    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Heating Plantroom 7400 mm wide x 6000 mm deep x 3000 mm high (overall)

  • 8/12/2019 Solutions Schedule3

    3/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Plantroom

    Reference Area Location NotesHeating Plantroom 44 m Ground Floor -

    Equipment

    Reference Duty SelectionSidestream Filter 1 No. sidestream filter(s) Sidestream filter, 600 mm wide x 600 mm deep x 2000 mm high,

    100 kg, 100 kgEnwamatic, TBCwww.enwamatic.com

    Calorifiers 2 No. calorifiers @ 1340 litres/hr to meet 2000 litres/hr total capacityVenting: unvented

    Arrangement: vertical

    Generic semi storage vertical, 440 litres/hr, 735 mm wide x 1060mm deep x 2050 mm high, 850 kgIMI Rycroft semi storage vertical, model MX440V, 1760 litres/hrhttp://www.rycroft.com/ HRS semi storage vertical, model Aquasave AS515, 2500 litres/hrhttp://www.hrs.co.uk/

    Calorifiers heating pumps 1 No. duty / 1 No. standby @ 6.52 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519mm high, 56 kg

    Armstrong in-line vertical pump, model Starline50-150www.armstrongpumps.com

    Hot water circulating pump 1 No. duty @ 10.8 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg

    Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com

    Calorifiers expansion vessels 2 No. expansion vessels3350 litres system volume3.00 bar g feed pressure3.55 bar g final pressure75C maximum system temperature

    0% glycol370 litres expansion volume

    Generic expansion vessel, 500 litres, 581 kgRycroft expansion vessel, model EXP500V, 500 litreshttp://www.rycroft.com/ Smedegaard expansion vessel, model Type 2 500, 500 litreshttp://www.smedegaard.com/

    MCC 200 Amp incomer, 8 starters415 V, TP&N, 50 Hz

    Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp

    Primary Heating circulatingpumps

    1 No. duty / 1 No. standby @ 15.22 l/s, 250 kPaPump type: in-line vertical

    Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564mm high, 73 kg

    http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.comhttp://www.rycroft.com/http://www.rycroft.com/http://www.hrs.co.uk/http://www.hrs.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.rycroft.com/http://www.rycroft.com/http://www.smedegaard.com/http://www.smedegaard.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.smedegaard.com/http://www.rycroft.com/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hrs.co.uk/http://www.rycroft.com/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.enwamatic.com
  • 8/12/2019 Solutions Schedule3

    4/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Pump arrangement: singlePump fluid: water

    Armstrong in-line vertical pump, model Starline50-200www.armstrongpumps.com

    Boilers 3 No. boilers @ 400 kW to meet 700 kW loadMinimum natural gas efficiencies:- Maximum output: 90.0% (nett)- Seasonal (UK): 86.0% (gross)

    Minimum oil efficiencies:- Maximum output: 90.0% (nett)- Seasonal (UK): 84.0% (gross)

    Boiler type: condensingFuel: natural gas

    Generic condensing boiler, 410 kW, 1110 mm wide x 1755 mmdeep x 2095 mm high, 1342 kgHoval condensing boiler, model UltraGas450, 410 kWhttp://www.hoval.co.uk/

    Boiler shunt pumps 1 No. duty per boiler @ 8.7 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 196 mm wide x 381 mm deep x 519mm high, 56 kg

    Armstrong in-line vertical pump, model Starline50-150www.armstrongpumps.com

    Heating pressurisationunit(upper floors)

    1 No. pressurisation unit9000 litres system volume8.0 bar g maximum working pressure1.6 bar g maximum system pressure

    60C maximum system temperature0% glycolPressurisation unit types: standard, compressor

    Generic standard pressurisation unit, 1170 mm wide x 800 mm deepx 1660 mm high, 802 kgHoval standard pressurisation unit, model PressVal Micron SM600,600 litres

    http://www.hoval.co.uk/

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    Boilers vents Vent type: Natural high level, natural low level

    High level vents to provide 0.27 m/s ventilation air exhaustLow level vents to provide 0.52 m/s combustion and ventilation airintake(Based on BS6644, BS5410-2 and manufacturer recommendations)

    2 No. generic vents at high level, 800 mm wide x 200 mm high, 50

    % free area2 No. generic vents at low level, 800 mm wide x 400 mm high, 50 %free area

