SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large...
Transcript of SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large...
![Page 1: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/1.jpg)
1
SIMULATION OF THE RESPONSE OF A HYBRID BASE-ISOLATED
BUILDING DURING PUSH AND QUICK-RELEASE TESTS
Giuseppe OLIVETO1 and Anastasia ATHANASIOU
2
ABSTRACT
In the early spring of 2013, in the town of Augusta in eastern Sicily, a newly built reinforced concrete
commercial building, equipped with a hybrid base isolation system, was subjected to several push and
quick-release tests. The objectives of the tests were the evaluation of the performance of the base
isolation system and the verification of the design expectations. In order to conduct the tests without
excessive risk, a blind simulation of the same was performed beforehand by Oliveto et al. (2013). In
this simulation, the response of the isolation system was evaluated first by considering the
superstructure rigid, and then the obtained base motion was imposed to the superstructure to estimate
the complete response. Later, Oliveto and Athanasiou (2013) extended the Mixed Lagrangian
Formulation used in the previous model to simultaneously account for the flexibility of the
superstructure and the non-linear behaviour of the base isolation system. This new model is used
herein to simulate the push and quick-release tests performed on the Augusta building and to compare
the results with the experimental ones. The properties for the isolation system considered in the
performed simulations are obtained from the identification of the release tests. The experimental
records obtained during the loading phase of the tests, are used for the identification of the properties
of the isolators under quasi-static conditions.
INTRODUCTION
Seismic risk is a real threat for the countries of the Southern and Eastern European zone. One of the
most popular passive vibration techniques implemented nowadays in Europe for the reduction of
earthquake risk is base isolation. Base, or seismic isolation finds application in a large class of
structures of major or minor importance, such as hospitals, bridges, residential buildings, artefacts etc.
Its concept is simple and lies in the decoupling of motion between the substructure and the
superstructure through the interposition of elements of low stiffness. Structures constructed on firm
soils, where far-fault motion events are expected to occur, are favourable for implementations of the
method. This study considers a residential building in the city of Augusta, Italy, designed to withstand
seismic action by means of a hybrid base isolation system. Before being put into use, the building was
subjected to a series of free vibration tests. The release tests were performed in low amplitudes to
ensure that no damage would occur in the building. A preliminary simulation of the system response
of the building under the tests can be found in (Oliveto et al., 2013). The experiments provided a huge
amount of information that give light to the nonlinear behaviour of the isolation system under real-
time motions. Herein the output of the tests is used for the assessment of the isolation system and the
validation of the existing models that are used to simulate the dynamic response of the structure.
1 Professor, University of Catania, Catania, [email protected]
2 Graduate student, University of Catania, Catania, [email protected]
![Page 2: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/2.jpg)
2
THE AUGUSTA BUILDING
The Augusta building consists of a basement, two storeys above the ground level and a penthouse. The
foundation rests on site of class B according to the Italian technical regulations, that are in line with
Eurocode8 (D.M. 2008). The dimensions of the plan are 35.70 m x 16.00 m, the maximum height
above the ground level is 10.50 m and the basement storey height is 3.60 m. The isolation plane runs
along the top of the pillars of the basement storey slightly above the ground level and is composed by
16 High Damping Rubber Bearings (HDRB) and 20 Low Friction Sliding Bearings (LFSB).
According to the design the isolation period of the structure is Tis= 2.38s, while the displacement
demand for the isolation system at the collapse prevention limit state is ddc= 269 mm (Oliveto et al.,
2013). A picture of the building exterior and a plan view of the isolation system are shown in Fig.1.
The properties of the isolators shown in Fig.1(b) are given in Table 1.
Table 1. Technical requirements for the seismic isolators
High Damping Rubber Bearings (HDRB) Low Friction Sliding Bearings (LFSB)
Vertical load in seismic condition 1000 kN Load Displacement
Damping ratio at γ=1 ξ =15% 2000kN 300mm
Secant horizontal stiffness at γ =1 Ke = 1000 kN/m 1500kN 300mm
Vertical stiffness Kv > 800Ke 250kN 300mm
Horizontal displacement at γ =2 dc = 300 mm
a) b)
Figure 1. a) Exterior of the Augusta building and b) plan view of the hybrid isolation system
The HDRB isolators were produced by FIP Industriale S.p.A. with the following characteristics:
total bearing height 312 mm, external diameter 500 mm, bonded diameter 480 mm, total rubber
thickness 25×6 mm = 150 mm, steel height 24×3 mm= 72mm, end plates 2×20 mm = 40 mm. The
multidirectional VASOFLON bearings produced by the same industry (LFSB) are characterized by
maximum loading capacities that vary from 250 to 2000 kN, Table 1. The manufacturer provided also
a series of data obtained from static and dynamic laboratory tests performed on HDRB and LFSB
prototypes. These data were used earlier for the identification of the HDRB properties (Oliveto et al.,
2013).
