GRD

·

·

·

·

·

·

·

·

·

·

·

·

·

EXHAUST FAN

FAN ROOF SUPPORT

(BY CONTRACTOR)

PHP OR TYLOR (TYPICAL)

ROOF

DECK

ROOF CURB

INSTALLATION, ROOF

OPENING AND FLASHING

(BY CONTRACTOR)

METAL ROOF CURB, STORM

COLLAR COMPRESSION

CLAMP AND COUNTER

FLASHING BY MECHANICAL

CONTRACTOR

WEATHER

COVER

400AT H.P.ROOFCURB

FAN INLET

FAN OUTLET

AUXILIARY CHANEL STEEL

SUPPORT C/W VIBRATION

ISOLATORS

STEEL FRAME

BY

CONTRACTOR

ROOF JOIST

TRANSITION

·

·

·

·

·

·

·

·

·

·

·

·

·

·

DETAIL

NUMBER

LOCATION OR

DETAIL SHEET

Project Manager

Project Leader

Date

Client

Drawn

Checked

Project

Drawing Title

Check Scale (may be photo-reduced)

Drawing No.Project No.

0 1 Inch 0 10mm

Architect/Engineer

KEY PLAN

CONSULTANTS

DATE

ISSUED FOR REV

(mmm dd yyyy)

North Arrow Detail Symbol

THE REGIONAL MUNICIPALITY

OF DURHAM

IBI GROUP

100-175 Galaxy Boulevard

Toronto ON M9W 0C9 Canada

tel 416 679 1930 fax 416 675 4620

ibigroup.com

T-1038-2019

ROD Contract No.

AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
2
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
WIRE MESH
AutoCAD SHX Text
50mm THROW AWAY FILTER C/W FRAME FOR LATERAL SLIDING
AutoCAD SHX Text
MOTORIZED DAMPER
AutoCAD SHX Text
PREPAINTED INSULATED METAL WALL PANELS
AutoCAD SHX Text
SEALANT ON BOTH SIDES
AutoCAD SHX Text
PREPAINTED METAL FLASHING. EXTEND FLASHING BEHIND LOUVRE APPROX. 125
AutoCAD SHX Text
SILL FLASHING BY LOUVRE MFG.
AutoCAD SHX Text
ALUMINUM STORM LOUVRE C/W BIRD SCREEN
AutoCAD SHX Text
STEEL FRAMING REFER STRUCT. DWGS.
AutoCAD SHX Text
EL. VARIES. SEE PLAN
AutoCAD SHX Text
M
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
1
AutoCAD SHX Text
TYPICAL LOUVRE ARRANGEMENT
AutoCAD SHX Text
GARAGE SUPPLY GRILLE
AutoCAD SHX Text
TYPE 'D'-600x200
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
3
AutoCAD SHX Text
TYPICAL FRESH AIR INTAKE WALL HOOD
AutoCAD SHX Text
OPENING AND DRIP, SILL AND JAM FLASHINGS AROUND OPENING BY GENERAL TRADES. MECHANICAL CONTRACTOR TO COORDINATE OPENING SIZE AND LOCATION..
AutoCAD SHX Text
WEATHERPROOFING FLASHING BY MECHANICAL TRADES
AutoCAD SHX Text
14 GAUGE BLACK SHEET STEEL. PRE-PAINT TO MATCH COLOR OF SIDING
AutoCAD SHX Text
12mm ( ") MESH X 0.150" GAUGE 12") MESH X 0.150" GAUGE GALVANIZED BIRDSCREEN. SECURE TO ANGLE IRON FRAME WITH 6mm ( ") BOLTS AT 225mm (9") C/C.14") BOLTS AT 225mm (9") C/C..
AutoCAD SHX Text
25x25x3mm (1"x1"x ") ANGLE IRON 18") ANGLE IRON FRAME FOR SECURING SCREEN. BOLT TO INSIDE OF HOOD WITH 6mm ( ") BOLTS AT 300mm (12") C/C.14") BOLTS AT 300mm (12") C/C..
AutoCAD SHX Text
'A'
AutoCAD SHX Text
'B'
AutoCAD SHX Text
90°
AutoCAD SHX Text
'B'
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
VEHICLE EXHAUST SYSTEM
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
5
AutoCAD SHX Text
NOTES: 1. PROVIDE THE FOLLOWING FITTINGS AND ACCESSORIES FOR ABOVE GROUND LOW LEVEL PROVIDE THE FOLLOWING FITTINGS AND ACCESSORIES FOR ABOVE GROUND LOW LEVEL VEHICLE EXHAUST CAPTURE SYSTEM: (x4) MACHINE ADAPTER QF 100 (x4) 90° ELBOW QF 100MM 1.0CLR(X4) 100 MANUAL BLAST GATE QF(X4) 100 CLAMP WITH PIN QF(X2) 100 HOSE ADAPTER QF(X2) 100 5M LONG NFC4 HIGH TEMPEXHAUST HOSES, SILICON COATED FABRIC WITH GALV. STEEL HELIX WITH TWO CLAMPS (X2) 100 EXHAUST NOZZLE(X2) 100 EXHAUST NOZZLE(X4) 100 EXHAUST NOZZLE(X2) 100 DUAL EXHAUST ADAPTER W/ QUICK CONNECT(X4) 100 QUICK COUPLER(X4) 100 BRIDGE CLAMP W/ RUBBER SLEEVES(X1) 100 2.5M LONG NFC4 HIGH TEMPEXHAUST HOSE. FIELD CUT INTO 600mm LENGTHS FOR EACH NOZZLE ASSEMBLY CONTRACTOR TO VERIFY QUANTITIES AND FITTING WITH MANUFACTURER AND SUBMIT A SHOP DRAWING FOR ENGINEER'S REVIEW.
AutoCAD SHX Text
100MM NORDFAB QUICK-FIT DUCT PIPE
AutoCAD SHX Text
100MM NORDFAB QUICK-FIT MACHINE ADAPTER
AutoCAD SHX Text
100MM SPIRAL GALVANIZED 22GA ROUND DUCT BRANCH DROP SUPPORT ON WALL/COLUMN
AutoCAD SHX Text
100MM NORDFAB 90° 1.0CLRQUICK-FIT ELBOW
AutoCAD SHX Text
100MM NORDFAB QUICK-FIT MANUAL BLAST GATE
AutoCAD SHX Text
100MM NORDFAB QUICK-FIT CLAMP WITH PIN FOR HOSE ADAPATER
AutoCAD SHX Text
EXHAUST AIR DROP OUTLET DETAIL
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
4
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
METAL DECK CLOSURE
AutoCAD SHX Text
UNIT FRAME WITH MECHANICAL FASTENERS BY MANUFACTURER) AND WEATHER TIGHT BY MECH. CONTRACTOR
AutoCAD SHX Text
SOLID BLOCKING @ DECK FLUTES
AutoCAD SHX Text
CLOSURE & LOOSE INSULATION BY MECH. CONTRACTOR
AutoCAD SHX Text
DUCT BY MECH. CONTRACTOR
AutoCAD SHX Text
TYPICAL ROOFING ASSEMBLY
AutoCAD SHX Text
COMPRESSIBLE SEALANT BY MECH. CONTR.
AutoCAD SHX Text
METAL CURB BODY WITH BOLTS BY MECH. CONTR.
AutoCAD SHX Text
AHU UNIT BY MECH. CONTRACTOR
AutoCAD SHX Text
WIRE MESH SCREENING IRE MESH SCREENING 120WD-304 STAINLESS STEEL
AutoCAD SHX Text
