12B

10 7 x 0.43 18.4 0.6 1.3 17.2 345 CGC-T1210-OU12B

12 7 x 0.43 18.4 0.6 1.3 17.8 400 CGC-T1212-OU12B

1.3

2 7 x 0.49 14.2 0.6 1.0 11.4 165 CGC-T1202-OU12B

4 7 x 0.49 14.2 0.6 1.2 13.5 195 CGC-T1204-OU12B

6 7 x 0.49 14.2 0.6 1.3 14.7 260 CGC-T1206-OU12B

8 7 x 0.49 14.2 0.6 1.3 16.6 340 CGC-T1208-OU12B

10 7 x 0.49 14.2 0.6 1.3 18.1 410 CGC-T1210- OU12B

12 7 x 0.49 14.2 0.6 1.3 20.2 480 CGC-T1212-OU12B

1.5

2 7 x 0.53 12.6 0.6 1.2 12.9 195 CGC-T1202- OU12B

4 7 x 0.53 12.6 0.6 1.2 14.1 230 CGC-T1204-OU12B

6 7 x 0.53 12.6 0.6 1.3 17.8 390 CGC-T1206-OU12B

8 7 x 0.53 12.6 0.6 1.3 18.6 405 CGC-T1208-OU12B

10 7 x 0.53 12.6 0.6 1.3 20.6 490 CGC-T1210-OU12B

12 7 x 0.53 12.6 0.6 1.3 21.3 564 CGC-T1212-OU12B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Multipairs, Layers, Overall Screen of Plain or Tinned Copper Wire Braid

TECHNICAL INFORMATION

PE Insulation

Page 44: Special Cables Catalogue

B. Fire Resistant & Fire Alarm Cables

Page 45: Special Cables Catalogue

B 1

Fire Resistant Cables, Multicores, Layers, Collective Screen, Stranded Conductor ...…………...…………. 2

Fire Resistant Cables, Multipairs, Layers, Collective Screen, Stranded Conductor ...…………...………….. 3

Fire Resistant Cables, Multipairs, Layers, Individual and Collective Screen, Stranded Conductor ...…….. 5

Fire Alarm Cables, Multicores, Unscreened, Stranded Conductor ............................................................. 7

Fire Alarm Cables, Multipairs, Layers, Collective Screen, Stranded Conductor ....................................... 8

Fire Alarm Cables, Multicores, Unscreened, Solid Conductor ...................................................................... 9

Fire Alarm Cables, Multipairs, Layers, Collective Screen, Solid Conductor................................................. 10

Fire Alarm Cables, Multicores, Unscreened, Flexible Conductor ................................................................. 11

Fire Alarm Cables, Multipairs, Layers, Collective Screen, Flexible Conductor ........................................... 12

B. Fire Resistant & Fire Alarm Cables

Page 46: Special Cables Catalogue

B 2

Application: These cables are used in fire fighting alarm systems in hazardous area where the safety is highly required during fire condition.

Engineering Specification:

Standard: IEC 60502

Rated Voltage: 600 / 1000 V

Conductor: Stranded plain / tinned annealed copper

insulation: Flame barrier mica tape, cross-linked polyethylene

Assembly: Cores twisted together in concentric layers and wrapped by polyester tapes

Colour code: Black continuously numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes

Sheath: Halogen free, low smoke thermoplastic material, red colour

Minimum bending radius: 7.5 x d (d= overall diameter)

Fire resistant property: 750oC according to IEC 331

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.5

2 7 x 0.52 12.1 0.7 1.8 10.5 115 CBA-TL102-JU15B

5 7 x 0.52 12.1 0.7 1.8 12.8 204 CBA-TL105-JU15B

7 7 x 0.52 12.1 0.7 1.8 13.8 212 CBA-TL107-JU15B

10 7 x 0.52 12.1 0.7 1.8 17.2 352 CBA-TL110-JU15B

12 7 x 0.52 12.1 0.7 1.8 17.8 402 CBA-TL112-JU15B

19 7 x 0.52 12.1 0.7 1.8 20.6 582 CBA-TL119-JU15B

24 7 x 0.52 12.1 0.7 1.8 23.9 720 CBA-TL124-JU15B

30 7 x 0.52 12.1 0.7 1.8 25.3 870 CBA-TL130-JU15B

37 7 x 0.52 12.1 0.7 1.8 27.3 1040 CBA-TL137-JU15B

2.5

2 7 x 0.67 7.41 0.7 1.8 11.4 146 CBA-TL102-JU18B

5 7 x 0.67 7.41 0.7 1.8 14.1 260 CBA-TL105-JU18B

7 7 x 0.67 7.41 0.7 1.8 15.2 325 CBA-TL107-JU18B

10 7 x 0.67 7.41 0.7 1.8 19.0 435 CBA-TL110-JU18B

12 7 x 0.67 7.41 0.7 1.8 19.6 500 CBA-TL112-JU18B

19 7 x 0.67 7.41 0.7 1.8 22.8 700 CBA-TL119-JU18B

24 7 x 0.67 7.41 0.7 1.8 26.6 860 CBA-TL124-JU18B

30 7 x 0.67 7.41 0.7 1.9 28.4 1040 CBA-TL130-JU18B

37 7 x 0.37 7.41 0.7 1.9 30.1 1250 CBA-TL137-JU18B

The above data are approximate and subject to normal manufacturing tolerance.

Other types can be provided on specific request.

We can meet all other standard as BS 5308 and IEC 502.

Fire Resistant CablesMulticores, Layers, Collective Screen, Stranded Conductor

TECHNICAL INFORMATION

UIC

Els

ewed

y F

ire R

esis

tant

Cab

les

Page 47: Special Cables Catalogue

B 3

Fire Resistant Cables

Application: These cables are used in fire fighting alarm systems in hazardous area where the safety is highly required during fire condition.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Stranded plain / tinned annealed copper

insulation: Flame barrier mica tape, cross-linked polyethylene

Assembly: Cores twisted to form pairs, pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes.

Sheath: Halogen free, low smoke thermoplasticmaterial, red colour

Minimum bending radius: 6 x d (d= overall diameter)

Fire resistant property: 750oC according to IEC 331

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.2 11.1 98 CBC-TL202-JU05R

4 7 x 0.3 39.2 0.6 1.2 12.8 145 CBC-TL204-JU05R

6 7 x 0.3 39.2 0.6 1.2 15.3 200 CBC-TL206-JU05R

8 7 x 0.3 39.2 0.6 1.3 17.0 270 CBC-TL208-JU05R

10 7 x 0.3 39.2 0.6 1.3 18.8 310 CBC-TL210-JU05R

12 7 x 0.3 39.2 0.6 1.4 19.9 355 CBC-TL212-JU05R

16 7 x 0.3 39.2 0.6 1.4 22.5 454 CBC-TL216-JU05R

20 7 x 0.3 39.2 0.6 1.5 25.0 560 CBC-TL220-JU05R

24 7 x 0.3 39.2 0.6 1.5 27.1 650 CBC-TL224-JU05R

30 7 x 0.3 39.2 0.6 1.6 30.1 800 CBC-TL230-JU05R

0.75

2 7 x 0.37 24.6 0.6 1.2 11.8 110 CBC-TL202-JU08R

4 7 x 0.37 24.6 0.6 1.2 13.7 175 CBC-TL204-JU08R

6 7 x 0.37 24.6 0.6 1.3 16.6 245 CBC-TL206-JU08R

8 7 x 0.37 24.6 0.6 1.3 17.7 305 CBC-TL208-JU08R

10 7 x 0.37 24.6 0.6 1.3 20.1 370 CBC-TL210-JU08R

12 7 x 0.37 24.6 0.6 1.4 21.3 435 CBC-TL212-JU08R

16 7 x 0.37 24.6 0.6 1.4 24.1 555 CBC-TL216-JU08R

20 7 x 0.37 24.6 0.6 1.5 26.8 685 CBC-TL220-JU08R

24 7 x 0.37 24.6 0.6 1.5 29.1 800 CBC-TL224-JU08R

30 7 x 0.37 24.6 0.6 1.6 32.3 990 CBC-TL230-JU08R

TECHNICAL INFORMATION

Multipairs, Layers, Collective Screen, Stranded Conductor

UIC

Els

ewed

y F

ire R

esis

tant

Cab

les

Page 48: Special Cables Catalogue

B 4

Fire Resistant Cables

Conductor size

Number of

pairs

ConductorNominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1

2 7 x 0.43 18.4 0.6 1.2 12.4 127 CBC-TL202-JU12R

4 7 x 0.43 18.4 0.6 1.3 14.6 205 CBC-TL204-JU12R

6 7 x 0.43 18.4 0.6 1.3 17.5 285 CBC-TL206-JU12R

8 7 x 0.43 18.4 0.6 1.3 18.7 355 CBC-TL208-JU12R

10 7 x 0.43 18.4 0.6 1.3 21.3 435 CBC-TL210-JU12R

12 7 x 0.43 18.4 0.6 1.4 22.5 510 CBC-TL212-JU12R

16 7 x 0.43 18.4 0.6 1.5 25.7 685 CBC-TL216-JU12R

20 7 x 0.43 18.4 0.6 1.6 28.6 820 CBC-TL220-JU12R

24 7 x 0.43 18.4 0.6 1.6 31.0 962 CBC-TL224-JU12R

30 7 x 0.43 18.4 0.6 1.7 34.5 1185 CBC-TL230-JU12R

1.5

2 7 x 0.53 12.6 0.6 1.2 13.3 155 CBC-TL202-JU15R

4 7 x 0.53 12.6 0.6 1.3 15.8 258 CBC-TL204-JU15R

6 7 x 0.53 12.6 0.6 1.3 19.0 360 CBC-TL206-JU15R

8 7 x 0.53 12.6 0.6 1.3 20.3 455 CBC-TL208-JU15R

10 7 x 0.53 12.6 0.6 1.3 23.2 555 CBC-TL210-JU15R

12 7 x 0.53 12.6 0.6 1.4 24.5 660 CBC-TL212-JU15R

16 7 x 0.53 12.6 0.6 1.5 28.1 860 CBC-TL216-JU15R

20 7 x 0.53 12.6 0.6 1.6 31.2 1060 CBC-TL220-JU15R

24 7 x 0.53 12.6 0.6 1.7 34.2 1290 CBC-TL224-JU15R

30 7 x 0.53 12.6 0.6 1.7 37.7 1550 CBC-TL230-JU15R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

• We can meet all other standard as BS 5308 and IEC 502.

TECHNICAL INFORMATION

Multipairs, Layers, Collective Screen, Stranded Conductor

Page 49: Special Cables Catalogue

B 5

Fire Resistant CablesMultipairs, Layers, Individual and Collective Screen, Stranded Conductor

Application: These cables are used in fire fighting alarm systems in hazardous area where the safety is highlyrequired during fire condition.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Stranded plain / tinned annealed copper

insulation: Flame barrier mica tape, cross-linked polyethylene

Assembly: Cores twisted to form pairs, pairs screened by aluminium polyester tapes, screened pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Black / White continuously numbered, or Identification tapes numbered

Screen: Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes

Sheath: Halogen free, low smoke thermoplastic material, red colour

Minimum bending radius: 6 x d (d= overall diameter)

Fire resistant property: 750oC according to IEC 331

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

0.5

2 7 x 0.3 39.2 0.6 1.2 11.8 110 CBC-TL202-SU05R

4 7 x 0.3 39.2 0.6 1.2 13.7 170 CBC-TL204-SU05R

6 7 x 0.3 39.2 0.6 1.2 16.4 234 CBC-TL206-SU05R

8 7 x 0.3 39.2 0.6 1.3 17.7 296 CBC-TL208-SU05R

10 7 x 0.3 39.2 0.6 1.3 20.1 360 CBC-TL210-SU05R

12 7 x 0.3 39.2 0.6 1.4 21.3 425 CBC-TL212-SU05R

16 7 x 0.3 39.2 0.6 1.4 24.1 540 CBC-TL216-SU05R

20 7 x 0.3 39.2 0.6 1.5 26.8 670 CBC-TL220-SU05R

24 7 x 0.3 39.2 0.6 1.5 29.1 780 CBC-TL224-SU05R

30 7 x 0.3 39.2 0.6 1.6 32.3 960 CBC-TL230-SU05R

0.75

2 7 x 0.37 24.6 0.6 1.2 12.5 126 CBC-TL202-SU08R

4 7 x 0.37 24.6 0.6 1.2 14.5 200 CBC-TL204-SU08R

6 7 x 0.37 24.6 0.6 1.3 17.7 285 CBC-TL206-SU08R

8 7 x 0.37 24.6 0.6 1.3 18.8 350 CBC-TL208-SU08R

10 7 x 0.37 24.6 0.6 1.3 21.5 430 CBC-TL210-SU08R

12 7 x 0.37 24.6 0.6 1.4 22.7 505 CBC-TL212-SU08R

16 7 x 0.37 24.6 0.6 1.4 25.8 650 CBC-TL216-SU08R

20 7 x 0.37 24.6 0.6 1.5 28.7 800 CBC-TL220-SU08R

24 7 x 0.37 24.6 0.6 1.5 31.1 935 CBC-TL224-SU08R

30 7 x 0.37 24.6 0.6 1.6 34.6 1155 CBC-TL230-SU08R

TECHNICAL INFORMATION

UIC

Els

ewed

y F

ire R

esis

tant

Cab

les

Page 50: Special Cables Catalogue

B 6

Fire Resistant CablesMultipairs, Layers, Individual and Collective Screen, Stranded Conductor

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1

2 7 x 0.43 18.4 0.6 1.2 13.1 142 CBC-TL202-SU12R

4 7 x 0.43 18.4 0.6 1.3 15.5 230 CBC-TL204-SU12R

6 7 x 0.43 18.4 0.6 1.3 18.6 325 CBC-TL206-SU12R

8 7 x 0.43 18.4 0.6 1.3 19.8 405 CBC-TL208-SU12R

10 7 x 0.43 18.4 0.6 1.3 22.6 490 CBC-TL210-SU12R

12 7 x 0.43 18.4 0.6 1.4 23.9 585 CBC-TL212-SU12R

16 7 x 0.43 18.4 0.6 1.5 27.4 760 CBC-TL216-SU12R

20 7 x 0.43 18.4 0.6 1.6 30.4 940 CBC-TL220-SU12R

24 7 x 0.43 18.4 0.6 1.6 33.0 1100 CBC-TL224-SU12R

30 7 x 0.43 18.4 0.6 1.7 36.7 1360 CBC-TL230-SU12R

1.5

2 7 x 0.53 12.6 0.6 1.2 14.0 166 CBC-TL202-SU15R

4 7 x 0.53 12.6 0.6 1.3 16.7 286 CBC-TL204-SU15R

6 7 x 0.53 12.6 0.6 1.3 20.1 400 CBC-TL206-SU15R

8 7 x 0.53 12.6 0.6 1.3 21.5 505 CBC-TL208-SU15R

10 7 x 0.53 12.6 0.6 1.3 24.5 620 CBC-TL210-SU15R

12 7 x 0.53 12.6 0.6 1.4 26.0 735 CBC-TL212-SU15R

16 7 x 0.53 12.6 0.6 1.5 29.7 960 CBC-TL216-SU15R

20 7 x 0.53 12.6 0.6 1.6 33.0 1185 CBC-TL220-SU15R

24 7 x 0.53 12.6 0.6 1.7 36.1 1410 CBC-TL224-SU15R

30 7 x 0.53 12.6 0.6 1.7 40.0 1725 CBC-TL230-SU15R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

• We can meet all other standard as BS 5308 and IEC 502.

