Installation Manual Version 1.0 Smart Temp Apollo P/n 44-800

Transcript of Smart Temp Apollo - Thermostat · Smart Temp Apollo P/n 44-800. ... The Smart Temp 44-800...

Installation ManualVersion 1.0

Smart Temp

ApolloP/n 44-800

TABLE OF CONTENTS

Introduction .........................................................................................................6

Getting started ....................................................................................................7

Installing the thermostat ....................................................................................8

Disassembly ...........................................................................................8Thermostat location ...............................................................................8Mounting the subbase .........................................................................8, 9Terminal designations ..........................................................................10

Installing the batteries ......................................................................................11

Setting the system switches .....................................................................12, 13

1

System switch functions ...................................................................13

Typical wiring diagrams ...............................................................14-24

Heat Only (Gas)......................................................................14Heat Only (Electric).................................................................15Cool Only.................................................................................162 or 3 Cool ...............................................................................171 Heat / 1 Cool .......................................................................182 Heat / 1 Cool........................................................................191 Heat / 2 Cool........................................................................201 Heat / 1 Cool Heat Pump.....................................................212 Heat / 1 Cool Heat Pump.....................................................222 Heat / 2 Cool Heat Pump.....................................................232 Wire - Gas Heating...............................................................24

TABLE OF CONTENTS

2

Installer setup menu ...................................................................................25-46

Entering the menu ...............................................................................25Selecting programmable or non-programmable operation ..................26Selecting program days (programmable mode)...................................27Selecting programmable fan option.....................................................28Selecting mode of operation................................................................29Touchscreen lock options.....................................................................30Selecting the cooling setpoint limit.......................................................31Selecting the heating sepoint limit........................................................32Selecting the temperature display.........................................................33Selecting time format............................................................................34Selecting setpoint display option..........................................................35Selecting back light option...................................................................36

TABLE OF CONTENTS

3

Installer setup menu (Continued)

Selecting Adaptive Recovery................................................................37Filter reminder......................................................................................38Selecting the heating and cooling differential.......................................39Internal sensor calibration....................................................................40Remote sensor options........................................................................41Assigning the ‘A’ relay..........................................................................42Selecting low balance point.................................................................43Selecting high balance point................................................................44Audible beep option.............................................................................45Factory reset........................................................................................46

Remote sensor installation.........................................................................47-51

Remote sensors..................................................................................................47

TABLE OF CONTENTS

4

Remote sensor installation (Continued)Indoor sensor wiring ....................................................................................47-48Using multiple sensors for temperature averaging.............................................49Outdoor sensor wiring...................................................................................50-51Temperature sensor calibration chart.................................................................51

Testing .........................................................................................................52-55Testing fan operation...........................................................................................52Testing conventional heating and cooling operation.....................................52-53Testing conventional heat pump operation........................................................53Testing fossil fuel operation...........................................................................53-54Testing low balance point (heat pump or fossil fuel)...........................................54Testing high balance point (heat pump or fossil fuel).........................................55

Adaptive recovery ............................................................................................55

Basic troubleshooting ................................................................................56-58

Specifications ...................................................................................................59

TABLE OF CONTENTS

5

The Smart Temp 44-800 “Apollo” is a feature-rich touchscreen thermostat that can be battery powered or hardwired to the HVAC equipment. Using a common sense approach to the installation will ensure this product is installed properly and to the customer’s satisfaction. Please take time to read and understand this manual so that installation and testing is performed in an efficient manner.

This manual is to be used in conjunction with the supplied User Manual.

Although great care has been taken in the preparation of this manual, Smart Temp Aust P/L takes no responsibility for errors or omissions contained herein. It is the responsibility of the installer to ensure that this thermostat and the equipment connected to it operate in a safe and efficient manner.

Due to ongoing product improvements, Smart Temp reserves the right to change the specifications of the 44-800 thermostat or its components without notice.

All rights reserved.© Smart Temp Australia P/L.

Intellectual rights apply.

