spark_gap

81
© 2007 DEHN + SÖHNE / protected by ISO 16016 EXFS 100 11.12.07 / 5392

description

CATALOGO

Transcript of spark_gap

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100 11.12.07 / 5392

  • 2007 DEHN + SHNE / protected by ISO 16016

    Ex Isolating Spark Gaps

    EXFS 100 (923 100)and

    EXFS 100 KU (923 101)

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Ex isolating spark gap EXFS 100; Part No. 923 100 Product description / Specifications

    14.01.08 / 5240e

    Lightning impulse current (10/350 s): 100 kA

    Class of lightning currentcarrying capability: H

    Nominal discharge current (8/20 s): 100 kA

    Rated impulse sparkovervoltage (1.2/50 s): 1250 V

    Power frequency sparkovervoltage (50Hz): 500 V

    Rated short-duration power frequency withstand voltage (50 Hz): 250 V

    Rated discharge current (50 Hz): 500 A / 0.5 s

    With M10x25 connection bolt and spring washer on both sides

    Gases: II 2G Ex d IIC T6Dusts: II 2D Ex tD A21 IP67 T 80C

    Ex isolating spark gap EXFS 100 according to EN 50164-3 for lightning equipotential bonding according to IEC 62305-3,especially for use in hazardous areas on account of explosive gas or dust atmospheres in zone 1 / 2 or 21 / 22.ATEX-certified (94/9/EG)

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    (17) Special conditions for safe use None

    Document:BVS 06 ATEX E 099

    EXAM BBG Prf- und Zertifizier GmbH

    EC-Type Examination Certificate forEXFS 100 (KU); Part No. 923 100 (923 101)

    14.01.08 / 5237

  • 2007 DEHN + SHNE / protected by ISO 16016

    Ex isolating spark gaps

    Examples of use

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Ex isolating spark gap EXFS 100; Part No. 923 100Application environment

    14.01.08 / 5242e

    Isolating spark gaps or protective spark gaps are supposed to establish a galvanic isolation of electric parts of the installation, which are not connected with each other under normal operating conditions.

    - Specific applications: for establishing a galvanic isolation of insulating

    flanges and insulated couplings (e.g. fuel pipes) Cathodic corrosion protection of tanks Cathodic corrosion protection of pipelines Lightning equipotential bonding of gas pressure regulation stations

    Assembly:Isolating spark gaps can be mounted between the parts of the installation to be bridged by means of brackets or connectors. When mounting isolating sparks, the shortest possible cable length should be used as long cables increase the danger of inductive voltages putting unnecessary stress on the isolation.

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Ex isolating spark gap EXFS 100; Part No. 923 100Application

    14.01.08 / 5238e

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100

    Cathodic corrosion protection of tank installations

    building earth

    +

    ~

    14.01.08 / 5300e

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Insulating flange of fuel or product pipelines

    insulating flange

    insulating flange

    gas pressure regulator

    14.01.08 / 5303e

    EXFS 100

    EXFS 100

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    ground

    16 mm Cu

    earth-termination system

    14.01.08 / 5305e_c

    detail

    EXFS 100

    cathodiccorrosion protection

    Installation of EXFS 100

    electric actuator, e.g. MOV (motor operated valve)

    Insulatingflange

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Ex isolating spark gaps EXFS 100 (KU)Application

    Reference: Schwelm Anlagentechnik GmbH, Austria

    14.01.08 / 5317e_b

  • 2007 DEHN + SHNE / protected by ISO 16016

    5 Steps for selection and correct installation

    of Ex isolating Spark Gaps in accordance with

    AfK Recommendation No. 5Edition: 2010

    andIEC 62561-3:2011 (81/387/CDV)

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    DEHN + SHNEGMBH + CO.KG

    HANS-DEHN-STR. 1POSTFACH 1640D-92306 NEUMARKTTEL. +49 9181 906 401FAX +49 9181 906 55 401

    SALES DEPT. INDUSTRYMARKET MANAGERLIGHTNING AND SURGE PROTECTION

    Manfred Kienlein

    eMail: [email protected]: http://www.dehn.de

  • 2007 DEHN + SHNE / protected by ISO 16016

    1. StepLightning Protection Level (LPL)

    acc. to IEC 62305-1

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Risk of lighting strikes and overvoltage for pipelinesCurrent distribution

    S1

    When lightning strikes a pipeline, the lightning current is evenly distributed in both directions (50:50 rule). This means that the following maximum parameters must be taken into account for the spark gapand its installation environment

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Lightning current parameters

    In the following the maximum values of the first short stroke for the different lightning protection levels (LPL) (see Table 5 of IEC 62305-1) are used. The lightning protection level is used to implement protection measures according to the relevant set of lightning current parameters.