TECHNICAL INFORMATION

Page 51: Special Cables Catalogue

B 7

Fire Alarm CablesMulticores, Unscreened, Stranded Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Stranded annealed plain copper

insulation: polyvinylchloride rated for 105oC

Assembly: Cores twisted together in concentric layers

Colour code: Two Core: red, blackThree Core: red, black, blueFour Core: red, yellow, blue, black

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1

2 7 x 0.43 18.1 0.6 0.8 6.6 65 CSC-TA202-AU12R

3 7 x 0.43 18.1 0.6 0.8 7.0 79 CSC-TA203-AU12R

4 7 x 0.43 18.1 0.6 0.8 7.6 98 CSC-TA204-AU12R

1.5

2 7 x 0.52 12.1 0.6 0.8 7.1 81 CSC-TA202-AU15R

3 7 x 0.52 12.1 0.6 0.9 7.8 103 CSC-TA203-AU15R

4 7 x 0.52 12.1 0.6 0.9 8.5 128 CSC-TA204-AU15R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 52: Special Cables Catalogue

B 8

Multipairs, Layers, Collective Screen, Stranded Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Stranded annealed plain copper

insulation: Polyvinylchloride rated for 105oC

Assembly: Cores twisted to form pairs, pairs twisted in concentric layers and wrapped by polyester tapes.

Colour code: Red / Black continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminium polyester tap with tinned drainwire and wrapped by polyester tapes

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.5

2 7 x 0.53 12.6 0.6 1.2 12.0 155 CSC-TA202-JU12R

4 7 x 0.53 12.6 0.6 1.2 14.0 253 CSC-TA203-JU12R

8 7 x 0.53 12.6 0.6 1.3 18.1 457 CSC-TA208-JU12R

12 7 x 0.53 12.6 0.6 1.3 21.6 652 CSC-TA212-JU15R

16 7 x 0.53 12.6 0.6 1.5 24.7 860 CSC-TA216-JU15R

20 7 x 0.53 12.6 0.6 1.5 27.5 1058 CSC-TA220-JU15R

24 7 x 0.53 12.6 0.6 1.7 30.2 1270 CSC-TA224-JU15R

30 7 x 0.53 12.6 0.6 2.0 33.9 1600 CSC-TA230-JU15R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Fire Alarm Cables

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 53: Special Cables Catalogue

B 9

Multicores, Unscreened, Solid Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Solid annealed plain copper

insulation: polyvinylchloride rated for 105oC

Assembly: Cores twisted together in concentric layers

Colour code: Two Core: red, blackThree Core: red, black, blueFour Core: red, yellow, blue, black

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor Size

Number of Cores

Conductor Nominal Insulation thickness

Nominal Theath

Thickness

Approximate overall

Diameter

Approximate net Weight UIC-CodeNo.x Dia

Max.dc Resis. At

20C

mm2 No. No.x mm Ohm/Km mm mm mm kg/km

1

2 1x1.13 18.1 0.6 0.8 6.3 49 CSC-SA102-AU12R

3 1x1.13 18.1 0.6 0.8 6.6 65 CSC-SA103-AU12R

4 1x1.13 18.1 0.6 0.8 7.2 81 CSC-SA104-AU12R

1.5

2 1x1.35 12.1 0.6 0.8 6.7 60 CSC-SA102-AU15R

3 1x1.35 12.1 0.6 0.9 7.3 84 CSC-SA103-AU15R

4 1x1.35 12.1 0.6 0.9 8 105 CSC-SA104-AU15R

TECHNICAL INFORMATION

Fire Alarm Cables

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 54: Special Cables Catalogue

B 10

Multipairs, Layers, Collective Screen, Solid Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Solid annealed plain copper

insulation: Polyvinylchloride rated for 105oC

Assembly: Cores twisted to form pairs, pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Red / Black continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminium polyester tap with tinned drain wire and wrapped by polyester tapes

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor Size

Number of Pairs

Conductor Nominal Insulation thickness

Nominal Theath

Thickness

Approximate overall

Diameter

Approximate net Weight UIC-CodeNo. x Dia

Max.dc Resis. At

20C

mm2 No. No. x mm Ohm/Km mm mm mm kg/km

1.5

2 1x1.35 12.1 0.6 1.2 11.3 142 CSC-SA202-JU15R

4 1x1.35 12.1 0.6 1.2 13.1 232 CSC-SA204-JU15R

8 1x1.35 12.1 0.6 1.3 16.9 418 CSC-SA208-JU15R

12 1x1.35 12.1 0.6 1.3 20.1 596 CSC-SA212-JU15R

16 1x1.35 12.1 0.6 1.5 23.3 293 CSC-SA216-JU15R

20 1x1.35 12.1 0.6 1.5 25.6 967 CSC-SA220-JU15R

24 1x1.35 12.1 0.6 1.5 27.8 1139 CSC-SA224-JU15R

30 1x1.35 12.1 0.6 1.7 31.1 1426 CSC-SA230-JU15R

TECHNICAL INFORMATION

Fire Alarm Cables

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 55: Special Cables Catalogue

B 11

Multicores, Unscreened, Flexible Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V

Conductor: Flexible annealed plain copper

insulation: Polyvinylchloride rated for 105oC

Assembly: Cores twisted together in concentric layers

Colour code: Two Core: red, blackThree Core: red, black, blueFour Core: red, yellow, blue, black

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor Size

Number of Cores

ConductorNominal Insulation thickness

Nominal Theath

Thickness

Approximate overall

Diameter

Approximate net Weight UIC-CodeNo.x Dia

Max.dc Resis. At

20C

mm2 No. No.x mm Ohm/Km mm mm mm kg/km

1

2 32x0.19 19.5 0.6 0.8 6.5 49 CSC-FA102-AU12R

3 32x0.19 19.5 0.6 0.8 6.9 75 CSC-FA103-AU12R

4 32x0.19 19.5 0.6 0.8 7.5 92 CSC-FA104-AU12R

1.5

2 36x0.22 13.3 0.6 0.8 7.1 78 CSC-FA102-AU15R

3 36x0.22 13.3 0.6 0.9 7.7 99 CSC-FA103-AU15R

4 36x0.22 13.3 0.6 0.9 8.4 122 CSC-FA104-AU15R

TECHNICAL INFORMATION

Fire Alarm Cables

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 56: Special Cables Catalogue

B 12

Multipairs, Layers, Collective Screen, Flexible Conductor

Application: These cables are used for communication and signaling in fire alarm systems.

Engineering Specification:

Standard: BS-5308

Rated Voltage: 300 / 500 V Conductor: Flexible annealed plain copper

insulation: Polyvinylchloride rated for 105oC

Assembly: Cores twisted to form pairs, pairs twisted in concentric layers and wrapped by polyester tapes

Colour code: Red/Black continuously numbered, or identification tapes numbered

Screen: Collective screen of aluminium polyester tap with tinned drain wire and wrapped by polyester tapes

Sheath: Flame retardant polyvinylchloride, red coloured

Minimum bending radius: 7.5 x d (d= overall diameter)

Packing: On non-returnable wooden drums

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATIONConductor

SizeNumber of

Pairs

Conductor Nominal Insulation thickness

Nominal Theath

Thickness

Approximate overall

Diameter

Approximate net Weight UIC-CodeNo.x Dia Max.dc

Resis. At 20C

mm2 No.No.x mm

Ohm/Km mm mm mm kg/km

1.5

2 36x0.22 13.3 0.6 1.2 11.8 143 CSC-FA202-JU15R

4 36x0.22 13.3 0.6 1.2 13.7 229 CSC-FA204-JU15R

8 36x0.22 13.3 0.6 1.3 17.8 412 CSC-FA208-JU15R

12 36x0.22 13.3 0.6 1.5 21.6 585 CSC-FA212-JU15R

16 36x0.22 13.3 0.6 1.5 24.4 777 CSC-FA216-JU15R

20 36x0.22 13.3 0.6 1.5 26.9 947 CSC-FA220-JU15R

24 36x0.22 13.3 0.6 1.7 29.6 1143 CSC-FA224-JU15R

30 36x0.22 13.3 0.6 1.7 32.7 1395 CSC-FA230-JU15R

Fire Alarm Cables

UIC

Els

ewed

y F

ire A

larm

Cab

les

Page 57: Special Cables Catalogue

B 13

Page 58: Special Cables Catalogue

C 14C. Control Cables

Page 59: Special Cables Catalogue

C. Control Cables

Solid Copper Conductors, PVC Insulation, PVC Sheathed ……………………………………………….… 2

Stranded Copper Conductors, PVC Insulation, PVC Sheathed ………………………………... .………. 4

Stranded Copper Conductors, PVC Insulation, Copper Tape Screened, PVC Sheathed .......………. 6

Stranded Copper Conductors, PVC Insulation, Steel Tape Armoured, PVC Sheathed ....….…………. 8

Stranded Copper Conductors, PVC Insulation, Steel Wire Armoured, PVC Sheathed ..…………….… 10

Page 60: Special Cables Catalogue

C 2

Solid Copper Conductors PVC Insulation, PVC Sheathed

Application: For outdoor and indoor installations in damp and wet locations, connecting signaling and control units in industry, in railways, in traffic signals, in thermopower and hydropower stations. They are laid in air, in ducts, in trenches, in steel support brackets or direct in ground, when well protected.

Engineering Specification:

Standard: IEC – 60502

Rated Voltage: 300 / 500 V

Conductor: Soft annealed solid copper wire as per class 1 of IEC 228

insulation: Polyvinylchloride rated 70oC or 85oC

Assembly: Cores twisted together to form a round assembly cable with fillers whenever necessary

Colour code: Black cores with white numbers and one green yellow core

Sheath: Flame retardant polyvinylchloride, black or grey colour

Minimum bending radius: 15 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

1.5

5 1x1.38 12.1 0.8 1.8 11.8 200 CPA-SA105-UU15B

7 1x1.38 12.1 0.8 1.8 12.7 250 CPA-SA107-UU15B

10 1x1.38 12.1 0.8 1.8 15.7 340 CPA-SA110-UU15B

12 1x1.38 12.1 0.8 1.8 16.2 385 CPA-SA112-UU15B

14 1x1.38 12.1 0.8 1.8 17.0 435 CPA-SA114-UU15B

16 1x1.38 12.1 0.8 1.8 17.8 490 CPA-SA116-UU15B

19 1x1.38 12.1 0.8 1.8 18.7 560 CPA-SA119-UU15B

24 1x1.38 12.1 0.8 1.8 21.7 700 CPA-SA124-UU15B

30 1x1.38 12.1 0.8 1.8 23.8 850 CPA-SA130-UU15B

37 1x1.38 12.1 0.8 1.8 24.7 1000 CPA-SA137-UU15B

44 1x1.38 12.1 0.8 1.8 28.4 1200 CPA-SA144-UU15B

TECHNICAL INFORMATION

Page 61: Special Cables Catalogue

C 3

Solid Copper Conductors PVC Insulation, PVC Sheathed

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

2.5

5 1x1.78 7.41 0.8 1.8 12.9 260 CPA-SA105-UU18B

7 1x1.78 7.41 0.8 1.8 13.8 330 CPA-SA107-UU18B

10 1x1.78 7.41 0.8 1.8 17.2 450 CPA-SA110-UU18B

12 1x1.78 7.41 0.8 1.8 17.7 540 CPA-SA112-UU18B

14 1x1.78 7.41 0.8 1.8 18.6 600 CPA-SA114-UU18B

16 1x1.78 7.41 0.8 1.8 19.6 670 CPA-SA116-UU18B

19 1x1.78 7.41 0.8 1.8 20.6 780 CPA-SA119-UU18B

24 1x1.78 7.41 0.8 1.8 24.0 1030 CPA-SA124-UU18B

30 1x1.78 7.41 0.8 1.8 25.4 1160 CPA-SA130-UU18B

37 1x1.78 7.41 0.8 1.9 27.4 1410 CPA-SA137-UU18B

44 1x1.78 7.41 0.8 2.0 31.2 1670 CPA-SA144-UU18B

4.0

5 1x2.26 4.61 1.0 1.8 15.3 430 CPA-SA105-UU21B

7 1x2.26 4.61 1.0 1.8 16.5 480 CPA-SA107-UU21B

10 1x2.26 4.61 1.0 1.8 20.8 670 CPA-SA110-UU21B

12 1x2.26 4.61 1.0 1.8 21.5 780 CPA-SA112-UU21B

14 1x2.26 4.61 1.0 1.8 22.6 890 CPA-SA114-UU21B

16 1x2.26 4.61 1.0 1.8 23.8 1000 CPA-SA116-UU21B

19 1x2.26 4.61 1.0 1.9 25.1 1170 CPA-SA119-UU21B

24 1x2.26 4.61 1.0 2.0 29.6 1460 CPA-SA124-UU21B

30 1x2.26 4.61 1.0 2.1 31.6 1830 CPA-SA130-UU21B

37 1x2.26 4.61 1.0 2.2 34.1 2320 CPA-SA137-UU21B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 62: Special Cables Catalogue

C 4

Stranded Copper Conductors PVC Insulation, PVC Sheathed

Application: For outdoor and indoor installations in damp and wet locations, connecting signaling and control units in industry, in railways, in traffic signals, in thermopower and hydropower stations. They are laid in air, in ducts, in trenches, in steel support brackets or direct in ground, when well protected.

Engineering Specification:

Standard: IEC – 60502

Rated Voltage: 600 / 1000 V

Conductor: Soft annealed solid copper wire as per class 1 of IEC 228

insulation: Polyvinylchloride rated 70oC or 85oC

Assembly: Cores twisted together to form a round assembly cable with fillers whenever necessary

Colour code: Black cores with white numbers and one green yellow core

Sheath: Flame retardant polyvinylchloride, black or grey colour

Minimum bending radius: 15 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

1.5

5 7x 0.52 12.1 0.8 1.8 12.3 215 CPA-SA105-LU15B

7 7x 0.52 12.1 0.8 1.8 13.3 265 CPA-SA107-LU15B

10 7x 0.52 12.1 0.8 1.8 16.5 360 CPA-SA110-LU15B

12 7x 0.52 12.1 0.8 1.8 17.0 410 CPA-SA112-LU15B

14 7x 0.52 12.1 0.8 1.8 17.8 465 CPA-SA114-LU15B

16 7x 0.52 12.1 0.8 1.8 18.7 530 CPA-SA116-LU15B

19 7x 0.52 12.1 0.8 1.8 19.7 600 CPA-SA119-LU15B

24 7x 0.52 12.1 0.8 1.8 22.9 740 CPA-SA124-LU15B

30 7x 0.52 12.1 0.8 1.8 24.2 890 CPA-SA130-LU15B

37 7x 0.52 12.1 0.8 1.8 26.1 1070 CPA-SA137-LU15B

44 7x 0.52 12.1 0.8 1.8 30.2 1295 CPA-SA144-LU15B

TECHNICAL INFORMATION

Page 63: Special Cables Catalogue

C 5

Stranded Copper Conductors PVC Insulation, PVC Sheathed

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm Kg/Km -

2.5

5 7x0.67 7.41 0.8 1.8 13.4 275 CPA-SA105-UU18B

7 7x0.67 7.41 0.8 1.8 14.5 350 CPA-SA107-LU18B

10 7x0.67 7.41 0.8 1.8 18.1 480 CPA-SA110-LU18B

12 7x0.67 7.41 0.8 1.8 18.7 555 CPA-SA112-LU18B

14 7x0.67 7.41 0.8 1.8 19.6 630 CPA-SA114-LU18B

16 7x0.67 7.41 0.8 1.8 20.6 710 CPA-SA116-UU18B

19 7x0.67 7.41 0.8 1.8 21.7 820 CPA-SA119-LU18B

24 7x0.67 7.41 0.8 1.8 25.3 1020 CPA-SA124-LU18B

30 7x0.67 7.41 0.8 1.8 26.8 1235 CPA-SA130-LU18B

37 7x0.67 7.41 0.8 1.9 28.9 1495 CPA-SA137-LU18B

44 7x0.67 7.41 0.8 2.0 33.5 1800 CPA-SA144-LU18B

4.0

5 7x0.85 4.61 1.0 1.8 16.1 440 CPA-SA105-UU21B

7 7x0.85 4.61 1.0 1.8 17.4 520 CPA-SA107-LU21B

10 7x0.85 4.61 1.0 1.8 22.0 720 CPA-SA110-LU21B

12 7x0.85 4.61 1.0 1.8 22.7 840 CPA-SA112-LU21B

14 7x0.85 4.61 1.0 1.8 23.9 950 CPA-SA114-LU21B

16 7x0.85 4.61 1.0 1.8 25.2 1070 CPA-SA116-UU21B

19 7x0.85 4.61 1.0 1.9 26.6 1260 CPA-SA119-LU21B

24 7x0.85 4.61 1.0 2.0 31.4 1580 CPA-SA124-LU21B

30 7x0.85 4.61 1.0 2.1 33.5 1965 CPA-SA130-LU21B

37 7x0.85 4.61 1.0 2.2 36.2 2510 CPA-SA137-LU21B

TECHNICAL INFORMATION

Page 64: Special Cables Catalogue

C 6

Stranded Copper Conductors PVC Insulation, Copper Tape Screened, PVC Sheathed

Application: For outdoor installations in damp and wet locations, connecting signaling and control units in industry in railways, in traffic signals, in thermopower and hydropower stations. Where electrical interference could alter signal transmission, They are laid in air, in ducts, in trenches, in steel support brackets or direct in ground, when well protected.

