Why VAV?
Ryan R. Hoger, LEED AP
Single Zone Systems
ZC
ZONE 1
TMT TM TM
ZONE 2 ZONE 3 ZONE 4
ROOF
Heating/CoolingUnit
Heating/CoolingUnit
Heating/CoolingUnit
Heating/CoolingUnit
TM
2
Multiple Zone Systems
Why VAV?
• Comfort– Individual comfort controls
• Load Diversity– Different parts of the building require different loads during
the day• Energy Savings
– Improved part load performance• Design Flexibility
– Allow building to change throughout it’s life• Partial Operation
– Ability to cool or heat portions of the building
• Disadvantages?
3
VAV SystemSystemComponents:1. VAV RTU or AHU2. VAV Terminals
with Heating Coil3. Supply Diffuser4. Control Wiring5. Return Grille6. Zone Thermostat7. Supply Fan VFD8. Duct Static
Pressure Sensor9. Supply Duct
Zone 8 Zone 9 Zone 10
RTU or AHU
Variable Supply Constant Temperature Airflow
Return
g
Multiple Compression
Stages
T
Full-Face Active Cooling Coil
VAV unit operation is based on leaving air temperatureVFD Fan
ModulationSupply Air Temperature Sensor from Evaporator
Return Air Temperature
Reset
4
Zone Layout
INTERIOR ZONE
PERIMETER ZONE
Zone Layout
TTT
TTT
TTT
N
5
Zone Layout
VAV Rules• VAV is a cooling only system by definition
– 55 deg supply air needed year round to take care of interior cooling loads
– Do not expect AHU to provide heat during the day– Use AHU heat for morning warm-up sequence only– If high OA requirements, use AHU heat to bring discharge temp back up
to 55– Maybe be ok to reset cooling setpoint from 55 to 60 if zone average is
satisfied -never reset higher• Heat is handled at the zone level, as needed
– REPEAT: Do not expect AHU to provide heat during the day– Baseboard, radiant, or overhead (inside VAV box)– If heating from overhead, stay under 90 deg discharge or 25% extra OA
required per ASHRAE 62.1
6
VAV Rules (con’t)• Modulating cooling needed
– Unlike constant volume, cooling capacity control for VAV is based on supply air temp
– Need chilled water or variable speed compressors• Or several compression stages w/ HGB (6 stages or more is best, 4 at absolute
minimum)
• Variable capacity fans needed– As dampers shut down, static in duct builds, fan capacity needs to be
reduced– VFD most common method (older methods: IGV, DD, BPD, ride curve)– Control to static pressure 2/3 down the duct
• Variable exhaust needed– As fan speed changes, OA intake changes, and affects building
pressure, so building exhaust must be actively controlled– Control to building static pressure in hallway
Energy Savings• Diversity Credit
– Smaller equipment– Part load efficiency vs. on/off or even 2-stage cooling– Reduced compressor cycling
• Variable Frequency Drives (VFD)– Reduces fan horsepower– Affinity Laws
• Running at 75% CFM uses 42% of energy• Running at 50% CFM uses 12.5% of energy
• DDC w/ Supply Air Reset– Increases discharge air temp from 55 deg to a max of 60 on low load days to
reduce use of reheat in perimeter zones• DDC w/ Static Pressure Reset
– Reduces duct static pressure whenever possible– Looks at zone damper positions and if all zones are less than 80-90% open,
static is reset lower• DDC w/ CO2-based Demand Controlled Ventilation (DCV)
– Modulates OA damper below normal code minimum when less people are in the space
7
12 Types of VAV Boxes:
•Single Duct
•Single Duct w/Reheat
•Retro-fit Dampers
•Supply-Return tracking
•Dual Duct
•Parallel Fan Powered
•Series Fan Powered
•Low Profile Fan Powered
When to Use Single Duct Terminals
• Interior spaces– Where only cooling is required. Heating not
necessary due to climate, internal loads, and heating from perimeter areas.
• Perimeter with reheat– Cooling along outer walls with some small
reheat on the coldest days.• Interior with reheat to maintain ventilation
minimums• Supply return tracking
– Airflow measurement and control into and out of a laboratory space.
LMHS –Standard
Single Duct
8
When to Use Retro-Fit Single Duct Terminals
• Retrofitting old terminal units.– Mechanical constant volume dual duct dampers
for high pressure systems replaced with round retrofits for measuring and controlling airflow.