    Notes

    Auditorium AHU 8200 mm wide x 3500 mm deep x 1700 mm high

    http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.com
  • 8/12/2019 Solutions Schedule3

    5/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Plantroom

    Reference Area Location Notes Auditorium AHU 28 m Ground Floor -

    Equipment

    Reference Duty SelectionBasement AHU Air flow 1.2 m/s

    Configuration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components:- Louvre- Attenuator (600 mm)

    - Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)

    Generic modular AHU, SFP 1.6 W/l/s (estimated), 7000 mm wide x1404 mm deep x 1548 mm high, 1820 kgFlakt Woods modular AHU, model EU22http://www.flaktwoods.com/products/air-handling-units/

    http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/
  • 8/12/2019 Solutions Schedule3

    6/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    - ConnectionExtract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel- Access (short)- Humidifier (steam)- Fan (backward curved)- Panel filter- Access (short)- Attenuator (600 mm)- Connection

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    7/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Main AHU 11300 mm wide x 8500 mm deep x 5400 mm high

    Plantroom

    Reference Area Location NotesMain AHU 96 m Ground Floor -

    Equipment

    Reference Duty SelectionBasement AHU Air flow 8.5 m/s

    Configuration: stacked, intake bottomMaximum velocity 2.2 m/sSupply components:- Louvre- Attenuator (600 mm)- Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)

    Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62http://www.flaktwoods.com/products/air-handling-units/

    http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/
  • 8/12/2019 Solutions Schedule3

    8/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    - ConnectionExtract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel- Access (short)- Humidifier (steam)- Access (short)- Fan (backward curved)- Panel filter- Attenuator (600 mm)- Connection

    Basement AHU Air flow 8.5 m/sConfiguration: stacked, intake bottomMaximum velocity 2.2 m/s

    Supply components:- Louvre- Attenuator (600 mm)- Bag filter (long)- Access (short)- Thermal wheel- Thermal wheel- Access (short)- Fan (backward curved)- Access (short)- Humidifier (steam)- Attenuator (600 mm)- Connection

    Extract components:- Louvre- Attenuator (600 mm)- Access (short)- Thermal wheel- Heating coil (2 row)- Access (short)- Thermal wheel

    Generic modular AHU, SFP 1.8 W/l/s (estimated), 10050 mm wide x2650 mm deep x 4100 mm high, 9630 kgFlakt Woods modular AHU, model EU62

    http://www.flaktwoods.com/products/air-handling-units/

    http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/http://www.flaktwoods.com/products/air-handling-units/
  • 8/12/2019 Solutions Schedule3

    9/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    - Access (short)- Humidifier (steam)- Access (short)- Fan (backward curved)- Panel filter- Attenuator (600 mm)- Connection

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    10/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Sump Pump 2000 mm wide x 2000 mm deep x 1200 mm high (overall)

    Plantroom

    Reference Area Location NotesSump Pump 4 m Roof -

    Equipment

    Reference Duty SelectionSump pump 1 No. @ 2 l/s, 100 kPa

    Pump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 131 mm wide x 285 mm deep x 446

    mm high, 21 kg Armstrong in-line vertical pump, model Starline32-120www.armstrongpumps.com

    Notes

    ...

    http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.com
  • 8/12/2019 Solutions Schedule3

    11/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Rain Water Storage Plantroom 8000 mm wide x 4600 mm deep x 4000 mm high (overall)

    Plantroom

    Reference Area Location NotesRain Water Storage Plantroom 37 m Ground Floor -

    Equipment

    Reference Duty SelectionRain water pre-treatment tank 1 No. water tanks @ 7,000 litres Generic water tank, 2000 mm wide x 2000 mm deep x 3000 mm

    high300 mm bund height requirement

    Treated Rain Water booster 1 No. booster @ 2 l/s, 20 mwg1 No. pump + standby

    Generic cold water booster, 665 mm wide x 1034 mm deep x 1565mm high, 270 kgGrundfos cold water booster, model Multi E 1 CRE10http://www.grundfos.com/

    AquaTech Pressmain cold water booster, model Aquamatic BTE210http://www.aquatechpressmain.co.uk/

    http://www.grundfos.com/http://www.grundfos.com/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.grundfos.com/
  • 8/12/2019 Solutions Schedule3