Engineering Specification:

Standard: IEC – 60502

Rated Voltage: 600 / 1000 V

Conductor: Soft annealed stranded copper wire as per class 2 of IEC 228

insulation: Polyvinylchloride rated 70oC or 85oC

Assembly: Cores twisted together to form a round assembly cable with fillers whenever necessary

Colour code: Black cores with white numbers and one green yellow core

Bedding: Polyvinylchoride rated 70oC

Screen :Copper tape helically applied over the bedding

Sheath: Flame retardant polyvinylchloride, black or grey colour

Minimum bending radius: 15 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drum

Conductor size

Number of

cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

1.5

5 7x 0.52 12.1 0.8 1.8 15.3 340 CPA-TA105-NU15B

7 7x 0.52 12.1 0.8 1.8 15.7 370 CPA-TA107-NU15B

10 7x 0.52 12.1 0.8 1.8 18.9 495 CPA-TA110-NU15B

12 7x 0.52 12.1 0.8 1.8 19.4 550 CPA-TA112-NU15B

14 7x 0.52 12.1 0.8 1.8 20.2 610 CPA-TA114-NU15B

16 7x 0.52 12.1 0.8 1.8 21.1 670 CPA-TA116-NU15B

19 7x 0.52 12.1 0.8 1.8 22.1 760 CPA-TA119-NU15B

24 7x 0.52 12.1 0.8 1.8 25.3 930 CPA-TA124-NU15B

30 7x 0.52 12.1 0.8 1.8 27.5 1115 CPA-TA130-NU15B

37 7x 0.52 12.1 0.8 1.9 28.5 1290 CPA-TA137-NU15B

44 7x 0.52 12.1 0.8 2.0 31.0 1500 CPA-TA144-NU15B

TECHNICAL INFORMATION

Page 65: Special Cables Catalogue

C 7

Stranded Copper Conductors PVC Insulation, Copper Tape Screened, PVC Sheathed

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC

Res. At 20oC

mm2 No. No. x mm Ohm /Km mm mm mm Kg/Km -

2.5

5 7x0.67 7.41 0.8 1.8 15.8 390 CPA-TA105-NU18B7 7x0.67 7.41 0.8 1.8 16.9 470 CPA-TA107-NU18B

10 7x0.67 7.41 0.8 1.8 20.5 630 CPA-TA110-NU18B12 7x0.67 7.41 0.8 1.8 21.1 710 CPA-TA112-NU18B14 7x0.67 7.41 0.8 1.8 22.0 800 CPA-TA114-NU18B16 7x0.67 7.41 0.8 1.8 23.0 875 CPA-TA116-NU18B19 7x0.67 7.41 0.8 1.8 24.1 1000 CPA-TA119-NU18B24 7x0.67 7.41 0.8 1.8 27.7 1225 CPA-TA124-NU18B30 7x0.67 7.41 0.8 1.9 29.8 1470 CPA-TA130-NU18B37 7x0.67 7.41 0.8 2.0 31.5 1750 CPA-TA137-NU18B44 7x0.67 7.41 0.8 2.1 35.7 2140 CPA-TA144-NU18B

4.0

5 7x0.85 4.61 1.0 1.8 18.5 540 CPA-TA105-NU21B7 7x0.85 4.61 1.0 1.8 19.5 670 CPA-TA107-NU21B

10 7x0.85 4.61 1.0 1.8 24.4 850 CPA-TA110-NU21B12 7x0.85 4.61 1.0 1.8 25.2 980 CPA-TA112-NU21B14 7x0.85 4.61 1.0 1.8 26.3 1160 CPA-TA114-NU21B16 7x0.85 4.61 1.0 1.9 27.6 1310 CPA-TA116-NU21B19 7x0.85 4.61 1.0 2.0 29.0 1520 CPA-TA119-NU21B24 7x0.85 4.61 1.0 2.1 33.8 1900 CPA-TA124-NU21B30 7x0.85 4.61 1.0 2.3 35.9 2350 CPA-TA130-NU21B37 7x0.85 4.61 1.0 2.4 38.8 2970 CPA-TA137-NU21B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 66: Special Cables Catalogue

C 8

Stranded Copper Conductors PVC Insulation, Steel Tape Armoured, PVC Sheathed

Conductor size

Number of

Cores

ConductorNominal insulation thickness

Nominal Thickness

of Steel tape

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km

mm mm mm mm Kg/Km -

1.5

5 7x 0.52 12.1 0.8 0.2 1.8 14.6 350 CPA-TA105-LU15B

7 7x 0.52 12.1 0.8 0.2 1.8 17.0 430 CPA-TA107-LU15B

10 7x 0.52 12.1 0.8 0.2 1.8 19.3 570 CPA-TA110-LU15B

12 7x 0.52 12.1 0.8 0.2 1.8 19.8 625 CPA-TA112-LU15B

14 7x 0.52 12.1 0.8 0.2 1.8 20.6 690 CPA-TA114-LU15B

16 7x 0.52 12.1 0.8 0.2 1.8 21.5 800 CPA-TA116-LU15B

19 7x 0.52 12.1 0.8 0.2 1.8 22.5 850 CPA-TA119-LU15B

24 7x 0.52 12.1 0.8 0.2 1.8 25.7 1030 CPA-TA124-LU15B

30 7x 0.52 12.1 0.8 0.2 1.8 27.3 1285 CPA-TA130-LU15B

37 7x 0.52 12.1 0.8 0.2 1.8 28.9 1400 CPA-TA137-LU15B

44 7x 0.52 12.1 0.8 0.2 1.9 31.0 1800 CPA-TA144-LU15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Application: For outdoor and indoor installations in damp and wet locations, Laid Direct in the ground, where mechanical damages are expected to occur. They are normally used in connecting signalingand control units in industry, in railways, in traffic signals, in thermopower and hydropower stations.

Engineering Specification:

Standard: IEC – 60502

Rated Voltage: 600 / 1000 V

Conductor: Soft annealed Stranded Copper wire as per class 2 of IEC 228

insulation: Polyvinylchloride rated 70oC or 85oC

Assembly: Cores twisted together to form a round assembly cable with fillers whenever necessary

Colour code: Black cores with white numbers and one green yellow core

Bedding: Polyvinylchoride rated 70ºC

Armouring: Double layers of steel tapes are applied helically

Sheath: Flame retardant polyvinylchloride, black or grey colour

Minimum bending radius: 15 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

TECHNICAL INFORMATION

Page 67: Special Cables Catalogue

C 9

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

Nominal Thickness

of Steel tape

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At 20oC

mm2 No.No. x mm

Ohm /Km mm mm mm mm Kg/Km -

2.5

5 7x 0.67 7.41 0.8 0.2 1.8 16.2 440 CPA-TA105-UA18B

7 7x 0.67 7.41 0.8 0.2 1.8 17.3 530 CPA-TA107- UA18B

10 7x 0.67 7.41 0.8 0.2 1.8 20.9 710 CPA-TA110- UA18B

12 7x 0.67 7.41 0.8 0.2 1.8 21.5 790 CPA-TA112- UA18B

14 7x 0.67 7.41 0.8 0.2 1.8 22.4 880 CPA-TA114- UA18B

16 7x 0.67 7.41 0.8 0.2 1.8 23.4 970 CPA-TA116- UA18B

19 7x 0.67 7.41 0.8 0.2 1.8 24.5 1090 CPA-TA119- UA18B

24 7x 0.67 7.41 0.8 0.2 1.8 28.1 1140 CPA-TA124- UA18B

30 7x 0.67 7.41 0.8 0.2 1.9 27.3 1630 CPA-TA130- UA18B

37 7x 0.67 7.41 0.8 0.2 1.9 31.9 1875 CPA-TA137- UA18B

44 7x 0.67 7.41 0.8 0.5 2.1 36.0 2500 CPA-TA144- UA18B

4.0

5 7x 0.85 4.61 0.8 0.2 1.8 18.9 660 CPA-TA105-UA21B

7 7x 0.85 4.61 0.8 0.2 1.8 20.3 740 CPA-TA107- UA21B

10 7x 0.85 4.61 0.8 0.2 1.8 24.9 960 CPA-TA110- UA21B

12 7x 0.85 4.61 0.8 0.2 1.8 25.6 1120 CPA-TA112- UA21B

14 7x 0.85 4.61 0.8 0.2 1.8 26.7 1270 CPA-TA114- UA21B

16 7x 0.85 4.61 0.8 0.2 1.8 28.0 1390 CPA-TA116- UA21B

19 7x 0.85 4.61 0.8 0.2 1.8 29.4 1610 CPA-TA119- UA21B

24 7x 0.85 4.61 0.8 0.2 2.0 34.4 2030 CPA-TA124- UA21B

30 7x 0.85 4.61 0.8 0.2 2.1 36.5 2660 CPA-TA130- UA21B

37 7x 0.85 4.61 0.8 0.5 2.2 39.4 3250 CPA-TA137- UA21B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Stranded Copper Conductors PVC Insulation, Steel Tape Armoured, PVC Sheathed

Page 68: Special Cables Catalogue

C 10

Application: For outdoor and indoor installations in damp and wet locations, laid direct in the ground, where mechanical damages are expected to occur. They are normally used in connecting signaling and control units in industry, in railways, in traffic signals, in thermopower and hydropower stations.

Engineering Specification:

Standard: IEC – 60502

Rated Voltage: 600 / 1000 V

Conductor: Soft annealed stranded copper wire as per class 2 of IEC 228

insulation: Polyvinylchloride rated 70oC or 85oC

Assembly: Cores twisted together to form a round assembly cable with fillers whenever necessary

Colour code: Black cores with white numbers and one green yellow core

Bedding: Polyvinylchoride rated 70oC

Armouring: Single layers of steel wire are applied helically

Sheath: Flame retardant polyvinylchloride, black or grey colour

Minimum bending radius: 15 x d (d= overall diameter)

Temperature rating: +5oC up to + 50oC during operation

Packing: On non-returnable wooden drums

Conductor size

Number of

Cores

Conductor Nominal insulation thickness

NominalDiameter of steel

wire

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.Max. DC Res. At 20oC

mm2 No. No. x mm Ohm/Km mm mm mm mm Kg/Km -

1.5

5 7x 0.52 12.1 0.8 0.8 1.8 16.6 500 CPA-TA105-UW15B

7 7x 0.52 12.1 0.8 0.8 1.8 18.0 550 CPA-TA107-UW15B

10 7x 0.52 12.1 0.8 0.8 1.8 21.0 770 CPA-TA110-UW15B

12 7x 0.52 12.1 0.8 1.6 1.8 23.3 1080 CPA-TA112-UW15B

14 7x 0.52 12.1 0.8 1.6 1.8 24.2 1140 CPA-TA114-UW15B

16 7x 0.52 12.1 0.8 1.6 1.8 25.0 1260 CPA-TA116-UW15B

19 7x 0.52 12.1 0.8 1.6 1.8 26.0 1370 CPA-TA119-UW15B

24 7x 0.52 12.1 0.8 1.6 1.8 28.9 1620 CPA-TA124-UW15B

30 7x 0.52 12.1 0.8 1.6 1.8 31.0 1850 CPA-TA130-UW15B

37 7x 0.52 12.1 0.8 1.6 1.9 34.0 2250 CPA-TA137-UW15B

44 7x 0.52 12.1 0.8 2.0 2.0 37.3 2560 CPA-TA144-UW15B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Stranded Copper Conductors PVC Insulation, Steel Wire Armoured, PVC Sheathed

Page 69: Special Cables Catalogue

C 11

Stranded Copper Conductors PVC Insulation, Steel Wire Armoured, PVC Sheathed

Conductor size

Number of

Cores

ConductorNominal insulation thickness

NominalDiameter of steel

wire

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC – codeNo.x

dia.

