  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    1/35

    FOR ADDITION OF TLF SHED IN HALDIA INSTALLATION OF THE

    INDIAN OIL CORPORATION AT HALDIA WEST BENGAL.

    GLORY ENGINEERS SYNDICATE568, D. H. ROAD, KOLKATA- 34

    Ph. No.- 033 2496-6970

    e-mail- [email protected]

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    2/35

    Job No.- GES/S/32/2013

    Date : 15thJune, 2013

    ToMr. Ashish Srivastava

    Managing Director,

    Structech Consulting Engineers India Pvt. Ltd,

    3No. Sulochana, Swami, Samrth Marg,

    Sector 16A, Vashi Novi Mumbai 400705.

    Subject : Soil investigation work for addition of TLF Shed in HaldiaInstallation of the Indian Oil Corporation at Haldia,West Bengal.

    Dear Sir,

    Glory Engineers Syndicate is pleased to present the attached geotechnical

    investigation report for addition of TLF Shed in Haldia Installation of the

    Indian Oil Corporation at Haldia, West Bengal purpose of our investigationwas to explore and evaluate the subsurface conditions at various locations on the

    site in order to develop geotechnical engineering recommendation for projectdesign and construction. Based on the results of our field investigation, laboratory

    testing, and engineering analysis, it is our professional opinion that the site may be

    developed for the proposed structure using conventional grading and foundationconstruction techniques. Recommendation regarding the geotechnical aspects of

    project design and construction are presented in the herein.

    We appreciate the opportunity of providing our services for this project. If you

    have any queries regarding this report or if we may be of further assistance, pleasecontact us.

    Sincerely,

    Glory Engineers Syndicate

    S. Halder

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    3/35

    Site:

    TLF Shed in Haldia Installation of the Indian

    Oil Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013Createdby S Halder

    GLORY ENGINEERS SYNDICATE

    Table of contents

    Chapter : Sheet

    1. Introduction. 01

    2. Field Investigation... 03

    3. Laboratory Testing.. 05

    4. Ground Water Table .. 06

    5. Sequence of Sub-Soil Stratification 07

    6. Soil Properties 08

    7. Conclusions and Recommendations . 11

    Enclosures :

    1. Site Photo

    2. Calculation

    3. Bore Log Data Sheet and Soil Profile.

    4. Depth Vs. N-Value Curves

    5. Layout Plan & Bore Hole Locations.

    6. Laboratory Test Result Sheet.

    7. Graph for Number of Blows Vrs. Moisture Content

    8. Graph for Particle Size Distribution Curve

    9. Graph for Triaxial Compression Test

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    4/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 1

    GLORY ENGINEERS SYNDICATE

    INTRODUCTION

    GENERALIn this report we present the result of our Geotechnical investigation work for

    addition of TLF Shed in Haldia Installation of the Indian Oil Corporation at

    Haldia, West Bengal.A detail geotechnical investigation has been carried out by us, as desired by

    client

    To

    Indian Oil Corporation Ltd (MD)

    Haldia, West Bengal.

    The purpose of our investigation was to explore and evaluate the sub-

    surface conditions at various locations on the site in order to develop geotechnical

    engineering recommendation for project design and construction. The site location

    relative to topographic features is shown in site plan.

    This reports includes our recommendations related to the geotechnical

    aspects of project design and construction. Conclusion and recommendation

    presented in this report are based on the subsurface conditions encountered at the

    locations of our explorations and the provisions and requirements outlined in theADDITIONAL SERVICE and LIMITATIONS sections of this report.

    Recommendation presented herein should not be extrapolated to

    other areas or used for other projects without prior review.

    This report gives an idea about the subsurface strata and their

    Engineering properties such as strength, deformation and hydraulic characteristics,

    of the proposed site of construction and has been

    formulated to serve as a Guideline for a Structural Engineer.

    The bore holes were sunk at 2(Two) locations as shown in the site

    plan map the termination depth of the bore holes were 15.0m, & 15.0m below

    the Existing Ground Level. The fieldwork was carried from 21.05.2013 to

    22.05.2013.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    5/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 2

    GLORY ENGINEERS SYNDICATE

    Undisturbed and disturbed soil samples were tested in the Soil Mechanics

    Laboratoryfor identification to determine there strength and other characteristics.

