    1/200Siemens ST 70 2011

    SIMATIC S7-400

    Brochures

    For brochures serving as selectionguides for SIMATIC products refer to:

    http://www.siemens.com/simatic/printmaterial

    6/2 Introduction

    6/4 Central processing units

    6/4 Standard CPUs

    6/4 CPU 412

    6/17 CPU 414

    6/32 CPU 416

    6/47 CPU 417

    6/52 SIPLUS Standard CPUs

    6/54 Fail-safe CPUs

    6/54 CPU 414F

    6/62 CPU 416F

    6/75 Fault-tolerant CPUs

    6/75 CPU 412H

    6/75 CPU 414H

    6/75 CPU 417H

    6/84 Sync-module for couplingthe CPU 41xH

    6/85 Y-Link for S7-400H

    6/88 SIPLUS fault-tolerant CPUs

    6/91 SIPLUS sync module for connectingthe CPU 41xH

    6/92 SIPLUS Y-Link for S7-400H

    6/93 Interface modules

    6/93 IF-964 DP PROFIBUS module

    6/94 SIPLUS IF-964 DP interface module

    6/95 Digital modules

    6/95 SM 421 digital input module

    6/98 SM 422 digital output module

    6/101 SIPLUS digital modules

    6/103 Analog modules

    6/103 SM 431 analog input module

    6/112 SM 432 analog output module

    6/114 SIPLUS analog modules

    6/116 Function modules

    6/116 FM 450-1 counter module

    6/118 FM 451 positioning module

    6/120 FM 452 cam controller

    6/122 FM 453 positioning module6/124 FM 455 controller module

    6/128 FM 458-1 DP application module

    6/139 SIPLUS function modules

    6/141 Communication

    6/141 CP 440

    6/142 CP 441-1, CP 441-2

    6/144 Loadable drivers for CP 441-2 andCP 341

    6/146 CP 443-5 Basic

    6/148 CP 443-5 Extended

    6/150 CP 443-1

    6/153 CP 443-1 Advanced

    Ch. 5 TIM 4R-IE for WAN and Ethernet

    Ch. 5 TIM 4R-IE DNP3

    6/158 SIPLUS communication

    6/162 Connection methods

    6/162 Front connectors

    6/163 SIMATIC TOP connect for SIMATIC S7

    6/172 Racks

    6/172 Racks

    6/174 Fan subassembly

    6/175 Expansion devices

    6/176 SIPLUS module racks

    6/177 Interface modules

    6/177 IM 460-0

    6/178 IM 461-0

    6/179 IM 460-1

    6/180 IM 461-1

    6/181 IM 460-3

    6/182 IM 461-3

    6/183 IM 463-2

    6/184 SIPLUS interface modules

    6/186 Power supplies

    6/190 Accessories

    6/190 Labeling sheets

    6/191 Spare parts

    6/192 Modules for SIMATIC S7-400F/FH

    6/192 IM 153-1/153-2

    6/196 SIPLUS IM 153-6/153-2

    6/198 Isolation module

    6/199 SIPLUS isolation module

    6/200 Fail-safe input/output modules

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    2/200

    SIMATIC S7-400Introduction

    S7-400/S7-400H/S7-400F/FH

    6/2 Siemens ST 70 2011

    Overview

    The S7-400 is the most powerful PLC in the family of SIMATICcontrollers. It enables successful automation solutions withTotally Integrated Automation (TIA). The S7-400 is an automationplatform for system solutions in production and process

    engineering, and it is characterized primarily by its modularityand performance reserves.

    S7-400

    The power PLC for the mid to high-end performance ranges.

    The solution for even the most demanding tasks.

    With a comprehensive range of modules and performance-graded CPUs for optimal adaptation to the automation task.

    Flexible in use through simple implementation of distributedstructures; user-friendly connections.

    Optimal communication and networking options.

    User-friendly handling and uncomplicated design without a

    fan. Can be expanded without problems when the tasks increase.

    Multicomputing: Simultaneous operation of several CPUs inone S7-400 central controller. Multicomputing distributes theoverall performance power of an S7-400. For example,complex tasks can be divided into technologies such asopen-loop control, computing or communication, andassigned to different CPUs. And every CPU can be assignedits own local I/O.

    Modularity: The powerful backplane bus of the S7-400 and thecommunication interfaces that can be connected direct to theCPU enable high-performance operation of a host of commu-nication lines. This enables, for example, division into onecommunication path for HMI and programming tasks, one forhigh-performance and equidistant motion control compo-nents, and one for a "normal" I/O fieldbus. Additionally

    required connections to MES/ERP systems or the Internet canalso be implemented.