A bi-linear model is adopted for the description of the HDRB constitutive behaviour; this model
is used commonly in research and engineering practice for the description of the nonlinearity of the
rubber bearings (Kelly and Naeim, 1999). Three parameters are needed for the definition of the bi-
linear model: the elastic stiffness k0, the post-elastic stiffness k1 and the characteristic strength Q,
Fig.2(a). The properties of the rubber bearings, as identified from the acceptance tests provided by the
manufacturer, are shown in Table 2. It can be noticed how the values for k0, k1 and Q are significantly
larger when the tests are performed under dynamic conditions. All tests refer to a maximum shear
strain of 1. In the same table, the static and dynamic friction coefficients provided by FIP for the three
classes of LFSB are shown. The Constant Coulomb Friction Model (CCFM) is considered herein for
the description of the constitutive F-u behaviour of the friction sliders, Fig.2(b), where Ff0=μ·N, μ is
the friction coefficient and N the axial load acting on the bearing.
![Page 3: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/3.jpg)
G.Oliveto and A.Athanasiou 3
Table 2. Mechanical properties of the isolators, as identified from the available laboratory tests
HDRB LFSB
at γ = 1 Static test 1 Static test 2 Dynamic test 1 Dynamic test 2 Axial load μst (%) μdyn (%)
k0 (kN/m) 3509 3521 5413 6199 0.50Vmax 0.30 0.15
k1 (kN/m) 658 708 802 847 0.75Vmax 0.175 0.10
Q (kN) 27 28 37 40 Vmax 0.15 0.09
Figure 2. F-u constitutive model for a) the rubber bearing and b) the friction slider
FREE VIBRATION TESTS
Ten free vibration tests were performed on the seismically isolated building of Augusta in late March
2013. During the tests the building was displaced statically from its initial position and then was left to
oscillate. The initial displacements varied in the range 50-100 mm (γ=0.40-0.80). The loading device
consisted of a reaction wall, a hydraulic jack, a sudden release device and a load cell and was the same
one used in a previous set of free vibration tests that took place in the city of Solarino, Italy, in 2004
(Oliveto et al., 2004). The loading velocity during the pushing phase was of the order of 6mm/min.
The experimental results include the histories of the loading force, displacements and
accelerations. The horizontal displacements were measured at various positions below and above the
isolation level through 15 channels, while the horizontal and vertical accelerations were measured at
the various floor levels using 16 channels. The displacement curves of Fig. 3 show the deformation
histories of the rubber bearings 8 and 25, Fig. 1(b), for the free vibration tests 4 and 10. During test 4,
the building was displaced statically by 68 mm applying a maximum load of 1305 kN. In the free
vibration phase, the system completed one full cycle of motion before coming to rest with a residual
displacement of the order of 8 mm (8.8 mm for rubber bearing 25 and 8.3 mm for rubber bearing 8),
Fig. 3 (a). The residual displacements were slightly larger in test 10, where an initial displacement of
a) b)
Figure 3. Deformation histories for HDRB 8 and 25, a) during test 4 (u0=68mm) and b) test 10 (u0=100mm)
460 470 480 490 500 510 520-10
0
10
20
30
40
50
60
70
80
t [s]
uR
B [
mm
]
Test 4 [ u0 = 68 mm, = 0.45 ]
RB-25
RB-8T=1.7 s
ur=8.8 mm
ur=8.3 mm
1040 1045 1050 1055 1060 1065 1070 1075-10
0
20
40
60
80
100
120
t [s]
uR
B [
mm
]
Test 10 [ u0 = 100 mm, = 0.67 ]
RB-25
RB-8T=1.9 s
ur=13.4 mm
ur=13.7 mm
![Page 4: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/4.jpg)
4
a) b)
Figure 4. Longitudinal floor acceleration records, a) for test 4 (u0=68mm) and b) test 10 (u0=100mm)
a) b)
Figure 5. Fourier amplitude spectra of the longitudinal accelerations measured during tests 4 (black line)
and 10 (red line), a) at the various floors and b) the foundation
100 mm under a static load of 1597 kN was applied, Fig. 3(b). The residual displacements occur due to
the non-linearity of the isolation system. A simple re-centring mechanism was set up so that in the end
of each dynamic test the building was re-centred to the initial, zero displacement, equilibrium position.
The damped period of vibration for the system can be estimated from the displacement response
histories; that would be T = 1.7 s for test 4 and T = 1.9 s for test 10.