    Based on the findings of the subsoil conditions, their strength and compressibility

    characteristic, soil parameters were obtained and are used as suggesting

    guidelines for designof foundation.

    PROPOSED CONSTRUCTION

    The propose project will involve for addition of TLF Shed in Haldia

    Installation of the Indian Oil Corporation at Haldia,West Bengal.

    PURPOSE AND SCOPE OF SERVICES

    i) Exploration of the subsurface conditions at various locations within the area of

    the proposed construction utilizing two borings.

    ii) Limited laboratory testing of representative samples obtained during the field

    investigation to evaluate relevant engineering parameters of the

    subsurface soils.

    iii) Engineering analysis on which to base our recommendations for the designand construction of the geotechnical aspect of the project.

    iv)

    Preparation of this report which includes :

    A description of the proposed project.

    A description of the surface and subsurface site conditions

    encountered during outfield investigation.

    Recommendations related to the geotechnical aspect of :

    Site preparation and engineered fill.

    Foundation design and construction.

    An appendix which includes a summary of our field

    investigation and laboratory testing programs.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    6/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 3

    GLORY ENGINEERS SYNDICATE

    FIELD INVESTIGATION

    GENERALThe sub-surface conditions at the were explored from 21

    stMay, 2013 to 22

    2ndMay,

    2013. The boring was located in the field by visual sighting and / or pacing from

    existing site features. The locations of the bore holes is shown in the site plan.

    Our site in-charge maintained a log of the borings, visually classified soils

    encountered according to the Standard Soil Classification system and obtained

    relatively undisturbed and bulk samples for the sub-surface materials.

    BORINGBoring through the soil was carried out by Shell and Augar method to sink 150

    mm diameter bore holes by using manually operated equipment with which.

    Suitable casings were used upto about 3.0 mbelow Ground Level to prevent cave-

    in of soil inside the boreholes. Bentonite slurry was used for stabilizing boreholes.

    During the progress of boring, undisturbed soil samples were collected at suitable

    intervals or at the change of strata whichever is encountered earlier by open drive

    sampling method since it was intended to a certain the sub-soil characteristics.

    SAMPLING PROCEDURES

    Undisturbed sample are obtained by forcing a thin wall sample of internal diameter

    100 mm and 400 mm length open drive sampling assembly having area ratio

    within 20% ( as per I.S.2132-1972 ). The sampling assembly were driven to the

    required depth manually with the help of jarring link. The undisturbed samples

    retained in the lowest tube is brought to the surface and both the ends of the tube

    were sealed by a thin layer of molten wax. Further the end of the tube were closed

    by screwed caps or tight fittings lids. The top of the sample should be marked on

    the tube and other particulars are given on the label. When the sample is taken out

    of the tube, its direction of movement relative to the tube should be kept the same

    as it was during sampling.

    Disturbed samples are collected from Augar, cutting shoe of the

    undisturbed sampling assembly and split spoon of standard penetrometer at close

    intervals to maintain a continuous record of were and tagged in airtight polythene

    bags/packets and transported to the laboratory for testing and classification.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    7/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 4

    GLORY ENGINEERS SYNDICATE

    All samples (both disturbed and undisturbed ) should be clearly labeled with

    details about project name, date of sampling, borehole number, depth and method

    of sampling.

    STANDARD PENETRATION TEST (SPT):

    These test were conducted in the bore holes at regular intervals or the

    change of strata whichever is encountered earlier at certain depth using standard

    sampler (a split-spoon sampler) driven by a 65 kg. drive weight (monkey) which is

    allowed to fall on the top of the drill rod from a height of 750 mm several times

    until the sample penetrates about 150 mm into the soil as a seating drive. The

    numbers of blows required to drive the spoon from 150 mm to 450 mm i.e.,beyond the seating drive, were recorded and this number of blows is called N value

    or Standard Penetration test value of the sub-soil at that particular depth where the

    test has been carried out. On completion of a test, the split spoon sampler was

    opened and the soil sample was preserved in air tight polythene bag/packets for

    classification purpose. This procedure was conducted as per guidelines laid by

    I.S:2131-1981.