INTRODUCTION

6

As with any HVAC project, careful installation is the key to a successful outcome. Time taken during the installation process will be rewarded with fewer call-backs.

The steps required to install the 44-800 thermostat are as follows:

1. Read and understand this Installation Manual and Thermostat User Manual.

2. Mount and wire the subbase

3. Install the batteries

4. Set the 4 system switches to match the equipment application.

5. Wire optional remote temperature sensor(s).

6. Power the thermostat.

7. Set the Advanced Installer settings.

8. Test the thermostat.

GETTING STARTED

7

DISASSEMBLYThere are two release slots located on the bottom of the thermostat. Gently push the flat blade of a small screwdriver into one slot at a time and pry upward until the catch disengages. Carefully swing the thermostat upward and away from the subbase. (Figure 1)

THERMOSTAT LOCATIONThe 44-800 should be installed in a location that represents the ambient space temperature. Do not install the thermostat in an area where drafts are present, near the floor, behind doors or on an external wall. Avoid placing the thermostat in areas where the air movement is limited, affected by direct sunlight or other areas not typical of the temperature in the space.

MOUNTING THE SUBBASEWhen mounting the 44-800 subbase, be aware that drafts may travel down wall cavities and enter the back of the thermostat through the control wire hole in

INSTALLING THE THERMOSTAT

FIGURE 1

8

the wall. It is important to seal the hole to prevent any drafts that might affect the internal temperature sensor. Pull the control wires through the large opening in the thermostat subbase. Next, level and mount the subbase on the wall using the supplied anchors and screws. (Figure 2)

Do not over tighten the mounting screws as the subbase may warp causing the improper seating of the thermostat connecting pins to the terminal blocks.

Use a properly sized screwdriver and back each screw terminal out (counter clockwise) before landing each wire to its dedicated terminal. Do not over tighten the terminal screws.Check to ensure that all wires are landed correctly and dressed properly to prevent any shorts. Refer to Typical System Wiring Diagrams in this manual for proper wiring. FIGURE 2

Out SC In A W Y G Com R C

Smart Temp Aust P/L

www.thermostat.com.au

WIREACCESS

HOLE

BATTERYCOMPARTMENT

MOUNTING HOLESMOUNTING

HOLE

MOUNTING HOLES

INSTALLING THE THERMOSTAT

9

TERMINAL DESIGNATIONSBased on the 44-800 slide switch and installer option configurations, some terminals have multiple output functions.

TERMINAL DESIGNATION

Outside Outdoor Sensor

Sensor Common Sensor Common

Inside Indoor Sensor

A W2, Y2, Compressor 2, Aux, EH

W W1, Y3, Reversing Valve

Y Y1, Compressor 1

R 24 Volt (Hot)

C 24 Volt (Common)

INSTALLING THE THERMOSTAT

10

The 44-800 comes with two AAA batteries. Insert the batteries as illustrated for primary or backup power. Even if the thermostat is hardwired, battery backup is essential to maintain the real-time clock in the event of a power failure. All other memory is non-volatile in the event of battery or primary power loss. (Figure 3)

FIGURE 3

Out SC In A W Y G Com R C

Smart Temp Australia P/L

www.thermostat.com.au

INSTALLING THE BATTERIES

11

The 44-800 contains a set of four system switches located on the thermostat printed circuit board. (Figure 4) The switches are used to match the thermostat with the HVAC system requirements. Refer to the system switch functions on the next page to properly configure the thermostat.

FIGURE 4

1 2

3 4

ON

SYSTEM SWITCHES

SETTING THE SYSTEM SWITCHES

. . . . . . . . .

12

SW 1 - Equipment Type Switch 1 sets the equipment type. For heat / cool equipment, set the switch to the OFF position (factory default). For heat pump equipment, set switch 1 to the ON position.

SW 2 - Fan or Reversing Valve Heat Cool Logic (SW 1OFF).For gas systems, set the switch 2 to the OFF positionFor electric heat systems, set switch 2 to the ON position.