The longitudinal acceleration histories, measured during tests 4 and 10 at the basement and the
superstructure, are shown in Fig. 4. The beneficial effect of base isolation is straightforward; de-
amplification of motion is observed along the superstructure height. The record at the roof seems to be
somewhat important, including some low frequency content, probably due to the irregularity of the
structure in height and to the low stiffness of the last storey, Fig. 1. Comparing the signals obtained
from the two tests it becomes clear that the higher is the initial displacement, the higher are the
acceleration amplitudes and the longer is the period of vibration. The Fourier amplitude spectra of the
acceleration signals shown in Fig. 4, are given in Fig. 5(a). The Fourier spectrum amplitudes of the
accelerations recorded on the ground floor (just above the isolation plane) and on the upper floors are
very similar in the neighbourhood of the fundamental isolation frequency; that is approximately equal
to fis = 0.60 Hz for test 4. The following peaks, located in the higher frequency range, correspond to
the superstructure’s modes. The dominant frequencies and corresponding Fourier spectrum
amplitudes, obtained from the Fourier analysis of the acceleration signals of test 4 are shown in Table
3. It is interesting to notice that the ground floor and the first floor spectra have a relatively sharp peak
at the frequency of 32 Hz. This high frequency is less important for the second floor acceleration
response and absent in the roof signal. A comparison between the spectra of tests 4 and 10, confirms
the previous observations that larger initial displacements result to larger amplitudes and shift of the
463 464 465 466 467-0.3
0
0.4
a (
g) roof0.21 g
463 464 465 466 467-0.3
0
0.4
a (
g) 2
nd floor0.16 g
463 464 465 466 467-0.3
0
0.4
a (
g) 1
st floor0.20 g
463 464 465 466 467-0.3
0
0.4
a (
g) ground floor0.34 g
463 464 465 466 467-0.3
0
0.4
t (s)
a (
g) basement0.07 g
1052 1053 1.054 1055 1056 1057-0.3
0
0.4
a (
g) roof0.26 g
1052 1053 1054 1055 1056 1057-0.3
0
0.4
a (
g) 2
nd floor0.18 g
1052 1053 1054 1055 1056 1057-0.3
0
0.4
a (
g) 1
st floor0.26 g
1052 1053 1054 1055 1056 1057-0.3
0
0.4
a (
g) ground floor0.37 g
1052 1053 1054 1055 1056 1057-0.3
0
0.4
t (s)
a (
g) basement0.08 g
1 10 100 2500
2
4
f (Hz)
[cm
/s]
basement
1 10 100 2500
10
20
[cm
/s]
ground floor
1 10 100 2500
10
20
[cm
/s]
1st
floor
1 10 100 2500
10
20
[cm
/s]
2nd
floor
1 10 100 2500
10
20roof
[cm
/s]
f (Hz)
1 10 100 2500
0.5
1
1.5
2
2.5
3
3.5
4
f (Hz)
[cm
/s]
test 4 (u
0=68 mm)
test 10 (u0=100 mm)
![Page 5: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/5.jpg)
G.Oliveto and A.Athanasiou 5
Table 3. Dominant frequencies and corresponding Fourier spectrum amplitudes,
obtained from the Fourier analysis of the acceleration signals of test 4
Ground floor 1st floor 2nd floor Roof
fmax (Hz) Smax (cm/s) fmax (Hz) Smax (cm/s) fmax (Hz) Smax (cm/s) fmax (Hz) Smax (cm/s)
0.61 10.19 0.61 10.39 0.61 10.55 0.61 10.55
6.59 6.48 6.71 1.40 6.47 4.07 6.59 8.00
13.79 2.06 13.67 2.36 13.79 2.42 13.67 3.22
- - 19.41 2.86 19.53 1.67 19.04 1.49
31.98 6.96 32.23 3.68 32.23 2.52 - -
fundamental frequency to the left. Fig. 5(b) is an enlargement of the Fourier spectrum of the
longitudinal acceleration recorded at the foundation, shown in the last subplot of Fig. 5(a). The Fourier
spectrum of the foundation response has a sharp peak in the proximity of 7 Hz, significantly above the
isolation frequency, justifying why there was no amplification of motion at the basement during the
tests.