    12/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    Rain water booster pre-treatment

    1 No. booster @ 2 l/s, 20 mwg2 No. pumps + standby

    Generic cold water booster, 920 mm wide x 1034 mm deep x 1565mm high, 310 kgGrundfos cold water booster, model Multi E 2 CRE5http://www.grundfos.com/

    AquaTech Pressmain cold water booster, model Aquamatic BTE3 5http://www.aquatechpressmain.co.uk/

    Treated Rain water tank 1 No. water tanks @ 7,500 litres Generic water tank, 3000 mm wide x 2000 mm deep x 2000 mmhigh300 mm bund height requirement

    Notes

    ...

    http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.grundfos.com/http://www.grundfos.com/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.aquatechpressmain.co.uk/http://www.grundfos.com/http://www.eaton.com/ukhttp://www.moeller.co.uk/
  • 8/12/2019 Solutions Schedule3

    13/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    HV Plantroom 7100 mm wide x 4900 mm deep x 3400 mm high (overall)

    Plantroom

    Reference Area Location NotesHV Plantroom 35 m Ground Floor -

    Equipment

    Reference Duty SelectionRMU Rating 200 Amps

    12000 V, TP&N, 50 HzGeneric RMU, 771 mm wide x 765 mm deep x 1510 mm high, 300kg

    ABB RMU, model SafeRinghttp://www.abb.com/ Schneider RMU, model Ringmaster RN2http://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm

    HV switchpanel 12000 V, TP&N, 50 HzModule type: withdrawable

    Generic HV switchpanel, 2600 mm wide x 1550 mm deep x 2300mm high

    http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/
  • 8/12/2019 Solutions Schedule3

    14/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Modules:- Incomer- Bus section- Feeder

    Future expansion 25%Note: For some manufacturers VTs are integral to other components

    ABB HV switchpanel, model Unigear ZS1http://www.abb.com/ Schneider HV switchpanel, model MCSethttp://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm

    Notes

    ...

    http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/
  • 8/12/2019 Solutions Schedule3

    15/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)

    lantroomReference Area Location NotesLV Plantroom 21 m Ground Floor -

    Equipment

    Reference Duty SelectionLV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,

    100 kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    16/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Life Safety LV Plantroom 6000 mm wide x 3500 mm deep x 3000 mm high (overall)

    PlantroomReference Area Location Notes

    Life Safety LV Plantroom 21 m Ground Floor -

    Equipment

    Reference Duty SelectionLV Board 1 No. lv board(s) Lv board, 4000 mm wide x 1200 mm deep x 600 mm high, 100 kg,

    100 kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    17/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Gas Meter Plantroom 1200 mm wide x 2000 mm deep x 2500 mm high (overall)

    PlantroomReference Area Location NotesGas Meter Plantroom 3 m Ground Floor -

    Equipment

    Reference Duty Selection

    Gas Meter 1 No. gas meter(s) Gas meter, 800 mm wide x 480 mm deep x 600 mm high, 100 kg,100 kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    18/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Telecoms Plantroom 4000 mm wide x 2000 mm deep x 2500 mm high (overall)

    Plantroom

    Reference Area Location NotesTelecoms Plantroom 8 m Ground Floor -

    Equipment

    Reference Duty SelectionCopper Rack 1 No. rack(s) Rack, 2000 mm wide x 500 mm deep x 1600 mm high, 100 kg, 100

    kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    19/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Transformers Plantroom 5200 mm wide x 4300 mm deep x 3500 mm high (overall)

    Plantroom

    Reference Area Location NotesTransformers Plantroom 22 m Ground Floor -

    Equipment

    Reference Duty SelectionTransformers supply duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximum

    Maximum aspect ratio: 4.0Insulation: none(Air flow requirement based on transformers losses)

    500 mm wide x 300 mm deepNo insulation

    Transformers 1 No. @ 800 kVAHV 12000 V, LV 415 V, TP&N, 50 HzTransformer type: dryDerating factor: 1.25

    Generic dry transformer, 1000 kVA, 2000 mm wide x 1210 mm deepx 2400 mm high, 2870 kg

    ABB dry transformer, model Cast resin 1000, 1000 kVAhttp://www.abb.com/ Schneider dry transformer, model Cast Resin 1000, 1000 kVAhttp://www.schneider-electric.co.uk/ Minimum connection space above: 600 mm