    The parameters for the subsequent negative short stroke are neglected since no significantly high current steepness is to be expected (values based on experience over the last decades) if lightning current is coupled (galvanic coupling) into the pipeline at the place of installation of the spark gap (insulating piece).

    Ex isolating spark gaps - Selection procedure in accordance with AfK -

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Symbol Unit I II III IV

    I kA 200 150

    Qshort C 100 75

    W/R MJ/ 10 5.6

    LPL

    s/s 10/350

    100

    50

    2.5

    Ref.: Excerpt from IEC 62305-1:2006-1, Table 5

    T1/T2

    AfK recommendation No. 5: Lightning current parametersCurrent parameters

    Peak current

    Short stroke charge

    Specific energy

    Time parameters

    First short stroke

    Average steepness di/dt kA/s 20 15 10

    Ex isolating spark gaps - Selection procedure in accordance with AfK No. 5 and IEC 62305-1

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Symbol Unit I II III IV

    I kA 100 75

    Qshort C 50 37.5

    W/R MJ/ 5 2.8

    LPL

    s/s 10/350

    50

    25

    1.25

    Maximum lightning current parameters for connecting cables

    T1/T2

    AfK recommendation No. 5: Lightning current parameters

    Current parameters

    Peak current

    Short stroke charge

    Specific energy

    Time parameters

    First short stroke

    When lightning strikes a pipeline, the lightning current is evenly distributed in both directions (50:50 rule). This means that the following maximum parameters must be taken into account for the spark gap and its installation environment:

    Average steepness di/dt kA/s 10 7.5 5

    Ex isolating spark gaps - Selection procedure in accordance with AfK No. 5 and IEC 62305-1

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Lightning current parameters

    Thus, in the following the average steepness of the first short stroke is used for assessing the voltage drop in all connecting cables.

    It is certainly possible that lightning directly strikes the insulating piece orthe spark gap. This, however, needs to be prevented by taking adequateexternal lightning protection measures in accordance with IEC 62305-3.

    Ex isolating spark gaps - Selection procedure in accordance with AfK -

  • 2007 DEHN + SHNE / protected by ISO 16016

    2. Stepvoltage withstand capability of

    insulating jointsacc. AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Two classifications:

    Class 1 UPW : 5 kVrms

    Class 2 UPW : 2.5 kVrms

    AfK recommendation No. 5:

    22.12.2010 / 5321e_e

    Voltage withstand capability of insulating joints

    UPW

    Insulating joint

  • 2007 DEHN + SHNE / protected by ISO 16016

    3. Stepconnection cable length

    acc. AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Depending on the max. current steepnessof the first short stroke for the relevant class of LPS (LPL) and the connecting cable length, the electric strength of the insulating piece might be exceeded due to the voltage drop across the connecting cable.

    This might already occur (based on a class I insulating piece and class of LPS I ) for a cable length of more than 300 mm (for this reason the standard connecting cable lengths are limited to 300mm).

    22.12.2010 / 5320e_a_MAK

    Max. cable length of connection cables

    Note:Connection cable min. 16 mm Cu or equal

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    (di/dt)max

    (di/dt)max

    L

    R

    of the connecting cable

    Ref.: Hasse, P.: berspannungsschutz fr Niederspannungsanlagen, TV - Verlag GmbH, Kln, 1998

    Ex isolating spark gaps Connecting cable lengths

  • 2007 DEHN + SHNE / protected by ISO 16016

    4. Stepselection of spark gap

    acc. AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Selection and installation

    Adequate explosion-proof isolating spark gaps should feature the following characteristics:

    Tested in accordance with IEC 62561 -3

    Lightning current carrying capability: class H or N

    d.c. sparkover voltage: > 600 V 1)