BEHAVIOUR OF ISOLATORS UNDER THE STATIC PHASE OF TESTS
The quasi-static force-displacement curves obtained during the loading phase of the free field tests are
used herein for the identification of the mechanical properties of the isolators. The constitutive
behaviour of the HDRB is described by the bi-linear model shown in Fig. 2(a). For the LFSB, an
elastic-perfectly plastic model is considered; the initial stiffness k0f of the elastic branch accounts for
the fact that the friction force doesn’t reach instantaneously its breakaway value ff0. Although there are
three classes of sliders, all sliders are assigned the same coefficient of friction. The axial load N acting
on the three groups of LFSB is considered equal to N= 750 kN, 900 kN, 25 kN resulting to an overall
vertical load Ntotal =13900 kN=0.58W=0.52Nmax, where W=24000 kN is the weight of the superstructure
as evaluated for the building design and Nmax is the maximum axial load that could act on the sliding
bearings accordingly to their load capacities. These N values were evaluated by the designer
considering the building conditions under the experiments.
The identification process is performed using the Covariance Matrix Adaptation Evolution
Strategy (CMA-ES). The CMA-ES is an non-elitist continuous domain evolutionary algorithm used
for difficult non-linear, non-convex optimization problems in continuous domain (Hansen, 2011). In
each generation the algorithm generates λ candidate solutions xi, which are then evaluated according to
the objective function e2, i.e. the function to be minimized. The sampled solutions are re-ordered
according to their value (fitness). At the end of each generation the (λ-μ) worst solutions are discarded,
while the μ best ones are used for the update of the internal state variables and the sampling of the new
population. Over the generations the search is oriented towards solutions of minimum fitness. The
optimization is terminated when there is no more improvement in the fitness function.
In the present case the candidate solution vectors xi include the properties (k0, k1, Q, k0f, μ) of the
isolators. For each set of feasible solutions the static force-displacement curves (F-u)sim are produced
according to the constitutive laws of the bi-linear and the elastic-perfectly plastic model. The
simulated curves are then compared to the experimental curves (F-u)exp. The static experimental
curves are fitted using a 10th order polynomial in order to remove the noisy content (function polyfit,
MATLAB 2013). The fitness or error function is defined as the normalized distance between
simulated (Fsim) and experimental data (Fexp):
2
2
2
exp
exp
sime
F F
F
.
The identification process was performed 10 times on each set of static F-u data available,
Fig. 6(a). The results for the most successful run, in terms of fitness, per set of data (release test) are
given in Table 4. The tests are ordered according to increasing maximum imposed shear strain γ. The
mean value and coefficient of variation (c.o.v.) for the ten identified system parameters are given in
the last two columns of Table 4. The average of the identified static laboratory values for k0, k1, Q,
![Page 6: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/6.jpg)
6
Table 4. Mechanical properties of the isolators,
as identified from the static loading force–displacement Augusta records
test 1 test 3 test 4 test 2 test 10 test 8 test 9 test 5 test 6 test 7 lab mean c.o.v.
γ 0.40 0.44 0.45 0.61 0.67 0.68 0.68 0.73 0.78 0.79 1.0
k0 (kN/m) 1396.1 4292.5 1253.3 1298.6 1140.1 3053.4 1127.6 2445.6 1227.5 1228.3 3515 1846.3 0.58
k1 (kN/m) 945.2 966.9 857.6 896.1 773.9 852.3 757.1 879.3 806.9 810.8 683 854.6 0.08
Q (kN) 7.4 20.0 11.9 11.4 12.8 21.9 13.2 18.1 12.5 12.9 27.5 14.2 0.31
k0f (kN/m) 8808.5 61916.7 3398.9 4874.0 1707.4 3891.6 2377.7 36891.6 2008.6 1867.9 - 12774.3 1.59
μ (%) 1.46 0.60 1.51 2.00 1.20 0.27 1.50 0.42 1.50 1.24 - 1.17 0.48
e2 (E-04) 1.4 8.0 1.4 2.8 1.4 3.0 2.0 2.7 1.4 0.91 -
a) b)
Figure 6. a) Static loading force – displacement curves for the tests of Augusta and
b) comparison between fitted experimental and identified F-u curves for test 8 (Fmax=1792 kN, u0=103 mm)
Figure 7. Comparison of the 3rd
cycle static laboratory data and the identified F-u curves
a) for tests 1-5 and b) tests 6-10
shown in Table 2, are provided herein to facilitate the comparison between identified laboratory and
field data.
It can be seen how the CMA-ES yielded solutions of minimum fitness of the order of 10-4
,
resulting to a very good matching between experimental and identified data, Fig. 6(b). However, as
seen from Table 4, the identified properties of the isolators vary significantly from test to test. The
initial stiffness of the friction model k0f is the variable with the largest scatter (c.o.v.=1.59), while the
post-elastic stiffness of the bi-linear spring k1 is the one with the smallest one (c.o.v.=0.08).
