SIPLUS SM 322 DIGITAL OUTPUT MODULE
Function
Digital output modules convert the internal signal level of the controller to the external signal levelrequired by the process.Various output voltages support the output of different process signals:
24 V DC, rated current 0.5 A/channel 48 to 125 V DC 120/230 V AC
Apart from cost-effective, easy-to-handle digital output modules, modules with special functions arealso available for process engineering.
Technical specifications
Page 993 Mar 2008 Siemens ITS
6ES7 322-1BH01-0AA0
6ES7 322-1BH10-0AA0
6ES7 322-1BL00-0AA0
6ES7 322-1BP00-0AA0
6ES7 322-1BP50-0AA0
6ES7 322-8BF00-0AB0
Supply voltageLoad voltage L+•Rated value(DC)
24 V 24 V 24 V 24 V 24 V 24 V
Input currentfrom load voltageL+ (without load),max.
80 mA 110 mA 160 mA 75 mA 75 mA 90 mA
from backplanebus 5 V DC,max.
80 mA 70 mA 110 mA 100 mA 100 mA 70 mA
Power lossesPower loss, typ. 4.9 W 5 W 6.6 W 6 W 6 W 5 WDigital outputsNumber/binaryoutputs
16 16 32 64 64 8
Limitation ofinductiveshutdown voltageto
L+ (-53 V) L+ (-53 V) L+ (-53 V) L+ (-53 V) M+ (45 V) L+ (-45 V)
Lamp load, max. 5 W 5 W 5 W 5 W 5 W 5 W
Page 994 Mar 2008 Siemens ITS
Output voltage•for signal "1",min.
L+ (-0.8V)
L+ (-0.8V)
L+ (-0.8V)
L+ (-0.5V)
M+ (0.5V)
L+ (-0.8 to -1.6 V)
Output current•for signal "1"rated value
0.5 A 0.5 A 0.5 A 0.3 A 0.3 A 0.5 A
•for signal "1"permissiblerange, min.
2.4 mA 2.4 mA
•for signal "1"permissiblerange, max.
0.36 A 0.36 A
•for signal "1"permissiblerange for 0 to40 °C, min.
5 mA 5 mA 5 mA 10 mA
•for signal "1"permissiblerange for 0 to40 °C, max.
0.6 A 0.6 A 0.6 A 0.6 A
•for signal "1"permissiblerange for 40 to60 °C, min.
5 mA 5 mA 5 mA 10 mA
Page 995 Mar 2008 Siemens ITS
•for signal "1"permissiblerange for 40 to60 °C, max.
0.6 A 0.6 A 0.6 A 0.6 A
•for signal "1"minimum loadcurrent
5 mA 5 mA 5 mA 10 mA
•for signal "0"residual current,max.
0.5 mA 0.5 mA 0.5 mA 0.1 mA 0.5 mA
Switchingfrequency•with resistiveload, max.
100 Hz 1 000 Hz 100 Hz 100 Hz 100 Hz 100 Hz
•with inductiveload, max.
0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 2 Hz
•on lamp load,max.
10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz
Aggregatecurrent ofoutputs (pergroup)•horizontalinstallation
Page 996 Mar 2008 Siemens ITS
• up to 40°C, max.
4 A 4 A 4 A 1.6 A 1.6 A 4 A
• up to 60°C, max.
3 A 3 A 3 A 1.2 A 1.2 A 3 A
•verticalinstallation
• up to 40°C, max.
2 A 2 A 2 A 1.6 A 1.6 A 4 A
Total current ofthe outputs (permodule)•horizontalinstallation
• up to 60°C, max.
4.8 A 4.8 A
•all othermountingpositions
• up to 406.4 A 6.4 A
Page 997 Mar 2008 Siemens ITS
°C, max.Load resistancerange•lower limit 48 Ω 48 Ω 48 Ω 80 Ω 80 Ω 48 Ω•upper limit 4 kΩ 4 kΩ 4 kΩ 10 kΩ 10 kΩ 3 kΩCable length•Cable length,shielded, max.
1 000 m 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
•Cable lengthunshielded, max.
600 m 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/statusinformationAlarms•Diagnosticalarm
No No No No No Yes;Parameterizable
Diagnoses•Diagnostics No No No No No YesGalvanicisolationGalvanicisolation digitaloutputs•between the 8 8 8 16 16 8
Page 998 Mar 2008 Siemens ITS
channels, ingroups of•between thechannels and thebackplane bus
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
IsolationIsolationchecked with
500 V DC 500 V DC 500 V DC500 V DC 500 V DC500 V DC
Connectionmethodrequired frontconnector
20-pin 20-pin 40-pin Cable:6ES7 392-4Bxx0-0AA0terminalblocks:6ES7 392-1xN00-0AA0
Cable:6ES7 392-4Bxx0-0AA0terminalblocks:6ES7 392-1xN00-0AA0
20-pin
DimensionsWidth 40 mm 40 mm 40 mm 40 mm 40 mm 40 mmHeight 125 mm 125 mm 125 mm 125 mm 125 mm 125 mmDepth 120 mm 120 mm 120 mm 112 mm 112 mm 120 mmWeight
Page 999 Mar 2008 Siemens ITS
Weight, approx. 190 g 200 g 260 g 230 g 230 g 210 g
6ES7 322-5GH00-0AB0
6ES7 322-1CF00-0AA0
6ES7 322-1BF01-0AA0
6ES7 322-1FF01-0AA0
6ES7322-5FF00-0AB0
6ES7 322-1FH00-0AA0
SupplyvoltageLoadvoltage L+•Ratedvalue (DC)
24 V; 24 /48
48 V; 48 to125 V DC
24 V
Loadvoltage L1•Ratedvalue (AC)
230 V;120/230 VAC
230 V;120/230 VAC
230 V;120/230 VAC
Inputcurrentfrom loadvoltage L+(withoutload),max.