    Transformers extract duct 0.82 m/s @ 10.0 m/s maximum, 1.0 Pa/m maximumMaximum aspect ratio: 4.0Insulation: none

    500 mm wide x 300 mm deepNo insulation

    http://www.abb.com/http://www.abb.com/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.schneider-electric.co.uk/http://www.abb.com/
  • 8/12/2019 Solutions Schedule3

    20/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    (Air flow requirement based on transformers losses)

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    21/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Satellite 4000 mm wide x 2200 mm deep x 1800 mm high (overall)

    Plantroom

    Reference Area Location NotesSatellite 9 m Roof -

    Equipment

    Reference Duty SelectionSATELLITE DISH 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100

    kg, 100 kgSATELLITE DISH 1 1 No. satellite dish(s) Satellite dish, 1200 mm wide x 1200 mm deep x 1200 mm high, 100

    kg, 100 kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    22/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Computer AC Units 10100 mm wide x 2200 mm deep x 1200 mm high

    Plantroom

    Reference Area Location NotesComputer AC Units 22 m Roof -

    Equipment

    Reference Duty SelectionComputer Room AC units 5 No. condensers @ 10 kW

    Condenser type: vertical air flowMean condensing temperature: 50C

    Ambient temperature: 35CNoise: 70 dBA @ 10 m

    Generic vertical air flow condenser, 14 kW, 907 mm wide x 972 mmdeep x 1076 mm high, 62 kg

    Airedale vertical condenser, model CR12, 14 kWhttp://www.airedale.com/

    Notes

    ...

    http://www.airedale.com/http://www.airedale.com/http://www.airedale.com/
  • 8/12/2019 Solutions Schedule3

    23/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    MER Room 5900 mm wide x 4200 mm deep x 3400 mm high (overall)

    Plantroom

    Reference Area Location NotesMER Room 25 m Ground Floor -

    Equipment

    Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100

    kgRack, Rack

    IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack, Rack

    IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack

  • 8/12/2019 Solutions Schedule3

    24/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Battery Unit 1 No. battery unit(s) Battery unit, 800 mm wide x 1000 mm deep x 2200 mm high, 100kg, 100 kg

    AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,500 kg

    AC Unit 1 No. ac unit(s) Ac unit, 1200 mm wide x 800 mm deep x 2000 mm high, 500 kg,500 kg

    Electrical board 160 Amp incomer, 12 waysType: MCCB415 V, TP&N, 50 Hz

    Generic mccb electrical board, 12 way, 400 Amp incomer, 900 mmwide x 230 mm deep x 1605 mm high, 168 kgMoeller mccb electrical board, model PB12-400, 12 way, 400 Ampincomerhttp://www.moeller.co.uk/ MEM mccb electrical board, model PBJG1240M, 12 way, 400 Ampincomerhttp://www.eaton.com/uk

    UPS 1 No. ups(s) Ups, 800 mm wide x 1000 mm deep x 2200 mm high, 100 kg, 100kg

    IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack

    IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack

    IT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgrack

    Notes

    ...

    http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/
  • 8/12/2019 Solutions Schedule3

    25/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Security Room 5600 mm wide x 3600 mm deep x 3700 mm high (overall)

    Plantroom

    Reference Area Location NotesSecurity Room 20 m Ground Floor

    Equipment

    Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100

    kgRack, Rack

    IT Rack Copy 1 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack, Rack

    IT Rack Copy 2 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100kgRack

    Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100kg

    AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30kg, 30 kg

    Desk 1 No. desk(s) Desk, 1800 mm wide x 850 mm deep x 850 mm high, 100 kg, 100kg

    Electrical board 100 Amp incomer, 12 ways Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mm

  • 8/12/2019 Solutions Schedule3

    26/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Type: MCB415 V, TP&N, 50 Hz

    wide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg

    AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 1200 mm wide x 250 mm deep x 400 mm high, 30kg, 30 kg

    http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/
  • 8/12/2019 Solutions Schedule3

    27/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    AV Room 2900 mm wide x 2300 mm deep x 3700 mm high (overall)