    100 % lightning impulse sparkover voltage (1.2/50 s): 1.25 kV

    1) Normally > at the place of installation

    Ex isolating spark gapstechnical data

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Selection and installation

    Adequate explosion-proof isolating spark gaps should feature the following characteristics:

    Rated discharge current (8/20 s): 100 kA

    Lightning impulse current Iimp (10/350 s): 100 kA (H), 50 kA (N)

    Rated withstand voltage (50 Hz): 250 V 1)

    1) Normally > at the place of installation

    Ex isolating spark gaps technical data

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Selection and installation

    Adequate explosion-proof isolating spark gaps should feature the following characteristics:

    Rated alternating discharge current (50 Hz): 500 A / 0.5s 2)

    IECEx and ATEX certification for the relevant hazardous zone at the place of installation

    2) Max. discharge current in case of interference at the place of installation

    Ex isolating spark gaps technical data

  • 2007 DEHN + SHNE / protected by ISO 16016

    5. Stepcoordination

    spark gap to insulating joints acc. AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016

    Mode of Operation of Ex isolating Spark Gaps

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    EXTINGUISH

    Isolate = Circuit openDuring normal operation the EXFS 100 isolating spark gap has a high resistance (> 500 kOhms). Normal operation of the system is thus not compromised.

    Trigger = Circuit closesAs soon as the sparkover voltage Uag or Uas is reached, the EXFS 100 isolating spark gap immediately triggers and reduces the voltage to a safe level.

    Discharge = Circuit closedAfter the EXFS 100 isolating spark gap triggered, it discharges the energy content of the interference pulse without posing a risk to the environment.

    Extinguish = Circuit opensAfter the energy of the interference pulse has been discharged, the EXFS 100 isolating spark gap extinguishes and changes back to normal operation. The original electrical characteristics are retained and the system is protected again.

    DISCHARGE

    TRIGGER

    ISOLATE

    Ex isolating spark gaps Mode of operation

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Coordination Ex isolating spark gaps / insulating joints

    Coordination between the insulating clearance of the insulating joints and the associated spark gap is to ensure that the discharge process following a lightning discharge is performed via the spark gap and not via the insulating clearance of the insulating joints .

    The isolating spark gap thus represents a defined flashover point which prevents discharge with uncontrolled sparking. At the same time, ignition of an explosive atmosphere is prevented.

    Coordination during lightning discharge is basically ensured if the voltagecaused by the discharge process does not reach the value of the electric strength across the insulation of the insulating joints .

    Ex isolating spark gaps - Selection procedure in compliance with AfK -

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Voltage characteristic for insulating joints in case of lightning effects (schematic)

    insulating joints

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Trigger = Circuit closesAs soon as the sparkover voltage Uag or Uas is reached, the EXFS 100 isolating spark gap immediately triggers and reduces the voltage to a safe level.

    TRIGGER

    Ex isolating spark gaps Trigger function

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Coordination Ex isolating spark gaps / insulating joints

    The following requirements are to be fulfilled to ensure insulation coordination:

    The impulse sparkover voltage Uas (1.2 / 50 s) of the spark gap must be 50 % smaller than the r.m.s. power-frequency test voltage UPW of the insulating joints .Requirement: Uas

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Uas 0.5 * UPWClass 1: UPW = 5 kVClass 2: UPW = 2.5 kV

    Class 1 insulating joints : Uas 0.5 * 5 kVUas 2.5 kV

    Class 2 insulating joints : Uas 0.5 * 2.5 kVUas 1.25 kV

    AfK recommendation No. 5:

    The impulse sparkover voltage (1.2/50) of the isolating spark gap should be below 50% of the 50 Hz power-frequency flashover voltage (r.m.s. value) of the insulating joints .

    22.12.2010 / 5321e_e

    Uas

    EXFS 100 (KU) Ex isolating spark gaps Trigger function

    UPW.

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Coordination Ex isolating spark gaps / insulating joints

    The impulse sparkover voltage (1.2 / 50 s) is determined and specified in a test procedure in accordance with IEC 62561 -3. This ensures that changes of the impulse sparkover voltage as a result of ageing and thus of the coordination requirement are excluded / considered.

