Single phase transformer
-
Upload
ritu-rajan -
Category
Engineering
-
view
1.004 -
download
5
description
Transcript of Single phase transformer
Single Phase Transformer
Prepared By:
RITU K.R.
Assistant Professor (EE)
SISTec-E1
SISTec-e 2
Coil 1
i1(t) i2(t)
Coil 2
M
e1(t) e2(t)
S1 S2i1(t) i2(t)
The Transformer
(Primary has N1 turns) (Secondary has N2 turns)
V2
SISTec-e 3
Transformer Construction
Left: Windings shown only on one legRight: Note the thin laminations
SISTec-e 4
Transformer Construction
SISTec-e 5
• The source side is called Primary • The load side is called Secondary
• Ideally
1. The resistance of the coils are zero.
2. The relative permeability of the core in infinite.
3. Zero core or iron loss.
4. Zero leakage flux
The Transformer
SISTec-e 6
The Transformer
i) Switch ‘S1’ is closed and ‘S2’ is open at t=0
The core does not have a flux at t=0
The voltage induced across each coil is proportional to its number of turns.
SISTec-e 7
The Transformer
ii) Switch ‘S2’ is now closed
A current now starts to flow in resistance R. This currentis i2(t) (flows out of the dotted terminal).
R
)t(2V
R
)t(e)t(i 2
2
Thus a MMF N2i2(t) is applied to the magnetic circuit. This will immediately make a current i1(t) flow into the dot of the primaryside, so that N1i1(t) opposes N2i2(t) and the original flux in the core remains constant. Otherwise, N2i2(t) would make the core flux change drastically and the balance between V1 and e1(t) will be disturbed.
8
The Transformer
Observation: It was shown that the flux in the core ism Sin(t). Since the permeability of the core is infinite ideallyzero current can produce this flux! In actuality, a current Im, knownas magnetizing current is required to setup the flux in the transformer. This current is within 5% of the full load current ina well designed transformer.
21
11
;1 N
LL
rmsVIm
L1 is the primary side self inductance.
SISTec-e 9
Polarity (dot) convention
Terminals of different windings are of same polarity if currentsentering (or leaving) them produce flux in the same direction in the core.
SISTec-e 10
How to check polarity?
1) Measure e12 and e34
2) Connect 2 and 4 and measure e13
3) If e13= e12+e34, 1 and 4 have same polarity
4) If e13= e12-e34, 1 and 4 have different polarity
The transformer’s equivalent circuit
To model a real transformer accurately, we need to account for the following losses:
1.Copper losses – resistive heating in the windings: I2R.2.Eddy current losses – resistive heating in the core: proportional to the square of voltage applied to the transformer.3.Hysteresis losses – energy needed to rearrange magnetic domains in the core: nonlinear function of the voltage applied to the transformer.4.Leakage flux – flux that escapes from the core and flux that passes through one winding only.
SISTec-e 12
Transformer Equivalent Circuit
The Exact Equivalent Circuit Of A Real Transformer
The transformer’s equivalent circuit
However, the exact circuit is not very practical.
Therefore, the equivalent circuit is usually referred to the primary side or the secondary side of the transformer.
Equivalent circuit of the transformer referred to its primary side.
Equivalent circuit of the transformer referred to its secondary side.
Approximate Equivalent Circuit Of A Transformer
For many practical applications, approximate models of transformers are used.
Referred to the primary side.
Without an excitation branch referred to the primary side.
Referred to the secondary side.
Without an excitation branch referred to the secondary side.
The values of components of the transformer model can be determined
experimentally by an open-circuit test or by a short-circuit test.
SISTec-e 15
Open circuit Test
•It is used to determine Lm1 (Xm1)and Rc1
•Usually performed on the low voltage side
•The test is performed at rated voltage and frequency underno load
Open Circuit TestFinds Iron Losses
(Fe)
Full Supply Voltage
SecondaryOpen Circuit
Wattmeter indicates Iron Losses (Fe)
16
SISTec-e 17
Short circuit Test
•It is used to determine Llp (Xeq) and Rp(Req)
•Usually performed on the high voltage side
•This test is performed at reduced voltage and rated frequency with the output of the low voltage winding short circuited such that rated current flows on the high voltage side.