300x200 EXHAUST DUCT. TERMINATE WITH GOOSENECK 1800 ABOVE ROOF
AutoCAD SHX Text
ROOF CURB FOR MECH AHU UNIT
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
6
AutoCAD SHX Text
FIXED EXHAUST EXTRACTION SYSTEM ON DOUBLE ARTICULATING BOOM
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
7
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
NOTES: 1. PROVIDE THE FOLLOWING FITTINGS AND ACCESSORIES FOR ABOVE GROUND HIGH LEVEL PROVIDE THE FOLLOWING FITTINGS AND ACCESSORIES FOR ABOVE GROUND HIGH LEVEL VEHICLE EXHAUST CAPTURE SYSTEM: FIXED EXHAUST ON A DOUBLE ARTICULATED PIVOTING BOOM, BOOM LENGTH 6000mm SET UP FOR 200 HOSE, FOR 200 HOSE, MODEL: FEB-6-200 PLYMOVENT OR ACCEPTED EQUAL. BLACK EXHAUST HOSE, 200 TEMP RESISTANCE UP TO 288°C c/w INTERNAL STEEL HELIX, MAX SPIKE TEMP 677°C, MODEL SNF2-200-8 PLYMOVENT OR ACCEPTED EQUAL.RUBBER BAND 200 TO PROVIDE A COVER OVER HOSE CLAMP.STAINLESS STEEL HOSE CLAMP FOR EXHAUST HOSES 200 .STACKER NOZZLE 150-250 c/w ROTATING HANDLE RECEIVER, 200 HOSE CONNECTION WITH 250 LARGE END OPENING.TELESCOPIC POLE HANDLE FOR STACKER NOZZLE WITH MALE FITTING RECEIVER ON STACKER NOZZLE, MODEL TH-90 OR ACCEPTED EQUAL SPRING CLIP FOR USE WITH STACKER OR STAINLESS STEEL CONE NOZZLES, MODEL SC-90 OR ACCEPTED EQUAL. SPRING RECOIL CONSTANT FORCE BALANCER FOR 13-16Kg LIFTING CAPACITY, CABLE LENGTH 4500mm WITH CAPABILITY OF LATCH & LOCK OR CONSTANT PULL, MODEL: BRC-450-16 OR ACCEPTED EQUAL. MICRO SWITCH KIT FOR BRC-450 BALANCER, SINGLE THROW, DOUBLE POLE SWITCH, MODEL BRC-SC OR ACCEPTED EQUAL. RUBBER HOSE SADDLE BELT FOR 200 HOSE, INCLUDES HOSE CLAMP AND STEEL RING AUTOMATIC MOTORIZED DAMPER ASSEMBLY, 200 , 24v OPERATIONAL VOLTAGE, CONNECT TO TRANSFORMER OR THROUGH A PLYMOVENT SA-24, ES-90 OR ICE-LC CONTROL BOX, ACTIVATE WITH MSR OR BRC MICRO SWITCH, MODEL: MD-200/8" OR ACCEPTED EQUAL TRANSFORMER, 115-230 TO 24v STEP DOWN TRANSFORMER, WALL MOUNTED, MODEL: TR-24-100 OR ACCEPTED EQUAL. DCV FAN CONTROLLER, 3-PHASE c/w PID REGULATOR, EMC FILTER, NEMA 12/IP55 ENCLOSURE, CE, AND cUL APPROVED, MODEL VFD-3-575 OR ACCEPTED EQUAL. PRESSURE TRANSMITTER FOR 0-10" SP APPLICATIONS. MODEL TG-2500 OR ACCEPTED EQUAL PARTS NOTED ABOVE FROM 'PLYMOVENT' ARE THE BASIS OF DESIGN, ANY SUBSTITUTES SHALL BE AN APPROVED EQUIVALENT. CONTRACTOR TO VERIFY QUANTITIES AND FITTING WITH MANUFACTURER AND SUBMIT A SHOP DRAWING FOR ENGINEER'S REVIEW.
AutoCAD SHX Text
User Name: Shujun Liu Plot Date\Time: Thursday, May 16, 2019 3:23:26 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwgShujun Liu Plot Date\Time: Thursday, May 16, 2019 3:23:26 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwg Plot Date\Time: Thursday, May 16, 2019 3:23:26 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwgThursday, May 16, 2019 3:23:26 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwg Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwgj:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m56-00-01.dwg
AutoCAD SHX Text
This drawing has been prepared solely for the use of the Regional Municipality of Durham and there are no representations of any kind made by IBI Group to any party with whom IBI Group has not entered into a contract
AutoCAD SHX Text
A. VAN VEEN
AutoCAD SHX Text
EXPAND GARAGE
AutoCAD SHX Text
SCUGOG DEPOT
AutoCAD SHX Text
24RX12.0113
AutoCAD SHX Text
10 REGIONAL RD. 21, R.R.#14, PORT PERRY
AutoCAD SHX Text
ONTARIO
AutoCAD SHX Text
WHITBY
AutoCAD SHX Text
WORKS DEPARTMENT
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
JAN 31 2018
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
HVAC
AutoCAD SHX Text
DETAILS
AutoCAD SHX Text
02-M56-00-01
AutoCAD SHX Text
S. LIU
AutoCAD SHX Text
MAY 15 2019
AutoCAD SHX Text
TENDER
AutoCAD SHX Text
0
shujun.liu
PEO-Shujun
Page 10: Snyder Construction
Page 11: Snyder Construction