Max. DC Res. At

20oC

mm2 No.No. x mm

Ohm /Km

mm mm mm mm Kg/Km -

2.5

5 7x 0.67 7.41 0.8 0.8 1.8 17.8 600 CPA-TA105-UW18B7 7x 0.67 7.41 0.8 0.8 1.8 19.2 660 CPA-TA107-LW18B10 7x 0.67 7.41 0.8 1.6 1.8 23.8 1160 CPA-TA110-LW18B12 7x 0.67 7.41 0.8 1.6 1.8 25.0 1280 CPA-TA112-LW18B14 7x 0.67 7.41 0.8 1.6 1.8 26.0 1390 CPA-TA114-LW18B16 7x 0.67 7.41 0.8 1.6 1.8 27.0 1510 CPA-TA116-UW18B19 7x 0.67 7.41 0.8 1.6 1.9 28.3 1670 CPA-TA119-LW18B24 7x 0.67 7.41 0.8 1.6 1.9 31.4 2030 CPA-TA124-LW18B30 7x 0.67 7.41 0.8 1.6 1.9 34.5 2450 CPA-TA130-LW18B37 7x 0.67 7.41 0.8 1.6 2.0 37.4 2870 CPA-TA137-LW18B44 7x 0.67 7.41 0.8 2.0 2.1 40.5 3280 CPA-TA144-LW18B

4.0

5 7x 0.85 4.61 1.0 1.6 1.8 20.8 780 CPA-TA105-UW21B7 7x 0.85 4.61 1.0 1.6 1.8 23.5 1190 CPA-TA107-LW21B10 7x 0.85 4.61 1.0 1.6 1.8 27.2 1510 CPA-TA110-LW21B12 7x 0.85 4.61 1.0 1.6 1.8 29.0 1700 CPA-TA112-LW21B14 7x 0.85 4.61 1.0 1.6 1.8 30.0 1850 CPA-TA114-LW21B16 7x 0.85 4.61 1.0 1.6 1.9 31.6 2040 CPA-TA116-LW21B19 7x 0.85 4.61 1.0 1.6 1.9 33.0 2260 CPA-TA119-UW21B24 7x 0.85 4.61 1.0 2.0 2.1 38.4 3070 CPA-TA124-LW21B30 7x 0.85 4.61 1.0 2.0 2.1 41.3 3560 CPA-TA130-LW21B37 7x 0.85 4.61 1.0 2.0 2.2 43.2 4120 CPA-TA137-LW21B

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 70: Special Cables Catalogue

D. LAN AND TeLephoNe CAbLesD. LAN And Telephone Cables

Page 71: Special Cables Catalogue

Unscreened Twisted Pairs (UTP), Data Cable - Category. 5e................................................................... 2

Foil Screened Twisted Pairs (STP), Data Cable - Category. 5e................................................................. 3

Unscreened Twisted Pairs (UTP), Data Cable - Category. 6..................................................................... 4

Telephone Cable, PVC Insulated Multipairs .............................................................................................. 5

D. LAN And Telephone Cables

Page 72: Special Cables Catalogue

D 2

Unscreened Twisted Pairs (UTP) Data Cable – Category 5e

Frequency(MHz)

Characteristic impedance

(ohms)

MaximumAttenuation

( dB /100m @ 20oC )

Near End Cross talkMinimum

Minimum Structural Return Loss

(dB) at 100mm

1 100 + 15% 2.1 65 23

4 100 + 15% 4.1 56 23

10 100 + 15% 6.5 50 23

16 100 + 15% 8.3 47 23

20 100 + 15% 9.3 46 23

31.25 100 + 15% 11.7 43 21

62.5 100 + 15% 17.0 38 18

100 100 + 15% 22.0 36 16

125 100 + 15% 25.0 34 16

ELECTRICAL CHARACTERISTICS

Application: The cable is used for Local Area Computer Networks mainly in office or business environments.

Engineering Specification:

Type: UTP- Cat 5e

Standard: TIA / EIA 568 A, ISO / IEC 11801

Conductor: 24 AWG (0.528mm) solid bare conductor

insulation: Solid polyethylene, diameter 0.95mm

Pairs: 2 insulated conductors twisted together, Lay varied to minimize crosstalk

Assembly: 4 pairs twisted together

Sheath: Flame retardant PVC Grey RAL 7032, 5.86mmnominal diameter

Pair Colours: One Pair : blue & white / blueTwo Pairs : orange & white / orange Three Pairs : green & white / greenFour Pairs : brown & white / brown

Bending radius: 8 x O.D during installation

Temperature range during operation: +5oC up to + 50oC

Pakaging Available in easy – pull boxes of 1000 feet (305m) capacity. This assures the cable will not be damaged during installation due to the “figure 8” internal coiling.It also enables easy, tidy storage before and during installation.

UIC

Els

ewed

y LA

N C

at. 5

e U

TP

Page 73: Special Cables Catalogue

D 3

Foil Screened Twisted Pairs (STP)Data Cable – Category 5e

Application: The cable is used for Local Area Computer Networks mainly in electrically noisy office or industrial environments.

Engineering Specification:

Type: STP- Cat 5e

Standard: TIA/ EIA 568 A, ISO / IEC 11801

Conductor: 24 AWG (0.528mm) solid bare conductor

insulation: Solid polyethylene, diameter 1.09mm

Pairs: 2 insulated conductors twisted together, lay varied to minimize crosstalk

Assembly: 4 pairs twisted together

Screen: Aluminium polyester tape and 0.5mm plain or tinned copper drain wire

Pair Colours: One Pair : blue & white / blueTwo Pairs : orange & white / orange Three Pairs : green & white / greenFour Pairs : brown & white / brown

Bending radius: 8 x O.D during installation

Temperature range during operation: +5oC up to + 50oC

Pakaging Available in easy – pull boxes of 1000 feet (305m) capacity. This assures the cable will not be damaged during installation due to the “figure 8” internal coiling.It also enables easy, tidy storage before and during installation.

ELECTRICAL CHARACTERISTICS Frequency

(MHz)Characteristic impedance

(ohms)Maximum Attenuation

( dB /100m @ 20oC )Near End Cross talk

Minimum

Minimum Structural Return Loss

(dB) at 100mm

0.772 - 1.8 64 -

1 100 + 15% 2.0 62 23

4 100 + 15% 4.1 53 23

10 100 + 15% 6.5 47 23

16 100 + 15% 8.2 44 23

20 100 + 15% 9.2 42 23

31.25 100 + 15% 11.7 39 21

62.5 100 + 15% 17.0 35 18

100 100 + 15% 22.0 32 16

125 100 + 15% 25.0 32 16

UIC

Els

ewed

y LA

N C

at. 5

e S

TP

Page 74: Special Cables Catalogue

D 4

Unscreened Twisted Pairs (UTP)Data Cable – Category 6

Frequency(MHz)

Characteristic impedance

(ohms)

MaximumAttenuation

( dB /100m @ 20oC )

Near End Cross talkMinimum

Minimum Structural Return Loss

(dB) at 100mm

1 100 ± 15% 1.9 80.0 78.0

4 100 ± 15% 3.8 74.0 70.3

10 100 ± 15% 6.0 68.0 62.2

16 100 ± 15% 7.6 64.0 56.6

20 100 ± 15% 8.6 62.2 53.8

31.25 100 ± 15% 10.9 59.0 48.6

62.5 100 ± 15% 15.8 54.0 39.2

100 100 ± 15% 20.5 50.0 31.2

125 100 ± 15% 20.9 48.0 27.1

200 100 ± 15% 27.0 42.0 15.0

ELECTRICAL CHARACTERISTICS

Application: The cable is used for Local Area Computer Networks where performance greater than that available from category 5 specification is required.

Engineering Specification:

Type: UTP- Cat 6

Standard: TIA/ EIA 568 A, ISO / IEC 11801

Conductor: 24 AWG (0.54mm) solid bare conductor

insulation: Solid polyethylene, diameter 0.97mm

Pairs: 2 insulated conductors twisted together, Lay varied to minimize crosstalk

Assembly: 4 pairs twisted together

Sheath: Flame retardant PVC Grey RAL 7032, 5.94mmnominal diameter

Pair Colours: One Pair : blue & white / blueTwo Pairs : orange & white / orange Three Pairs : green & white / greenFour Pairs : brown & white / brown

Bending radius: 8 x O.D during installation

Temperature range during operation: +5oC up to + 50ohC

Pakaging Available in easy – pull boxes of 1000 feet (305m) capacity. This assures the cable will not be damaged during installation due to the “figure 8” internal coiling.It also enables easy, tidy storage before and during installation.

UIC

Els

ewed

y LA

N C

at. 5

e U

TP

Page 75: Special Cables Catalogue

D 5

Telephone CablePVC Insulated Multipairs

No. of Pairs

AWire

BWire

No. ofPairs

AWire

BWire

Unit No. Colour of Bindings

1 white Blue 11 Black Blue 1 Blue

2 White Orange 12 Black Orange 2 Orange

3 White Green 13 Black Green 3 Green

4 White Brown 14 Black Brown 4 Brown

5 White Grey 15 Black Grey 5 Grey

6 Red Blue 16 Yellow Blue 6 White

7 Red Orange 17 Yellow Orange 7 Red

8 Red Green 18 Yellow Green 8 Black

9 Red Brown 19 Yellow Brown 9 Yellow

10 Red Grey 20 Yellow Grey 10 Violet

COLOUR CODE OF INSULATION

Pakaging Cables supplied on coils of (200m) or in non-returnable wooden drums.

Application: The cable is used for Indoor installation and interconnection of Transmission, Telephone, Telegraph and Electronic equipment.

Engineering Specification:

Standard: IEC-189 & TC-113

Conductor: Solid, plain / tinned copper.

insulation: PVC rated 70oC as per IEC 189.2

Assembly: Cores are twisted into pairs and pairs twisted together to form a cable core

Sheath: Polyvinylchloride as per IEC 189-2 and rip cord is provided under the sheath for easy stripping

Temperature rating: +5ºC to +50ºC during operation

UIC

Els

ewed

y Te

leph

one

Cab

le

Page 76: Special Cables Catalogue

D 6

Telephone CablePVC Insulated Multipairs

Conductor size

Number of

pairs

Conductor Nominal insulation thickness

Nominal sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At

20oC

mm2 No. No. x mm Ohm /Km mm mm Mm Kg/Km -

0.4

1 1x0.4 153.0 0.15 0.6 3.0 12 TEL04-1U

2 1x0.4 153.0 0.15 0.6 4.1 19 TEL04-2U

3 1x0.4 153.0 0.15 0.6 4.2 23 TEL04-3U

4 1x0.4 153.0 0.15 0.6 4.6 28 TEL04-4U

5 1x0.4 153.0 0.15 0.6 5.0 33 TEL04-5U

6 1x0.4 153.0 0.15 0.7 5.6 40 TEL04-6U

7 1x0.4 153.0 0.15 0.7 5.9 44 TEL04-7U

10 1x0.4 153.0 0.15 0.7 6.7 57 TEL04-10U

15 1x0.4 153.0 0.15 0.7 7.9 79 TEL04-15U

20 1x0.4 153.0 0.15 0.8 9.1 104 TEL04-20U

25 1x0.4 153.0 0.15 0.8 10.0 125 TEL04-25U

30 1x0.4 153.0 0.15 0.8 10.7 143 TEL04-30U

40 1x0.4 153.0 0.15 0.9 12.4 191 TEL04-40U

50 1x0.4 153.0 0.15 0.9 13.6 230 TEL04-50U

60 1x0.4 153.0 0.15 0.9 14.7 270 TEL04-60U

80 1x0.4 153.0 0.15 1.0 16.9 355 TEL04-80U

100 1x0.4 153.0 0.15 1.0 18.6 430 TEL04-100U

200 1x0.4 153.0 0.15 1.4 28.0 1012 TEL04-200U

300 1x0.4 153.0 0.15 1.5 33.4 1486 TEL04-300U

400 1x0.4 153.0 0.15 1.6 38.4 1952 TEL04-400U

0.5

1 1x0.5 97.8 0.15 0.6 3.4 16 TEL05-1U

2 1x0.5 97.8 0.15 0.6 4.8 6 TEL05-2U

3 1x0.5 97.8 0.15 0.6 4.9 32 TEL05-3U

4 1x0.5 97.8 0.15 0.6 5.4 38 TEL05-4U

5 1x0.5 97.8 0.15 0.6 5.9 45 TEL05-5U

6 1x0.5 97.8 0.15 0.7 6.6 56 TEL05-6U

7 1x0.5 97.8 0.15 0.7 7.0 63 TEL05-7U

10 1x0.5 97.8 0.15 0.7 8.0 82 TEL05-10U

15 1x0.5 97.8 0.15 0.7 9.5 114 TEL05-15U

20 1x0.5 97.8 0.15 0.8 10.9 150 TEL05-20U

25 1x0.5 97.8 0.15 0.8 12.0 180 TEL05-25U

30 1x0.5 97.8 0.15 0.9 13.2 215 TEL05-30U

40 1x0.5 97.8 0.15 0.9 14.9 280 TEL05-40U

50 1x0.5 97.8 0.15 0.9 16.5 340 TEL05-50U

60 1x0.5 97.8 0.15 0.9 17.9 400 TEL05-60U

80 1x0.5 97.8 0.15 1.0 20.5 520 TEL05-80U

100 1x0.5 97.8 0.15 1.0 22.7 640 TEL05-100U

200 1x0.5 97.8 0.15 1.5 30.6 1350 TEL05-200U

300 1x0.5 97.8 0.15 1.6 37.0 2000 TEL05-300U

TECHNICAL INFORMATION

Page 77: Special Cables Catalogue

D 7

Telephone CablePVC Insulated Multipairs

Conductor size

Number of

pairs

Conductor Minimum insulation thickness

Minimum sheath

thickness

Approximate overall

diameter

Approximatenet

weightUIC - code

No.x dia.Max. DC Res. At

20oC

Mm2 No. No. x mm Ohm /Km mm mm Mm Kg/Km -

0.6

1 1x0.6 67.9 0.15 0.6 3.6 19 TEL06-1U

2 1x0.6 67.9 0.15 0.6 5.1 31 TEL06-2U

3 1x0.6 67.9 0.15 0.6 5.2 38 TEL06-3U

4 1x0.6 67.9 0.15 0.6 5.8 47 TEL06-4U

5 1x0.6 67.9 0.15 0.6 6.4 57 TEL06-5U

6 1x0.6 67.9 0.15 0.7 7.1 69 TEL06-6U

7 1x0.6 67.9 0.15 0.7 8.7 77 TEL06-7U

10 1x0.6 67.9 0.15 0.7 10.5 103 TEL06-10U

15 1x0.6 67.9 0.15 0.8 12.0 150 TEL06-15U

20 1x0.6 67.9 0.15 0.9 13.2 195 TEL06-20U

25 1x0.6 67.9 0.15 0.9 14.3 235 TEL06-25U

30 1x0.6 67.9 0.15 0.9 16.2 275 TEL06-30U

40 1x0.6 67.9 0.15 0.9 17.9 355 TEL06-40U

50 1x0.6 67.9 0.15 0.9 19.6 430 TEL06-50U

60 1x0.6 67.9 0.15 1.0 22.3 515 TEL06-60U

80 1x0.6 67.9 0.15 1.0 25.1 670 TEL06-80U

100 1x0.6 67.9 0.15 1.2 26.0 845 TEL06-100U

150 1x0.6 67.9 0.15 1.4 26.7 1240 TEL06-150U

200 1x0.6 67.9 0.15 1.5 30.71 1260 TEL06-200U

250 1x0.6 67.9 0.15 1.6 34.0 2000 TEL06-250U

0.8

1 1x0.8 37.5 0.25 0.7 6.4 30 TEL085-1U

2 1x0.8 37.5 0.25 0.7 6.5 50 TEL08-2U

3 1x0.8 37.5 0.25 0.7 7.3 62 TEL08-3U

4 1x0.8 37.5 0.25 0.7 7.9 78 TEL08-4U

5 1x0.8 37.5 0.25 0.7 9.0 91 TEL08-5U

6 1x0.8 37.5 0.25 0.9 9.5 115 TEL08-6U

7 1x0.8 37.5 0.25 0.9 11.0 128 TEL08-7U

10 1x0.8 37.5 0.25 0.9 13.1 171 TEL08-10U

15 1x0.8 37.5 0.25 0.9 14.8 240 TEL08-15U

20 1x0.8 37.5 0.25 0.9 16.5 310 TEL08-20U

25 1x0.8 37.5 0.25 1.0 17.9 385 TEL08-25U

30 1x0.8 37.5 0.25 1.0 20.3 450 TEL08-30U

40 1x0.8 37.5 0.25 1.0 22.9 580 TEL08-40U

50 1x0.8 37.5 0.25 1.2 24.8 735 TEL08-50U

60 1x0.8 37.5 0.25 1.2 28.7 865 TEL08-60U

80 1x0.8 37.5 0.25 1.4 31.7 1150 TEL08-80U

100 1x0.8 37.5 0.25 1.4 32.5 1410 TEL08-100U

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 78: Special Cables Catalogue

E. Coaxial Cables

Page 79: Special Cables Catalogue

E 1

E. Coaxial CablesMATV Cables …………………………………………………………………...........…......................................... 2

RG Cables ……………………………………….....................................................……………………….…….. 4

Page 80: Special Cables Catalogue

E 2

Coaxial CablesMATV Cables

TECHNICAL INFORMATION

Application: TV patented coaxial cables for satellite and digital installations.