Short Circuit TestCopper Losses
(Cu)
SecondaryShort
Circuited
Limited
Supply Voltage ≈ 5-10 %
Wattmeter indicates Copper Losses (Cu)
18
SISTec-e 19
Transformer Regulation
•Loading changes the output voltage of a transformer.Transformer regulation is the measure of such a deviation.
Definition of % Regulation
100*|V|
|V||V|
load
loadloadno
Vno-load =RMS voltage across the load terminals without load
V load = RMS voltage across the load terminals with a specifiedload
SISTec-e 20
Maximum Transformer Regulation
1212
1
011
02
'2
0'21
;0
max
.0
eqeq
eqeq
or
whenimumisVClearly
ZIVV
SISTec-e 21
Transformer Losses and Efficiency•Transformer Losses
•Core/Iron Loss =V12 / Rc1
•Copper Loss = I12 R1+ I2
2 R2
Definition of % efficiency
100*222
222
CosIVLosses
CosIV
100*/ 2222
221
211
21
222
CosIVRIRIRV
CosIV
c
2Cos = load power factor
100*/ 2222
221
21
222
CosIVRIRV
CosIV
eqc
Transformer Losses
Copper Losses (Cu)
•Varies with load current
•Produces HEAT •Created by resistance of windings
•Short circuit test supplies copper losses
22
Transformer LossesIron Losses
(Fe)•Fixed
•Always present
•Related to transformers construction
Eddy Currents
Reduced by laminations
Produces HEAT
Hysteresis
Reduced by using special steels in laminations
23
Efficiency
PowerInputPowerOutput
η
LossesOutputInput
LossesPowerOutput
PowerOutputη
Ratio between Input power and Output Power
PowerInputLossesPowerInput
η
24
Transformer Efficiency
PowerIn
PowerOut
OvercomeIron
Losses
Overcome Copper Losses
Some Poweris used to:
η = 100%
25
SISTec-e
SISTec-e 26
Maximum Transformer Efficiency
The efficiency varies as with respect to 2 independent quantitiesnamely, current and power factor•Thus at any particular power factor, the efficiency is maximum if
core loss = copper loss .This can be obtained by differentiating theexpression of efficiency with respect to I2 assuming power factor, andall the voltages constant.
•At any particular I2 maximum efficiency happens at unity power factor.This can be obtained by differentiating the expression of efficiency with respect to power factor, and assuming I2 and all the voltages constant.
•Maximum efficiency happens when both these conditions are satisfied.
SISTec-e 27
100
0
% full load current
pf=1
pf= 0.8
pf= 0.6
At this load currentcore loss = copper loss
Maximum efficiency point
All Day Efficiency
• Most Transformers are connected permanently
• The time that the transformer has to be calculated when determining efficiency
• Able to determine the best transformer for the
application by its efficiency
28SISTec-e
All Day EfficiencyTransformer A
Sout = 300 kVA Fe = 1.25 kVA Cu = 3.75 kVAHours Load kW kWh % Load Cu Loss Cu kWh Fe kWh Losses kWh Input kWh
1.00 6.00 5 100 500.0 33.33 0.42 2.08 6.25 8.33 508.336.00 7.00 1 200 200.0 66.67 1.67 1.67 1.25 2.92 202.927.00 8.00 1 300 300.0 100.00 3.75 3.75 1.25 5.00 305.008.00 9.00 1 360 360.0 120.00 5.40 5.40 1.25 6.65 366.659.00 12.00 3 300 900.0 100.00 3.75 11.25 3.75 15.00 915.0012.00 14.00 2 280 560.0 93.33 3.27 6.53 2.50 9.03 569.0314.00 18.00 4 300 1200.0 100.00 3.75 15.00 5.00 20.00 1220.0018.00 20.00 2 360 720.0 120.00 5.40 10.80 2.50 13.30 733.3020.00 22.00 2 280 560.0 93.33 3.27 6.53 2.50 9.03 569.0322.00 1.00 3 200 600.0 66.67 1.67 5.00 3.75 8.75 608.75
5900.0 5998.02
98.37
Time Period
P out kWh = P in kWh =
% Eff =29SISTec-e
Thank You
30