From Open Electrical Derating factors for installing cables in soil with thermal resistivity other than 2.5 K·m/W. Soil Thermal Resistivity (K·m/W) Soil Thermal Resistivity Derating Factor Buried Direct Buried in Conduit 0.5 1.88 1.28 0.7 1.62 1.2 1 1.5 1.18 1.5 1.28 1.1 2 1.12 1.05 2.5 1 1 3 0.9 0.96 Back to Low Voltage Cable Data Reference Retrieved from "http://www.openelectrical.org /wiki/index.php?title=Soil_Thermal_Resistivity_Derating_Factors" This page was last modified on 15 March 2011, at 10:20. Soil Thermal Resistivity Derating Factors - Open Electrical http://www.openelectrical.org/wiki/index.php?title=Soil_Thermal_Resi... 1 of 1 6/10/2011 3:20 PM
-
Upload
chihiya-fitria-nurhayati -
Category
Documents
-
view
320 -
download
4
description
cvcv
Transcript of Soil Thermal Resistivity Derating Factors - Open Electrical
From Open Electrical
Derating factors for installing cables in soil with thermal resistivity other than 2.5 K·m/W.
Soil ThermalResistivity (K·m/W)
Soil Thermal ResistivityDerating Factor
BuriedDirect
Buried inConduit
0.5 1.88 1.28
0.7 1.62 1.2
1 1.5 1.18
1.5 1.28 1.1
2 1.12 1.05
2.5 1 1
3 0.9 0.96