    GROUND WATER TABLE :

    During the field investigation, ground water observation was made during boring.

    Moreover the standing water level was measured in the boreholes after 24 hours of

    removal of casings. It was noticed that the ground water table was located for two

    numbers of boring during the period of field work. These levels of ground water

    are likely to change with the seasonal variation.

    For design purpose, it is suggested to consider ground water level at E.G.L.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    8/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 5

    GLORY ENGINEERS SYNDICATE

    LABORATORY TESTING

    Relevant laboratory test were conducted on selected disturbed and undisturbed soil

    samples collected during the field investigation for proper identification,

    classification and for determining the various engineering properties of these sub-

    soils deposits and to evaluate its bearing capacity, settlement, etc. The following

    tests were conducted on the soil samples collected from exploratory bore holes :

    1. Liquid Limit

    2.

    Plastic Limit

    3.

    Grain size Analysis (Sieve as well as Hydrometer Analysis ).

    4.

    Bulk Density

    5.

    Dry Density

    6.Natural Moisture Content

    7.

    Specific Gravity

    8.

    Unconfined Compressive Strength Test

    9. Triaxial Compression Tests

    10.Direct shear

    11.

    Consolidation Tests

    All the above mentioned laboratory tests were conducted as per the

    relevant Indian Standard Codes of Practice and the results of these tests are

    furnished in the tabular form in the Annexure of this Investigation Report.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    9/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 6

    GLORY ENGINEERS SYNDICATE

    STRATIFICATION OF THE SUB-SOIL DEPOSIT :

    Based on the physical characteristics, index and mechanical properties as

    revealed from both field as well as laboratory test results, the sub-soil deposit at

    this exploratory site are classified into different stratum and are shown in the

    individual bore log data sheet. The sequence of average sub-soil profile across the

    respective bore hole location is also shown for conveniences and appended below

    in summarized from for ready reference.

    GROUND WATER TABLE:

    Whenever ground water was stuck, boring was stopped for half an hour to

    allow the water level to stabilize. The depth of water table was then measured. Half

    an hour after the completion of the boreholes a further reading of the water level

    was taken. The boreholes were then back-filled. No piezometers or standpipes

    were installed.

    Location of G.W.T. at this exploratory site were recorded both during and after

    boring operation as per normal practices and the same is considered to be located

    for the two numbers of boring. However, the depth of termination and location of

    G.W.T. of the respective bore hole are reflected here with in tabular form :-

    SL. NO. B.H.NO.

    TERMINATION

    DEPTH

    IN M

    LOCATION OF G.W.T.

    BELOW E.G.L.

    IN M

    1. B.H.-1 15.00 0.60 m.

    2. B.H.-2 15.00 1.75 m.

    The aforesaid stratification, their description and depth etc. may however, be

    restricted to the limited numbers of bore holes, their location and termination depthetc.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    10/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 7

    GLORY ENGINEERS SYNDICATE

    SEQUENCE OF SUB-SOIL STRATIFICATION

    Strata Description

    Depth in meter

    Thickness

    In meter

    N-

    ValuesFrom To

    Filled up with bricks bats

    concrete & loose soil etc.

    0.0 0.50 0.50 -

    I Soft to medium grey clayey

    silt.

    0.50 3.50 3.00 4 to 5

    II Very soft to soft grey clayey

    silt with decomposed wood

    & vegetation.

    3.50 9.50 6.00 2 to 4

    III Medium to stiff grey clayey

    silt with low% sand mixed.

    9.50 12.5 3.00 5 to 12

    IV Soft grey clayey silt with

    decomposed wood &

    vegetation.

    12.50 15.0 2.50 3 to 4

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    11/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 8

    GLORY ENGINEERS SYNDICATE

    SOIL PROPERTIES

    The summary of all laboratory tests results are given in the following:-

    From the study of the test results the engineering properties of different strata may

    be summarized as follows:-

    STRATUM- I :

    This stratum consists of Soft to medium grey clayey silt and extend upto a depth

    of 0.50m to 3.50m below E. G. L.

    N of this stratum is found to be 4 to 5.

    STRATUM- II :

    This stratum consists of Very soft to soft grey clayey silt with decomposed wood

    & vegetationand extend upto a depth of 3.50m to 9.50m below E. G. L.