    Ex isolating spark gaps - Selection procedure in accordance with AfK - Trigger function

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Discharge = Circuit closedAfter the EXFS 100 isolating spark gap has triggered, it discharges the energy content of the interference pulse without posing a risk to the environment.

    DISCHARGE

    Ex isolating spark gapsDischarge function

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Coordination Ex isolating spark gaps / insulating piece

    The following requirements are to be fulfilled to ensure insulation coordination:

    After the spark gap has triggered, the max. voltage drop between the connecting points of the Ex isolating spark gap (Umax) must not exceed the peak value of the power-frequency test voltage ().Requirement: Umax < e.g. class 1 insulating piece: UPW = 5 kV; = 7 kV

    Ex isolating spark gaps - Selection procedure according to AfK - Discharge function

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Determination of the connecting cable length

    Spark gap

    Insulation

    Ex isolating spark gaps - Selection procedure according to AfK - Discharge function

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Formulas for calculating the voltage drop

    Ex isolating spark gaps - Selection procedure calculation according to AfK No. 5

    insulating piece

    (depends on the Ex isolating spark gap)

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Sample calculation

    Installation height H of the loop: 15 cmConnecting point clearance (cable length) SL: 70 cmTotal length of connecting cables l = SL + 2 * H = 100 cmEx isolating spark gap used: EXFS 100Type of conductor: flexible circular conductor, 25 mm, Cu (rho = 0.0178 Ohms * mm / m); L = 1 H / m Class 1 insulating flange (5 kVrms) = 5 kV x Sqr (2) = 7 kV

    insulation

    spark gap

    Ex isolating spark gaps - Selection procedure calculation according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Sample calculation

    Umax = Ubo + Imax * RL + L * di / dtUbo = 30 V (const.)Iimp = 100 kA (wave form 10/350 s) di / dt = 10 kA / sRL = rho * l / A = (0.0178 Ohms * mm / m) * 1 m / 25 mm = 0.712 mOhms L = 1 H / m (typical value)

    (depends on the Ex isolating spark gap)

    insulating joint

    Ex isolating spark gaps - Selection procedure calculation according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Sample calculation

    Umax = 30 V + 100 kA * 0.712 mOhms + 1 H * 10 kA / sUmax = 10.10 kVUmax [10.10 kV] > [7 kV]

    Coordination requirements not fulfilled !!!

    insulation

    spark gap

    Ex isolating spark gaps - Selection procedure calculation according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Voltage drop depending on the connecting cablesV

    o

    l

    t

    a

    g

    e

    d

    r

    o

    p

    [

    k

    V

    ]

    Connecting cable length [cm]

    steepness:

    steepness:

    steepness:

    LPL 1

    LPL 2

    LPL 3

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel connection of spark gaps

    If the voltage drop Umax exceeds the value of the test voltage UPW specified for the insulating piece (e.g. class 1: 5 kVrms), this can be compensated by installing additional spark gaps.

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel connection of spark gaps

    Insulation coordination is assured if the number of spark gaps (down conductors N) multiplied with the peak value of the test voltage of the insulating piece () is equal to or greater than the value calculated for the voltage drop across all connecting cables (Umax).

    Requirement: >= Umax / N

    Note:Type of spark gap and cable length have to be the same

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel connection of spark gaps

    Formula: N = Umax / = 10.10 kV : 7 kV 2N: number of spark gaps

    In order to protect the insulating piece, two spark gaps must be installed in parallel (symmetrical arrangement) at the flange.

    If several spark gaps are connected in parallel, the spark gaps ignite one after the other and the electric strength of the insulating piece is never exceeded.

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel connection of spark gaps

    Note:It is advisable to perform a type test (verification of coordination between insulating piece and spark gap with connecting cables) for the parallelarrangement of spark gaps with insulating piece in an impulse current laboratory with the relevant lightning current parameters according to the LPL.

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel routing of the feed and return cable

    Parallel routing of the feed and return cable(might be additionally twisted) e.g. if the spark gap is installed above ground.