• Adding a control zone.– Round retrofits added to a round duct or slip-in
retrofits to a square duct to measure and control airflow in a new occupied zone monitored with room sensor.
• Replacing VVT-type zone dampers– Round or slip-in retrofits to replace existing high
pressure, high velocity zone controlled units with low pressure VAV units.
• As a return damper– Added to existing ductwork to measure and
control leaving airflow as required from controls.• As a bypass or ‘dump box’
– Installed at the end of a duct system to maintain relatively constant pressure at the air handler
Square Slip In Retro-Fit
Round Retro-Fit
When to Use Supply - Return Tracking
• Volumetric pressure control - Standard unit on supply, round unit on exhaust
• Stainless Steel construction available on exhaust unit
• Excellent low flow control is MANDATORY!• With several DDC systems, pressure control
logic is a standard configuration• Direct control of pressure requires door
interlock!
9
By-Pass Terminals
• Low pressure systems only• Requires balancing damper upstream
of unit• Bypass damper should be set so A/H
unit sees little change in pressure/airflow.Bypass
By-Pass Terminals
Bypass
PrimaryInletTo VAV’s for
Occupied Spaces
Excess Returned to Air Handler
or Dumped into Plenum
10
When to Use Dual Duct Terminals
• Perimeter Heating & Cooling– Allows air of required temperature as climate changes load.
• Positive Ventilation Control (measured ventilation to the zone)
– Allows volume of mixed air for ventilation requirements at temperature for comfort requirements.
• Laboratories / Constant Volume Applications– Allows constant volume of mixed air at needed comfort
temperature.• Supply / Return Tracking
– Can supply air of needed temperature at varying flow rates as ventilation changes.
• Underfloor Air Conditioning– Allows heating and cooling when both are available.
• Upstream vs. Downstream Flow Sensing Issues– Discharge sensor measures TOTAL heating and cooling
airflow for controls not set up to measure two different varying airflows.
LMHD – Non Mixing Dual Duct
LMHDT – Premium Mixing Dual Duct
Non-Mixing Dual Duct
l No Mixingl Two Single Duct Units
Joinedl S&D Dischargel Inlet Sensing Only
Standard Dual Duct
Std Single Ducts
Joining Strip
11
Premium Dual Duct
l Attenuated Dual Ductl Inlet or Total Discharge
Sensingl Unequal Inlet Size
Combinationsl S&D Discharge Nozzlel Mixing Baffle Standard
(20:1 Mixing Ratio)l Accurate discharge flow
sensing Premium Dual Duct
20:1 Mixing Ratio
50%(95oF)+50%(55oF) = 75oF
95oF-55oF= 40oF
40oF ÷ 20 = 2oF
+/- 1oF IN DISCHARGE
74 75 74 76
74 75 75 76
75 74 74 75
76 74 75 76
95oF
55oF
12
When to use fan powered terminals
• Perimeter Heating and Cooling– Unit can provide supplemental heat to plenum air
• Constant Volume Applications (Series)– Unit fan provides constant airflow with varying
temperatures.
• Variable Volume Applications (Parallel)– Unit provides variable primary airflow as required by
occupied zone temperature
• Interior Zones– Units can provide supplemental heat and provide
constant CFM and/or minimum airflow as required.
• Energy Concerns– Unit provides supplemental heat from warm plenum
air and may not require additional energy of heating cold primary air
QFC – Standard Fan Powered Terminal Unit
KQFS – Premium Fan Powered Terminal Unit
Series vs. Parallel Fan Boxes
SERIES FAN POWERED BOXES• Fan is on discharge of unit - all air
goes through the fan (primary airflow cannot exceed fan airflow)
• Fan runs at all times during occupancy• Fan must be started before primary air
is supplied (DDC logic?)• Note: there is no such thing as an “anti-
backward rotation device”.