02-M74-00-01

1

₂₂

Δ

Δ₂

²MAX.

02-M74-00-01

2

02-M74-00-01

5

02-M74-00-01

4

02-M74-00-01

5

SEQUENCE OF OPERATION

CEILING FANS CF-101 TO CF-104

CEILING FAN CONTROLS BY A MANUAL SPEED CONTROLLER

02-M74-00-01

6

CONTROL SEQUENCE

02-M74-00-02

7

02-M74-00-02

8

·

·

·

·

·

02-M74-00-02

3

DETAIL

NUMBER

LOCATION OR

DETAIL SHEET

T

r

u

e

N

o

r

th

Project Manager

Project Leader

Date

Client

Drawn

Checked

Project

Drawing Title

Check Scale (may be photo-reduced)

Drawing No.Project No.

0 1 Inch 0 10mm

Architect/Engineer

KEY PLAN

CONSULTANTS

DATE

ISSUED FOR REV

(mmm dd yyyy)

North Arrow Detail Symbol

THE REGIONAL MUNICIPALITY

OF DURHAM

IBI GROUP

100-175 Galaxy Boulevard

Toronto ON M9W 0C9 Canada

tel 416 679 1930 fax 416 675 4620

ibigroup.com

T-1038-2019

ROD Contract No.