    Engineering and diagnostics: The S7-400 is configured andprogrammed extremely efficiently together with the SIMATICEngineering Tools particularly in the case of extensiveautomation solutions with a high engineering component. Forthis purpose, high-level languages such as SCL and graphicalengineering tools for sequential controls, state graphprograms and technology-oriented diagrams are available, forexample.

    S7-400H

    Fault-tolerant automation system with redundant design. For applications with high fail-safety requirements. Processes

    with high restart costs, expensive downtimes, little super-vision, and few maintenance options.

    Redundant central functions.

    Increases availability of I/O: switched I/O configuration.

    Also possible to use I/Os with standard availability: single-sided configuration.

    Hot stand-by: automatic reaction-free switching to the standbyunit in the event of a fault.

    Configuration with two separate or one divided central rack.

    Connection of switched I/O via redundant PROFIBUS DP.

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    3/200

    SIMATIC S7-400Introduction

    S7-400/S7-400H/S7-400F/FH

    6/3Siemens ST 70 2011

    Overview(continued)

    S7-400F/FH

    Failsafe automation system for plants with increased safetyrequirements

    Complies with safety requirements to SIL 3 in accordance withIEC 61508, AK6 in accordance with DIN V 19250 and Cat. 4 inaccordance with EN 954-1

    If required, also fault tolerant through redundant design

    Without additional wiring of the safety-related I/O:

    Safety-relevant communication via PROFIBUS DP withPROFIsafe profile

    Based on S7-400H and ET 200M with fail-safe modules

    Standard modules for non-safety-related applications canalso be used in the automation system

    Isolation module for joint use of fail-safe and standardmodules in safety mode in one ET 200M

    Technical specifications

    For brochures serving as selection guides for SIMATIC productsrefer to:

    www.siemens.com/simatic/printmaterial

    General technical specifications

    Degree of protection IP20

    Ambient temperature 0 to 60 C

    Relative humidity 5 to 95%, no condensationAtmospheric pressure 1080 to 795 hPa (corresponds to

    an altitude of 1000 m to 2000 m)

    Electromagnetic compatibility

    Interference immunity According to EN 61000-6-2

    E mitted interference According to EN 61000-6-4

    Mechanical load

    Vibration, test according to /tested with

    IEC 60068-2-6 (sine)

    10 to 58 Hz; constant amplitude0.075 mm;58 to 500 Hz; constant acceler-ation 1 g; duration of oscillation: 10frequency sweeps per axis in eachdirection of the three mutuallyperpendicular axes

    Shock, test according to / tested

    with

    IEC 60068-2-27

    Type of shock: Half-sine;strength of the shock 10 g(peak value), duration 6 msdirection of shock: 100 shocks ineach of the 3 mutually perpen-dicular axes.

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    4/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/4 Siemens ST 70 2011

    Overview

    The low-cost starter solution for the medium performancerange

    Can be used in small and medium-sized systems with require-ments of the medium performance range

    Technical specifications

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Product type designation CPU 412-1 CPU 412-2 CPU 412-2 PN

    Product version

    Hardware product version 03 03 01

    Firmware version V5.3 V5.3 V6.0

    Associated programming package STEP7 V 5.3 SP2 or higher with HWupdate

    STEP7 V 5.3 SP2 or higher with HWupdate

    STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher

    Supply voltages

    Rated value

    24 V DC No; Power supply via systempower supply

    No; Power supply via systempower supply

    No; Power supply via systempower supply

    Feeding of external backup voltage

    to CPU

    5 to 15 V DC 5 to 15 V DC 5 to 15 V DC

    Current consumption

    from backplane bus 5 V DC, max. 0.6 A 1.1 A 1.3 A

    from interface 5 V DC, max. 90 mA 90 mA; At each DP interface 90 mA; At the DP interface

    Power losses

    Power loss, typ. 2.5 W 4.5 W 5.5 W

    Power loss, max. 3 W 5 W 6.5 W

    Backup battery

    Battery operation not relevant not relevant not relevant

    Backup current, typ. 125 A; (up to 40 C) 125 A; (up to 40 C) 125 A; (up to 40 C)

    Backup current, max. 300 A 550 A 450 A

    Memory

    Work memory

    integrated (for program) 144 Kibyte 256 Kibyte 0.5 Mbyte

    integrated (for data) 144 Kibyte 256 Kibyte 0.5 Mbyte expandable No No No

    Load memory

    expandable FEPROM Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH)

    expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte

    expandable RAM Yes; with Memory Card (RAM) Yes; with Memory Card (RAM) Yes; with Memory Card (RAM)

    expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    Backup

    present Yes Yes Yes

    with battery Yes; All data Yes; All data Yes; All data

    without battery No No No

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    5/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/5Siemens ST 70 2011