• Radiated sound is critical sound application factor
13
Series Operation
Heating Only
Series Operation
Min Cooling Make-Up Heating
14
Series Operation
Cooling Only
Series Operation
1000 CFM FAN
1200 CFM PRIMARY
200 CFMLOST
Situation to Avoid:Short-circuiting can result in sub-cooling the plenum and loss
of control
IncorrectApplication
15
Series OperationConstruction Options
Standard Premium
Construction Highlights
Perf Baffle –Blocks Primary Noise
Blower Panel –Isolates Motor-blower
From Casing
Baffle-Blocks Noise From Escaping to Plenum Opening
Integral Attenuator –Additional Insulation Absorbs Sound
Attenuator Panel –Gives Additional Rigidity to Unit
Larger Cabinet –Allows low airflow
velocities and additional insulation
Standard
Premium
16
Series vs. Parallel Fan Boxes
PARALLEL FAN POWERED BOXES• Fan is in parallel with VAV damper• Fan airflow independent of primary
airflow• Fan only runs in heating mode• Fan is essentially first stage of heat• Backdraft damper is standard• Discharge sound is critical
application factor
Standard Parallel Operation
Cooling OnlyBack Draft
Damper Closed
17
Standard Parallel Operation
Heating OnlyBack Draft
Damper Open
Parallel Construction Highlights
Discharge Opening –Straight path for motor blower
Blower Panel –Isolates Motor Blower From Unit Casing
Integral Attenuator –Additional Insulation
Absorbs Noise
Blower Orientation-Wheel turned sideway away from plenum opening
Attenuator Panel –Gives Additional Rigidity to Unit
Larger Cabinet –Allows low airflow
velocities and additional insulation
QFVKQFP
18
Fan Box - Series vs. Parallel
Series Parallel
Fan Box - Series vs. Parallel Rules of Thumb
• Constant Volume = Series• Variable Volume = Parallel• Series Boxes
– Constant Fan Operation– Max Primary Airflow ≤ Fan Airflow
• Parallel Boxes– Fan is essentially 1st Stage of Heat– Fan Operates in Heating Mode Only– Fan Airflow ~ 40-60% Cooling Airflow (typically)
Note: There is no cure for a noisy fan box except to relocate or replace with quieter designClearly written specifications will reduce field issues
19
• The use of ECM motors can reduce the energy consumption of Fan Powered Terminals
• An ECM motor is a brushless DC motor, with an integral computer controlled inverter.
• At reduced rpm and load, an ECM motor can use as little as 60% of the energy of a standard Permanent Split / Capacitor Start (PSC) motor
• An ECM motor can be programmed to be pressure independent, resulting in true constant volume performance, easier balancing, and even DDC controlled performance.
• ECM motor has greater turn-down.
ECM MotorsPSC vs. ECM Motors
PSC vs. ECM
20
ECM Motor Controllers
ACU•CFM is adjustable
•0-10 dc Volt Signal from DDC Controls modulates Motor Speed.
Example
3.8 Volts = 38 Setting
VCU•CFM is constant
•CFM is set manually at the board with Fan Adjust Knob
•Board alternates display
•Fan Airflow Setting
•RPM
Air Flow Setting RPM Display
Some Cautions, however:• An ECM motor can add $250 to the purchase price of a Fan Powered Terminal.• Power consumption CAN be greater than an equivalent PSC motor, and the connected load requirement is usually higher because of this. • There are issues with the power factor of these types of devices which may cloud true energy savings.
ECM MotorsECM Motors
21
ECM vs. PSC for Fan Powered Box
2500 cfm Series Fan Box, ECM/PSC motor
0
25
50
75
100
0.00 0.20 0.40 0.60 0.80
Efficiency, Watts/cfm
% F
low ECM
PSC
Which Fan Box to choose?
• Standard• When acoustics is not an issue or• Fan Air flows are < 1200 CFM
• Quiet• When premium construction is
desired• When double wall is specified• For wider selection of inlet/fan
combinations• Low Profile
• Space is restricted and• Airflows < 1200 cfm
What Product to Use
•Clearly written specifications will reduce field problems
•There is no field cure for a noisy fanbox except to replace it with a quieter design.
22
• ½” thick 1.5lb dual density (Standard) • 1” thick 1.5lb dual density (drops 1 NC*)• Duct board with steel flanges (adds 7-10 NC*)• Double-Wall with 5 internal insulation options
– Solid metal (adds 12 NC*) – Perforated metal (adds 8 NC*)
• ½” or 1” thick foil faced fiberglass (Adds 7-10 NC*) • No liner (adds 12 NC*)• Cellular (adds 3-5 NC*)
– 3/8” standard– 3/4”now available on select single duct models
Up to 15 Lining Options
* Data for Premium Series Fan Box is shown above -the effect is not the same with all models.