    N of this stratum is found to be 2 to 4.

    STRATUM- III :

    This stratum consists of Medium to stiff grey clayey silt with low% sand mixedand extend upto a depth of 9.50m to 12.50m below E. G. L.

    N of this stratum is found to be 5 to 15.

    STRATUM- IV :

    This stratum consists of Soft grey clayey silt with decomposed wood &

    vegetationand extend upto a depth of 12.50m to 15.00m below E. G. L.

    N of this stratum is found to be 3 to 4.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    12/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 9

    GLORY ENGINEERS SYNDICATE

    Foundation Design Criteria :

    Foundation for a given structure, in a given sub-soil condition, should satisfy the

    following design criteria :

    a)

    There must be adequate factor of satisfy against bearing capacity failure.

    b)

    The settlement of the foundation must be within permissible limits.

    The factor of safety and the permissible settlement to be adopted for design

    depends upon the type of structure and the sub-soil condition. For conventionalResidential / office buildings design should be based on the factor of safety of

    2.5 and permissible settlement of 75mm for isolated / strip footings and 125mm

    for raft foundation.

    Foundation Analysis :

    Bearing Capacity :

    Shallow Foundation:

    The bearing capacity of the sub soil has been arrived at considering strength

    parameters obtained from laboratory soil testing. The bearing capacity obtained

    thus is factored by applying factor of safety (2.5 to 3.0 generally) taken to

    determine the allowable bearing capacity as per IS 64031981 have recommended

    the following general expression for arriving net ultimate capacity of shallow

    foundation.

    For general shear failure

    qu = cNcscdcic + DNqsqiqdq 0.5 BN s d i w

    For local shear failure

    qu = 2/3(cNcscdcic + DNqsqiqdq 0.5 BN s d i w)

    qnu = qu - D

    qns = (qnu / Fs)

    for > 360, general shear failure

    < 280, local shear failure

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    13/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 10

    GLORY ENGINEERS SYNDICATE

    Settlements have been calculated using the following expression:-

    Immediate Settlement:

    qB ( 1 -2)

    Si = Ip

    E

    q = Intensity of pressure

    B = Width of foundation

    =Poissons Ratio

    E = 500 Cu = Deformation Modulus

    Ip = Influence Factor

    Consolidation Settlement:

    Sc :mvH P

    Where

    mv : Coefficient of volume compressibility

    H : Thickness of the stratum considered

    P : Increase of effective pressure at the centre of the stratum considered

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    14/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 11

    GLORY ENGINEERS SYNDICATE

    CONCLUSIONS & RECOMMENDATIONS :

    GENERAL :-

    Based on the results of our field investigation, laboratory testing and engineering

    analysis, it is our professional opinion the site may be developed for the proposed

    structure using conventional grading and foundation construction techniques.

    Recommendations regarding the geotechnical aspects of project design and

    construction are presented in the herein.

    GUIDELINES FOR DESIGN OF FOUNDATION :-

    Structural foundations may be grouped under two broad categories (i) Shallow

    Foundation, (ii) Deep Foundation. This classification indicates the depth of

    foundation installation. A deep foundation is thought only when the sub-soil at

    shallow depth cannot provide effective bearing to the structure and/or the total

    settlement of the layer within the pressure bulb is more than the allowable

    settlement.

    The safe design of foundation for a given loading system must satisfy certain

    design requirements. The three basic requirements are:-

    (i) Foundation placement, which involves the location and depth of foundation.

    This requires a careful investigation of the past usage of the site and detailed

    information of the subsurface stratum. The foundation placement should be such

    that any future influence should not affect its performance adversely.

    (ii) Safety against bearing capacity failure, which involves suitable proportioning

    of footing to avoid a catastrophic collapse of the soil beneath the foundation. This

    occurs if the shear strength of the soil is inadequate to support the applied load.

    Therefore, there must be adequate factor of safety of foundation against possible

    bearing capacity failure.