    Technical specifications(continued)

    CPU-blocks

    DB

    N umber, max. 1 500; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FB

    Number, max. 750; Number range: 0 to 7999 1 500; Number range: 0 to 7999 1 500; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FC

    Number, max. 750; Number range: 0 to 7999 1 500; Number range: 0 to 7999 1 500; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    OB

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Nesting depth

    per priority class 24 24 24

    additional within an error OB 1 1 1

    CPU processing times

    for bit operations, min. 75 ns 75 ns 75 ns

    for word operations, min. 75 ns 75 ns 75 ns

    for fixed point arithmetic, min. 75 ns 75 ns 75 ns

    for floating point arithmetic, min. 225 ns 225 ns 225 ns

    Counters, timers and theirretentivity

    S7 counter

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7

    Counting range

    - lower limit 0 0 0

    - upper limit 999 999 999

    IEC counter

    present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    S7 times

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset No times retentive No times retentive No times retentive

    Time range

    - lower limit 10 ms 10 ms 10 ms

    - upper limit 9 990 s 9 990 s 9 990 s

    IEC timer

    present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    6/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/6 Siemens ST 70 2011

    Technical specifications(continued)

    Data areas and their retentivity

    retentive data area, total Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Flag

    Number, max. 4 Kibyte; Size of bit memoryaddress area

    4 Kibyte; Size of bit memoryaddress area

    4 Kibyte; Size of bit memoryaddress area

    Retentivity available Yes Yes Yes

    Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)

    Data blocks

    N umber, max. 1 500; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000 3 000; Number range: 1 to 16,000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Local data

    adjustable, max. 8 Kibyte 8 Kibyte 8 Kibyte

    preset 4 Kibyte 4 Kibyte 4 Kibyte

    Address area

    I/O address area

    overall 4 Kibyte 4 Kibyte 4 Kibyte

    Outputs 4 Kibyte 4 Kibyte 4 Kibyte of which, distributed

    - MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte

    - MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte

    - DP interface, inputs 4 Kibyte

    - DP interface, outputs 4 Kibyte

    - PN interface, inputs 4 Kibyte

    - PN interface, outputs 4 Kibyte

    Process image

    Inputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte

    Outputs, adjustable 4 Kibyte 4 Kibyte 4 Kibyte

    Inputs, preset 128 byte 128 byte 128 kbyte

    Outputs, preset 128 byte 128 byte 128 Kibyte

    Consistent data, max. 244 byte 244 byte 244 byte

    Access to consistent data inprocess image

    Yes Yes Yes

    Subprocess images

    Number of subprocess images,max.

    15 15 15

    Digital channels

    Inputs 32 768 32 768 32 768

    Outputs 32 768 32 768 32 768

    Inputs, of which central 32 768 32 768 32 768

    Outputs, of which central 32 768 32 768 32 768

    Analog channels

    Inputs 2 048 2 048 2 048

    Outputs 2 048 2 048 2 048

    Inputs, of which central 2 048 2 048 2 048

    Outputs, of which central 2 048 2 048 2 048

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    7/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/7Siemens ST 70 2011

    Technical specifications(continued)

    Hardware configuration

    connectable OPs 31 31 47

    Central devices, max. 1 1 1

    Expansion devices, max. 21 21 21

    Multicomputing Yes; 4 CPUs max. (with UR1 orUR2)

    Yes; 4 CPUs max. (with UR1 orUR2)

    Yes; 4 CPUs max. (with UR1 orUR2)

    Interface modules

    Number of connectable IMs (total),max.

    6 6 6

    Number of connectable IM 460s,max.

    6 6 6

    Number of connectable IM 463s,max.

    4; IM 463-2 4; IM 463-2 4; IM 463-2

    Number of DP masters

    integrated 1 2 1

    via IM 467 4 4 4

    via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended

    Mixed mode IM + CP permitted No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    via interface module 0 0 0

    Number of pluggable S5 modules(via adapter capsule in centraldevice), max.

