Appendix B

Alarm List

Refer to the following tables for the alarms and their default levels and output relays.Table B-1Table B-2Table B-3Table B-4 and Table B-5.

Note:

A1 to A6 are the six output relays. quick installation and commissioning ZXDU58/ZXDU68 DC power system.

For their corresponding interfaces, refer to the guide or product description manual of the

Table B-1 Battery and System Alarms

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

1Common AlarmMaskA1The CSU detects that an alarm

occurs.

2Batt.Test FailMaskA2A battery test is terminated

when the battery voltage

reaches Test Stop Volt. while

the battery capacity does not

reach Test Stop Cap.

3LLVD1 AlarmCriticalA2WithDisconnect Modeset

to Batt.Volt., the battery

voltage is lower than

LLVD1 Voltage.

With Disconnect Mode

set to Batt.Rem.Cap., the

battery voltage is lower

than LLVD1 Voltage or the

remaining battery capacity

is lower than LLVD1

Capacity.

With Disconnect Mode

set to PowerOff Time, the

battery voltage is lower

than LLVD1 Voltage or the

B-1

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

power-off time is longer

than LLVD1 Duration.

WithLLTD Enabledset to

Enabled.

4LLVD2 AlarmCriticalA2WithDisconnect Modeset

to Batt.Volt., the battery

voltage is lower than

LLVD2 Voltage.

With Disconnect Mode

set to Batt.Rem.Cap., the

battery voltage is lower

than LLVD2 Voltage or the

remaining battery capacity

is lower than LLVD2

Capacity.

With Disconnect Mode

set to PowerOff Time, the

battery voltage is lower

than LLVD2 Voltage or the

power-off time is longer

than LLVD2 Duration.

WithLLTD Enabledset to

Enabled.

5CAN Bus AbnormalMaskA2The CAN bus cannot send

or receive data normally

due to some communication

exception.

6Batt.Det.Abnor.CriticalA2The battery voltage gets lower

than Test Stop Volt. in the

process of the battery test.

7BLVD AlarmCriticalA2WithDisconnect Modeset

to Batt.Volt., the battery

voltage is lower than BLVD

Voltage.

With Disconnect Mode

set to Batt.Rem.Cap., the

battery voltage is lower

than BLVD Voltage or

the remaining battery

capacity is lower than

BLVD Capacity.

B-2

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

Appendix B Alarm List

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

WithDisconnect Mode

set to PowerOff Time, the

battery voltage is lower

than BLVD Voltage or the

power-off time is longer

than BLVD Dura.

WithBHTD Enabledset to

Enabled.

8LLTD AlarmCriticalA2When the environment

temperature is lower than

LLTD Env.Temp., the system

disconnects the LLVD1 and

LLVD2 loads.

9BHTD AlarmCriticalA2When the battery temperature

is higher than BHTD Temp.,

the system disconnects the

batteries.

10All Alarm BlockedCriticalA2The system does not display

any other real-time alarms. This

can be set through Alm.Ctrl.

Table B-2 AC Alarms

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

11AC Power OffMajorA3The mains power fails and there

is no standby AC input.

12AC In.Switch OffMaskA3The main AC input circuit

breaker trips.

13Pha.Volt.HighMajorA3The detected phase voltage is

higher than Pha.Volt.H.Thre.

14Pha.Volt.LowMajorA3The detected phase voltage is

lower than Phase Under Volt.

15AC Phase LackMajorA3The AC input lacks one phase

or two.

16Pha.Volt.ImbalaMajorA3The difference between phase

voltages is greater than Phase

Volt.Imbala.

B-3

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

17Pha.Curr.HighMajorA3The phase current is higher

than AC Curr.High.Thre.

18AC Out.Switch OffMaskA3The auxiliary AC output circuit

breaker trips.

19AC SPD AbnorMajorA3The AC surge protection device

(SPD) is damaged or not

installed.

Table B-3 Rectifier Alarms

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

20SMR Fan FaultMajorA4The rectifier fan is faulty.

21SMR Ra.T.H.OMajorA4The temperature of the PFC

heat radiator is higher than the

maximum radiator temperature

(110 ).

22SMR In.V.H.O.MajorA4The AC input voltage of the

rectifier is higher than the

maximum input voltage (300 V).

23SMR In.V.L.O.MajorA4The AC input voltage of the

rectifier is lower than the

minimum input voltage (80 V).

24SMR Out.V.H.O.MajorA4The output voltage of the

rectifier is higher than the

maximum output voltage (56.6

V to 62 V, which can be set).

25SMR Out.C.H.MajorA4The output current of the

rectifier is higher than the

maximum output current (68 A).