Engineering Specification:

Conductor: Solid plain copper

insulation: Cellular polyethylene

Shield: Aluminium polyester with tinned or plain copper braid

Jacket: Polyvinylchloride, white or black colour

Packing: Available in easy – pull boxes 100m or 500m on wooden drums

Type: RG - 59 / U MATV

ConductorDiameter

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

mm mm % mm Ohms PF / m % MHz dB / 100 m

0.81 3.71 100% Al /PET 6.16 75 + 2% 53 82 100 8.2

Tape + 40% 200 11.5

T. CU braid 400 16.1

700 21.3

Type: RG - 11 / U MATV

ConductorDiameter

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

mm mm % mm Ohms PF / m % MHz dB / 100 m

1.63 7.25 100% Al /PET 10.3 75 + 2% 53 82 100 3.9

Tape + 40% 200 5.6

T. CU braid 400 7.9

700 11.5

UIC

Els

ewed

y C

oax

ial C

able

s 75

oh

ms

Page 81: Special Cables Catalogue

E 3

Coaxial CablesMATV Cables

TECHNICAL INFORMATIONType: RG - 6 / U MATV

ConductorDiameter

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

mm mm % mm Ohms PF / m % MHz dB / 100m

1.02 4.59 100% Al /PET 7.0 75 + 2% 53 82 100 6.6

Tape + 40% 200 9.2

T. CU braid 400 13.1

700 17.4

Type: CF -160 MATV

ConductorDiameter

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

Mm mm % mm Ohms PF / m % MHz dB / 100 m

1.14 5.1 100% Al /PET 7.0 75 + 2% 53 82 100 6

Tape + 70% 300 9

T. CU braid 500 13

800 16

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Page 82: Special Cables Catalogue

E 4

Coaxial CablesRG Cables

Type: RG - 58 / U

ConductorMat. /Const.

InsulationDiameter

Shield type

& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

mm mm % mm Ohms PF / m % MHz dB / 100 m

CU / 1x0.82 2.95 96% 4.9 53 + 2% 93 66 100 14.8

T. CU braid 200 22.3

400 32.8

700 45.9

Application: Cables used for transmitting and receiving high frequency signals in radio frequency devices and connections.

Engineering Specification:

Conductor: Solid or stranded plain / tinned copper

insulation: Solid polyethylene

Shield: Plain or tinned copper braid

Jacket: Polyvinylchloride, white or black colour

Packing: Available in easy – pull boxes 100m or 500m on wooden drums

TECHNICAL INFORMATION

UIC

Els

ewed

y C

oax

ial C

able

s 50

oh

ms

Page 83: Special Cables Catalogue

E 5

Coaxial CablesRG Cables

Type: RG -216

ConductorMat. /Const.

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

Mm mm % mm Ohms PF / m % MHz dB / 100 m

CU / 7 x 0.4 7.25 95% 10.8 75 + 2% 67.3 66 100 6.6

2 CU braid 200 9.5

400 13.8

700 19.0

Type: RG - 8 / U

ConductorMat. /Const.

InsulationDiameter

Shield type& Coverage

OuterDiameter

NominalImpedance

NominalCapacitance

NominalVelocity of

Propag.

Nominal AttenuationAt 20oC

Mm mm % mm Ohms PF / m % MHz dB / 100 m

CU / 7 x 0.74 7.16 97% 10.29 52 + 2% 96.8 66 100 6.2

CU braid 200 8.9

400 13.4

700 26.2

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

Page 84: Special Cables Catalogue

F. Automotive Wires

Page 85: Special Cables Catalogue

F. Automotive Wires

PVC Insulation …………………………………………………………...................................…………….………. 2

Heat – Resistant PVC Insulation…………….…………………………………....…………….............................. 3

Heat – Pressure Resistant PVC Insulation …..………………………………….……..……................................ 4

Cold – Resistant PVC Insulation …………………………………..........……...…….……................................. 5

Concentric Conductors with PVC Insulation …..………………………………….……..……......................... 6

PVC Thin Insulation ……………………………………………………………………………................................. 7

Page 86: Special Cables Catalogue

Automotive WiresPVC Insulation

F 2

Application: This wire is used in the manufacture of electrical harnesses for cars and other automotive products.

Engineering Specification:

Conductor:Soft annealed stranded fine wires according to DIN ISO 6722, part 3

insulation: Polyvinylchloride, according to DIN ISO 6722, part 2, class A

Colour coding : Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -40oC up to + to 90 oC

Conductor size

Conductor Nominal insulation thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter Max. DC Res. At

20oC

mm2 No. x mm mm Ohm /Km mm mm Kg/Km -

0.5 16 x 0.21 1.0 37.1 0.6 2.2 9 CHC-F0101-AU050

0.75 24 x 0.21 1.2 24.7 0.6 2.4 12 CHC-F0101-AU080

1.0 32 x 0.21 1.35 18.5 0.6 2.6 15 CHC-F0101-AU120

1.5 30 x 0.26 1.7 12.7 0.6 2.9 20 CHC-F0101-AU150

2 40 x 0.26 2.0 9.42 0.6 3.2 26 CHC-F0101-AU170

2.5 50 x 0.26 2.2 7.6 0.7 3.6 32 CHC-F0101-AU180

3 60 x 0.26 2.5 6.0 0.7 3.9 37 CHC-F0101-AU180

4 56 x 0.31 2.75 4.71 0.8 4.4 49 CHC-F0101-AU210

6 84 x 0.31 3.3 3.14 0.8 4.9 68 CHC-F0101-AU230

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 87: Special Cables Catalogue

Application: This wire is used in the manufacture of electrical harnesses for cars and other automotive products.

Engineering Specification:

Conductor:Soft annealed stranded fine wires according to DIN ISO 6722, part 3

insulation: Heat – resistant polyvinylchloride, according to DIN ISO 6722, part 2, class B

Colour coding : Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -40oC up to + to 105 oC

Automotive WiresHeat – Resistant PVC Insulation

F 3

Conductor size

Conductor Nominal insulation thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter Max. DC Res. At

20oCmm2 No. x mm mm Ohm /Km mm mm Kg/Km -

0.5 16 x 0.21 1.0 37.1 0.6 2.2 9 CSC-F0101-AU050

0.75 24 x 0.21 1.2 24.7 0.6 2.4 11 CSC-F0101-AU080

1.0 32 x 0.21 1.35 18.5 0.6 2.6 14 CSC-F0101-AU120

1.5 30 x 0.26 1.7 12.7 0.6 2.9 19 CSC-F0101-AU150

2.5 50 x 0.26 2.2 7.6 0.7 3.6 31 CSC-F0101-AU180

4 56 x 0.31 2.75 4.71 0.8 4.4 49 CSC-F0101-AU210

6 84 x 0.31 3.3 3.14 0.8 4.9 68 CSC-F0101-AU230

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 88: Special Cables Catalogue

Application: This wire is used in the manufacture of electrical harness for cars and other automotive products.

Engineering Specification: Conductor:Soft annealed stranded fine wires according to DIN ISO 6722, part 3

insulation: Heat – resistant polyvinylchloride, according to DIN ISO 6722, part 2 class B (hot pressure resistance test at 120oC)

Colour coding : Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -20oC up to + to 125 oC

Automotive WiresHeat – Pressure Resistant PVC Insulation

F 4

Conductor size

Conductor Nominal insulation thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter Max. DC Res. At

20oC

mm2 No. x mm mm Ohm /Km mm mm Kg/Km -

0.5 16 x 0.21 1.0 37.1 0.6 2.2 9 CZC-F0101-AU050

0.75 24 x 0.21 1.2 24.7 0.6 2.4 11 CZC-F0101-AU080

1.0 32 x 0.21 1.35 18.5 0.6 2.6 14 CZC-F0101-AU120

1.5 30 x 0.26 1.7 12.7 0.6 2.9 19 CZC-F0101-AU150

2.5 50 x 0.26 2.2 7.6 0.7 3.6 30 CZC-F0101-AU180

3 60 x 0.26 2.5 6.21 0.7 3.9 36 CZC-F0101-AU190

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 89: Special Cables Catalogue

Automotive WiresCold – Resistant PVC Insulation

Application: This wire is used in the manufacture of electrical harness for cars and other automotive products.

Engineering Specification:

Conductor:Soft annealed stranded super fine wires

insulation: Cold- resistant polyvinylchloride, according to DIN ISO 6722, part 2, class A. (Cold pressure resistance test at 120oC)

Colour coding : Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -40oC up to + to 90 oC

F 5

Conductor size

Conductor Nominal insulation thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter Max. DC Res. At

20oC

mm2 No. x mm Mm Ohm /Km mm mm Kg/Km -

0.5 28 x 0.16 1.1 37.7 0.6 2.3 9 CFC-F0101-AU050

0.75 24 x 0.16 1.3 25.1 0.6 2.5 12 CFC-F0101-AU080

1.0 57 x 0.16 0.5 18.8 0.6 2.7 15 CFC-F0101-AU120

1.5 84 x 0.16 1.8 12.4 0.6 3.0 20 CFC-F0101-AU150

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 90: Special Cables Catalogue

Automotive WiresConcentric Conductors with PVC Insulation

F 6

Conductor size

ConductorNominal insulation thickness

Approximate overall

diameter

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter Max. DC Res. At

20oC

mm2 No. x mm mm Ohm /Km mm mm Kg/Km -

0.35 7 x 0.26 0.8 52.0 0.2 1.3 4.5 CVE-F0101-AU030

0.5 19 x 0.19 1.0 37.1 0.22 1.6 6.6 CVE-F0101-AU050

0.75 19 x 0.23 1.2 24.7 0.24 1.9 9.0 CVE-F0101-AU080

1.0 19 x 0.32 1.35 18.5 0.24 2.1 11.0 CVE-F0101-AU120

1.5 19 x 0.32 1.7 12.7 0.24 2.4 16.0 CVE-F0101-AU150

2.0 19 x 0.37 2.0 9.42 0.24 2.6 22.5 CVE-F0101-AU170

2.5 19 x 0.41 2.2 7.6 0.28 3.0 26.0 CVE-F0101-AU180

Application: This wire is used in the manufacture of electrical harnesses for cars and other automotive products.

Engineering Specification: Conductor:Concentric stranded copper conductor according to DIN ISO 72551, part 6, type A

insulation: Polyvinylchloride, according to DIN ISO 72551, part 5

Colour coding : Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -40oC up to + to 105 oC

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 91: Special Cables Catalogue

Automotive WiresPVC Thin Insulation

F 7

Conductor size

Conductor Details Minimum insulation thickness

Approximate overall

diameter

MinimumConcent.

Factor

Approximatenet

weightUIC – code

No.x dia.Approx.

Diameter

Max. DC Res. At 20oC

mm2 No. x mm mm Ohm /Km mm mm % Kg/Km -

0.35 12 x 0.21 0.9 52.0 0.2 1.4 55 4.5 CQE-F0101-AU030

0.5 16 x 0.21 1.0 37.1 0.22 1.6 55 6.6 CQE-F0101-AU050

0.75 24 x 0.21 1.2 24.7 0.24 1.9 55 9.0 CQE-F0101-AU080

1.0 32 x 0.21 1.35 18.5 0.24 2.1 55 11.0 CQE-F0101-AU120

1.5 30 x 0.26 1.7 12.7 0.24 2.4 55 16.0 CQE-F0101-AU150

2.0 30 x 0.31 1.9 9.31 0.24 2.6 55 22.5 CQE-F0101-AU170

2.5 50 x 0.26 2.2 7.6 0.28 3.0 55 26.0 CQE-F0101-AU180

3 45 x 0.31 2.4 6.21 0.28 3.2 55 32.5 CQE-F0101-AU190

4 56 x 0.31 2.75 4.7 0.32 3.7 55 42.0 CQE-F0101-AU210

6 84 x 0.31 3.30 3.10 0.32 4.3 55 61.0 CQE-F0101-AU230

Application: This wire is used in the manufacture of electrical harnesses for cars and other automotive products.

Engineering Specification:

Conductor:Fine wires stranded copper conductor according to DIN ISO 72551, part 6, type B.

insulation: Polyvinylchloride, according to DIN ISO 72551, part 5

Colour coding: Two colours are marked by two diametrically opposed longitudinal stripes

Packing: Cables are packed in carton boxes

Temperature range: -40oC up to + to 105 oC

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

Page 92: Special Cables Catalogue

G. Appliance Cables And Cords

Page 93: Special Cables Catalogue

G. Appliance Cables And Cords

Appliance Cables, Flexible PVC Cables, HO5VV-F .................................................................................... 2

Appliance Cords, Flat Cords ......................................................................................................................... 4

Appliance Cords, Round Cords with Double Earthing System .................................................................. 5

Page 94: Special Cables Catalogue

High Resolution Pls

Page 95: Special Cables Catalogue

G 3

Flexible PVC CablesHO5VV-F

Application: These cables can be used for domestic cooking and heating appliances provided that the cable does not come into contract with the heating elements.

Engineering Specification:

Standard: BS 6500

Rated Voltage: 300 / 500 V

Conductor: Stranded plain annealed copper as per BS - 6360

insulation: PVC type TI – 2 as per BS - 6746

Colour code: Blue, Brown

Three cores: Green / yellow, Blue, Brown

Four Cores: Green / yellow, Black, Blue, Brown.

Assembly: Cores twisted together to form a round cable

Sheath: PVC type TM-2 as per BS6746 - white colour

Temperature rating: +5oC up to + 70oC

Conductor size

Conductor Nominal insulation thickness

NominalSheath

Thickness

Approximateoverall

diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res. At

20oC

mm2 No. x mm Ohm /Km mm mm mm Kg/Km -

2 x 0.75 24 x 0.2 26.4 0.6 0.8 6.5 61 HO5VV-F2-2*0.75R

2 x 1.0 32 x 0.2 19.5 0.6 0.8 6.8 70 HO5VV-F2-2*1.0R

2 x 1.5 30 x 0.25 13.3 0.7 0.8 7.7 91 HO5VV-F2-2*1.5R

2 x 2.5 50 x 0.25 7.98 0.8 1.0 9.4 139 HO5VV-F2-2*2.5R

2 x 4 56 x 0.3 4.95 0.8 1.1 10.7 192 HO5VV-F2-2*4.0R

3 x 0.75 24 x 0.2 26.4 0.6 0.8 6.9 73 HO5VV-F2-3*0.75R

3 x 1.00 32 x 0.2 19.5 0.6 0.8 7.2 85 HO5VV-F2-3*1.0R

3 x 1.5 30 x 0.25 13.3 0.7 0.9 8.4 114 HO5VV-F2-3*1.5R

3 x 2.5 50 x 0.25 7.98 0.8 1.1 10.2 175 HO5VV-F2-3*2.5R

3 x 4 56 x 0.3 4.95 0.8 1.2 11.6 244 HO5VV-F2-3*4.0R

4 x 0.75 24 x 0.2 26.4 0.6 0.9 7.7 91 HO5VV-F2-4*0.75R

4 x 1.0 32 x 0.2 19.5 0.6 0.9 8.1 106 HO5VV-F2-4*1.0R

4 x 1.5 30 x 0.25 13.3 0.7 1.0 9.3 142 HO5VV-F2-4*1.5R

4 x 2.5 50 x 0.25 7.98 0.8 1.1 11.1 211 HO5VV-F2-4*2. 5R

4 x 4 56 x 0.3 4.95 0.8 1.2 12.6 297 HO5VV-F2-4*4.0R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

UIC

Els

ewed

y H

05V

V-F

300

500

V

Page 96: Special Cables Catalogue

G 4

Flexible PVC CablesHO3VV-F

Application: These cables are useful in domestic premises, kitchens, offices or light duties for light portable appliances.