    Plantroom

    Reference Area Location Notes AV Room 7 m Ground Floor

    Equipment

    Reference Duty SelectionIT Rack 1 No. it rack(s) It rack, 800 mm wide x 800 mm deep x 2200 mm high, 100 kg, 100

    kgRack, Rack

    Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg

    Desk 1 No. desk(s) Desk, 1200 mm wide x 750 mm deep x 850 mm high, 100 kg, 100kg

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Amp

    incomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,30 kg

    AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,30 kg

    http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/
  • 8/12/2019 Solutions Schedule3

    28/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    BEMS and Maintenance Room 3600 mm wide x 2300 mm deep x 3700 mm high (overall)

    Plantroom

    Reference Area Location NotesBEMS and Maintenance Room 9 m Ground Floor

    Equipment

    Reference Duty SelectionDesk 1 No. desk(s) Desk, 1800 mm wide x 750 mm deep x 850 mm high, 100 kg, 100

    kgLocker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,

    100 kg AC Unit 1 No. hi-wall ac unit(s) Hi-wall ac unit, 750 mm wide x 250 mm deep x 400 mm high, 30 kg,

    30 kgElectrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.moeller.co.uk/
  • 8/12/2019 Solutions Schedule3

    29/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Locker 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg

    Locker2 1 No. locker(s) Locker, 1200 mm wide x 450 mm deep x 1800 mm high, 100 kg,100 kg

  • 8/12/2019 Solutions Schedule3

    30/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Sprinkler Tank 8800 mm wide x 7300 mm deep x 4000 mm high (overall)

    PlantroomReference Area Location NotesSprinkler Tank 64 m Basement -

    Equipment

    Reference Duty SelectionWater tank 1 No. water tanks @ 70,000 litres Generic water tank, 6000 mm wide x 5000 mm deep x 3000 mm

    highBunding requirement exceeds 1000 mm

    Sprinkler Pump Set 1a 1 No. sprinkler pump set 1a(s) Sprinkler pump set 1a, 750 mm wide x 2200 mm deep x 1000 mmhigh, 100 kg, 100 kgTBC, TBCTBC

    Sprinkler Pump Set 2a 1 No. sprinkler pump set 2a(s) Sprinkler pump set 2a, 600 mm wide x 600 mm deep x 1000 mmhigh, 100 kg, 100 kgTBC, TBCTBC

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomer

    http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBChttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/TBC
  • 8/12/2019 Solutions Schedule3

    31/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    http://www.eaton.com/uk MCC 200 Amp incomer, 5 starters

    415 V, TP&N, 50 HzGeneric MCC, 1200 mm wide x 652 mm deep x 2263 mm high

    ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp

    Notes

    ...

    http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.eaton.com/uk
  • 8/12/2019 Solutions Schedule3

    32/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Chillers Plantroom 9600 mm wide x 8200 mm deep x 3200 mm high (overall)

    Plantroom

    Reference Area Location NotesChillers Plantroom 78 m Basement -

    Equipment

    Reference Duty SelectionWater cooled chillers 2 No. chillers @ 850 kW to meet 300 kW total load

    Minimum EER (or CoP):- 3.85 kW/kW 750 kW

    Chiller types: scroll, screw, c entrifugalChilled water: 12C on / 7C off

    Condenser water: 30C on / 35C off

    Generic water cooled chiller, 892 kW, 3924 mm wide x 1600 mmdeep x 2060 mm high, 6202 kgTrane screw water cooled chiller, model RTHD C2-D5-E4, 892 kWhttp://www.trane.com/ Carrier screw water cooled chiller, model 30HXC0260, 897 kWhttp://www.carrieraircon.co.uk/

    Cooling primary pumps 1 No. duty / 1 No. standby @ 11.96 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg

    Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com

    Heat rejection pumps 1 No. duty / 1 No. standby @ 17.43 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg

    Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com

    http://www.trane.com/http://www.trane.com/http://www.carrieraircon.co.uk/http://www.carrieraircon.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.carrieraircon.co.uk/http://www.trane.com/
  • 8/12/2019 Solutions Schedule3

    33/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Heat rejection pressurisationunit

    1 No. pressurisation unit2190 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure50C maximum system temperature35% glycolPressurisation unit types: standard, compressor

    Generic standard pressurisation unit, 1199 mm wide x 634 mm deepx 1446 mm high, 347 kgHoval standard pressurisation unit, model PressVal Micron SM200,200 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N200, 200 litreshttp://www.mikrofill.com/