Comparing the obtained results with the available static laboratory data, it can be seen how the
identified parameters k0 and Q are significantly lower than the corresponding laboratory ones with
differences reaching -73%. k1 results generally greater than its static laboratory value, the maximum
difference being 42%; however this could be due to the smaller shear strains experienced during the
0 25 50 75 100 125 1500
500
1000
1500
2000
u [mm]
F [
kN
]
test 1
test 2
test 3
test 4
test 5
test 6
test 7
test 8
test 9
test 10
[ ]0 0.330.17 0.50 0.67 0.83 1
0 25 50 75 100 125 1500
500
1000
1500
2000
u [mm]
F [
kN
]
fitted record, test 8
identified record
[ ]0 0.330.17 0.50 0.67 0.83 1
![Page 7: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/7.jpg)
G.Oliveto and A.Athanasiou 7
field tests (γ =0.40-0.80). In fact, the identified values for k1 show a decreasing trend with increasing
shear strain γ. All static and dynamic laboratory tests were performed at γ=1. The 10 identified bi-
linear models for the HDRB are compared against the 3rd
cycle static laboratory data in Figs 7(a) and
(b). Tests 6 and 7 and tests 9 and 10 yielded similar results, therefore the corresponding curves cannot
be distinguishable in the scale of Fig. 7(b).
The coefficient of friction μ takes a minimum value of 0.27% for test 8 and a maximum value of
2 % for test 2, Table 4. Under a similar axial load of 0.50Nmax, the static and dynamic coefficients of
friction provided by the manufacturer are significantly smaller, 0.30% and 0.15% respectively, Table
2.The majority of data (tests 1, 4, 6, 7, 9, 10) provided values of μ coherent with the ones found from
the Solarino experiments (Oliveto et al., 2010). μ tends to take lower values when k0 and Q are higher
and vice versa; see for instance tests 8, 9 and 10.
The identification was repeated in a narrow domain to ensure that the isolator properties would
not vary more than 10% from the laboratory data. That operation resulted to worse results in terms of
fitness function and curve matching; hence those results are not shown herein. It should be mentioned
that the identification procedure provides the parameters that minimize the considered fitness function.
Those parameters, while satisfying the mathematical problem, do not necessarily match the physics of
the problem.
IDENTIFICATION OF THE 1D ISOLATION SYSTEM
In the following the deformation histories of the rubber bearings 25 and 8 obtained from tests 4 and
10, Figs 3(a) and (b), are used for the identification of the isolation system properties. For the purposes
of the identification a simple 1D model is adopted for the structure. The superstructure is considered a
rigid block; this assumption is reasonable given the similarity of the Fourier amplitude spectra of the
superstructure’s floor acceleration records, Fig. 5(a). The Augusta HBIS is symmetrical with respect to
the short (y) axis, while not symmetrical with respect to the long (x) axis due to the presence of the
four sliding bearings under the elevator. However during the tests no significant transverse records
were observed and hence the response to a 1D excitation along the x direction is expected to be
unidirectional and can be adequately predicted by the 1D model. The mechanical system considered
herein is shown in Fig. 8. The bi-linear spring and the viscous damper together account for the HDRB,
while the plastic slider accounts for friction in the LFSB. The friction law is described by the CCFM,
shown in Fig. 2(b). All HDRB are of one class, and hence have the same properties. The same
coefficient of friction is assigned to all the LFSB. Hence, the system parameter vector to be identified
includes the mass m of the structure, the 3 properties (k0, k1, Q) of the bi-linear spring, the coefficient
of friction of the sliders μ and the damping ratio ζ describing the linear viscous damper.
Figure 8. Mechanical model for the isolation system
20 runs of CMA-ES were performed. In runs 1-10 the input for the identification were the
displacement records of test 4, while in runs 11-20 input were the displacement records of test 10. The
system response was simulated using the 1D Mixed Lagrangian Formulation (Oliveto et al., 2014).
The Mixed Lagrangian Formulation (MLF) is an algorithm developed for the simulation of the
dynamical response of base isolated buildings. The MLF is an energy formulation of the dynamic
problem; the governing equations are derived by setting the first variation of an appropriate Hamilton's
action integral to zero introducing suitable Lagrangian and dissipation functionals. The time step
solution is provided in the form of a constrained non-linear optimization problem. The reliability and
![Page 8: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/8.jpg)
8
Table 5. Identified properties for the isolation system for tests 4 and 10
m (tons) k0 (kN/m) k1 (kN/m) Q (kN) μ (%) ζ e2
Runs 1-10, test 4 (γ = 0.45) 2942.4 3289.5 782.2 36.3 0.91 0 1.38 E-03
Runs 11-20, test 10 (γ = 0.67) 2824.5 2395.8 616.3 42.2 1.09 0 1.75 E-03
robustness of the method is demonstrated through a series of numerical applications that can be found
in (Oliveto et al., 2014).
