South Carolina Research Authority 2010 M2G Certification
-
Upload
charles-rice -
Category
Documents
-
view
30 -
download
1
Transcript of South Carolina Research Authority 2010 M2G Certification
Greffen Systems M2G Evaluation – 21 September 2010
1
EXTERNAL MEMORANDUM TO SCEO
Subject: Evaluation Summary of Greffen Systems
Applicant: Greffen Systems
Proposed Product Evaluation:
Greffen Systems M2G Microprocessor Boiler Controller
SCRA Reviewer: Mark McCormick
Date Submitted to SCEO: 22 September 2010
Product Claims:
Greffen Systems (Green Efficient Energy) manufacturers a boiler control product that claims
to reduce natural gas or oil consumption by more accurately monitoring and controlling
boiler conditions and reducing the frequency of the burner firing. The reduction of burner
firings will reduce the consumption of fossil fuels; reduce energy costs; increase the lifespan
of the boiler and the burner; and reduce carbon emissions.
The device is compatible with existing boilers and controls. Reductions from 7 to 30% for
energy cost and carbon emissions are claimed by Greffen Systems. The system is Boiler
Industry Standards and Requirements compliant and will work with, or without Building
Management Systems (BMS). The control device is stated in product literature to be in
operation on over 4,000 boilers in Europe; and based on conversations with a Greffen
representative, approximately 100 boilers in the United States.
Product Concept and Specifications:
The M2G is designed to be retrofitted on older, existing boilers in operation, as well as new
installations. The product works with existing heating systems and BMSs. The M2G is
attached to the boiler and all wiring is connected locally to the specific boiler. Installation
time is approximated at 2- 4 hours and performs with gas or oil boilers, preferably 1,000,000
BTUs or higher.
Hot water is needed from the boiler to keep the heating system in operation and the
occupants comfortable. Boiler sizing and hot water temperature settings are basically
Greffen Systems M2G Evaluation – 22 September 2010
2
established for the peak demand on the coldest anticipated day so the building occupants will
have consistent, available heat. The water in the boiler is re-heated and circulated when the
loop water temperature falls below a certain set-point.
Reheating will occur because ambient temperatures will drop or water in the boiler and
piping will gradually cool. Many of these reheat cycles occur because of a predictable drop
in outside temperature instead of an actual need for more heat in the building. For example,
it is a cold, but sunny day. By late afternoon and early evening, the heat from the sun has
transferred through the building envelope and is aiding in keeping the indoor temperature
comfortable. However, the boiler controls are sensing a drop in the outdoor temperature and
will signal the boiler to reheat even though temperatures within the space are acceptable.
Using this same situation, natural cooling of the water in the boiler and associated piping will
also activate boiler sensors to reheat, even though the indoor temperature settings are met.
The Greffen Systems M2G microprocessor uses algorithms to allow the boiler and loop
water temperatures to fall below typical set points without reheating, only when the heating
system can still provide the needed heat within the building spaces. The M2G monitors
inside space temperatures and water temperatures at the inlet and outlet of the boiler. The
temperature data from all of these sources are monitored over time and the M2G “learns”
when boiler reheat is necessary, thus reducing reheat cycles.
The product has a manufacturer’s model number of “M2G” and is Underwriters Laboratories
(UL) tested and approved and certified as an Energy Technology List product in Europe.
The following are the unit specifications:
Power Requirements 110V AC, 50mA
Relay Switching Capacity 2A at 120 V AC (resistive)
Isolation Technology Opto-Isolation
Fuse Rating 1.6A 120 V AC
Dimensions 6.9 in (175mm) W x 7.9 in (200mm) H x 2.1 in (54mm) D
Sensors (2) Digital Thermometer
Sensor Range 131 degrees F to 257 degrees F
Weight 3.6 pounds
Case Metal
Measured Savings:
The Reviewer verified SCEO provided validation reports from the U.S. Navy, Naval Air
Station in Jacksonville, Florida and the Internal Revenue Service building in Chamblee,
Georgia. In addition, the Reviewer conducted telephone interviews with three other
applications from a list provided by Greffen Systems. All interviews were with the facility
Greffen Systems M2G Evaluation – 22 September 2010
3
Energy Coordinator/Manager responsible for the procurement, installation and monitoring of
the devices. The other installed applications are:
State of Michigan – Department of Corrections – Lansing, Michigan
Yahoo – Sunnyvale, California – buildings managed by Jones Lang LaSalle
Baylor Medical Center – Dallas, Texas - buildings managed by CB Richard Ellis
In all of the above referenced applications, an independent, validated data collection device
was installed and energy usage information was recorded. The data collection duration of
these applications ranged from approximately 45 days to three months. The quantity of
boilers monitored ranged from one to as many as four boilers at a time.
The direct energy consumption savings were measured as:
US Navy – Jacksonville, FL – 11 %
IRS Building – Chamblee, GA – 11%
State of Michigan – Dept of Corrections – Lansing, MI – 12 – 17%
Yahoo – Sunnyvale, CA – 10 – 15%
Baylor Medical Center – Dallas, TX – 12 – 14%
Recommendations:
Based on the reviewers’ assessment of the provided information, telephone interviews and
industry standards, the product should be approved by the State of South Carolina in its
facilities for the intended use of the product.
The reviewer believes the product will average a reduction in direct consumption of natural
gas or oil in the range of 12 to 15% and payback on investment periods will on average be 12
months or less.