200 mA 2 mA 60 mA 2 mA
Page 1000 Mar 2008 Siemens ITS
from loadvoltage L1(withoutload),max.
2 mA 2 mA 3 mA
frombackplanebus 5 VDC, max.
100 mA 100 mA 40 mA 100 mA 100 mA 200 mA
PowerlossesPowerloss, typ.
2.8 W 7.2 W 6.8 W 8.6 W 8.6 W 8.6 W
DigitaloutputsNumber/binaryoutputs
16 8 8 8 8 16
Limitationofinductiveshutdownvoltage to
M (-1 V) L+ (-48 V)
Page 1001 Mar 2008 Siemens ITS
Lampload, max.
2.5 W 15 W; 15 W(48 V) or40 W (125V)
10 W 50 W 50 W 50 W
Outputvoltage•for signal"1", min.
L+ (-0.25 V)L+ (-1.2 V) L+ (-0.8 V) L1 (-1.5 V) L1 (-8.5 V)
Outputcurrent•for signal"1" ratedvalue
0.5 A 1.5 A 2 A 2 A 2 A 1 A
•for signal"1"permissiblerange for0 to 40°C, min.
10 mA 5 mA 10 mA 10 mA 10 mA
•for signal"1"permissiblerange for0 to 40
1.5 A 2.4 A 2 A 2 A 1 A
Page 1002 Mar 2008 Siemens ITS
•for signal"1"permissiblerange for0 to 40°C, max.
1.5 A 2.4 A 2 A 2 A 1 A
•for signal"1"permissiblerange for40 to 60°C, min.
10 mA 5 mA 10 mA 10 mA 10 mA
•for signal"1"permissiblerange for40 to 60°C, max.
1.5 A 2.4 A 1 A 1 A 0.5 A
•for signal"1"minimumloadcurrent
10 mA 5 mA 10 mA 10 mA 10 mA
•for signal 1.5 A; for 503 A; for 10 20 A; max. 20 A; with 2 20 A; with 2
Page 1003 Mar 2008 Siemens ITS
•for signal"1"permissiblesurgecurrent,max.
1.5 A; for 50ms, 1 A 2 sone-time
3 A; for 10ms
20 A; max.1 AC cycle
20 A; with 2half waves
20 A; with 2half waves
•for signal"0"residualcurrent,max.
10 µA 0.5 mA 0.5 mA 2 mA 2 mA 2 mA
Switchingfrequency•withresistiveload, max.
10 Hz 25 Hz 100 Hz 10 Hz 10 Hz 10 Hz
•withinductiveload, max.
0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
•on lampload, max.
0.5 Hz 10 Hz 10 Hz 1 Hz 1 Hz 1 Hz
Aggregatecurrent ofoutputs
Page 1004 Mar 2008 Siemens ITS
(pergroup)•horizontalinstallation
• upto40°C,max.
4 A 8 A 4 A
• upto60°C,max.
0.5 A; (8 Aper module)
4 A 2 A 4 A 2 A
•verticalinstallation
• upto40
4 A 2 A 4 A 2 A
Page 1005 Mar 2008 Siemens ITS
°C,max.
•all othermountingpositions
• upto40°C,max.
0.5 A; (8 Aper module)
Loadresistancerange•lowerlimit
12 Ω
•upperlimit
4 kΩ
Cablelength•Cablelength,shielded,
1 000 m 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
Page 1006 Mar 2008 Siemens ITS
max.•Cablelengthunshielded,max.
600 m 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/statusinformationAlarms•Diagnosticalarm
Yes;Parameterizable
No No No Yes;Parameterizable
No
Diagnoses•Diagnostics
Yes;Parameterscan beassigned
No No Yes Yes Yes
GalvanicisolationGalvanicisolationdigital
Page 1007 Mar 2008 Siemens ITS
outputs•betweenthechannels,in groupsof
1 4 4 4 1 8
•betweenthechannelsand thebackplanebus
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
IsolationIsolationcheckedwith
1500 V AC 1500 V AC 500 V DC 1500 V AC 1500 V AC 4000 VDC
Connection methodrequiredfrontconnector
40-pin 20-pin 20-pin 20-pin 40-pin 20-pin
DimensionsWidth 40 mm 40 mm 40 mm 40 mm 40 mm 40 mm
Page 1008 Mar 2008 Siemens ITS
Height 125 mm 125 mm 125 mm 125 mm 125 mm 125 mmDepth 120 mm 120 mm 120 mm 120 mm 120 mm 120 mmWeightWeight,approx.