Once the system response was simulated for each candidate solution the fitness function was
evaluated as the normalized quadratic distance between simulated and experimental response. The
experimental response is evaluated as the average of the two displacement records available for the
two monitored isolators. A search space, established on the basis of the dynamic laboratory data
provided by the manufacturer was considered for the search. The search space was enlarged after the
first run to account for larger variations in the friction coefficients. Τhe identified system properties for
tests 4 and 10, obtained from the best run performed, are given in Table 5. Runs 1-10 yielded similar
properties for the isolation system, the identified parameters varying from run to run not more than
6%. The same observation holds for runs 11-20.
The identification of the two tests yielded two different systems. However, it is true that test 4
was performed at a smaller shear strain level with respect to test 10 and hence it is reasonable that k1
was identified with a larger value. Comparing the identified parameters of Table 5 with the dynamic
laboratory data shown in Table 2, it can be seen how the elastic stiffness k0 of the rubber bearings is
approximately 50% lower than the corresponding laboratory one. The differences between the
identified Q and the corresponding laboratory parameters are less than 10%. The post-elastic stiffness
results are always slightly smaller than the laboratory ones. The coefficient of friction is 6-7 times
greater than the dynamic coefficient provided by the manufacturer under similar axial load (0.50Nmax),
Table 2, however the identified friction value is in line with the results of the Solarino experiments
(Oliveto et al. 2010).
a) b)
Figure 9. Recorded and identified displacements for tests 4 and 10, a) and b)
a) b)
Figure 10. Recorded and simulated ground floor and first floor accelerations for test 4, a) and b)
0 1 2 3 4 5-10
0
10
20
30
40
50
60
70
Test 4
t (s)
u (
mm
)
recorded displacement
identified displacement
ur = 13.4 mm
0 1 2 3 4 5-10
0
20
40
60
80
100
Test 10
t (s)
u (
mm
)
recorded displacement
identified displacement
ur = 17.5 mm
0 1 2 3 4 5-0.1
-0.05
0
0.05
0.1
0.15
0.2
0.25Test 4 - ground floor
t (s)
a (g
)
recorded acceleration
identified acceleration
0 1 2 3 4 5-0.1
-0.05
0
0.05
0.1
0.15
0.2
0.25Test 4 - 1
st floor
t (s)
a (g
)
recorded acceleration
identified acceleration
![Page 9: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/9.jpg)
G.Oliveto and A.Athanasiou 9
a) b)
Figure 11. Recorded and simulated second floor and roof accelerations for test 4, a) and b)
The identified displacement and acceleration histories are plotted against the experimental ones
in Figs 9-11. The good matching between experimental and identified displacements demonstrates that
the unidirectional system response can be successfully identified using a simple 1D model. The
matching between experimental and identified accelerations is good but less satisfactory. The isolation
frequency is identified correctly, however the rigid superstructure model cannot account for the high
frequency content induced from the superstructure flexibility. A more refined model is expected to
provide better results. Nevertheless, the identification of a complex NDOF model would increase
significantly the problem dimension and consequently the computational time.
SIMULATION OF THE SUPERSTRUCTURE RESPONSE
The 1D Mixed Lagrangian Formulation algorithm, initially presented in (Oliveto et al., 2011) was
extended to account for 2D horizontal earthquake motions (Oliveto et al., 2012). The superstructure
was still considered as a rigid block, however 3 DOFs were accounted for the isolation system: 2
horizontal displacements and a rotation about the vertical axis. In the ultimate extension of the MLF,
the method is updated to account for the flexibility of the building (Oliveto and Athanasiou, 2013).
Each floor is considered as a rigid diaphragm, hence 3 DOFs are considered per floor. A complete
description of the method can be found in (Oliveto and Athanasiou, 2013).
Several efforts were made for the simulation of the flexible superstructure response under test 4
using the MLF for NDOF systems. The system properties obtained from the identification of test 4
were used for the simulation of the isolation system. A diagonal mass matrix was constructed using
the mass data provided by the designer. The mass matrix was scaled so that the total mass equaled the
one identified by the experiment. The stiffness matrix for the superstructure was also provided by the
designer. The mass and stiffness matrix coefficients for the superstructure can be found in (Oliveto
and Athanasiou, 2013). The performed simulations showed that the superstructure was more rigid than
expected. In order to match the frequency content present in the signal the stiffness matrix available
for the superstructure, Kinitial , had to be amplified; a good compromise was found to be K=4.5Kinitial.