26SMR Inter.T.H.MajorA4The temperature at the air inlet

of the rectifier is higher than the

maximum internal temperature

(70 ).

27SMR Out.FuseMajorA4The output fuse of the rectifier

blows.

B-4

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

Appendix B Alarm List

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

28SMR Curr.ShareMajorA4When multiple rectifiers are

working in parallel, the output

current difference between

these rectifiers is greater than

the threshold (8 A).

29SMR Input OffMajorA4The power input of the rectifier

is interrupted.

30PFC Out.V.H.MajorA4The output voltage of PFC is

higher than the threshold (450

V).

31PFC Out.V.L.MajorA4The output voltage of PFC is

lower than the threshold (345

V).

32SMR EEPROMMajorA4Errors occur when the rectifier

reads and writes the EEPROM.

33SMR In.Comm F.MajorA4Some exception occurs to the

communication of the Serial

Communication Interface (SCI).

34SMR Primy.C.H.MajorA4The primary current of the

transformer is higher than the

threshold (28 A).

35PFC Input C.H.MajorA4Reserved alarm

36SMR Start Abr.MajorA4The starting time of the rectifier

exceeds 5 minutes.

37SMR In.FuseMajorA4The input fuse of the rectifier

blows.

38SMR Comm.FailMajorA4The communication between

the rectifier and the CSU is

interrupted because the rectifier

is removed or there is some

communication exception.

39SMR In.Freq.MajorA4The input frequency of the

rectifier is too high (higher than

73 Hz) or too low (lower than 40

Hz).

40SMR Out.V.L.MajorA4The output voltage of the

rectifier is lower than the

threshold (36 V).

B-5

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

Table B-4 DC Alarms

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

41DC Volt.HighMajorA5The DC output voltage is higher

than DC Volt.High Thre.

42DC Volt.LowMajorA5The DC output voltage is lower

than DC Volt.Low Thre.

43DC SPD Abnor.MajorA5The DC SPD is faulty.

44Batt.Volt.LowMajorA5The voltage of a battery pack is

lower than Batt.Volt.L.Thre.

45Batt.Curr.Abr.MinorA5The rate of the detected

battery current to the highest

detectable current is greater

than Batt.Curr.Abn.Rate.

46Batt.Temp.HighMajorA5The battery temperature is

higher than Batt.Temp.H.Thre.

47Batt.Temp.LowMajorA5The battery temperature is

lower than Batt.Temp.L.Thre.

48Batt.Loop Brk.CriticalA5The battery loop is

disconnected.

49Batt.Dischg.MinorA5The battery discharge current is

higher than Batt.Dischg Thre.

50Batt.T.InvalidWarningA5The system is configured

with batteries, but the battery

temperature detection is

ineffective. The battery

temperature sensor is not

installed or the battery

temperature is out of the

detection range.

51LLVD1 Extend Brk.MinorA5The circuit breaker or fuse of

the extended LLVD1 loop trips

or blows.

52LLVD1 Loop B.MinorA5The circuit breaker or fuse of

the LLVD1 loop trips or blows.

53LLVD2 Extend Brk.MinorA5The circuit breaker or fuse of

the extended LLVD2 loop trips

or blows.

B-6

SJ-20110425090737-001|2011-09-09 (R1.3)ZTE Proprietary and Confidential

Appendix B Alarm List

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

54BLVD Extend Brk.MinorA5The fuse of the extended BLVD

loop blows.

55BLVD Loop Brk.MinorA5The fuse of the BLVD loop

blows.

Table B-5 Environment Alarms

S/NAlarm NameDefaultOutput RelayDescription

Level

DefaultModified

56Env.Temp.HighMinorA6The environment temperature is

higher than Env.Temp.H.Thre.

57Env.Temp.LowMinorA6The environment temperature

is lower than Env.Temp.L.Thre.

58Env.Hum.HighMinorA6The environment humidity is

higher than Env.Hum.H.Thre.

59Env.Hum.LowMinorA6The environment humidity is

lower than Env.Hum.L.Thre.

60Smog AlarmMajorA6The sensor detects smog.

61Flood AlarmMajorA6The sensor detects the flooding

danger.

62Access Ctrl.Alm.MinorA6The sensor detects the intrusion

of something.

63Door AlarmMinorA6The door with the door status

switch is opened.

64Glass Brk.Alm.MinorA6The sensor detects broken

glasses.

65Env.Temp.InvalidWarningA6The environment temperature

sensor is damaged or not

installed.

66Env.Hum.InvalidWarningA6The environment humidity

sensor is damaged or not

installed.

B-7