Heat Pump Logic (SW 1 ON).For ‘O’ reversing valve, set switch 2 to the OFF position For ‘B’ reversing valve, set switch 2 to the ON position.

SW 3 - Short Cycle Timer For 4 minutes short cycle protection, set switch 3 tothe OFF position (factory default). For no shortcycle protection, set switch 3 to the ON position.

SW 4 - Fossil Fuel Mode This is a USA requirement - leave OFF in AustraliaFor conventional heat pump equipment,set switch 4 to the OFF position (factory default).For fossil fuel equipment, set switch 4 to the ONposition.

SYSTEM SWITCH FUNCTIONS

13

SC In A Y G R Com C

HEAT 1RELAY

FAN 1RELAY

LINE24 V

W Out

HEAT ONLY (Gas)

OPTIONALREMOTE SENSOR

TERMINALS

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = OFF (Equipment controls fan)Sw3 = OFF (No affect on setup)Sw4 = OFF (Leave OFF)

In Installer Menu, set 4Fn = H (Heat Only)

TYPICAL SYSTEM WIRING DIAGRAMS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

FanOptional

OUTDOORSENSOR

INDOORSENSOR

14

HEAT ONLY (Electric)

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = ON (Thermostat controls fan)Sw3 = OFF (No affect on setup)Sw4 = OFF (Leave OFF)

In Installer Menu, set 4 Fn = H (Heat Only)

TYPICAL SYSTEM WIRING DIAGRAMS

15

SC In A Y G R Com C

HEAT 1RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

COOL ONLY

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = ON (Thermostat controls fan)Sw3 = OFF (No affect on setup)Sw4 = OFF (Leave OFF)

In Installer Menu, set 4 Fn = C (Cool Only)

TYPICAL SYSTEM WIRING DIAGRAMS

16

SC In A Y G R Com C

COOL 1RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

2 OR 3 COOL (3 COOL ILLUSTRATED)

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = ON (Thermostat controls fan)Sw3 = OFF (4 min anti cycle delay)Sw4 = OFF (Leave OFF)

In Installer Menu, set 4EF = C (Cool Only) Set 17:R4 = C2 (A Relay = Cool 2) Set 17:R4 = C3 (A Relay = Cool 3 and W = Cool 2)

Set 4:Fn = C (Cool Only Mode

TYPICAL SYSTEM WIRING DIAGRAMS

17

SC In A Y G R Com C

COOL 1RELAY

COOL 2RELAY

COOL 3RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

1 HEAT / 1 COOL (GAS)

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = OFF (Equipment controls fan)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

In Installer Menu, set 4Fn = - (Manual Changeover) or 4Fn = A (Auto Changeover)

TYPICAL SYSTEM WIRING DIAGRAMS

18

SC In A Y G R Com C

COOL 1RELAY

HEAT 1RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

2 HEAT / 1 COOL (GAS)

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = OFF (Equipment controls fan)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

In Installer Menu, set 17:R4 = H2

TYPICAL SYSTEM WIRING DIAGRAMS

19

SC In A Y G R Com C

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

COOL 1RELAY

HEAT1RELAY

HEAT 2RELAY

1 HEAT / 2 COOL (GAS)

Switch Settings

Sw1 = OFF (Heat / Cool)Sw2 = OFF (Equipment controls fan)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

In Installer Menu, set 17R4 = C2

TYPICAL SYSTEM WIRING DIAGRAMS

20

SC In A Y G R Com C

COOL 1RELAY

HEAT 1RELAY

COOL 2RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

1 HEAT / 1 COOL HEAT PUMP

Switch Settings

Sw1 = ON (Heat Pump)Sw2 = OFF (OFF=‘O’ reversing valve, ON=’B’ reversing valve)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

TYPICAL SYSTEM WIRING DIAGRAMS

21

SC In A Y G R Com C

COMP 1RELAY

R/VALVERELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

2 HEAT / 1 COOL HEAT PUMP

Switch Settings

Sw1 = ON (Heat Pump)Sw2 = OFF (OFF=’O’ reversing valve ON=’B’ reversing valve)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