    Coaxial cable arrangement e.g. if the spark gap is installed above ground (see Figure B.1)

    isolating point

    reinforcement

    concretefoundation

    spark gap

    coaxial cable:sheath at least 1 x 162

    tube at least 1 x 162

    e.g. type 1/2Cu 2Y 75 Ohms

    e.g. measur-ing pile

    DIN rail

    terminals

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    AfK recommendation No. 5: Measures to be taken if the coordination requirement is not fulfilled

    Parallel routing of the feed and return cable

    Note:It is advisable to perform a type test (verification of coordination between insulating piece and spark gap with connecting cables) for the parallel arrangement of spark gaps with insulating piece in an impulse current laboratory with the relevant lightning current parameters according to the LPL.

    isolating point

    reinforcement

    concretefoundation

    spark gap

    coaxial cable:sheath at least 1 x 162

    tube at least 1 x 162

    e.g. type 1/2Cu 2Y 75 Ohms

    e.g. measur-ing pile

    DIN rail

    terminals

    Ex isolating spark gaps - Selection procedure Measures according to AfK No. 5

  • 2007 DEHN + SHNE / protected by ISO 16016

    Type Tests for Insulating Joints with Ex isolating Spark Gaps

  • 2007 DEHN + SHNE / protected by ISO 16016

    Test Set-up

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Schematic test set-up

    Insulating joint

    Connecting cable length l (25 mm2)

    External EXFS 100 spark gap

    Lightning current generator200 kA, 10/350 s

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Photo of the test set-up

    Earthing

    Injection ofimpulse current

    Impulse current generator200 kA, 10/350 s

    Insulating jointat the pipeline

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Photo of the test set-up

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Photo of the test set-up

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Photo of the test set-up

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Oscillograms of the impulse current testWave form 10 / 350 s

    Total current

    Oscillogram 1: Test 1 - Connecting cable length of 40 cm

    Current flowing through the external EXFS spark gap

    Total current

    current through EXFS

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011

    Oscillograms of the impulse current testWave form 10 / 350 s

    Total currentCurrent flowing through the external EXFS spark gap

    Oscillogram 2: Test 2 - Connecting cable length of 60 cm

    Total current

    current through EXFS

  • 2007 DEHN + SHNE / protected by ISO 16016

    EXFS 100 (923 100)and

    EXFS 100 KU (923 101)

    -

    more than just spark gaps

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100 14.01.08 / 5297e_a

    EXFS 100 -more than just an isolating spark gap

    Lightning impulse current (10/350): 100 kA

    Class of lightning current carrying capability: H

    Rated short-duration power frequencywithstand voltage (50Hz): 250 V

    Rated impulse sparkovervoltage (1.2/50): 1250 V

    A.c. sparkover voltage (50 Hz): 300 V

    Nominal discharge current (8/20): 100 kA

    Rated discharge current (50 Hz): 500 A / 0.5 s

    Connection enclosure with M10 x 25 connection bolt and spring washer on both sides

    Test acc. to EN 50164-3 - Lightningprotection

    Testing of further practice relevent loadings of the spark gap

    AfK-recommendation

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Pipelines affected by interferences

    pipeline

    lightning strike

    electromagneticinterference

    earth fault /short-circuit current

    earth electrode earth electrode leakage currents caused by electrical railway systems

    14.01.08 / 5422e_a

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    leakage currents caused by electrical railway systems

    galvanic pulse injection via the soil

    electromagnetic fields caused by high-voltage transmission lines

    inductive pulse injection

    earth faults and short circuits caused by high-voltage transmission lines

    galvanic / inductive pulse injection

    lightning interference caused by thunderstorms

    galvanic / inductive pulse injection

    Sources of interference can be

    14.01.08 / 5422e_b

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100 -more than just an isolating spark gap

    transientswitch

    additionallyswitch for controlling of short-term interferencesof high-voltage systems(up to 500 ms)

    14.01.08 / 5297e_b

  • 2007 DEHN + SHNE / protected by ISO 16016

    Non-standard parametersfrom practice

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100 -more than just an isolating spark gap

    If pipeline systems are in the influence area of high-voltage systems, the spark gap has to carry high alternating currents in case of response. This short-term interference (AfK recommendation No. 3) causes a thermal loading which can damage the spark gap. The max. break-time at earth faults is approx. 0.5 seconds.