    6 6 6

    Number of IO controllers

    integrated 0 0 1

    via CP 4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller

    4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller

    4; No mixed operation ofCP443-1 EX40 andCP443-1 EX 41/EX20/GX20,max. 4 in central controller

    Number of operable FMs and CPs(recommended)

    FM Limited by number of slots andnumber of connections

    Limited by number of slots andnumber of connections

    Limited by number of slots andnumber of connections

    CP, point-to-point CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections

    CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections

    CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections

    PROFIBUS and Ethernet CPs 14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum

    14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum

    14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller

    Time

    Clock

    Hardware clock (real-time clock) Yes Yes Yes

    battery-backed and synchronizable Yes Yes Yes

    Resolution 1 ms 1 ms 1 ms

    Runtime meter

    Number 16 16 16

    Clock synchronization

    supported Yes Yes Yes to MPI, master Yes Yes Yes

    to MPI, slave Yes Yes Yes

    to DP, master Yes Yes Yes

    to DP, slave Yes Yes Yes

    in AS, master Yes Yes Yes

    in AS, slave Yes Yes Yes

    on Ethernet via NTP No; Via CP No; Via CP Yes; as client

    to IF 964 DP No No

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    8/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/8 Siemens ST 70 2011

    Technical specifications(continued)

    S7 message functions

    Number of login stations formessage functions, max.

    31; Max. 31 with alarm_S andalarm_D (OP's);

    max. 8 with alarm_8 and alarm_P(e.g. WinCC)

    31; Max. 31 with alarm_S andalarm_D (OP's);

    max. 8 with alarm_8 and alarm_P(e.g. WinCC)

    47; Max. 47 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 with

    Alarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)

    Symbol-related messages Yes Yes Yes

    SCAN procedure Yes Yes Yes

    Number of messages

    overall, max. 512 512 512

    Block related messages Yes Yes Yes

    Process diagnostic messages Yes Yes Yes

    Alarm 8-blocks Yes Yes Yes

    Process control messages Yes Yes Yes

    Test commissioning functions

    Status/control

    Status/control variable Yes; Up to 16 variable tables Yes; Up to 16 variable tables Yes; Up to 16 variable tables

    Forcing Forcing Yes Yes Yes

    Status block Yes; Up to 2 simultaneously Yes; Up to 2 simultaneously Yes; Up to 16 simultaneously

    Single step Yes Yes Yes

    Number of breakpoints 4 4 16

    Diagnostic buffer

    present Yes Yes Yes

    Number of entries, max. 200 400 400

    - adjustable Yes Yes Yes

    - preset 120 120 120

    Service data

    can be read out Yes

    Communication functions

    PG/OP communication Yes Yes Yes

    Data record routing Yes Yes Yes

    Routing Yes; S7 routing Yes; S7 routing Yes; S7 routing

    Global data communication

    supported Yes Yes Yes

    Size of GD packets, max. 54 byte 54 byte 54 byte

    S7 basic communication

    supported Yes Yes Yes

    User data per job, max. 76 byte 76 byte 76 byte

    S7 communication

    supported Yes Yes Yes

    as server Yes Yes Yes

    as client Yes Yes Yes

    User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte

    S5-compatible communication supported Yes; Via FC AG_SEND and

    AG_RECV, max. via 10 CP 443-1 or443-5

    Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5

    Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5

    User data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte

    Standard communication (FMS)

    supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    9/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/9Siemens ST 70 2011

    Technical specifications(continued)

    Web server

    supported No No Yes

    Number of HTTP clients 5

    User-defined websites Yes

    Open IE communication

    TCP/IP Yes; Via integrated PROFINETinterface and loadable FBs

    - Number of connections, max. 46

    - Data length, max. 32 Kibyte

    - Several passive connections perport, supported

    Yes

    ISO-on-TCP (RFC1006) Via CP 443-1 Adv. and loadable FB Via CP 443-1 and loadable FB Yes; Via integrated PROFINETinterface or CP 443-1 Adv. andloadable FBs

    - Number of connections, max. 46

    - Data length, max. 1452 bytes via CP 443-1 Adv. 1452 bytes via CP 443-1 Adv. 32 Kibyte; 1452 bytes via CP 443-1Adv.

    UDP Yes; Via integrated PROFINETinterface and loadable FBs

    - Number of connections, max. 46- Data length, max. 1 472 byte

    Number of connections

    overall 32 32 48

    PROFINET CBA (at set setpointcommunication load)

    Number of remote interconnectionpartners

    32

    Number of functions, master/slave 150

    Total of all Master/Slaveconnections

    4 500

    Data length of all incomingconnections master/slave, max.

    45 000 byte

    Data length of all outgoingconnections master/slave, max.

    45 000 byte

    Number of device-internal andPROFIBUS interconnections

    1 000

    Data length of device-internal andPROFIBUS interconnections, max.

    16 000 byte

    Data length per connection, max. 2 000 byte

    Remote interconnections withacyclic transmission

    - Sampling frequency: Samplingtime, min.