Simulations with K=4.5Kinitial provided a better matching between recorded and simulated data at the
ground floor and the top two floors, Figs 12(a), 15(a) and 16(a). The matching is fair for the
accelerations of the ground and first floor, Figs 13(a) and 14(a). The comparison of recorded and
simulated accelerations confirms that there is a high frequency content present in the signals of the two
bottom floors of the order of 32 Hz, see Table 3, that cannot be accounted for by the present model.
The presence of high acceleration spikes in the simulated signal during the last cycle of motion, absent
in the original signal, stresses the need for the introduction of a supplementary damping mechanism in
the model. The existent damping mechanisms seem unable to damp properly the acceleration
response. The rubber bearings undergo pure elastic behavior in the last cycle of motion while the
viscous damper is inactive; the corresponding damping ratio was found to be 0 from the identification
of test 4, Table 5. Hence there is only friction to account for energy dissipation.
In a further attempt to tune the simulated response, a damping matrix was introduced for the
superstructure. The damping matrix was constructed using superposition of modal damping matrices
0 1 2 3 4 5-0.1
-0.05
0
0.05
0.1
0.15
0.2
0.25Test 4 - 2
nd floor
t (s)
a (g
)
recorded acceleration
identified acceleration
0 1 2 3 4 5-0.1
-0.05
0
0.05
0.1
0.15
0.2
0.25Test 4 - roof
t (s)
a (g
)
recorded acceleration
identified acceleration
![Page 10: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/10.jpg)
10
(Chopra, 2007). The superstructure mode 5, i.e. the mode describing unidirectional deflections along
the x axis, was assigned a light damping ratio of 1%. No damping was assigned to the rest of the
modes. The obtained simulated displacement and acceleration histories for the damped superstructure
model are shown in Figs 12(b)-16(b). Close observation of Figs 12(a)-16(a) and Figs 12(b)-16(b)
shows that the introduction of classical damping had a slight beneficial effect in damping the response
at all floors but floor 1. That could be justified by the fact that mode 5 has a node at floor 1.
Introduction of larger damping ratios for mode 5 improved the system response, though not as
satisfactorily as expected.
a) b)
Figure 12. Recorded and simulated ground floor displacements for test 4,
a) when no and b) light damping is assigned to the superstructure
a) b)
Figure 13. Recorded and simulated ground floor accelerations for test 4,
a) when no and b) light damping is assigned to the superstructure
a) b)
Figure 14. Recorded and simulated first floor accelerations for test 4,
a) when no and b) light damping is assigned to the superstructure
0 1 2 3 4 5-10
0
10
20
30
40
50
60
70Displacement at GFL, no damping in the superstructure
t (s)
u (
mm
)
signal
simulation
0 1 2 3 4 5-10
0
10
20
30
40
50
60
70Displacement at GFL, damping in the superstructure
t (s)
u (
mm
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at GFL, no damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at GFL, damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at 1FL, no damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at 1FL, damping in the superstructure
t (s)
a (g
)
signal
simulation
![Page 11: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/11.jpg)
G.Oliveto and A.Athanasiou 11
a) b)
Figure 15. Recorded and simulated second floor accelerations for test 4,
a) when no and b) light damping is assigned to the superstructure
a) b)
Figure 16. Recorded and simulated roof accelerations for test 4,
a) when no and b) light damping is assigned to the superstructure
The simulation output stress the inability of the present model to account for frequencies higher
than 30Hz and to damp properly the superstructure response. This model inadequacy could be
attributed to possible inconsistencies in the considered superstructure mass and stiffness matrices, but
this is something yet to be investigated. Future research shall be towards identifying the mass and
stiffness matrices for the superstructure and implementing appropriate damping mechanisms. A
modification of the isolation system model, where the viscous damper acts in parallel with the elastic
spring ke instead of in parallel to the bi-linear spring, Fig. 8, is believed to describe more effectively
the response of the isolation system, observed during the experiments.