    (iii) Tolerable foundation settlement, which involves keeping a check on the

    exclusive settlement of a structure. Excessive settlement are caused due to the

    distortion of the soil mass as a result of the applied shear stresses, and due to the

    consolidation of the supporting soil. Therefore, the settlement of the foundation

    must be within permissible limit.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    15/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 12

    GLORY ENGINEERS SYNDICATE

    DISCUSSION ON FOUNDATIONS :-

    The prime objective of this investigation has been to study that the sub-soil

    characteristics at this site for Proposed constructionand to assess the safe bearing

    capacity of soil along with the settlements of characteristics for design and

    construction of appropriate foundation systems. On the basic of field exploration

    and laboratory testing on samples it has been observed that the sub-soil profile is

    more or less same throughout the site.

    SHALLOW FOUNDATION :

    From the sub-soil investigation it is seen that stratum -I have Soft to medium greyclayey silt,stratum -II have Very soft to soft grey clayey silt with decomposed

    wood & vegetation, stratum-III have Medium to stiff grey clayey silt with low%

    sand mixed, stratum-IV have Soft grey clayey silt with decomposed wood &

    vegetation, till adepth of 15.0m below the E.G.L. So, for estimation of bearing

    capacity of shallow footings adequate considerations is given to the

    compressibility characteristics of these four strata. These are determined using the

    expressions given in earlier section and are presented below:-

    Depth of foundation = 1.50m below E.G.L.

    Size of footing Capacity (t/m2) Settlement (mm)

    Isolated

    1.50m x 1.50m

    2.00m x 2.00m

    2.50m x 2.50m

    3.00m x 3.00m

    Allowable

    B. C.

    Net allowable

    B. C.

    Calculated Permissible

    9.50

    9.12

    8.90

    8.75

    9.50

    9.01

    7.13

    5.92

    57.35

    75.93

    93.64

    110.88

    75.0

    75.0

    75.0

    75.0

    Strip1.50m wide

    2.00m wide

    2.50m wide

    3.00m wide

    7.34

    7.05

    6.88

    6.76

    7.34

    7.05

    6.57

    5.46

    48.24

    63.73

    78.53

    92.90

    75.0

    75.0

    75.0

    75.0

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    16/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo.

    GES/S/32/2013

    Page No.- 13

    GLORY ENGINEERS SYNDICATE

    In designing shallow foundationfollowing precaution must be taken

    1.

    To counteract differential settlement, adequate tie-beams at plinth/ground level

    are to be provided.

    2.

    Refilling should be done through compaction of sand with proper watering

    from the excavated depth of 1.8m to 1.50m below E.G.L. sand filling should be

    compacted to achieve at least 90% if its maximum density, which should be

    checked in the field by standard penetration tests at one or two points (Expected

    N= 8 to 10).

    3. Due consideration should be given to open excavation of any sort. Adequate

    precautionary measures should be taken so that no damage is caused to the

    adjoining structure, if any,4. For strip footing interconnected beams should be provided.

    5. Construction in stages is advised.

    6. For higher loads, the shallow foundation is not suitable. In that case pile

    foundation is recommended.

    SANJOY HALDER

    B.E. (CIVIL), M.C.E.(J.U.)

    M. I. G. S.

    CHARTERED ENGG., M.I.C.I.

    M A S C E I S

    (GEOTECHNICAL CONSULTANT)

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    17/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    JobNo. GES/S/31/2013

    GLORY ENGINEERS SYNDICATE

    BORING WORK ON PROGRESS

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    18/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    Job No.-

    GES/S/32/2013

    CALCULATION OFBEARING CAPACITY

    Isolated Footing (size -1.5 x 1.5m ):(Depth of foundation 1.50m below EGL.)

    qu= CNcScdcic+ qNqSqdqiq

    C = 2.8,Nc= 5.14,Sc=1.3, dc= 1+ 0.2 Df/B = 1.2, q = 0.72 x 1.50 = 1.08, Nq= 1,

    Sq=1.2, dq = 1, ic = i = 1, F. O. S. = 2.5

    qu= 2.8 x 5.14 x 1.3 x 1.2 x 1 + 1.08 x 1 x 1.2 x 1 x 1

    = 22.45 + 1.30

    = 23.75 t/m2

    Allowable bearing capacity = qu / F.O.S = 23.75 / 2.5 = 9.50 t/m2

    SETTLEMENT

    Immediate settlement :

    ( 1 -2) i = Immediate settlement

    i = qB I = Poissons ratio = 0.5,E E = Modulus of Elasticity = 500 Cu

    for clay ) ; Cu = Cohesion = 2.8 ton /m2 I = Influence factor = 1.12,

    q = Bearing capacity = 9.50 ton /m2

    9.50 x 1500 x ( 1 0. 52)

    i = X 1.12 B = Width of fdn. = 1500 mm

    1400

    = 8.55 mm

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    19/35

    Site TLF Shed in Haldia Installation of the Indian Oil

    Corporation at Haldia, West Bengal.