AutoCAD SHX Text
CS402 ROOFTOP AIR HANDLING UNIT (AHU-101)
AutoCAD SHX Text
CONTROLS
AutoCAD SHX Text
H
AutoCAD SHX Text
150 EXHAUST HOSE(TYP)
AutoCAD SHX Text
CS810 TAIL PIPE AND WALL MOUNTED EXHAUST SYSTEM
AutoCAD SHX Text
HAND SWITCH STATION
AutoCAD SHX Text
AHU-101
AutoCAD SHX Text
EXHAUST
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
PROCESS EXHAUST FANS
AutoCAD SHX Text
CONTROL NOTES
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
HEAT PIPE
AutoCAD SHX Text
AHU-101
AutoCAD SHX Text
M
AutoCAD SHX Text
Δp11
AutoCAD SHX Text
T1
AutoCAD SHX Text
Δp22
AutoCAD SHX Text
M
AutoCAD SHX Text
M
AutoCAD SHX Text
M
AutoCAD SHX Text
T2
AutoCAD SHX Text
105% EA
AutoCAD SHX Text
100% OA
AutoCAD SHX Text
T
AutoCAD SHX Text
SA
AutoCAD SHX Text
RA
AutoCAD SHX Text
BMS
AutoCAD SHX Text
CENTRAL GAS DETECTION PANEL*
AutoCAD SHX Text
* ONE PANEL FOR WHOLE FACILTY
AutoCAD SHX Text
NOTE: LIMITS INDICATED ARE AS PER VALUES INDICATED BY SENTENCE # 6.2.2.3.7. FROM OBC LIMITS INDICATED ARE AS PER VALUES INDICATED BY SENTENCE # 6.2.2.3.7. FROM OBC LATEST EDITION & EH40/2005 WORKPLACE EXPOSURE LIMITS, OSHA STANDARD 29 CFR 1910.1000 TABLES Z-1, Z-2 FOR TWA (TIME WEIGHTED AVERAGE) OF 8 HOURS AND 40 HOURS WORKWEEK.
AutoCAD SHX Text
SF
AutoCAD SHX Text
EF
AutoCAD SHX Text
DI
AutoCAD SHX Text
FAS
AutoCAD SHX Text
FIRE ALARM SIGNAL
AutoCAD SHX Text
AI
AutoCAD SHX Text
AH(CO)
AutoCAD SHX Text
CO FLOOR
AutoCAD SHX Text
AI
AutoCAD SHX Text
AH(NO2)
AutoCAD SHX Text
NO FLOOR FLOOR
AutoCAD SHX Text
AI
AutoCAD SHX Text
AH(NO2)
AutoCAD SHX Text
NO TRUSS TRUSS
AutoCAD SHX Text
CO
AutoCAD SHX Text
NO
AutoCAD SHX Text
2
AutoCAD SHX Text
25 PPM LOW LEVEL
AutoCAD SHX Text
0.72 PPM LOW LEVEL 0.72 PPM HIGH LEVEL
AutoCAD SHX Text
NO
AutoCAD SHX Text
2
AutoCAD SHX Text
ROOF MOUNTED EF-101
AutoCAD SHX Text
150 WALL MOUNTEDEXHAUST PIPE (TYP)
AutoCAD SHX Text
AIR DISTRIBUTION SCHEMATIC
AutoCAD SHX Text
DO
AutoCAD SHX Text
ESS
AutoCAD SHX Text
UNIT ENABLE / DISABLE
AutoCAD SHX Text
DO
AutoCAD SHX Text
ESS
AutoCAD SHX Text
DI
AutoCAD SHX Text
EST
AutoCAD SHX Text
AO
AutoCAD SHX Text
DX
AutoCAD SHX Text
BYPASS DAMPER
AutoCAD SHX Text
SUPPLY FILTER Δp1p1
AutoCAD SHX Text
EXHAUST FILTER Δp2p2
AutoCAD SHX Text
SUPPLY FAN ENABLE / DISABLE
AutoCAD SHX Text
SUPPLY FAN STATUS
AutoCAD SHX Text
DO
AutoCAD SHX Text
ESS
AutoCAD SHX Text
DI
AutoCAD SHX Text
EST
AutoCAD SHX Text
EXHAUST FAN ENABLE / DISABLE
AutoCAD SHX Text
EXHAUST FAN STATUS
AutoCAD SHX Text
DAMPER CONTROL
AutoCAD SHX Text
AO
AutoCAD SHX Text
GX
AutoCAD SHX Text
GAS BURNER CONTROL
AutoCAD SHX Text
AI
AutoCAD SHX Text
AT1
AutoCAD SHX Text
AIR TEMP. T1
AutoCAD SHX Text
DO
AutoCAD SHX Text
GSS
AutoCAD SHX Text
GAS BURNER ENABLE / DISABLE
AutoCAD SHX Text
AI
AutoCAD SHX Text
AT
AutoCAD SHX Text
SPACE AIR TEMP. T
AutoCAD SHX Text
BMS APPLICABLE SIGNALS
AutoCAD SHX Text
H
AutoCAD SHX Text
HAND SWITCH STATION
AutoCAD SHX Text
DI
AutoCAD SHX Text
APD1
AutoCAD SHX Text
DI
AutoCAD SHX Text
APD2
AutoCAD SHX Text
DO
AutoCAD SHX Text
DX
AutoCAD SHX Text
CIRCULATING FAN
AutoCAD SHX Text
AI
AutoCAD SHX Text
AT2
AutoCAD SHX Text
AIR TEMP. T2
AutoCAD SHX Text
CO
AutoCAD SHX Text
NO
AutoCAD SHX Text
2
AutoCAD SHX Text
1. AHU CONTROLLED BY BMS (BUILDING MANAGEMENT SYSTEM) AND OPERATOR. AHU CONTROLLED BY BMS (BUILDING MANAGEMENT SYSTEM) AND OPERATOR. ALL POINTS WILL BE PROVIDED ON GRAPHICS AT BMS. 2. ALL ANALOG INPUT AHU POINTS WILL HAVE ASSOCIATED HIGH AND LOW ALARM. ALL ANALOG INPUT AHU POINTS WILL HAVE ASSOCIATED HIGH AND LOW ALARM. 3. EACH ANALOG OUTPUT POINT WILL HAVE AN ASSOCIATED SET POINT. EACH ANALOG OUTPUT POINT WILL HAVE AN ASSOCIATED SET POINT. 4. ONE , TEMPERATURE SENSOR, CONTROLS AHU. ONE , TEMPERATURE SENSOR, CONTROLS AHU. ALL SET VALUES ARE FIELD ADJUSTABLE. 