    MCC 200 Amp incomer, 6 starters415 V, TP&N, 50 Hz

    Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/ MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomer

    http://www.eaton.com/uk Cooling circulating pumps 1 No. duty / 1 No. standby @ 14.35 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 214 mm wide x 458 mm deep x 564mm high, 73 kg

    Armstrong in-line vertical pump, model Starline50-200www.armstrongpumps.com

    Cooling pressurisation unit 1 No. pressurisation unit2700 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure40C maximum system temperature0% glycolPressurisation unit types: standard, compressor

    Generic standard pressurisation unit, 1077 mm wide x 600 mm deepx 1095 mm high, 207 kgHoval standard pressurisation unit, model PressVal Micron SM80,80 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N80, 80 litreshttp://www.mikrofill.com/

    Notes

    ...

    http://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.eaton.com/ukhttp://www.moeller.co.uk/http://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.mikrofill.com/http://www.hoval.co.uk/
  • 8/12/2019 Solutions Schedule3

    34/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Generators Plantroom 9100 mm wide x 4200 mm deep x 4200 mm high (overall)

    Plantroom

    Reference Area Location NotesGenerators Plantroom 38 m Basement -

    Equipment

    Reference Duty SelectionLV generators board 1 No. incomer

    1 No. feeder415 V, TP&N, 50 Hz

    Access: front

    Generic generators LV switchboard, 2650 mm wide x 655 mm deepx 2429 mm highGE Power Controls generators LV switchboard, model System 4http://www.ge.com/ Eaton generators LV switchboard, model Bill Classic Form 4http://www.eaton.com/ Minimum connection space above: 600 mm

    Generators 1 No. generators @ 400 kVA415 V, TP&N, 50 Hz

    Generic diesel generator, 400 kVA, 3500 mm wide x 1150 mmdeep x 2158 mm high, 3700 kgBroadcrown diesel generator, model BCC 440-50 E2, 440 kVA,Emissions compliance EU Stage 2http://www.broadcrown.com/ FG Wilson diesel generator, model P350P4, 400 kVA, Emissionscompliance EU Stage 2http://www.fgwilson.com/

    http://www.ge.com/http://www.ge.com/http://www.eaton.com/http://www.eaton.com/http://www.broadcrown.com/http://www.broadcrown.com/http://www.fgwilson.com/http://www.fgwilson.com/http://www.fgwilson.com/http://www.broadcrown.com/http://www.eaton.com/http://www.ge.com/
  • 8/12/2019 Solutions Schedule3

    35/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Day tanks 1 No. day tanks @ 8 hours storageGenerator fuel tank capacity : 650 litresDay tank capacity (nett): 38 litres

    Generic day tank , 1364 litres, 1750 mm wide x 1170 mm deep x1250 mm highJoseph Ash day tank, model D01, 1364 litreshttp://www.jaenvirotanks.com/ Blake day tank, model TEBU FO 1000, 1000 litreshttp://www.blakegroup.co.uk/

    Notes

    ...

    http://www.jaenvirotanks.com/http://www.jaenvirotanks.com/http://www.blakegroup.co.uk/http://www.blakegroup.co.uk/http://www.blakegroup.co.uk/http://www.jaenvirotanks.com/
  • 8/12/2019 Solutions Schedule3

    36/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Hybrid Coolers 13000 mm wide x 4400 mm deep x 2600 mm high

    Plantroom

    Reference Area Location NotesHybrid Coolers 58 m Roof To reject 500 kW of heat to roof

    Equipment

    Reference Duty SelectionHybrid Cooler 1 1 No. hybrid cooler 1(s) Hybrid cooler 1, 5000 mm wide x 2400 mm deep x 2500 mm high,

    100 kg, 100 kgHybrid Cooler 2 1 No. hybrid cooler 2(s) Hybrid cooler 2, 5000 mm wide x 2400 mm deep x 2500 mm high,

    100 kg, 100 kg

    Notes

    ...