    Job No.-

    GES/S/32/2013

    Consolidation Settlement :

    Sc = mvH P

    Where

    mv : Coefficient of volume compressibility

    H : Thickness of the stratum considered

    P : Increase of effective pressure at the centre of the stratum considered

    Sc =mvH P

    = (0.0052 x 2000 x 6.916) + (0.0062 x 1000 x 3.680)

    = 94.74 mm

    Corrected Settlement :

    Rigidity factor = 0.8 & P.W. P factor = 0.8

    Depth factor = 0.85

    Corrected settlement = 0.8 x 0.85 x (8.55+ 94.74 x 0.8)

    = 57.35 mm < 75mm

    Hence, settlement within permissible limit.

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    20/35

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    21/35

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    22/35

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    23/35

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    24/35

    B.H.-2

    B.H.-1

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    25/35

    ncon

    fine

    d

    Tes

    t

    i r e c

    t S h e a r

    Location: TLF Shed in Haldia Installation of the Indian Oil Corporation at

    Haldia, West Bengal.Triaxial Test

    (UU)

    D

    Depth

    ( inDescription

    uidLimit

    stic

    Limit

    ass

    ing

    75%

    ron

    Iss

    ieve

    lkDens

    ity

    (gm

    /cc

    )

    yDens

    ity

    (gm

    /cc

    )

    er

    Con

    tent

    (%)

    ificGrav

    ity

    ohes

    ion

    Kg

    /cm

    2)

    ohes

    ion

    Kg

    /cm

    2)

    eo

    ffriction

    egrees

    )

    e o

    f f r i c t i o n

    meter) Liq

    Pla P

    mic

    Bu

    l (Dr (

    Wa

    t

    Spec C( C(

    Ang

    l (

    A n g

    l

    B. H. No.-1 (One)

    1.50

    (UDS)Soft grey clayey silt. 48 33

    98

    (hyd)1.72 1.33 28.9 2.64 0.28 0.3 0

    5.00

    (UDS)

    Very soft grey clayey silt with

    decomposed wood & vegetation.70 35

    98

    (hyd)1.68 1.25 34.3 . 0.25 0.28 0

    9.00

    (SPT)

    Soft grey clayey silt with

    decomposed wood & vegetation.66 32

    97

    (hyd)1.69 1.28 32.4 2.66 . . .

    12.00 Medium grey clayey silt with 95

    (SPT)

    low% sand mixed. (hyd). . . . . . .

    15.00

    (SPT)

    Soft grey clayey silt with

    decomposed wood & vegetation.65 31

    97

    (hyd)1.73 1.30 32.8 2.64 . . .

    B. H. No.-2 (Two)

    3.00 97

    (UDS)o grey c ayey s .

    (hyd). . . . . .

    6.00

    (SPT)

    Soft grey clayey silt with

    decomposed wood & vegetation.65 33

    97

    (hyd)1.70 1.28 33.3 . . . .

    7.00

    (UDS)

    Very soft grey clayey silt with

    decomposed wood & vegetation.68 35

    98

    (hyd)1.67 1.24 34.5 2.64 0.27 0.29 0

    9.00

    (SPT)

    Soft grey clayey silt with

    decomposed wood & vegetation.66 31

    98

    (hyd)1.72 1.31 31.5 . . . .

    12.00

    (SPT)

    Medium grey clayey silt with

    low% sand mixed.42 27

    95

    (hyd)1.77 1.41 25.8 2.65 . . .