Engineering Specification:

Standard: BS 6500

Rated Voltage: 300 / 300 V

Conductor: Stranded plain annealed copper as per BS - 6360

insulation: PVC type TI – 2 as per BS - 6746

Colour code: Blue, Brown

Three cores: Green / yellow, Blue, Brown

Four Cores: Green / yellow, Black, Blue, Brown

Assembly: Cores twisted together to form a round cableFor flat cables, two cores re laid parallel

Sheath: PVC type TM-2 as per BS6746 - white colour

Temperature rating: -5oC up to + 70oC

Conductor size

Conductor Nominal insulation thickness

NominalSheath

Thickness

Approximateoverall diameter

Approximatenet

weightUIC – code

No.x dia.Max. DC Res.

At 20oC

mm2 No. x mm Ohm /Km mm mm mm Kg/Km -

2 x 0.5 16 x 0.2 39.0 0.5 0.6 3.6 x 6.0 30 HO3VV-F2-2* 0.5F

2 x 0.5 16 x 0.2 39.0 0.5 0.6 5.2 40 HO3VV-F2- 2* 0.5R

2 x 0.75 24 x 0.2 26.4 0.5 0.6 3.9 x 6.4 40 HO3VV-F2- 2* 0.75F

2 x 0.75 24 x 0.2 26.4 0.5 0.6 5.7 49 HO3VV-F2- 2* 0.75R

3 x 0.5 16 x 0.2 39.0 0.5 0.6 5.6 48 HO3VV-F2- 3* 0.5R

3 x 0.75 24 x 0.2 26.4 0.5 0.6 6.0 60 HO3VV-F2- 3* 0.75R

4 x 0.5 16 x 0.2 39.0 0.5 0.6 6.1 58 HO3VV-F2- 4* 0.5R

4 x 0.75 24 x 0.2 26.4 0.5 0.6 6.6 72 HO3VV-F2- 4* 0.75R

• The above data are approximate and subject to normal manufacturing tolerance.

• Other types can be provided on specific request.

TECHNICAL INFORMATION

UIC

Els

ewed

y H

05V

V-F

300

300

V

Page 97: Special Cables Catalogue

G 5

Flat Cords:

Suitable Cables: HO3VV-F : 2 x 0.75

HO5VV-F : 2 x 0.75

HO5VV-F : 2 x 1.0

Group: PVC Pug for Safety Class II

Voltage rating

300 / 300 V & 300 / 500 V only allowed for double insulated appliances

Description: Straight flat plug without earthing contract

Material : Glass – reinforced polyamide, black or white colour

Permitted current rating: 2.5 Amps AC or 10 Amps AC

Permitted Voltage: 250 V AC

Pins: 4.0 mm Ø solid metal Pins, nickel – plated

Page 98: Special Cables Catalogue

G 6

Round Cords with Double Earthing System

Pins: 4.8 mm Ø solid metal Pins, nickel – plated

Suitable Cables: HO5VV-F : 3 G 0.75

HO5VV-F : 3 G 1.0

HO5VV-F : 3 G 1.5

Group: PVC Pug for Safety Class I

Voltage rating 300 / 500 V

Description: 2- pin angled plug with double earthing system

Material : PBTP 30% glass – reinforced, anthracite black or white colour

Permitted current rating: 10 / 16 Amps AC

Page 99: Special Cables Catalogue

G 7

Pins: 4.8 mm Ø solid metal Pins, nickel – plated

Group: PVC Plug for Safety Class I

Voltage rating: 300 / 300 V & 300 / 500 V

Description: 2 - pin angled plug with lateral earthing system

Material : PBTP 30% glass – reinforced, anthracite black or white colour

Permitted current rating: 10 / 16 Amps AC

Suitable Cables: HO3VV-F : 3 G 0.75

HO5VV-F : 3 G 0.75

HO5VV-F : 3 G 1.0

Round Cords with Double Earthing System

Page 100: Special Cables Catalogue

H. Technical Information

Page 101: Special Cables Catalogue

H. Technical information

Page 102: Special Cables Catalogue

H 2

Technical Information

DC resistance of conductor:DC resistance per unit length of the conductor at another conductor temperature t is given by:

Where: R = DC resistance at temperature to C Ω/KmRo = DC resistance at temperature 20oC Ω/Kmt = conductor temperature oC

20 = temperature coefficient at 20oC 1/oC

AC Resistance of Conductor: To calculate the AC resistance of the conductor at its operating temperature the following formula is used:

Where: KP and KS are proximity effect and skin effect factors

inductance: Self mutal inductance is defined as follows:

Where: L = Inductance in mH / KmK = A constant depending on the number of wires in the conductord = Conductor diameter in mmn = Axial spacing between cables in trefoil formation in mm = 1.26 x axial spacing between cables in flat formation in mm

R=RO [1+ 20 (t-20OC)]

Rac = R ( 1 + Kp + Ks)

L = K + 0.2 Ln 25d

Page 103: Special Cables Catalogue

H 3

Technical Information

Capacitance: The mutual capacitance of the pairs or adjacent cores shall not exceed a maximum of 250 PF/m at a frequency of 1KHz1- Mutual capacitance of unshielded twisted pair

2- Mutual capacitance of shielded twisted pair

3- Mutual capacitance of overall shielded & cables

Where: C : Mutual Capacitance In PF/m ε : Dielectric constant of insulation materialD : Diameter over insulation in mm d : Diameter over conductor in mm

L / R ratio: The L / R ratio for adjacent cores shall not exceed the following maximum value:

Conductormm2

Maximum L/R ratioµH / Ω

0.5 25

0.75 25

1.5 40

C =1.3D

fd

7.218

log

C =1.2D

fd

21.14

log

C =1.5D

fd

9.515

log

Page 104: Special Cables Catalogue

H 4

Technical Information

impedance Zo (ohms):

1- Unshielded twisted pair :

2- Shielded twisted pair :

3- Overall shield & cabled :

Where: C : Mutual Capacitance In PF/m ε : Dielectric constant of insulation materialf : Stranding factor depend on no. of wires in conductorD : Diameter over insulation in mmd : Diameter over conductor in mm

Attenuation: The power loss in an electrical system, in cables, generally expressed in decibels (dB) per unit length

Attenuation : (A) = 86.8

Where: A: Attenuation in dB per 100 ftR: Resistance (AC)G: ConductanceW: 2∏ f (f= test frequency MHz)

Velocity of Propagation: The speed of an electrical signal down a length of cable compared to speed in free space expressed as a percent. It is inversely proportional to the dielectric constant. Lowering the dielectric constant. Lowering the dielectric constant increases the velocity

Where: E : Dielectric constantL: InductanceC: Capacitance

Dielectric medium or material

Vp(%)

Air 100.0

Solid polyethylene 65.9

Foamed polyethylene 80.0

PVC 45.0

Zo =310

C

Zo =276

log 1.2Df(d)

Zo =347

log 1.5Df(d)

RGW

2

Vp =1

or Vp =1

Lc

Page 105: Special Cables Catalogue

H 5

Technical Information

Fire Resistant cables:

A cable can be described as fire resistant when it complies with the severe test in IEC 331 in which the middle

portion of a sample of cable 1200 mm long is supported by two metal rings 300 mm apart and exposed to the

flame from a tube type gas burner at 750oC. Simultaneously the rated voltage of the cable is applied continuously

throughout the test period. Furthermore, not less than 12 hours after the flame has been extinguished, the cable is

reenergized. No electrical failure must occur under these conditions.

Halogen Free Material:

What are Halogens?

Halogens are salts of the elements Fluorine, Chlorine, Bromine and lodine.

Fluorine and chlorine are important in cable design. For example; Flourine, Chlorine and Bromine are common

components of flame protection additives.

When is a cable Halogen–free?

The burning behavior of cables is very important for the safety of buildings and also in control plants.

Consequently the following points are important:

• Behavior under flame influence ie. the inflammability as the propagation of fire.

• Development of smoke density (darkening of emergency exits, hindrance of the fire fighters).

Cables produced of non halogen – free materials such as those with chlorine in the molecule – chain :

polyvinylchloride (PVC), chloroprene rubber (CR), chlorinated polyethylene (CM), have a better behavior in case

of fire.

These are barely combustible or not flammable and self-extinguishing, in case of fire molecules of Chlorine

(or Fluorine) are released which hinder the access of oxygen at the fire location and hence suffocate the flame.

The disadvantage of these materials is that the released Chlorine (or Flourine) atoms combine with hydrogen

which is decomposed from the plastic material as wel as hydro choleric acid or hydroflouoric acid from the existing

air. These compounds are extremely corrosive and toxic in consequence, damage by corrosion may be higher

than the damage caused by fire.

Halogen-free cables contain no halogens, le. the insulation and sheath materials of these cables are composed

of polymers of pure hydrocarbons. Burning these materials, produce no corrosive compounds or toxic gases, only

water vapor and carbon dioxide gas.

For maximum security halogen free cable must be hardly flammable and self-extinguishing . This is achieved by

using special polymer compounds, containing high percentages of flame protective materials.

Application:

Halogen-free cable are increasingly specified for public buildings and areas where large numbers of people may

be present.

Page 106: Special Cables Catalogue

H 6

Technical Information

LAN Cables:

The necessity to communicate through digital information, to share data, to reach calculation – resources and

to share costly devices has encourages the development of local area networks. A local area network (LAN) is

a computer network linking users in a small area. Generally, a local area network connects users located either

in the same office, or at the same floor, or in the same building. The success of local area networks is due to their

ability to satisfy communication needs at a reasonable price. Compatibility is a critical element.

Local area networks require high–speed channels for data–transmission, permitting the transfer of large blocks of

data, images, and video-signals.

The technology used in local networks can reach a transmission rate which is higher that 100 Mbps, Ie. higher

than that of traditional direct connections. Moreover, the traditionally low transfer – capacity of public

telecommunications is increasing therefore the distinction between direct connection, local area networks and

wide area networks is going to loose significance, at least as far as transmission – capacity is concerned.

The transmission media is the cable. Common media are phone-pairs, coaxial cables and purpose designed LAN

cables which are essentially extremely high performance telephone pairs, sometimes provided with shielding. This

kind of shielded cable is more immune to electrical interference and permits high speed transmission over longer

distances. Pairs are still the most versatile media for transmission and are often the best choice for new network

installations.

Attenuation:

The reduction in a transmitted signal as it passes through wires or equipment in an electrical circuit.

Frequency(MHz)

Maximum attenuation dB

0.1 N / A

1.0 2.5

4.0 4.8

10.0 7.5

16.0 9.4

20.0 10.5

31.25 13.1

62.5 18.4

100.0 23.2

MAXIMUM ATTENUATION VALUES OF CAT 5

Characteristic impedance: The nominal differential characteristic impedance of a cabling link shall be 100Ω at frequencies between 1 MHz and the highest specified frequency for the cabling class. The tolerance of the characteristic impedance in a given link shall not exceed the chosen nominal impedance by more than + 15Ω from 1Mhz up to the highest specified frequency for the class.

Page 107: Special Cables Catalogue

H 7

Technical Information

Frequency(MHz)

Maximum attenuation dB

1< F < 10 18

10< F < 16 15

16< F < 20 15

20< F < 100 10

Near end crosstalk loss (Next): The near–end crosstalk loss of a link shall meet or exceed the values shown in table below, and shall be consistent with the design values of cable length and cabling materials used.

Frequency(MHz)

Maximum attenuation dB

1.0 54

4.0 45

10.0 39

16.0 36

20.0 35

31.25 32

62.5 27

100 24

Attenuation to crosstalk loss ration (ASR): This is the difference between the crosstalk and the attenuation of the link in dB.ACR(dB) = an (dB)- a(dB).

Return loss: The return loss of the cabling, measured at any interface, shall meet or exceed the values shown in the table below:

MAXIMUM NEXT LOSS OF CAT 5

Page 108: Special Cables Catalogue

H 8

Technical InformationCoaxial Cable : A cable consisting of two cylindrical with a common axis, separated by a dielectric

Electrical Parameters:

1- Characteristic impedance:

2- Velocity of Propagation:

3- Capacitance:

4- inductance:

5- Braiding Details:

Braid angle:

Braid picks per cm:

Braid resistance:

Where:

D = Diameter under shield in mm

d = conductor diameter in mm

ε = dielectric constant of insulation

= 1.56 cellular polyethylene

= 2.26 solid polyethylene

C= number of carriers

n = number of wires in one carrier

M = D + build of braid on one shield wall in mm

e = diameter of each wire in mm

R = DC resistance of the braid in ohm/km

r = DC resistance of each wire in ohm/km

p = picks per cm

Degrees

Zo =138

logDd

Vp =100%

C =Dd

24.148

logPF / m

L = 0.459 log Dd

H / m

P = 0.394(c) tan 2 M

R = r

n (C) (cos )/km

= tan-12 (D+e)P

C

Page 109: Special Cables Catalogue

H 9

Technical Information

Packing:

1- LAN Cable:

Available in easy – pull boxes of 1000 feet (305m) capacity.This assures the cable will not be damaged during installation due to the “figure 8” coiling.It also enables easy, tidy storage before and during installation.

2 - Coaxial Cable: Available in easy – pull boxes of 100 m or 500m on wooden drum.

3 - Telephone Cable: Cables supplied on coils of (200m) or in non-returnable wooden drums.

4 - Automotive wires: Wires are packed in Carton boxes which reduces storage area & cost.Boxes may be delivered individually or as a solid cube on wooden pallet.

Page 110: Special Cables Catalogue

H 10

Technical Information

5- instrumentation, Fire Resistant and Control Cables:

International practice is to supply cables on wooden drums. At the customers request we will also supply on steel drums for improved on-site performance and handling.

DRUM DIMENSIONS

D D d1 B1 B2 W1 W2

600 300 85 410 530 16 300

700 350 85 410 530 20 350

800 400 85 410 530 24 400

1000 500 85 610 710 46 800

1250 580 85 580 680 60 1700

1400 700 85 800 950 160 2000

1600 700 110 800 950 170 2500

1800 920 110 900 1050 240 3000

2000 1020 110 1200 1350 335 4000

Where:

D : Flange diameter mm.

d : Barrel diameter mm.

d1: Axis hole diameter mm.

B1 : Distance between flanges mm.

B2 : Overall width mm.

W1: Approximate net weight of drum Kg.

W2: Maximum gross weight of drum Kg.