260 g 250 g 190 g 275 g 275 g 275 g
6ES7 322-1FL00-0AA0
6ES7 322-1HF01-0AA0
6ES7 322-1HF10-0AA0
6ES7 322-5HF00-0AB0
6ES7 322-1HH01-0AA0
Supply voltageLoad voltage L+•Rated value (DC) 24 V 120 V 24 V 120 VLoad voltage L1•Rated value (AC) 120 V;
120/230 VAC
230 V 230 V 230 V
Input currentfrom load voltageL+ (without load),max.
110 mA;Currentconsumptionof relay
from load voltageL1 (without load),max.
10 mA 110 mA
Page 1009 Mar 2008 Siemens ITS
from backplanebus 5 V DC,max.
190 mA 40 mA 40 mA 100 mA 100 mA
Power lossesPower loss, typ. 25 W 3.2 W 4.2 W 3.5 W 4.5 WDigital outputsNumber/binaryoutputs
32 8; Relay 8; Relay 8; Relay 16; Relay
Lamp load, max. 50 W 50 W 1 500 W; 230V AC
1 500 W; 230V AC
50 W; 230 VAC
Output voltage•for signal "1",min.
L1 (-0.8 V)
Output current•for signal "1"rated value
1 A 2 A 5 A 5 A 2 A
•for signal "1"permissible rangefor 0 to 40 °C,min.
10 mA
•for signal "1"permissible rangefor 0 to 40 °C,max.
1 A
Page 1010 Mar 2008 Siemens ITS
•for signal "1"permissible rangefor 40 to 60 °C,min.
10 mA
•for signal "1"permissible rangefor 40 to 60 °C,max.
1 A
•for signal "1"minimum loadcurrent
10 mA 5 mA 5 mA 10 mA 10 mA
•for signal "1"permissible surgecurrent, max.
10 A; pergroup (for 2AC cycles)
•for signal "0"residual current,max.
2 mA
Switchingfrequency•with resistiveload, max.
10 Hz 2 Hz 2 Hz 2 Hz 1 Hz
•with inductiveload, max.
0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
•on lamp load, 1 Hz 2 Hz 2 Hz 2 Hz 1 Hz
Page 1011 Mar 2008 Siemens ITS
max.•mechanical, max. 10 Hz 10 Hz 10 Hz 10 HzAggregate currentof outputs (pergroup)•horizontalinstallation
• up to 40°C, max.
4 A
• up to 60°C, max.
3 A 5 A 5 A 8 A
•verticalinstallation
• up to 40°C, max.
4 A 5 A 5 A 8 A
Cable length•Cable length,shielded, max.
1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
•Cable lengthunshielded, max.
600 m 600 m 600 m 600 m 600 m
Relay outputs
Page 1012 Mar 2008 Siemens ITS
Rated inputvoltage of relayL+ (DC)
24 V; 110mA
24 V 24 V
Number ofoperating cycles
300 000; 230V AC:100000; 120V AC:200000; 24V DC:300000 (at 2A)
300 000;300000 (24V DC, at 2A); 200000(120 V AC,at 3 A);100000 (230V AC, at 3A)
100 000;100000 (24V DC, at 5A), 100000(230 V AC,at 5 A)
100 000;50000 (24 VDC, at 2 A);700000 (120V AC, at 2A); 100000(230 V AC,at 2 A)
Switching capacityof contacts•with inductiveload, max.
2 A; 2 A(230 V AC),2 A (24 VDC)
3 A; 3 A(230 V DC);2 A (24 VAC)
5 A; 5 A(230 V DC);5 A (24 VAC)
2 A; 2 A (230V AC), 2 A(24 V DC)
•Switchingfrequency/contacts/at ohmicload/maximum
2 A 8 A; 8 A(230 V DC);5 A (24 VAC)
5 A; 5 A(230 V DC);5 A (24 VAC)
2 A; 2 A (230V AC), 2 A(24 V DC)
Page 1013 Mar 2008 Siemens ITS
Interrupts/diagnostics/statusinformationAlarms•Diagnostic alarm No No No Yes;
Parameterizable
No
Diagnoses•Diagnostics Yes No No Yes NoGalvanic isolationGalvanic isolationdigital outputs•between thechannels, ingroups of
8 2 1 1 8
•between thechannels and thebackplane bus
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
Yes;Optocoupler
IsolationIsolation checkedwith
4000 VDC 1500 V AC 2000 V AC 1500 V AC 1500 V AC
Connectionmethodrequired front 20-pin 20-pin 40-pin 40-pin 20-pin
Page 1014 Mar 2008 Siemens ITS
connector
DimensionsWidth 80 mm 40 mm 40 mm 40 mm 40 mmHeight 125 mm 125 mm 125 mm 125 mm 125 mmDepth 117 mm 120 mm 120 mm 120 mm 120 mmWeightWeight, approx. 500 g 190 g 320 g 320 g 250 g