In Installer Menu, set 17R4 = AU

TYPICAL SYSTEM WIRING DIAGRAMS

22

SC In A Y G R Com C

COMP 1RELAY

R/VALVERELAY

AUXRELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

2 HEAT / 2 COOL HEAT PUMP (NO AUXILIARY HEAT)

Switch Settings

Sw1 = ON (Heat Pump)Sw2 = OFF (OFF=’O’ reversing valve ON=’B’ reversing valve)Sw3 = OFF (4 minute short cycle protection)Sw4 = OFF (Leave OFF)

In Installer Menu, set 17R4 = Y2

TYPICAL SYSTEM WIRING DIAGRAMS

23

SC In A Y G R Com C

COMP 1RELAY

R/VALVERELAY

COMP 2RELAY

FAN 1RELAY

LINE24 V

W Out

OPTIONALREMOTE SENSOR

TERMINALS

THERMOSTAT

EQUIPMENT

Factory Link

24C Optional

OUTDOORSENSOR

INDOORSENSOR

SC S1 A Y G R CW S2

2 Wire - Gas Heating

THERMOSTAT

EQUIPMENT

OPTIONALREMOTE SENSOR

TERMINALS

Switch Settings

Sw1 = OFF (Heat Cool)Sw2 = OFF (OFF=Fan controlled by Gas Heater)Sw3 = ON (No short cycle protection required)Sw4 = ON (Leave OFF)

In Installer Menu, set 4 Fn = H

TYPICAL SYSTEM WIRING DIAGRAMS

OUTDOORSENSOR

INDOORSENSOR

24

Gas HeaterR

W

ENTERING THE MENU

Touch and hold both the Clock and Mode section for 5 seconds to enter the Installer Menu.

To advance through the menus, touch the Mode section.

E

E

INSTALLER SETUP MENU

25

SELECTING THE PROGRAM

The first menu 1:PR selects programmable or non-progrmmable operation. Press the UP or DOWN arrows to change the selection. The factory default is 4 (4 schedules per day).

E

0 = Manual Mode (non-programmable)2 = 2 Schedules Per Day (Day / Night)4 = 4 Schedules Per Day (Morning / Day / Evening / Night)

Program

INSTALLER SETUP MENU

Morning DayEvening Night

26

SELECTING PROGRAM DAYS

If menu 1:PR is set to 2 or 4, 2:PD is used to select 5 + 2 programming or 7 day programming. Touch the UP or DOWN arrows to change the selection. The factory default is 52.

52 = 5 + 2 (Same schedule Mon-Fri and Sat-Sun)7 = 7 (7 individual day programming)

E

INSTALLER SETUP MENU

27

SELECTING PROGRAMMABLE FAN OPTION

Menu 3:PF is the Programmable Fan option which allows selecting continuous or auto fan operation for each program event when programmable mode is enabled.

ON = Programmable FanOFF = No Programmable Fan

E

INSTALLER SETUP MENU

Program

28

SELECTING MODE

Menu 4:FN selects the mode of operation. The factory default is FN=A for auto changeover. Touch the UP and DOWN arrows to change the selection.

E

- = Manual ChangeoverA = Auto ChangeoverH = Heat OnlyC = Cool OnlyAO = Auto / Off Only

AUTO

INSTALLER SETUP MENU

29

TOUCHSCREEN LOCK OPTIONS Menu 5:LC allows you to prevent changes to all or part of the touchscreen functions. The factory default is OFF. Touch the UP and DOWN arrows to the selection.

E

INSTALLER SETUP MENU

OFF = All Functions Unlocked 4 = UP / DOWN Arrows Locked 8 = Fan / Program / Mode / Clock1 = Program Locked 5 = Clock Locked Locked2 = Mode Locked 6 = Fan / Mode Locked 9 = All Functions Locked3 = Fan Locked 7 = Fan / Program / Mode Locked

30

SELECTING THE COOLING LIMIT

Menu 6:CL selects the minimum cooling set point. The factory default is 10° FC. Touch the UP and DOWN arrows to adjust the limit from 6° - 50° C.