  • 8/12/2019 Solutions Schedule3

    37/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Chillers Plantroom 9000 mm wide x 6100 mm deep x 3000 mm high (overall)

  • 8/12/2019 Solutions Schedule3

    38/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    Plantroom

    Reference Area Location NotesChillers Plantroom 54 m Basement -

    Equipment

    Reference Duty SelectionWater cooled chillers 2 No. chillers @ 200 kW to meet 400 kW total load

    Minimum EER (or CoP):- 3.85 kW/kW 750 kW

    Chiller types: scroll, screw, c entrifugalChilled water: 12C on / 7C offCondenser water: 30C on / 35C off

    Generic water cooled chiller, 244 kW, 3510 mm wide x 980 mmdeep x 1929 mm high, 2664 kgTrane screw water cooled chiller, model RTWD70, 244 kWhttp://www.trane.com/ Carrier screw water cooled chiller, model 30HXC080, 286 kWhttp://www.carrieraircon.co.uk/

    Cooling primary pumps 1 No. duty / 1 No. standby @ 15.95 l/s, 100 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 255 mm wide x 635 mm deep x 753mm high, 120 kg

    Armstrong in-line vertical pump, model Starline100-200www.armstrongpumps.com

    Heat rejection pumps 1 No. duty / 1 No. standby @ 23.92 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com

    Heat rejection pressurisationunit

    1 No. pressurisation unit3000 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure50C maximum system temperature35% glycolPressurisation unit types: standard, compressor

    Generic standard pressurisation unit, 1199 mm wide x 634 mm deepx 1480 mm high, 447 kgHoval standard pressurisation unit, model PressVal Micron SM300,300 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N250, 250 litreshttp://www.mikrofill.com/

    MCC 200 Amp incomer, 6 starters415 V, TP&N, 50 Hz

    Generic MCC, 1200 mm wide x 652 mm deep x 2263 mm high ABB MCC, model MNShttp://www.abb.co.uk/ Eaton Moeller MCC, model Modanhttp://www.moeller.net/en/index.jsp

    Electrical board 100 Amp incomer, 12 waysType: MCB415 V, TP&N, 50 Hz

    Generic mcb electrical board, 12 way, 100 Amp incomer, 460 mmwide x 150 mm deep x 885 mm high, 28 kgMoeller mcb electrical board, model FG-B-12, 12 way, 100 Ampincomerhttp://www.moeller.co.uk/

    h h l h d l

    http://www.trane.com/http://www.trane.com/http://www.carrieraircon.co.uk/http://www.carrieraircon.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.abb.co.uk/http://www.abb.co.uk/http://www.moeller.net/en/index.jsphttp://www.moeller.net/en/index.jsphttp://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.co.uk/http://www.moeller.net/en/index.jsphttp://www.abb.co.uk/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.carrieraircon.co.uk/http://www.trane.com/
  • 8/12/2019 Solutions Schedule3

    39/39

    Chapman Bathurst Plantroom & Riser Schedule

    Chapman BDSP

    MEM mcb electrical board, model EBM121, 12 way, 125 Ampincomerhttp://www.eaton.com/uk

    Cooling circulating pumps 1 No. duty / 1 No. standby @ 19.14 l/s, 250 kPaPump type: in-line verticalPump arrangement: singlePump fluid: water

    Generic in-line vertical pump, 214 mm wide x 559 mm deep x 622mm high, 82 kg

    Armstrong in-line vertical pump, model Starline100-150www.armstrongpumps.com

    Cooling pressurisation unit 1 No. pressurisation unit3600 litres system volume1.9 bar g maximum working pressure1.6 bar g maximum system pressure40C maximum system temperature0% glycolPressurisation unit types: standard, compressor

    Generic standard pressurisation unit, 1077 mm wide x 600 mm deepx 1095 mm high, 231 kgHoval standard pressurisation unit, model PressVal Micron SM110,110 litreshttp://www.hoval.co.uk/ Mikrofill standard pressurisation unit, model Maxi N100, 100 litreshttp://www.mikrofill.com/

    Notes

    ...

    http://www.eaton.com/ukhttp://www.eaton.com/ukhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.hoval.co.uk/http://www.hoval.co.uk/http://www.mikrofill.com/http://www.mikrofill.com/http://www.mikrofill.com/http://www.hoval.co.uk/http://c/Documents%20and%20Settings/batess/Local%20Settings/Apps/2.0/DLT5HMO9.TN6/XEL1EHTY.P0X/spac..tion_e71897b51670c61b_0001.0000_e95580a25517a0b6/Resources/www.armstrongpumps.comhttp://www.eaton.com/uk