    By the rated discharge current thus a max. admissible 50 Hz current load is defined, which can be carried by the EXFS 100 (KU) for a certain time.The specified value for the EXFS 100 (KU) is: 500 A @ 0.5 s

    Within the test scope it had to be proved that the EXFS 100 (KU) will not be damaged electrically / mechanically, the limit temperature for the temperature class T6 (85 C at 40C ambient

    temperature) on the enclosure surface will not be exceeded and after the test the rated values according to EN 50164-3 are kept again.

    14.01.08 / 5329e_a

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    kV

    -1.0

    -0.5

    0.0

    0.5

    1.0

    -1.0

    -0.5

    0.0

    0.5

    1.0kA

    0.0 0.2 0.4 0.6 0.8 1.0 s

    EUT_01: I_follow

    EUT_01: U_total

    14.01.08 / 5298e_a

    0.1 0.3 0.5 0.7 0.9

    test voltage: 600 V / 50 Hztest current: 500 Aduration: 0.5 s

    a.c. withstand voltage: 250Vimpusle sparkover voltage: 1250Vleakage resistance: 500 k

    Before and after the test:

    EXFS 100 -50 Hz test

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    heating 40K

    EXFS 100 -50 Hz test

    Ex protection safety during the whole duration of interference!

    Heating by 40 K

    max. surface temperature < 85 C

    keeping of T6

    Test_01: Temperature C

    55

    60

    65

    70

    20

    35

    40

    45

    50

    0 100 200 300 400 500 s

    25

    30

    14.01.08 / 5298e_b

  • 2007 DEHN + SHNE / protected by ISO 16016

    Competitors on the EXFS 100 (KU)

    - OBO Bettermann- Leutron- Hakel

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Rated impulse sparkover voltage (1.2/50 s): 1250 V 3000 V ( 50%)min: 1500 V / max: 4500 V

    A.c. sparkover voltage (50 Hz): 500 V 1000 V ( 50%)min: 500 V / max: 1500 V

    D.c. sparkover voltage: > 600 V

    Nominal discharge current (8/20 s): 100 kA 100 kA

    Lightning impulse current (10/350 s): 100 kA 100 kA

    Class of lightning current carryingcapability acc. to EN 50164-3: H H

    Rated power frequency withstand voltage (50 Hz): 250 V

    Max. d.c. continuous operating voltage: 350 V

    Rated discharge current (50 Hz): 500 A / 0.5 sec.

    Ex isolating spark gaps - Competitors Comparison DEHN EXFS 100 - OBO PAREX 480

    PAREX 480EXFS 100

    14.01.08 / 5322e_a

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    PAREX 480EXFS 100

    EC-type examination certification: BVS 06 ATEX E 099 BVS 04 ATEX E 054

    Explosion protection - gases: II 2G Ex d IIC T6 II 2G EEx d IIC T6

    - dusts: II 2D Ex tD A21 IP67 T 80C not certificated

    for dust

    Degree of protection: IP 67

    Ambient temperature: (-20 ... +40)C (-20 ... +50)C

    Ex isolating spark gaps - Competitors Comparison DEHN EXFS 100 - OBO PAREX 480

    14.01.08 / 5322e_b

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Remarks to OBO / PAREX 480:

    No test units available; the data sheet, however, specifies Risol 100 M

    no KU types for underground application

    with a connecting cable length of 180 mm, 250 mmor 350 mm only at one side

    Ex isolating spark gaps - Competitors Comparison DEHN EXFS 100 - OBO PAREX 480

    14.01.08 / 5322e_d

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100

    Rated impulse sparkover voltage (1.2/50 s): 1250 V 950 V (typ. 650 V)A.c. sparkover voltage (50 Hz): 500 V 70 V ( 20%)

    max: 84 V

    D.c. sparkover voltage: > 600 V 100 V ( 20%)

    Nominal discharge current (8/20 s): 100 kA 100 kA

    Lightning impulse current (10/350 s): 100 kA 75 kA

    Class of lightning current carrying capability according to EN 50164-3: H N

    Rated power frequency withstand voltage (50 Hz): 250 V

    Max. d.c. continuous operating voltage: 350 V

    Rated discharge current (50 Hz): 500 A / 0.5 sec.