5. ONE DETECTOR AT +1.2M A.F.F. MONITORS CARBON MONOXIDE LEVEL AT 25 PPM, ONE DETECTOR AT +1.2M A.F.F. MONITORS CARBON MONOXIDE LEVEL AT 25 PPM, MAXIMUM LEVEL (ADJUSTABLE). 6. A PAIR OF DETECTOR CONTROLS, AT TWO HEIGHTS: +1.4M A.F.F. AND TRUSS LEVEL, A PAIR OF DETECTOR CONTROLS, AT TWO HEIGHTS: +1.4M A.F.F. AND TRUSS LEVEL, NO TO MAXIMUM 3PPM, MAX. LEVEL, MAINTAINING AHU IN OPERATION. TO MAXIMUM 3PPM, MAX. LEVEL, MAINTAINING AHU IN OPERATION. 7. BMS (DDC) CONTROLLERS CONTROL UNITS ACCORDING TO OCCUPIED/UNOCCUPIED MODE (IN BMS (DDC) CONTROLLERS CONTROL UNITS ACCORDING TO OCCUPIED/UNOCCUPIED MODE (IN OCCUPIED MODE UNITS ARE ON ACCORDING TO ITS SEQUENCE OF OPERATION). BALANCE THE UNIT TO MAINTAIN 3% NEGATIVE PRESSURE INSIDE AS SPECIFIED. 8. IN HIGH LEVEL GAS ALARM, INDEPENDENT OF ITS STATUS, AHU WILL BE ACTIVATED IN HIGH LEVEL GAS ALARM, INDEPENDENT OF ITS STATUS, AHU WILL BE ACTIVATED 9. BALANCING DAMPER ON COMMON SUPPLY HEADERS TO BE OPENED ONLY ONE OF THE BALANCING DAMPER ON COMMON SUPPLY HEADERS TO BE OPENED ONLY ONE OF THE JOINT AHUs OPERATES.
AutoCAD SHX Text
T
AutoCAD SHX Text
1.5 CFM/FT²
AutoCAD SHX Text
M
AutoCAD SHX Text
AI
AutoCAD SHX Text
DXX1
AutoCAD SHX Text
OUTDOOR AIR DAMPER POSITION
AutoCAD SHX Text
AI
AutoCAD SHX Text
DXX2
AutoCAD SHX Text
RETURN AIR DAMPER POSITION
AutoCAD SHX Text
AI
AutoCAD SHX Text
DXX3
AutoCAD SHX Text
EXHAUST AIR DAMPER POSITION
AutoCAD SHX Text
SEQUENCE OF OPERATION AHU-101 1.0 GENERAL GENERAL AHU-01 IS A VARIABLE VOLUME SYSTEM, 100% OUTSIDE AIR AND 100% EXHAUST AIR, UNIT WITH SUPPLY FAN, EXHAUST FAN, HEAT PIPE, FILTER, DIRECT GAS FIRED BURNER, VFD ON SUPPLY AND RETURN AIR FANS AND STANDALONE CONTROLLER. EXTERNAL TAIL PIPE EXHAUST FANS EF-101 AND EF-102 WORKS IN CONJUNCTION WITH AHU-101 2.0 MODE CONTROL MODE CONTROL 1. SUMMER AND WINTER MODE CONTROL IS DETERMINED BY THE OUTSUDE AIR TEMPERATURE. SUMMER AND WINTER MODE CONTROL IS DETERMINED BY THE OUTSUDE AIR TEMPERATURE. SUMMER - OA > 18° C (65° F), WINTER - OA 18° C (65° F) 2. THE BAS AUTOMATICALLY INITIATE THE OCCUPIED AND UN-OCCUPIED MODES ACCORDING TO ITS THE BAS AUTOMATICALLY INITIATE THE OCCUPIED AND UN-OCCUPIED MODES ACCORDING TO ITS PROGRAMMED SCHEDULE. 3.0 OCCUPIED MODE AND UN-OCCUPIED MODE OCCUPIED MODE AND UN-OCCUPIED MODE 1. AHU STARTS IN OCCUPIED MODE AND STOPS IN UN-OCCUPIED MODE AHU STARTS IN OCCUPIED MODE AND STOPS IN UN-OCCUPIED MODE 2. SIGNAL FROM GAS DETECTION SYSTEM STARTS AHU AT FULL SPEED (2265 L/S SUPPLY AND 2380 L/S SIGNAL FROM GAS DETECTION SYSTEM STARTS AHU AT FULL SPEED (2265 L/S SUPPLY AND 2380 L/S EXHAUST) WHEN CO AND NO2 LEVEL EXCEED HIGH LIMIT IN REPAIR GARAGES, 4.0 SUMMER, OCCUPIED MODE SUMMER, OCCUPIED MODE THE MINIMUM OUTSIDE AIR DAMPER OPENS, EXHAUST AIR DAMPER OPENS, WHEN THE END SWITCH PROOF THE DAMPERS OPEN, SUPPLY FAN AND EXHAUST FAN ARE ENERGIZED AND RUN CONTINUOUSLY. GAS BURNER IS DE-ENERGIZED WHEN BOTH EXHAUST FANS EF-101 AND 102 ARE OFF, VFD OF SUPPLY FAN RUNS AT FULL SPEED TO PROVIDE 2265 L/S (4800 CFM), VFD OF RETURN FAN RUNS AT FULL SPEED TO PROVIDE 2380L/S (5040 CFM), BURNER IS OFF WHEN EITHER OR BOTH EXHAUST FANS EF-05 AND 06 ARE STARTED, VFD OF SUPPLY FAN REMAINS AT FULL SPEED 2265L/S (4800 CFM), VFD OF RETURN FAN REDUCE FAN SPEED TO PROVIDE 1910L/S (4040 CFM), BURNER IS OFF 5.0 WINTER, OCCUPIED MODE WINTER, OCCUPIED MODE OUTSIDE AIR DAMPER AND EXHAUST AIR DAMPER OPEN. WHEN THE DAMPERS ARE FULLY OPEN AS PROOF THROUGH THE END SWITCHES, THE SUPPLY FAN AND EXHAUST FAN ARE ALLOWED TO START. WHEN BOTH EXHAUST FANS EF-101 AND EF-102 ARE OFF, VFD OF SUPPLY FAN RUNS AT REDUCED SPEED TO PROVIDE 1135L/S (2400 CFM), VFD OF RETURN RUNS AT REDUCED SPEED TO PROVIDE 1190L/S (2520 CFM), BURNER MODULATES TO MAINTAIN DISCHARGE AIR TEMPERATURE OF 18°C (65°F) AND RESET WITH SPACE TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 20°C (68°F). WHEN EITHER OR BOTH EXHAUST FANS EF-101 AND EF-102 ARE STARTED, VFD OF SUPPLY FAN RUNS TO PROVIDE 1135L/S (2400 CFM), VFD OF RETURN FAN RUNS AT REDUCED SPEED TO PROVIDE 717L/S (1520 CFM), BURNER MODULATES TO MAINTAIN DISCHARGE AIR TEMPERATURE OF 18°C (65°F) AND RESET WITH SPACE TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 20°C (68°F). 