Page 111: Special Cables Catalogue

H 11

Technical Information

Multiply By To Multiply By To obtain

Weight – imperial Length – imperial Ounces 28.495 grams Mils 0.001 InchesPounds (AV) 453.59 grams Mils 0.0254 mmPounds (AV) 0.45359 kilograms Inches 1000 MilsTons (short) 907.19 kilograms Inches 25.40 MmTons (long) 1016.05 kilograms Inches 2.54 Cm

Weight – Metric Feet 30.48 CmGrams 0.03527 Ounces Feet 0.3048 MetersGrams 0.002205 Pounds Feet (thousands of) 0.3048 KilometersKilograms 35.274 Ounces Yards 0.9144 MetersKilograms 2.2046 Pounds miles 1.3093 KilometersKilograms 0.001102 Tons (short) Length-metricKilograms 0.0009842 Tone (long) Millimeters 39.37 Mils

Millimeters 0.03937 inchesMiscellaneous – imperial Centimeters 0.3937 InchesPounds per 1000 feet 1.48816 Kg/ Km Centimeters 0.032808 FeetPounds per mile 0.28185 Kg/ Km Meters 39.37 InchesPounds per square inch 0.0007031 Kg. per square mm. Meters 3.2808 FeetPounds per square inch 0.07031 Kg. per square cm Meters 1.0936 YardsPounds per cubic 27.68 Grams per cubic cm Kilometers 3280.83 FeetFeet per second 18.288 Meters per minute Kilometers 0.62137 MilesFeet per second 1.09728 Kilometers per hour Miles per hour 1.60935 Kilometers per hour Area – imperial Ohms per 1000 feet 3.28083 Ohms per kilometer Square mils 1.2732 Circular milsOhms per mile 0.62137 Ohms per kilometer Square mils 0.000001 Square inches Decibels per 1000 feet 3.28083 Decibels per kilometer Circular mils 0.7854 Square mils Decibels per mile 0.62137 Decibels per kilometer Circular mils 0.0000007954 Square inchesDecibels 0.1153 nepers. Square mils 0.0005037 Square mm.

Square inches 1000000 Square milsMiscellaneous – Metric Square inches 1273240 Circular milsKg / Km 0.67197 Pounds per 100 feet Square inches 645.16 Square mmKg / Km 3.54795 Pound per mile Square inches 645.16 Square cm.Kg. per square mm 1422.34 Pound per square inch Square feet 0.09290 Square metersKg. per square cm 14.2234 Pound per square inch Square yards 0.8361 Square metersGrams per cubic cm 0.03613 Pound per cubic inchMeters per minute 0.05468 Feet per second Area – Metric Kilometers per hour 0.91134 Feet per second Square millimeters 1973.52 Circular mils Kilometers per hour 0.62137 Miles per hour Square millimeters 0.00155 Square inchesOhms per kilometer 0.3048 Ohms per 1000 feet. Square centimeters 0.155 Square inchesOhms per kilometer 1.6093 Ohms per mile Square meters 10.7638 Square feetDecibels per kilometer 0.3048 Decibels per 1000 feet Square meters 1.19599 Square yardsDecibels per kilometer 1.6093 Decibels per mile

Volume – imperialTemperature Cubic inches 16.38716 Cubic cm.Fahrenheit 5/9(*F)-32 *Celsius Cubic feet 0.028317 Cubic meters.Celsius 9/5 (*C)+32 * Fahrenheit Volume – U. S.

Quarts (liquid) 0.9463 Liters Gallons 3.7854 Liters

Volume – MetricCubic cm 0.06102 Cubic incuse Cubic meters 35.3145 Cubic feet.Liters 1.05668 Quarts.(liquid U.S)Liters 0.26417 Gallons (U.S.)

Page 112: Special Cables Catalogue

H 12

Page 113: Special Cables Catalogue

Glossary

Page 114: Special Cables Catalogue

Glossary

Page 115: Special Cables Catalogue

I 2

Glossary

A Area of conductorThe size of conductor cross-section measured in circular mils, square inches, etc.ArmorA braid or wrapping of metal, usually steel, used for mechanical protection. Armored cable A cable having a metallic covering for protection against mechanical injury.Astm The American society for Testing and materials AttenuationThe reduction in a transmitted signal as it passes through wires or equipment in an electrical circuit.AWGAbbreviation for American wire gauge.

Abrasion Resistance: Ability of a material or cable to resist surface wear.A.C. ResistanceThe total resistance offered by a device to alternating current circuit due to inductive and capacitive effects, as well as the direct current resistance. Active currentIn an alternating current, a component in phase with the voltage. The working component as distinguished from the idle or wattles component.Aerial cable A cable suspended in the air on poles or other overhead structure.Air core cableA telephone cable in which the interstices in the cable core are not filled with a moisture bloking material. Air spaced coaxial cable One in which air is the essential dielectric material. A spirally wound synthetic filament or spacer may be used to center the conductor.Alpeth A telephone cable having an aluminum shield and a polyethylene jacket.Alternating current (A.C.)An electric current that continually reverses its direction giving a rebetitive plus and minus wave form at fixed intervals.Alternating voltage: The voltage developed across a resistance or impedance through which alternating current is flowing.Ambient temperature The romal temperature within a given areaAmerican wire gaugeA standard used in the determination of the physical size of a conductor determined by its circular mil area. Usually expressed as AWG. Also referred to as brown and sharpe (B&S) wire gauge.Ampacity: The maximum current an insulated wire or cable can safely carry without exceeding either he insulation or jacket material limitations (Same as current carrying capacity).AmpereThe unit current. One ampere is the current flowing thought on ohm of resistance at one volt potential .Anneal To subject to high heat wit subsequent cooling. When annealing copper, the act of softening the metal by means of heat to render it less brittle AnodeThe electrode through which a direct current enters the liquid, gas or other discrete part of an electrical circuit; the positively charged pole of an electrochemical cell.Appliance wire and cable Appliance wiring material is a classification of underwriters’ laboratories, inc., covering insulated wire and cable, internal wiring of appliances and equipment. Each construction satisfies the requirements for use in particular applications.

B

Balance circuit A circuit so arranged that the impressed voltage on each conductor of the pair are equal in magnitude but opposite in polarity with respect to ground.Band width The frequency range of transmitted electrical signals, expressed in Hertz.Bare conductor A conductor having no covering. A conductor with no coating or cladding on the copper.Bedding A layer of material applied to a cable immediately below the armoring.BinderA spirally served tape or thread used for holding assembled cable components in place awaiting subsequent manufacturing operations. Bonded flat cableFlat cable consisting of individually insulated conductors lying parallel and bonded together typically for application in electronics, telecommunications. Or computers.Braid A fibrous or metallic group of filaments interwoven in cylindrical form to form a covering over one or more wires. Braid angle The smaller of the two angles formed by the shielding strand and the axis of the cable being shielded.Breakdown of insulationFailure of an insulated conductor resulting in a flow of current through the insulation. It may be caused by the application of excess voltage or by defects or decay.Breakdown voltageThe voltage at which the insulation between two conductors breaks down.Bunched StrandAny number of conductor strands twisted together in one direction with the same lay length. Buried CableA cable installed directly in the ground without use of underground conduit. Also called “ direct burial cable”.

Page 116: Special Cables Catalogue

I 3

C Colour CodeA colour system for circuit identification by use of solid colours, tracers, braids , surface printing, etc. Composite cable A cable consisting of two or more different types or sizes of wires.ConcentricityIn a wire or cable, the measurement of the location of the center of the conductor with respect to the geometric center of the circular insulation.Concentric Stranding A group of wires twisted so as to contain a center core with one or more distinct layers of spirally wrapped, wires laid overall. Conductance The ability of a conductor to carry electric current. It is the reciprocal of resistance and is measured in Mhos.ConductivityA term used in describing the capability of a material to carry an electrical charge. Usually expressed as a percentage of copper conductivity copper being one hundred (100%) percent.Conductor Any material capable of transferring electrical charge easily.Control cable A multi-conductor cable made for operation in control or signal circuits.Core In cables, a term used to denote a component or assembly of components, over which other materials are applied, such as additional components, shied, sheath, or armor. Cross-Sectional AreaThe area of the cut surface of an object cut at right angles to the length of the object. CrosstalkSignal interference between nearby conductors caused by pickup of stray energy. It is also called induced interference. CureTo change the physical properties of a material by chemical reaction, by the action of heat and catalysts, alone or in combination, with or without pressure.Current The rate of flow of electricity in a circuit , measured in amperes. Current Carrying CapacityThe maximum current an insulated conductor or cable can continuously carry without exceeding its temperature rating. It is also called ampacity.Current, Direct (D.C.)Electrical current whose electrons flow in one direction only ; it may be constant or pulsating as long as their movement is in the same direction.CycleThe complete sequence of alternation or reversal of alternation or reversal of the flow of an alternating electric current. (See Hertz)

CableA group of individually insulated conductors in twisted or parallel configuration, with or without an overall covering. Cable, Star QuadA multicore radio or television relay cable in which the conductors are arranged in quads and each quad consists of four conductors twisted together, the diagonally opposite conductors constituting a pair circuit. Also known as spiral four cable.CablingThe act of twisting together two or more insulated components by machine to form a cable.Capacitance: Storage of electrically separated charges between two plates having different potentials. The value depends on the surface area of the plates and the distance and material between them.Capacitance, Direct: The capacitance measured directly with all other conductors, including shield, short circuited to ground. Capacitance, MutualThe capacitance between two conductors with all other conductors, including shield, short circuited to ground.Capacitance unbalance The inequalities of the capacitances of the wires of a telephone circuit to other wires or to earth which produce interference. Various forms of unbalance arise according to the circuits concerned in the measurement, hence side-to-side, pair – to- pair unbalance.Capacitance unbalance to groundAn inequality of capacitance between the ground capacitance the conductors of a pair which results in a pickup of external source energy, usually from power transmission lines.Capacitance couplingElectrical interaction between two conductors caused by the capacitance between them.Characteristic impedanceThe impedance that , when connected to the output terminals of a transmission line of any length, makes the line appear infinitely long. The ratio of voltage to current at every point along a transmission line on which there are no stranding waves.Charge The quantity of electricity held statically in a capacitor or an insulated conductor.Circular MilA measurement used in determining the area of wire. The area of a circle one thousandth (.001) of an inch in diameter.CoatingA material applied to the surface of a conductor to prevent environmental deterioration, facilitate soldering or improve electrical performance.Coaxial CableA cable consisting of two cylindrical conductors with a common axis, separated by a dielectric.Cold TestAny test to determine the performance of cable during or after subjection to a specified low temperature for a specified time.

D

D.C.Abbreviation for “Direct Current”Decibel (dB)A unit to express differences of power level. Used to express power gain in amplifiers or power loss in passive circuits or cables.

Glossary

Page 117: Special Cables Catalogue

I 4

GlossaryDielectric Constant (K)The ratio of the capacitance of a capacitor (or consoles) with dielectric between the electrodes to the capacitance with air is between the electrodes. Also called permittivity and specific inductive capacity.Dielectric StrengthThe voltage which an insulation can withstand before breakdown occurs. Usually expressed as a voltage gradient (such as volts per mil).Dielectric testA test in which a higher than the rated voltage is applied for a specified time to determine the adequacy of the insulation under normal conditions. Direct capacitanceThe capacitance measured directly from conductor to conductor through a single insulation layer.Direction of LayThe direction, either clockwise or counterclockwise, of a conductor or group of conductors when looking axially down a cable length.Drain WireIn a cable, an uninsulated wire laid over the component or component and used as a ground connection. Normally laid in contact with a metallic foil shield.DrawingIn the manufacturing of wire, pulling the metal through a die or series of dies for reduction of diameter to a specified size.Drop Wire A telephone cable, usually consisting of one insulated telephone pair, which is used to connect a subscribers premises to open wires lines on poles.

Filler (1) A material used in the cable to fill large interstices

between electrical components; (2) A substance, often inert, added to a compound to

improve propertied and / or decrease cost.Film A thin plastic sheet.Flame Resistance Ability of the material to extinguish flame once the source of heat is removed Flat cable A cable with two essentially flat surfacesFlexible Cable A cable containing one or more cores, each formed of a group of wires, the diameters of the wires, the diameters of the wires being sufficiently small to afford flexibility.FlexibilityThe ease with which a cable may be bent Foamed PlasticsPlastic insulations having a cellular structure. Foamskin Polyethylene foam insulation Frequency Number of times an alternating current reverses itself in one second. Expressed in Hertz (Hz), which is one cycle per second.

G

GaugeA term used to denote physical size.

H

Harness An arrangement of wires and cables, usually with many breakouts , which have been tied together or pulled into a rubber or plastic sheath, used to interconnect electric circuit.Heat Resistance Ability of a substance to maintain physical chemical and electrical integrity under specified temperature conditions. Henry Unit of inductance such that the induced voltage in volts is numerically equal to the rate of change of current in amperes per second.Hertz (Hz)A term replacing cycles-per seconds as a unit of frequency.High Temperature wire and cable Those electrical wires and cable having thermal operating characteristics of 150oC and higher.HzAbbreviation for Hertz.

E

EccentricityLike concentricity, a measure of the center of a conductor’s location with respect to the circular cross-section of the insulation; expressed as a percentage of center displacement of one circle within the other.ElAAbbreviation for Electronic Industries Association. ElongationThe fractional increase in length of a material stressed in tension.Embossing A means of identification or lettering usingheat and or pressure to leave raised lettering on the sheath material of the cable.Emergency overloads Loads which occur when larger than normal currents are carried through a cable or wire oven a short period time.ExtrusionThe process of continuously forcing a plastic or elastomer and a conductor core through a die, thereby applying a continuous coating of insulation or jacket to the core or conductor.

I

iCEAInsulated Cable Engineers Association (formerly IPCEA).iECInternational Electrotechnical Commission, Similar to the ISO in structure and scope.iEEEInstitute of Electrical and Electronic Engineers.

F

Farad A unit of electrical capacityFextFar end crosstalk Figure 8 cable An aerial cable configuration in which the conductors and the strand which supports the cable are integrally jacketed a cross-section of the finished cable approximates the figure “eight”.

Page 118: Special Cables Catalogue

I 5

Glossaryimpedance The total opposition that a circuit offers to the flow of alternating current or any other varying current at a particular frequency. It is a combination of resistance R and reactance X, measured in ohms.impulse (Or pulse)A surge of unidirectional polarity.induced Current An electric current set up in a circuit by interacting electrical fields a current caused by electromagnetic induction.inductanceThe property of a circuit element that opposes a change in current flow, thus causing current change to lag behind voltage changes. It is measured in Henrys.inductionThe phenomenon of a voltage, magnetic field or electrostatic charge being produced in an object by lines of force from the source of such fields.Inductive coupling Crosstalk resulting from the action of the electromagnetic field of one conductor on the other. insulation A non-conductive material usually surrounding or separating two conductive materials. Often called the dielectric in a radio frequency cable. insulation Resistance That property of an insulating material which resists electrical current flow through the insulating material when a potential difference is applied. insulation Thickness The wall thickness of the applied insulation interference Any undesired electrical signal induced into a conductor by electrical or electromagnetic means (Noise)iSOInternational Standards Organization

Longitudinal shield A tap shield, flat or corrugated, applied longitudinally along the axis of the cable core being shieldedLoop Resistance The total resistance of two conductors measured round trip from one end. Loss Factor The product of the dissipation and dielectric constant of an insulating material.

M

Marker TapeA tap laid parallel to the conductors under the sheath in a cable, imprinted with the manufacture’s name and the specification to which the cable is made. Other information such as date of manufacture may also be included.MCMOne thousand circular Mils.Megohm One million ohmsMhoThe unit of conductivity. The reciprocal of an ohm.MhzMegahertz (one million cycles per second) MicrophonicsNoise in a system caused by mechanical vibration of components within the system.MicrowaveA short (usually less than 30cm.) Electrical wave.MillA unit used in measuring diameter of a wire or thickness of insulation over a conductor. One one-thousandth of an inch (0.001”).Moisture ResistanceThe ability of a material to resist absorbing moisture from the air or when immersed in water.Multi-ConductorMore than one conductor within a single cable.Mutual inductanceThe ratio of voltage induced in one conductor to the time rate of current change in the separate conductor causing this induction. MylarDuPont trademark for polyethylene terephthalate (polyester) film used in the form of a tape.