    Ex isolating spark gap - CompetitorsComparison DEHN EXFS 100 - LEUTRON TC 100 A

    TC 100 A

    14.01.08 / 5323e_a

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EC-type examination certification: BVS 06 ATEX E 099 ZELM 02 ATEX 0095X

    Explosion protection - gases: II 2G Ex d IIC T6 II 2G EEx m II T3

    - dusts: II 2D Ex tD A21 IP67 T 80C

    Degree of protection: IP 67 IP 67

    Ambient temperature: (-20 ... +40)C (-25 ... +90)C

    Ex isolating spark gaps - CompetitorsComparison DEHN - LEUTRON TC 100 A

    EXFS 100 TC 100 A

    14.01.08 / 5323e_b

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100 TC 500 A

    Rated impulse sparkover voltage (1.2/50 s): 1250 V 1300 V (typ. 950 V)

    A.c. sparkover voltage (50 Hz): 500 V 350 V ( 15%)

    D.c. sparkover voltage: < 600 V 500 V ( 15%)

    Nominal discharge current (8/20 s): 100 kA 100 kA

    Lightning impulse current (10/350 s): 100 kA 75 kA

    Class of lightning current carrying capability according to EN 50164-3: H N

    Rated power frequency withstand voltage (50 Hz): 250 V

    Max. d.c. continuous operating voltage: 350 V

    Rated discharge current (50 Hz): 500 A / 0.5 sec.

    Ex isolating spark gaps - CompetitorsComparison DEHN EXFS - LEUTRON TC 500 A

    14.01.08 / 5323e_c

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    EXFS 100 TC 500 A

    EC-type examination certification: BVS 06 ATEX E 099 ZELM 02 ATEX 0095X

    Explosion protection - gases: II 2G Ex d IIC T6 II 2G EEx m II T3

    - dusts: II 2D Ex tD A21 IP67 T 80C

    Degree of protection: IP 67 IP 67

    Ambient temperature: (-20 ... +40)C (-25 ... +90)C

    Ex isolating spark gaps - CompetitorsComparison DEHN EXFS - LEUTRON TC 500 A

    14.01.08 / 5323e_d

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    Remarks to LEUTRON TC100 A And TC 500 A:

    There are special requirements (X behind certification number); such as EXFS C1 (923 070)

    equalising currents enclosure 50 V dc constantly must not be exceeded isolating spark gap to be installed free from mechanical tensions the isolating spark gap has to be installed so that it is protected against direct weather

    influences

    Ex isolating spark gaps - CompetitorsLEUTRON TC 100 A and TC 500 A

    Fail Safe - performance

    no test units available; specification in the data sheet Risol 109

    KU-type available for underground application

    connecting cable set K1/300 with 30 cm cable length available

    14.01.08 / 5323e_e

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    HS 100 ExEXFS 100

    Rated impulse sparkover voltage (1.2/50 s): 1250 V < 1500 V

    A.c sparkover voltage (50 Hz): 500 V > 500 V

    D.c sparkover voltage: > 600 V 400 - 750 V

    Nominal discharge current (8/20 s): 100 kA 75 kA

    Lightning impulse current (10/350 s): 100 kA 100 kA

    Class of lightning current carrying capability according to EN 50164-3: H

    Rated power frequence withstand voltage (50 Hz): 250 V

    Max. d.c. continuous operating voltage: 350 V

    Rated discharge current (50 Hz): 500 A / 0.5 sec.

    Ex isolating spark gaps - Competitors Comparison DEHN EXFS - HAKEL HGS 100Ex

    14.01.08 / 5324e_a

  • 2007 DEHN + SHNE / protected by ISO 16016 EXFS 100

    HS 100 ExEXFS 100

    EC-type examination certification: BVS 06 ATEX E 099 FTZ 04 ATEX 0255X

    Explosion protection - gases: II 2G Ex d IIC T6 II 2GD EEx m II T3

    - dusts: II 2D Ex tD A21 IP67 T 80C

    no permission for dusts

    Degree of protection: IP 67 IP 66

    Ambient temperature: (-20 ... +40)C (-20 ... +90)C

    Ex isolating spark gaps - Competitors Comparison DEHN EXFS - HAKEL HGS 100Ex

    14.01.08 / 5324e_b

  • 2007 DEHN + SHNE / protected by ISO 16016 DEHN UK, 2011 11.12.07 / 5392

    For further information about lightning protectionplease visit us on our STAND No. U25

    Thank you for your attention