E

Set

INSTALLER SETUP MENU

31

SELECTING THE HEATING LIMIT

Menu 7:HL selects the maximum heating set point limit. The factory default is 35° C. Touch the UP and DOWN arrows to adjust the limit from 5° - 49° C.

E

Set

INSTALLER SETUP MENU

Heat

32

SELECTING TEMPERATURE DISPLAY

Menu 8:TD selects the temperature to be displayed in Fahrenheit or Celsius. The factory default is C (Celsius). Touch the UP and DOWN arrows to change the display setting.

E

INSTALLER SETUP MENU

F = FahrenheitC = Celsius 33

SELECTING TIME FORMAT

Menu 9:CL selects the time format which can be 12 hour or 24 hour. The factory default is 12 (12 hour). Touch the UP and DOWN arrows to change the format.

E

INSTALLER SETUP MENU

12 = 12 Hour24 = 24 Hour (Military Time)34

SELECTING SETPOINT DISPLAY OPTION

Menu 10:ST allows the option of continuously displaying the setpoint temperature with the space temperature. The factory default is OFF (no setpoint displayed).

E

INSTALLER SETUP MENU

Set

OFF = No Setpoint DisplayedON = Display Setpoint 35

SELECTING BACK LIGHT OPTION

Menu 11:BL allows you the select the back light option. The factory default is ON (Back light ON). Touch the UP and DOWN arrow to change the option.

E

INSTALLER SETUP MENU

ON = Back Light On (Light stays on for 10 seconds when screen is touched)OFF = No Back LightAll =Back Light on constantly. High with button press and low at other times(24V power only)36

SELECTING ADAPTIVE RECOVERY

Menu 12:RC allows you the select the Adaptive Recovery option when the thermostat is configured as programmable. Adaptive Recovery compares the space temperature deviation from setpoint and rate of recovery history to bring the equipment on and reach the setpoint at the scheduled time. Touch the UP and DOWN arrows to change the option.

E

INSTALLER SETUP MENU

OFF = No Adaptive RecoveryON = Adaptive Recovery On (For programmable mode only) 37

FILTER REMINDER

Menu 13:FT allows you to select a time when the thermostat will display FLT as a reminder that the HVAC system filters need to be changed. The factory default is OFF. Touch the UP and DOWN arrows to change the filter reminder time.

E

INSTALLER SETUP MENU

010 = 100 Hours100 = 1000 Hours (Up to 9,000 hours in 100 hour steps)38

CHANGING THE HEATING AND COOLING DIFFERENTIAL

Menu 14:SP allows you to select the temperature differential between the heating and cooling set point. The factory default is 1 (0.5° C) Touch the UP and DOWN arrows to change the differential.

E

INSTALLER SETUP MENU

1 = 0.5° C2 = 1° C3 = 1.5° C 39

INTERNAL SENSOR CALIBRATION

Menu 15:CA allows you to re-calibrate the internal temperature sensor. The factory default is 0 (0° C). Touch the UP and DOWN arrows to adjust the calibration from -5 . ° to +5° C

E

INSTALLER SETUP MENU

40

REMOTE SENSOR

Menu 16:TT allows you to select indoor remote sensor only or remote sensor with internal sensor. The factory default is RS which disables the internal sensor only when an indoor remote sensor is wired. Touch the UP and DOWN arrows to change the option to AU if you want to use the internal sensor with a remote sensor as part of temperature averaging.

E

INSTALLER SETUP MENU

RS = Indoor Remote Sensor OnlyAU = Indoor Remote Sensor With Internal Sensor 41

NoteIf using outside air or remote room temperature sensor(s) battery life will be drastically reduced.

If using remote sensors it is highly recommended to power the 44-800 from 24V

ASSIGNING THE ‘A’ RELAY

Menu 17:R4 allows you to assign the ‘A’ relay based on the specific equipment configuration. The factory default is OFF. Touch the UP and DOWN arrows to change the ‘A’ relay assignment. Note that selections change based on Heat / Cool or Heat Pump (Sw1) configuration.