CONCLUSIONS
This paper presents recent research on the response of base isolated structures under real-time strong
motion. The case study considers a newly constructed RC base isolated building, that was subjected to
a set of free vibration tests. The effectiveness of the seismic isolation to reduce the dynamic demand
for the superstructure was demonstrated throughout the tests. The displacement demands input during
the release tests were accommodated mainly by the isolators; the energy input was dissipated by the
isolation system through nonlinear mechanisms, while the superstructure remained elastic. The static
phase of the experiments was used herein for the assessment of the static nonlinear behaviour of the
bearings. The identified static properties of the isolators provided a good matching between recorded
and simulated curves; however they were significantly different from the corresponding laboratory
parameters. It may be assumed that the laboratory tests provide more reliable results, since they are
performed independently on the isolators under controlled conditions. Nevertheless, the attempts to
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at 2FL, no damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at 2FL, damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at roof, no damping in the superstructure
t (s)
a (g
)
signal
simulation
0 1 2 3 4 5-0.2
-0.1
0
0.1
0.2
0.3Acceleration at roof, damping in the superstructure
t (s)
a (g
)
signal
simulation
![Page 12: SIMULATION OF THE RESPONSE OF A HYBRID …Base, or seismic isolation finds application in a large class of structures of major or minor importance, such as hospitals, bridges, residential](https://reader035.fdocuments.us/reader035/viewer/2022080717/5f783b66e9dbf67ce7232b7d/html5/thumbnails/12.jpg)
12
restrict the identification towards solutions close to the laboratory parameters resulted to bad matching
between recorded and simulated data. That shows that the laboratory properties do not necessarily
predict sufficiently well the system response under real ground motions. The displacements histories
of two monitored isolators during two release tests were used for the dynamic identification of a
simple 1D model describing the isolation system. Although the flexibility of the superstructure was
not accounted for by the model adopted, the results were satisfactory. Consequently, the identified
dynamic properties of the isolators were used in combination with the available mass and stiffness
matrices of the superstructure for the simulation of the dynamic response of a more refined model. The
flexible superstructure model provided promising results; meanwhile pointing out the inefficiencies of
the present simulations. The model considered was unable to account for the high frequency content
present in the recorded signals. Furthermore, the attempts for the implementation of a suitable
damping mechanism that accounted for energy dissipation in the high frequency cycles of motion,
proved unsuccessful. The problems arisen with the performed simulations set the basis for future
developments. Future research will be focused on the improvement of the flexible superstructure
model so that the latter can simulate adequately the observed dynamic behaviour of the considered
system.
ACKNOWLEDGEMENTS
This work was performed with the financial support of ReLUIS (Italian National Network of
University Earthquake Engineering Laboratories), “Project D.P.C - ReLUIS 2014-2016, WP1”.
REFERENCES
Chopra A (2007) Dynamics of Structures : Theory and Applications to Earthquake Engineering, 3rd
edition,
Prentice Hall
D.M. 14/01/2008 “Norme Tecniche per le Costruzioni,” Gazzetta Ufficiale n. 29 del 4 febbraio 2008 - Suppl.
Ordinario n. 30
Hansen N (2011) “The CMA Evolution Strategy: A Tutorial”, available online at:
http://www.lri.fr/~hansen/cmatutorial.pdf
MATLAB Release 2013a (2013) The MathWorks, Inc., Natick, Massachusetts, USA
Naeim F and Kelly J M (1999) Design of Seismic Isolated structures: From Theory to Practice, John Wiley and
Sons, Inc.
Oliveto G, Oliveto N D, Athanasiou A (2014) “Mixed Lagrangian Formulation for the 1-D dynamic and
earthquake response of hybrid base isolation systems”, submitted for publication in Engineering Structures,
under review
Oliveto G, Athanasiou A, Granata M (2013) “Blind simulation of full scale free vibration tests on a three story
base isolated building”, Proceedings of the 10th
International Conference on Urban Earthquake
Engineering, Center for Urban Earthquake Engineering, Tokyo Institute of Technology, Japan,
1-2 March, 1303-1316
Oliveto G and Athanasiou A (2013) “Mixed Lagrangian Formulation for the dynamic response of base isolated
buildings to earthquake excitation”, Proceedings of the XXI CONGRESSO AIMETA, Torino, Italy, 17-20
September
Oliveto N D, Athanasiou A, Oliveto G (2012) “Mixed Lagrangian Formulation for dynamic and earthquake
response of 2D hybrid base isolation systems”, Proceedings of the 9th
International Conference on Urban
Earthquake Engineering/4th
Asia Conference on Earthquake Engineering, Tokyo Institute of Technology,
Japan , 6-8 March, 1373–1382
Oliveto G, Oliveto N D, Athanasiou A (2011) “Mixed Lagrangian Formulation versus exact solution in the
dynamic and earthquake response of hybrid base isolation systems”, Proceedings of the XX CONGRESSO
AIMETA, Bologna, Italy, 12-15 September
Oliveto N D, Scalia G, Oliveto G (2010) “Time domain identification of hybrid base isolation systems using free
vibration tests”, Earthquake Engineering and Structural Dynamics, 39(9): 1015-1038
Oliveto G, Granata M, Buda G, Sciacca P (2004) “Preliminary results from full-scale free vibration tests on a
four story reinforced concrete building after seismic rehabilitation by base isolation”, Proceedings of the
JSSI 10th
Anniversary Symposium on Performance of Response Controlled Buildings, Yokohama, Japan,
pages, 17-19 November