J

Jacket A material covering over a wire insulation or an assembly of components. An overall jacket on a complex cable grouping is also often referred to as a sheath.

K N

Kilohertz 1.000 Hertz (cycles per second)KilovoltA term denoting 1000 volts.KilowattA term denoting 1000 watts.

NextNear end crosstalk

O

Ohm Unit of resistance such that a constant current of one ampere produces a force of one volt.Overall DiameterFinished diameter over wire or cable Over Current The Current which causes and excessive temperature rise in a conductor.Overload CapacityThe maximum level of current, voltage, or power which a device can withstand before it is damaged.

L

Lay Direction The direction in which the strands of a conductor run over the top of the conductor as they recede from and observer looking along the axis of the conductor. Leakage CurrentThe undesirable flow of current through or over the surface of an insulation

Page 119: Special Cables Catalogue

I 6

GlossaryRFiRadio Frequency Interference.RG/URadio Government, Universal. RG is the military designation for coaxial cable and U stands for “ general Utility”.Round ConductorA conductor whose cross-section is substantially circular

Oxygen indexPercentage of Oxygen necessary to support combustion of specified material.

PPair Two insulated wires of a single circuit associated together. Peak VoltageThe maximum instantaneous voltage.Percent ConductivityConductivity of a material expressed as a percentage of that of copper Polyester Polyethylene terephthalate which is used extensively in the production of a high strength moisture resistant film used as cable core wrapping material.PolyethyleneA family of insulating materials derived from polymerization of ethylene gas. They are basically pure hydrocarbon resins, with excellent dielectric properties.PolypropyleneA thermoplastic polymer of propylene. Polyvinlychloride (PVC).A thermoplastic material composed of polymers of vinylchloride which may be rigid or eleastomeric, depending on specific formulation.Power Factor The ratio of resistance to impedance. The ratio of the actual power of an alternating current to apparent power. Mathematically, the cosine of the angle between the voltage applied and the current resulting.Propagation timeThe required for an electrical wave to travel between two points on a transmission line.Pulse A current or voltage which changes abruptly from one value to another and back to the original value in a finite length of time. Pulse Cable A type of coaxial cable constructed to transmit repeated high voltage pulses without degradation.

S

Sheath The material, usually an extruded plastic or elastomer, applied outermost to a wire or cable. Very often refereed to as a jacket. Shield A metallic layer around an insulated conductor or group of conductors to prevent electrostatic or electromagnetic interference between the enclosed wires and external fields. This shield can be braided or served wires, foil wrap, foil backed tape, a metallic tube , or conductors, the shielding effectiveness is in proportion to the amount of coverage, usually expressed in percentage.Shield CoverageThe physical area of a cable that is actually covered by the shielding material and is expressed in percentage. Signal Current used to convey information, either digital, analogue, audio or video. Single cable A cable designed to carry current of usually less than one ampere per conductor. Skin Effect The tendency of alternating current, as its frequency increases, to travel only on the surface of a conductor. Solid Conductor A conductor consisting of a single wire.Spark TestA test designed to locate imperfections (usually pin-holes) in a wire insulation by application of an electrical potential across the material for a short period of time while the wire is drawn through an electrode field with one end of the wire grounded.Specific GravityThe ratio of the weight of any volume of substance to a weight of an equal volume of some substance taken as a standard, usually water for liquids and hydrogen for gases. Square Mil The area of a square on mil by one mil.Stranded conductor A conductor composed of individual groups of wires twisted together to form an entire unit.Strand Lay length A distance of advance of on strand of a spirally stranded conductor, in one turn, measured axially.

Q

QuadA four- wire unit of insulated conductors. See star quad

R

Rated TemperatureThe maximum temperature at which an electric component can operate for extended periods without loss of its operating properties Rated VoltageThe maximum voltage at which an electric component can operate for extended periods without degradation of performance or safety hazard.Reactance The opposition offered to the flow of alternating current by the inductance or capacitance of a component or circuit Resistance In D.C. circuits , the opposition a material offers to current, measured in ohms. In A.C. Circuits, resistance is the real component of impedance , and may be higher than the value measured at D.C.

Page 120: Special Cables Catalogue

I 7

GlossaryT

Temperature Rating The maximum temperature at which insulating material may be used in continuous operation without loss of its basic properties.

Tensile strengthA term denoting the greatest longitudinal tensile stress a substance can bear without mechanical failure.Thermal Rating The maximum and / or minimum temperature at which a material will perform its functions without undue degration. Thermal Shock A test to determine the ability of a material to withstand heat and cold by subjecting it to rapid and wide change in temperature.

Tinned CopperTin coating over copper to aid in soldering and inhibit corrosion.

Tinned wire Copper wire that has been coated with a layer of tin or solder to simplify soldering.

Triple (Traid)A cable consisting of there insulated single conductors twisted together.

Tubing A tube of extruded non-supported plastic or metallic material.

Twin CableA cable composed of two separated insulated stranded conductors laid parallel under a common covering.Twin Coaxial cable A single cable consisting of two separate coaxial cables laid adjacent and parallel or twisted together. Twisted Pair A twisted pair is composed of two small separately insulated wires twisted together.

Twisted Triad Any three individually insulated conductors which are twisted together.

V

Velocity of Propagation The speed of an electric signal down a length of cable compared to speed in free space expressed as a percentage. It is the reciprocal of the square root of the dielectric constant of the cable insulation. Volt (potential difference)A unit of electrical pressure. One volt is the amount of pressure that will cause one ampere of current in one ohm of resistance.

VoltageThe term most often used in place of electromotive force, potential, potential difference, or voltage drop, to designate electric pressure that exists between two points and is capable of producing a flow of current when a circuit is connected between the two points. Voltage Drop. The amount of voltage loss between two power in a circuit.

Voltage Rating The highest voltage that may be continuously applied to a wire or cord in conformance with standards or specifications.

Volume Receptivity The electrical resistance between opposite face of a 1 cm cube of insulating material, commonly expressed in ohms/ centimeter.

W

Water Absorption Ratio of the weight of water absorbed by a material to the weight of the dry material.WattA unit of electrical power. One watt is equivalent to the power generated by one ampere of current under a pressure of one volt in a D.C. circuit.WavelengthThe distance, measured in the direction of propagation, of a repetitive electrical pulse or waveform between tow successive points.

Page 121: Special Cables Catalogue

J 1

System’s Certificates

Page 122: Special Cables Catalogue

J 2

Product’s Certificates

Page 123: Special Cables Catalogue

J 3

Product’s Certificates

Page 124: Special Cables Catalogue

J 4

Product’s Certificates Product’s Certificates

Page 125: Special Cables Catalogue

Elsewedy Cables Catalogues

Power Cables Catalogue - Overhead conductor - Service drop cables - Low voltage cables - Medium voltage cables - High voltage cable - Extra high voltage cables

Special Cables Catalogue - Control cables - Instrumentation cables - Flame retardant cables - Fire resistance cables - Telephone cables - LAN cables - Co-axial cables - Audio cables - Profibus cables - Irrigation cables - Pilot cables - Flat cables - Automotive wires - Appliance cables & cords

Winding Wires Catalogue - Enameled copper cables - Paper insulated flat wires - Plain copper wires - Tinned copper wires - Bare copper wires - Welding wires

Low Smoke Halogen Free (LSHF) Catalogue - Single core cable - Multi core cable

Telecom Cables Catalogue - OPGW - Fiber optics cables - Comcore

Page 126: Special Cables Catalogue

Elsewedy Cables ContactsElsewedy Cables Head OfficeLocal:16 Baghdad st. – EL Korba – Heliopolis, Cairo . Egypt

Tel.: +(202) 26904311/2-3 Fax: +(202) 24170173 Email: [email protected]

Export:

16 Baghdad st. – EL Korba – Heliopolis, Cairo . Egypt

Tel.: +(202) 26904311/2-3 Fax: +(202) 24170173

Email: [email protected]

Wires & Cables Sector1-Arab Cables (Power Cables) 14 Baghdad St. El Korba, Heliopolis, Cairo Egypt Tel.: +(202) 22909430 - 24187371 - 24187372, 24187361, 24187362 Fax: +(202) 22917078 Email: [email protected]

2-Egytech Cables (Power Cables) 16 Baghdad St. El Korba, Heliopolis, Cairo - Egypt Tel.: + (202) 24148366, 24148370 Fax: +(202) 24148373 Email: [email protected]

3-United industries (Enameled Wires - Special Cables - Fiber Glass Poles) Add. 68 El Tayran St., Nasr City, CairoTel.: +(202) 22 60 3196 – 22 61 8908 - 24 01 3606 Fax: +(202) 22 62 0473 Email: [email protected], [email protected]

4-United Metal (Copper Rods) 14 Baghdad St.EI Korba, Heliopolis, Cairo - Egypt Tel.: +(202) 24148369 - 22916507 Fax: +(202) 24196116 Email: [email protected]

5-Sedplast (PVC Compounds) 13 El Obour Bldg’s. Salah Salem St. Nasr City, Cairo - Egypt Tel.: +(202) 22623411, 22605405 Fax: +(202) 22623442 Email: [email protected]

6-Egyplast Elsewedy for Plastic Industry EGyPLAST Obour Buildings #13, Salah Salem Street, Nasr City, Cairo, Egypt Tel.: +(202) 22632411 – 22632442 Fax: +(202) 24033285

7-United Wires 10th of Ramadan City, Zone A3, El-Sharkia, Egypt Tel.: +2015411944 Fax: +2015411941 Email: [email protected]

8-Giad Elsewedy (Power Cables) Al Hourea St. Al Khartoum, Sudan Tel.: +249 183 2764117/8 Fax: +249 183 2764116 Email: [email protected]

9-Elsewedy Cables Syria (Power Cables) 139 Kafr Sousa Bldg

,s (Main Rood), Damascus, Syria-

RO.BOX: 36633 Tel.: +963-11-25850207-25850212 Fax: +963-11-25850206 E-mail: [email protected]

10-Elsewedy Cables Saudi Arabia (Wires & Cables)Nassar Center, King Fahd Road Al Aziziah, Jeddah Postal code: 860223337 Jeddah Tel.: +96626687380/88/99 Fax: +96626687480 Email: [email protected] [email protected]

11-Elsewedy Cables Algeria (Power Cables) 153 rue Ali Khodja, El Biar, Alger, Algérie. Tel.:+213 21 92 40 05/07 Fax: +213 21 92 39 97 Email: [email protected]

12-Elsewedy Cables Qatar (Power Cables)Elsewedy Cables - Nuiaja area, villa # 36 N.B.S. D-ring road, P.O. Box 3988, Doha Qatar. Tel.: +974 4652645 \ 4568612 Fax: +974 4653892 \ +974 5899047 Email: [email protected]

13-Elsewedy Cables Egypt (Power Cables) 16 Baghdad St. El Korba, Heliopolis, Cairo - Egypt Tel. : +(202) 24148366, 24148370 Fax: +(202) 24148373 Email: [email protected]

Electrical Products Sector1-SEDCO (Cables Accessories) 13 El Obour Bldg,s, Salah Salem St. Nasr City, Cairo - Egypt Tel.: +(202) 24023683 - 22626763 Fax: +(202) 22639155 Email: [email protected]

2-Elastimold (Cables Accessories) 13 El Obour BIdg’s, Salah Salem St. Nasr City, Cairo - Egypt Tel.: +(202) 24023683 - 22626763 Fax: +(202) 22639155 Email: [email protected]

3-Sudanese Egypt Electrical industries SUDATRAF (Transformers) El Kuwaiti Buildings -4th tower - 7th stage KhartoumSudan P.O.B 1380 Khartoum Tel.: +249 183 2764118

6-Elsewedy Transformers (Transformers)14 Baghdad St. El Korba, Heliopolis, Cairo - Egypt Tel.: +(202) 24144380- 24144381 Fax: +(202) 22905844 - 24144383 Email: [email protected] [email protected]

7-ltalsmia (Explosion Proof Equipment) Tel.: 015411141 Fax: 015 411142 Email: [email protected]

8-iSKRAEMECO (Meters)Iskraemeco Savaska loka 4 SI-4000 Krani, SloveniaPhone: +38642064000Email: [email protected]

Turn Key Projects Sector1-Power System Projects (PSP)31 Ramy Tower, El Shatr EL Sades, Zahraa El Maadi, Cairo, Egypt. Tel.: +(202) 25215810 / 20 / 30 Fax: +(202) 25165122 Email: [email protected]

2-Elsewedy Electric Transmission & DistributionAdd. 68 El Tayran St., Nasr City, CairoTel.: 22 60 3196 – 22 61 8908 - 24 01 3606 Fax.: 22 62 0473 Email: [email protected]

international Operations Sector1-Jordan & iraqElsewedy Cables - Jordan & IraqZahrat El Radwan Building Extension of Garden Street Opposite of Medass shop, Amman, Jordan Tel.: +962 6 5853802 Fax: +962 6 5853804 Email: [email protected]

2-MalawiElsewedy Cables - Malawi E263 Post Dot Net Blantyre-Malawi Tel.: +265 1 878 878 Fax: +265 1 878 788 Cell: +265 9 788 87 Email: [email protected]

3-EthiopiaElsewedy Cables - Ethiopia Ries Engineering Share Company PO Box 1116,Debrezeit Road Addis Ababa, Ethiopia Tel.: +251 11 440 17 39 Fax: +251 11 442 06 67 Email: [email protected]

4-Kuwait Elsewedy Cables - Kuwait Al Kazemi International for General Trading & Contracting Al Salmeya, Laila Tower, 4th floor PO Box 403 Safat, 13005 Kuwait Mob: +9657861325 Fax: +9656723196 Email: [email protected]

5-UAEElsewedy Cables - Emirates Business Avenue Building – Sheikh Rashid Road PO Box 90305 Dubai, UAE 3rd Floor – Office no. 312 Tel.: +97142955905 Fax: +97142955135 Email: [email protected]

6-YemenElsewedy Cables - yemenHadda Towers - Hadda PO BOX: 888-Tower No.6 7th Floor- Office No.13-Sanna-yemen Tel.: +967734023861 Fax : +9671430853 Email: [email protected]

7-GuineaElsewedy Electric - Guinea Equatorial Pork Of Africa, Caracoles, Beside Military Camp, Malabo, Equatorial Guinea Tel.: +(240) 096 569 Fax: +(240) 096 569 Email: [email protected]

8-Nigeria Elsewedy Cables - Nigeria 10 Bauchi Close Agbara Estate, Ogun State Lagos-NigeriaTel.: +234 7033475772

9-LibyaElsewedy Cables - Libya Gergarash -Hay El Andalous, Tripoli-Libya Tel.: +218 91 325 96 25 Email: [email protected]

8-indiaElsewedy Cables - India Office No. 412, ‘A’ Wing, Sagartech Plaza, Andheri-Kurla Road, Andheri (East) Mumbai-400072, IndiaTel.: +91-22-65283183 / 66790130 Fax: +91-22-66790131

4-Elsewedy Electric Ghana (Fiber Glass Poles)9, Light Industrial Area No. A/36/2B Tema - Ghana Tel.: +23311101 -311102 Fax: +23311103 Email: [email protected]

5-Elsewedy Electric Syria (Transformers)Tel.: +963 11 5850 215 Fax: +963 11 5850 216 Email: [email protected]