INSTALLER SETUP MENU

E

HEAT / COOL HEAT PUMPC2 = 2nd Stage Cooling EH = Emergency Heat OnlyH2 = 2nd Stage Heating AU = Auxiliary and Emergency HeatC3 = 3rd Stage Cooling Y2 = 2nd Stage Compressor42

LOW BALANCE POINT SELECTION USING OUTDOOR SENSOR

Menu 18:LB allows you to select a low balance point setting when the thermostat is configured for Fossil Fuel. When the outdoor temperature falls below the balance point setting, the compressor is locked out and only the fossil fuel furnace is used for heating. The factory default is OFF. Touch the UP and DOWN arrows to change the setting. Setting can be from -15° to 25° C.

INSTALLER SETUP MENU

E43

HIGH BALANCE POINT SELECTION USING OUTDOOR SENSOR

Menu 19:HB allows you to select a high balance point setting when the thermostat is configured for Fossil Fuel. When the outdoor temperature rises above the balance point setting, the furnace is locked out and only the compressor is used for heating. The factory default is OFF. Touch the UP and DOWN arrows to change the setting. Setting can be from 0° to 50° C.

INSTALLER SETUP MENU

E44

AUDIBLE BEEP

Menu 20:BP allows you to turn the audible beep on or off. The factory default is ON. Touch the UP and DOWN arrows to turn the audible beep OFF.

INSTALLER SETUP MENU

E45

FACTORY RESET

Menu 21:RS allows you to reset the thermostat to the original factory defaults. To reset the thermostat, touch the UP and DOWN arrows and set to ON.

INSTALLER SETUP MENU

E46

REMOTE SENSOR INSTALLATION

REMOTE SENSORSThere are two type of remote sensors. The RS-1 is a single sensor that can be used indoors or outdoors. The RS-2 contains two sensors. A combination of both sensors can be used for indoor temperature averaging with or without the onboard sensor. Use separate 18-2 shielded cable when wiring sensors.

INDOOR SENSOR WIRINGWhen the RS-1 is used as an indoor sensor, the 44-800 can be configured to allow only the remote sensor to control the temperature or a combination of remote and onboard sensors can be used for temperature averaging. Refer to 16:TT in the installer setup menu to select the proper remote sensor option. Indoor sensor wires to terminals S1 and SC. (FIGURE 5)

OUT SC IN

RS-1SENSOR

FIGURE 547

NoteIf using outside air or remote room temperature sensor(s) battery life will be drastically reduced.

If using remote sensors it is highly recommended to power the 44-800 from 24V

REMOTE SENSOR INSTALLATION

Locate the sensor in the same manner as the thermostat. Mount the sensor 300mm away

from any outside wall. Do not install the sensor behind doors, in corners or other dead air

spaces. Keep the sensor away from direct air flow, supply registers or near sources of heat

such as lamps and appliances. The maximum wire length from the sensor to the

thermostat is 30meters. Use a separate 18-2 shielded cable for sensor wiring. Prior to

wiring the sensor to the thermostat, use an ohm-meter or multimeter to measure the

resistance of the sensor. Measure at the end of the wires that will connect to the

thermostat. Confirm the resistance value (within 5%) to the temperature where the sensor

is mounted. Use a quality digital electronic thermometer to read the temperature at the

sensor. Remove the sensor cover and place the thermometer probe next to the remote

sensor to verify an accurate reading. Disconnect power to the thermostat when wiring the

sensor to the proper sensor terminals. Strip only as much insulation off of the wires as

necessary to provide a good contact with the terminals. The sensor is not polarity specific

so either sensor lead may be connected to either designated terminal on the thermostat.

48

USING MULTIPLE SENSORS FOR TEMPERATURE AVERAGING

Multiple indoor remote sensors can be wired in series/parallel for temperature averaging. The total value of the sensors must equal 10kÙ @ 25° C. The onboard sensor is not part of the equation even if it is configured as part of the averaging circuit. Figure 6 illustrates two RS-2 sensors used for averaging.