Note: Not all programs show the effect of insulation options!
Sensor Options
• K4 LineaCross• Four quadrant center averaging• Good amplification for greater
turndown• Minimal increase in pressure drop• Barbed tubing connections
• Linear Probe• Two parallel averaging tubes• Installed diagonally across duct• No measurable pressure drop• No measurable additional sound
Both Give Equivalent Pressure Signals
23
Multi-Point Inlet Sensors
INLET SENSORFROM BEHIND
INLET SENSORFROM FRONT
Sensor BasicsStatic Pressure – The outward force of air within a duct, measured in inches of water column.Velocity Pressure – The forward moving force of air within a duct, measured in inches of water column.
Inlet Sensor Pressure Signal
2.0”
2.0”1.97”1.2”1.0”Example 1: ∆P = 2.0 – 2.0 = 0Example 2: ∆P = 2.0 – 1.97” = 0.03”Example 3: ∆P = 2.0 – 1.2” = 0.8”Example 4: ∆P = 2.0” – 1.0” = 1.0”
24
Minimum/Maximum Airflows
l Airflows for ‘Standard’ controls below minimums shown cannot be guaranteed to be maintainable “uncontrollable range”
l Maximums based on 1.0” W.G. differential pressure
l Minimums based on 0.03” W.G. differential pressure
LMHS UnitsMax. Primary
inlet size Airflow - CFM Standard* Electric Heat**4 230 40 555 360 62 856 515 89 1107 700 121 1408 920 159 1909 1160 201 240
10 1430 248 30012 2060 357 42514 2800 486 58016 3660 634 750
24 x 16 7000 1212 1800
Min Airflow, CFM
• 1 to 4 row for single duct• 1 to 2 Row for fan powered
– Fan powered terminals need less rows because they heat a mixture of warm plenum air and primary air
• Left or Right Hand Piping Connections• Access Panels to clean water coil supply
side
Hot Water Coil Features
25
Electric Reheat Features
CAUTION: 480 3-Phase 3-Wirel Special for Single Ductl Must have Dual Point
Source for Fan Box
• 120/208/240/277 single phase • 208/3 phase (3-wire), 480/3 phase (4-wire) • 1-3 Stages (most types)• Side access - Leave clearance per NEC• Operation at minimum airflow is unlikely to provide comfort• Consider proportional electric heat with discharge temperature
control for maximum comfort
Patented LineaHeat Control:• Solid State Relay (SSR) vs. SCR
– Allows use of less expensive versions of DDC controllers (as much as $100 less)• Up to 4 VAV manufacturers offer SSR control now• Infinite adjustment (0 – 100%)• Low cost• Silent operation• Optional discharge temperature control• 7 different control inputs
Proportional Electric Reheat
26
LineaHeat Control input types:• LX1 – 1 step heater (PWM) - {24Vac Pulse from Controls}• LX2 – 2-stage heat• LX3 – 0-10 Volt / 0-20mA signal – {Common Control Function}• LX4 – 2-10 Volt / 4-20mA signal• LX5 – Thermostat (incremental) – {Mirrors a NC Water Valve}• LX6 – Binary (1, 2, or 1 & 2 stages)• LX7 – Three Point Floating – {Mirrors a 24Vac 3 point Water
Valve}
Proportional Electric Reheat
• Empty Enclosure (Field Mounting)• Pneumatic • Analog• DDC• Transformers
Control Options
l Many Control Options
l Library of current DDC wiring diagrams for factory mounting
27
VAV Terminals
POORLY ADJUSTED / SELECTED DIFFUSER
THERMOSTAT
Air Distribution, Poor Pattern Example
VAV Terminals
Air Distribution, Poor Pattern Example
THERMOSTAT
POORLY ADJUSTED / SELECTED DIFFUSER
28
VAV Terminals
PROPERLY ADJUSTED DIFFUSER
THERMOSTAT
Good Pattern Example
VAV Terminals
Perimeter Considerations:
• Maximum delta-t for effective mixing when heating, per ASHRAE handbook = ?.
• = 15°F (90°F discharge), continuous operation.
• Throw toward and away from glass.• 150 FPM should reach 4-5 feet from the
floor.• ASHRAE 62.1 requires that ventilation be
increased by 25% when heating, if the above rules are not followed.
• Typical perimeters require only 8°Fdelta-t @ 1 cfm/sq.Ft.