    15.00 Soft grey clayey silt with 96

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    26/35

    Location : TLF Shed in Haldia Installation o f the Indian Oil Corporation

    B.H:- 1, Depth :- 1.50m

    GRAPH : NUMBER OF BLOWS VRS. MOISTURE CONTENT

    at Haldia, West Bengal.

    10

    20

    30

    40

    50

    60

    MoistureContent%

    Number of blows vrs. moisture content

    LIQUID LIMIT = 48%

    0 10 20 30 40 50 60

    Number of blows 'N'

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    27/35

    Location : TLF Shed in Haldia Installation o f the Indian Oil Corporation

    GRAPH : NUMBER OF BLOWS VRS. MOISTURE CONTENT

    B.H:- 1, Depth :- 9.00mat Haldia, West Bengal.

    10

    20

    30

    40

    50

    60

    70

    80

    MoistureContent%

    Number of blows vrs. moisture content

    LIQUID LIMIT = 66%

    0

    0 10 20 30 40 50 60

    Number of blows 'N'

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    28/35

    B.H:- 2, Depth :- 3.00m

    GRAPH : NUMBER OF BLOWS VRS. MOISTURE CONTENTLocation : TLF Shed in Haldia Installation of the Indian Oil Corporation

    at Haldia, West Bengal.

    10

    20

    30

    40

    50

    60

    MoistureContent%

    Number of blows vrs. moisture content

    LIQUID LIMIT = 45%

    0 10 20 30 40 50 60

    Number of blows 'N'

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    29/35

    Location : TLF Shed in Haldia Installation o f the Indian Oil Corporation

    B.H:- 2, Depth :- 6.00m

    GRAPH : NUMBER OF BLOWS VRS. MOISTURE CONTENT

    at Haldia, West Bengal.

    10

    20

    30

    40

    50

    60

    70

    80

    MoistureContent%

    Number of blows vrs. moisture content

    LIQUID LIMIT = 65%

    0 10 20 30 40 50 60

    Number of blows 'N'

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    30/35

    SOIL SAMPLE AT BORE HOLE NO. - 1

    GRAPH : PARTICLE SIZE DISTRIBUTION CURVE

    Location : TLF Shed in Haldia Installation of the Indian Oil Corporation

    at Haldia, West Bengal.

    50

    60

    70

    80

    90

    100

    GEFINER

    PARTICLE SIZE DISTRIBUTION CURVE

    AT1.50M

    AT 5.00 M

    010

    20

    30

    40

    0.001 0.01 0.1 1 10

    PERCENT

    PARTICLE SIZE IN "MM"

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    31/35

    SOIL SAMPLE AT BORE HOLE NO. - 1

    GRAPH : PARTICLE SIZE DISTRIBUTION CURVE

    Location : TLF Shed in Haldia Installation of the Indian Oil Corporation

    50

    60

    70

    80

    90

    100

    GEFINER

    PARTICLE SIZE DISTRIBUTION CURVE

    AT9.00 M

    AT 12.00 M

    010

    20

    30

    40

    0.001 0.01 0.1 1 10

    PERCENT

    PARTICLE SIZE IN "MM"

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    32/35

    SOIL SAMPLE AT BORE HOLE NO. - 2

    GRAPH : PARTICLE SIZE DISTRIBUTION CURVE

    Location : TLF Shed in Haldia Installation of the Indian Oil Corporation

    50

    60

    70

    80

    90

    100

    GEFINER

    PARTICLE SIZE DISTRIBUTION CURVE

    AT 3.00 M

    AT 6.00M

    010

    20

    30

    40

    0.001 0.01 0.1 1 10

    PERCENT

    PARTICLE SIZE IN "MM"

  • 8/10/2019 Soil Investigation Report Haldia-A for TLF Construction

    33/35

    SOIL SAMPLE AT BORE HOLE NO. - 2

    GRAPH : PARTICLE SIZE DISTRIBUTION CURVE

    Location : TLF Shed in Haldia Installation of the Indian Oil Corporation

    50

    60

    70

    80

    90

    100

    GEFINER

    PARTICLE SIZE DISTRIBUTION CURVE

    AT 7.00 M

    AT 9.00M

    010

    20

    30

    40

    0.001 0.01 0.1 1 10

    PERCENT

    PARTICLE SIZE IN "MM"