REMOTE SENSOR INSTALLATION

S2 SC S1

RS-2SENSOR

RS-2SENSOR

FIGURE 649

OUTDOOR SENSOR WIRING

When the RS-1 is used as an outdoor sensor, the 44-800 will display the outside air temperature as well as control high and low balance points for fossil fuel systems. Refer to 16:TT in the installer setup menu to select the proper sensor option. The outdoor sensor wires to the Sensor Common and Outside air terminals. Figure 7 illustrates both an indoor and outdoor sensor configuration.

Out SC In

RS-1SENSOR

RS-1SENSOR

INDOOR SENSOROUTDOOR SENSOR

REMOTE SENSOR INSTALLATION

FIGURE 750

Mount the sensor on a vertical exterior surface below an overhang. Choose a location protected from direct sunlight and exposure to excessive moisture. Follow the same wiring procedures as installing an indoor sensor.

TEMPERATURE SENSOR CALIBRATION CHART

REMOTE OUTDOOR SENSOR INSTALLATION

Temperature Resistance Temperature Resistance (°C) (kÙ) (?C) (kÙ)

0 34.6 21 11.9

5 26.1 26 9.4

10 19.9 32 7.4

15 15.3 37 5.9

NTC type 3 sensor - 10K @ 25° CÙ

51

TESTING

The 44-800 incorporates a short-cycle timer which can be disabled during testing by setting slide switch 3 to the ON position. Once testing is completed, the timer needs to be re-initiated by setting the switch to OFF.

TESTING FAN OPERATIONTouch MODE until the word OFF is displayed. Touch FAN until the words Always On appear. After a brief moment, the internal fan relay ‘G’ will energize and the system fan should operate. Touch FAN again until the word Automatic appears. After a brief moment, the internal fan relay will de-energize and the system fan will shut off.

TESTING CONVENTIONAL HEATING AND COOLING OPERATIONTouch MODE until the word Heat appears. Touch the UP arrow and raise the set point a few degrees above the space temperature. After a brief moment, the internal heating relay ‘W’ will energize and the heating system should operate. The word Heat will flash continuously. If the thermostat has been configured for two stage heating, raise the set point a few degrees and the second stage heating relay ‘A’ will energize. Heat will flash twice, pause and repeat the sequence to indicate second stage has been energized.

52

TESTING

Touch MODE until Cool appears. Touch the DOWN arrow and lower the setpoint a few degrees below the space temperature. After a brief moment, the internal fan ‘G’ and cooling ‘Y’ relay will energize. The word Cool will flash. If the thermostat has been configured for two stage cooling, lower the set point a few degrees and the second stage cooling relay ‘A’ will energize. Cool will flash twice, pause and repeat the sequence to indicate second stage has been energized.

TESTING CONVENTIONAL HEAT PUMP OPERATION

When the 44-800 is configured for conventional heat pump operation, testing is the same as a heating and cooling system with the exception that the fan “G’ relay is always energized with compressor, auxiliary and emergency heat calls.

TESTING FOSSIL FUEL OPERATIONThis is NOT typically used in Australia.When the 44-800 is configured for fossil fuel operation, testing is the same as a

53

TESTING

conventional heat pump system with the exception that the heat pump is never allowed to run when the fossil fuel furnace is energized. Whenever the thermostat calls for second stage (auxiliary) heat, the compressor ‘Y’ relay is de-energized along with the fan ‘G’ relay and the ‘A’ relay energizes the fossil fuel furnace. With the installation of an outdoor sensor, both high and/or low balance point control can be used to prioritize heat pump or fossil fuel operation based on a selected outdoor temperature.