6.0 HEAT PIPE OPERATION HEAT PIPE OPERATION HEAT PIPE OPERATION BASED ON SUMMER AND WINTER MODE. IN WINTER MODE, THE TILT ANGEL OF THE HEAT PIPE VARIED TO PRE-HEAT THE SUPPLY AIR, AND PREVENT THE EXHAUST SIDE OF THE HEAT PIPE FROM FREEZING, THE BAS CONTROLS THE HEAT PIPE TILT ANGLE TO LIMIT HEAT TRANSFER AND KEEP THE EXHAUST AIR ABOVE THE FROST THRESHOLD. IN SUMMER NODE, THE TILE ANGLE IS VARIED TO PRE-COOL THE SUPPLY AIR. 7.0 SAFETIES: SAFETIES: 1. THE SUPPLY FAN AND BURNER IS DISABLED WHEN LOSS OF FAN AIR FLOW. THE SUPPLY FAN AND BURNER IS DISABLED WHEN LOSS OF FAN AIR FLOW. 2. THE BURNER IS DISABLED WITHOUT PROOF OF AIRFLOW AS PROVEN BY THE BURNER PRESSURE THE BURNER IS DISABLED WITHOUT PROOF OF AIRFLOW AS PROVEN BY THE BURNER PRESSURE DIFFERENTIAL SWITCH. 3. DISCHARGE SENSOR PREVENTS THE BURNER DISCHARGE TEMPERATURE FROM EXCEEDING 39°C DISCHARGE SENSOR PREVENTS THE BURNER DISCHARGE TEMPERATURE FROM EXCEEDING 39°C 4. SIGNAL FROM FIRE ALARM SYSTEM STOPS THE UNIT IN FIRE CONDITION BY BAS SYSTEM. SIGNAL FROM FIRE ALARM SYSTEM STOPS THE UNIT IN FIRE CONDITION BY BAS SYSTEM. 5. HIGH TEMPERATURE SENSOR STOPS THE FAN SYSTEM AND ALARM AT BAS WHEN THE LIMIT SETTING IS HIGH TEMPERATURE SENSOR STOPS THE FAN SYSTEM AND ALARM AT BAS WHEN THE LIMIT SETTING IS EXCEEDED. 8.0 HEAT RECOVERY UNIT STOP: HEAT RECOVERY UNIT STOP: 1. THE OUTSIDE AIR DAMPER AND EXHAUST AIR DAMPER CLOSE. THE OUTSIDE AIR DAMPER AND EXHAUST AIR DAMPER CLOSE. 2. SUPPLY AND EXHAUST FANS STOP. SUPPLY AND EXHAUST FANS STOP. 3. THE GAS BURNER ASSEMBLY IS DE-ENERGIZED. THE GAS BURNER ASSEMBLY IS DE-ENERGIZED. 9.0 HARDWIRE CONTACTS OF EF-101 AND EF-102 TO AHU-101 CONTROLLER. HARDWIRE CONTACTS OF EF-101 AND EF-102 TO AHU-101 CONTROLLER.
AutoCAD SHX Text
ROOF MOUNTED EF-102
AutoCAD SHX Text
PROCESS EXHAUST FANS
AutoCAD SHX Text
SEQUENCE OF OPERATION TAILPIPE EXHAUST FANS EF-101 AND EF-102 EF-101 AND EF-102 ARE CONTROLLED BY LOCAL MANUAL PUSH BUTTON. CURRENT SWITCHES IN FAN STARTERS (BY DIV 26) PROVIDE RUN SIGNAL TO AHU-101 WHEN CURRENT SWITCH IS PROOFED EITHER OR BOTH EXHAUST FANS ARE RUNNING
AutoCAD SHX Text
CS811 CEILING FAN
AutoCAD SHX Text
CEILING FAN
AutoCAD SHX Text
WALL SWITCH
AutoCAD SHX Text
REPAIR BAY-1 CO SENSORS
AutoCAD SHX Text
REPAIR BAY-1 NO SENSORS
AutoCAD SHX Text
NO
AutoCAD SHX Text
NO
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
CO
AutoCAD SHX Text
CS857 GAS DETECTION SYSTEM
AutoCAD SHX Text
OEM GAS DETECTION CONTROL PANEL
AutoCAD SHX Text
OEM
AutoCAD SHX Text
DI
AutoCAD SHX Text
LLH
AutoCAD SHX Text
CS 203 DRAINAGE INTERCEPTOR (OIL)
AutoCAD SHX Text
SOUND
AutoCAD SHX Text
BMS
AutoCAD SHX Text
VIA BACNET
AutoCAD SHX Text
ZONE 1
AutoCAD SHX Text
ZONE 1
AutoCAD SHX Text
ZONE 2
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
TRUSS
AutoCAD SHX Text
DI
AutoCAD SHX Text
EST
AutoCAD SHX Text
DI
AutoCAD SHX Text
AH(CO)
AutoCAD SHX Text
DI
AutoCAD SHX Text
AH(NO2)
AutoCAD SHX Text
REPAIR BAY-2 NO SENSORS
AutoCAD SHX Text
NO
AutoCAD SHX Text
NO
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
CO
AutoCAD SHX Text
ZONE 2
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
TRUSS
AutoCAD SHX Text
REPAIR BAY-2 CO SENSORS
AutoCAD SHX Text
DI
AutoCAD SHX Text
EST
AutoCAD SHX Text
DI
AutoCAD SHX Text
AH(CO)
AutoCAD SHX Text
DI
AutoCAD SHX Text
AH(NO2)
AutoCAD SHX Text
S
AutoCAD SHX Text
P
AutoCAD SHX Text
101
AutoCAD SHX Text
HIGH LEVEL SENSOR
AutoCAD SHX Text
PUMP ON LEVEL
AutoCAD SHX Text
PUMP OFF LEVEL
AutoCAD SHX Text
SEQUENCE OF OPERATION - SUMP LEVEL TO BE CONTROLLED BY LEVEL SWITCHES - HIGH WATER ALARM TO BE MAINTAINED THROUGH BMS.
AutoCAD SHX Text
SUMP PIT
AutoCAD SHX Text
SUMP PUMP REMOTE CONTROL PANEL
AutoCAD SHX Text
STROBE AND HORN ALARM
AutoCAD SHX Text
LEVEL SENSOR (TYP.)
AutoCAD SHX Text
DI
AutoCAD SHX Text
EST
AutoCAD SHX Text
SUMP PUMP ALARM STATUS
AutoCAD SHX Text
PUMP OFF LOW LEVEL SENSOR
AutoCAD SHX Text
REPAIR BAY-2
AutoCAD SHX Text
REPAIR BAY-1
AutoCAD SHX Text
SUMP PUMP CONTROL SCHEMATIC
AutoCAD SHX Text
INFRARED HEATERS IH-101 AND IH-102 INFRARED HEATERS CONTROLS WITH LOCAL THERMOSTAT TO MAINTAIN SPACE TEMPERATURE OF 20°C (68°F).
AutoCAD SHX Text
T
AutoCAD SHX Text
INFRARED HEATER CONTROLS
AutoCAD SHX Text
INFRARED HEATER
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
FIRE WATER STORAGE TANK CONTROL SCHEMATIC
AutoCAD SHX Text
HIGH LEVEL SENSOR
AutoCAD SHX Text
LOW LEVEL SENSOR (START TO FILL)
AutoCAD SHX Text
WATER LEVEL CONTROL PANEL
AutoCAD SHX Text
STROBE AND HORN ALARM
AutoCAD SHX Text
SEQUENCE OF OPERATION FIRE WATER STORAGE TANKS TO BE CONTROLLED BY LEVEL SWITCHES. LOW LEVEL AND HIGH LEVEL WATER ALARM TO BE MAINTAINED THROUGH BMS. WHEN WATER LEVEL REACHES DESIRED WATER LEVEL SENSOR, SOLENOID VALVE ON FILL LINE CLOSES. WHEN WATER LEVEL REACHES LOW LEVEL SENSOR, SOLENOID VALVE OPENS TO ALLOW WATER TO FILL TANKS AND LOW LEVEL ALARM IS SENT TO CONTROL PANEL AND BMS UNTIL DESIRED WATER LEVEL SENSOR IS REACHED. WHEN HIGH WATER LEVEL SENSOR IS REACHED, SOLENOID VALVE CLOSES AND HIGH LEVEL ALARM IS SENT TO CONTROL PANEL AND BMS.
AutoCAD SHX Text
DESIRED WATER LEVEL SENSOR
AutoCAD SHX Text
CS751 SPLIT A/C -ELECTRICAL ROOM (AC-101/ACC-101)
AutoCAD SHX Text
OEM
AutoCAD SHX Text
PACKAGED REFRIGERANT LINESETS
AutoCAD SHX Text
SEQUENCE OF OPERATION AC-101 - SPLIT A/C UNITS AC-101 CONTROLS WITH LOCAL THERMOSTAT TO MAINTAIN SPACE TEMPERATURE OF 21°C (70°F) IN THEWINTER AND 22°C (72°F) IN THE SUMMER
AutoCAD SHX Text
T
AutoCAD SHX Text
AC-101
AutoCAD SHX Text
ACC-101
AutoCAD SHX Text
P
AutoCAD SHX Text
102
AutoCAD SHX Text
REPAIR BAY-1
AutoCAD SHX Text
CONTROL LINES
AutoCAD SHX Text
User Name: Shujun Liu Plot Date\Time: Thursday, May 16, 2019 3:22:37 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwgShujun Liu Plot Date\Time: Thursday, May 16, 2019 3:22:37 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwg Plot Date\Time: Thursday, May 16, 2019 3:22:37 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwgThursday, May 16, 2019 3:22:37 PM Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwg Path and File Name: j:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwgj:\24rx12.0113_durham region orono & scugog depots\5.9 drawing\59mechanical\layouts\02-m74-00-01.dwg
AutoCAD SHX Text
This drawing has been prepared solely for the use of the Regional Municipality of Durham and there are no representations of any kind made by IBI Group to any party with whom IBI Group has not entered into a contract
AutoCAD SHX Text
A. VAN VEEN
AutoCAD SHX Text
EXPAND GARAGE
AutoCAD SHX Text
SCUGOG DEPOT
AutoCAD SHX Text
24RX12.0113
AutoCAD SHX Text
10 REGIONAL RD. 21, R.R.#14, PORT PERRY
AutoCAD SHX Text
ONTARIO
AutoCAD SHX Text
WHITBY
AutoCAD SHX Text
WORKS DEPARTMENT
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
JAN 31 2018
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
M. ALIKHANI
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
CONTROLS
AutoCAD SHX Text
SCHEMATICS
AutoCAD SHX Text
02-M74-00-01
AutoCAD SHX Text
S. LIU
AutoCAD SHX Text
MAY 15 2019
AutoCAD SHX Text
TENDER
AutoCAD SHX Text
0
shujun.liu
PEO-Shujun