TESTING LOW BALANCE POINT (Heat Pump or Fossil Fuel)When an outdoor sensor is used with the 44-800, Installer Option 18:LB allows you to select a low balance point temperature. When the outdoor temperature falls below the low balance point setting, a call for heat from the thermostat automatically energizes the auxiliary heat ‘A’ relay. To test the low balance point setting, set 18:LB above the displayed outdoor temperature and force a call for heating. The ‘A’ relay will energize the compressor ‘Y’ relay will be bypassed. Set 18:LB below the displayed outdoor temperature and force a call for heating. The compressor ‘Y’ relay will energize and the ‘A’ relay will not energize as long as the thermostat does not call for second stage. After testing, reset the low balance point temperature to a normal operating range.

54

TESTING

TESTING HIGH BALANCE POINT (Heat Pump or Fossil Fuel)

High balance point is designed to prevent the auxiliary heat ‘A’ relay from energizing when the outdoor temperature is above the balance point setting. To test the high balance point setting, set 19:HB below the displayed outdoor temperature and force a call for second stage heating. The ‘A’ relay will not energize and only the compressor ‘Y’ and fan ‘G’ relays will be active. If the thermostat is placed in the E.heat mode, the high balance point is ignored and the ‘A’ relay will energized on a call for heat. After testing, reset the high balance point temperature to a normal operating range.

Adaptive Recovery is only available in programmable mode (Installer Menu 12:RC = ON). The Adaptive Recovery function of the 44-800 permits the user to program a time that a desired set temperature is required. The thermostat then calculates the most energy efficient time to bring on the equipment to reach the set point at the designated time. This calculation involves a complex control algorithm that compares the space temperature deviation from set point and rate of recovery history.

ADAPTIVE RECOVERY

55

BASIC TROUBLESHOOTING

SYMPTOM POSSIBLE FAULT AND REMEDY

No LCD display If thermostat is battery powered only, remove battery compartmentand check to see that the positive (+) and negative (-) ends of eachbattery are oriented properly. If thermostat is hardwired, remove thethermostat from the subbase and check for 24 Volts across terminals‘C’ and ‘R’. If no voltage, fault could be equipment or wiring related.

Thermostat can not be set In the Installer Options menu, set 4:FN = A for auto changeover. for auto changeover 4:FN = - is for manual heat / cool

4:FN = C is for cooling only4:FN = H is for heating only

Temperature display is Air from wall cavity may be leaking into the rear of the thermostat. inaccurate Seal hole where wiring enters subbase to prevent air infiltration.

External influence from appliances, lighting or drafts may be affectingtemperature accuracy. Move lamps or other sources of heat awayfrom the thermostat.

56

BASIC TROUBLESHOOTING

SYMPTOM POSSIBLE FAULT AND REMEDY

Thermostat not displaying Check wiring at outdoor sensor and sensor terminals on outdoor temperature thermostat subbase. Outdoor sensor wires to terminals

Outside sensor and Sensor Common.

Heat or Cool is flashing This is not a fault but indicates that the thermostat heatingor cooling relay is energized.

Lock icon is displayed This is not a fault. The thermostat heating and cooling limits when trying to set a are preventing setting a temperature above or below the higher heating or lower limit values. These values can be changed in the Installer cooling temperature Options menu.

6:CL = Cooling Limit. Factory default is 10º C. Adjustablefrom 6º C - 50º C.7:HL = Heating Limit. Factory default is 90º F. Adjustablefrom 5º C - 49º C.

57

SPECIFICATIONS

Input Voltage (Hardwired) 20-30 VAC 50/60 HzRelay Rating 24 VAC @ 1 Amp maximum per relayBattery Power (2) AAA 1.5 VOperating Temperature 0° C to 55° COperating Relative Humidity 0-95% (non-condensing)Storage Temperature 0° C to 65° CSize: 125 W x 85 H x 25 D mmLCD Display Size 57 W x 99 H mmBack Light White (LED)Short-cycle Delay Off or 4 minutesDisplayed Temperature Resolution 0.1° CSetpoint Range Heating 5° C - 49° C Cooling 6° C - 50° CHeating and Cooling Limits Fully adjustableOnboard Sensors NTC type 3 100K @ 25cRemote Sensors NTC type 3 10K @ 25cWarranty 3 years (RTB)

59