    200 ms; Depending on presetcommuncation load, number ofinterconnections and data lengthused

    - Number of incominginterconnections

    250

    - Number of outgoinginterconnections

    250

    - Data length of all incominginterconnections, max.

    8 000 byte

    - Data length of all outgoinginterconnections, max.

    8 000 byte

    - Data length per connection, max. 2 000 byte

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    10/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/10 Siemens ST 70 2011

    Technical specifications(continued)

    Remote interconnections withcyclic transmission

    - Transmission frequency:

    Transmission interval, min.

    1 ms; Depending on preset

    communication load, number ofinterconnections and data lengthused

    - Number of incominginterconnections

    300

    - Number of outgoinginterconnections

    300

    - Data length of all incominginterconnections, max.

    4 800 byte

    - Data length of all outgoinginterconnections, max.

    4 800 byte

    - Data length per connection, max. 450 byte

    HMI variables via PROFINET(acyclic)

    - Number of stations that can log onfor HMI variables (PN OPC/iMap)

    2x PN OPC/1x iMap

    - HMI variable updating 500 ms

    - Number of HMI variables 1 000- Data length of all HMI variables,

    max.32 000 byte

    PROFIBUS proxy functionality

    - supported Yes; 32 PROFIBUS slaves max.connectable

    - Data length per connection, max. 240 byte; Slave-dependent

    1st interface

    Type of interface Integrated Integrated Integrated

    Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI

    Isolated Yes Yes Yes

    Power supply to interface(15 to 30 V DC), max.

    150 mA 150 mA 150 mA

    Number of connection resources MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16

    Functionality MPI Yes Yes Yes

    DP master Yes Yes Yes

    DP slave Yes Yes Yes

    MPI

    Number of connections 32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    Services

    - PG/OP communication Yes Yes Yes

    - Routing Yes Yes Yes

    - Global data communication Yes Yes Yes

    - S7 basic communication Yes Yes Yes

    - S7 communication Yes Yes Yes

    - S7 communication, as client Yes Yes Yes

    - S7 communication, as server Yes Yes Yes

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    11/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/11Siemens ST 70 2011

    Technical specifications(continued)

    DP master

    Number of connections, max. 16; if a diagnostic repeater is usedon the line, the number of

    connection resources on the line isreduced by 1

    16; if a diagnostic repeater is usedon the line, the number of

    connection resources on the line isreduced by 1

    16; if a diagnostic repeater is usedon the line, the number of

    connection resources on the line isreduced by 1

    Services

    - PG/OP communication Yes Yes Yes

    - Routing Yes Yes Yes

    - Global data communication No No No

    - S7 basic communication Yes Yes Yes

    - S7 communication Yes Yes Yes

    - S7 communication, as client Yes Yes Yes

    - S7 communication, as server Yes Yes Yes

    - Equidistance mode support Yes Yes Yes

    - Isochronous mode Yes Yes Yes

    - SYNC/FREEZE Yes Yes Yes

    - Activation/deactivation of DPslaves

    Yes Yes Yes

    - Direct data exchange

    (slave-to-slave communication)

    Yes Yes Yes

    - DPV1 Yes Yes Yes

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    Number of DP slaves, max. 32 32 32

    Address area

    - Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte

    - Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte

    User data per DP slave

    - User data per DP slave, max. 244 byte 244 byte 244 byte

    - Inputs, max. 244 byte 244 byte 244 byte

    - Outputs, max. 244 byte 244 byte 244 byte

    - Slots, max. 244 244 244

    - per slot, max. 128 byte 128 byte 128 byte

    DP slave

    Number of connections 16 16 16

    Services- PG/OP communication Yes; with interface active Yes; with interface active Yes; with interface active

    - S7 routing Yes; With interface active Yes; With interface active Yes; With interface active

    - Global data communication No No No

    - S7 basic communication No No No

    - S7 communication Yes Yes Yes

    - S7 communication, as client Yes Yes Yes

    - S7 communication, as server Yes Yes Yes

    - Direct data exchange(slave-to-slave communication)

    No No No

    - DPV1 No No No

    GSD file http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    Automatic baud rate search No No No

    Transfer memory

    - Inputs 244 byte 244 byte 244 byte- Outputs 244 byte 244 byte 244 byte

    Address area, max. 32; Virtual slots 32; Virtual slots 32; Virtual slots

    User data per address area, max. 32 byte 32 byte 32 byte

    User data per address area, ofwhich consistent, max.

    32 byte 32 byte 32 byte

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    12/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/12 Siemens ST 70 2011

    Technical specifications(continued)

    2nd interface

    Type of interface Integrated PROFINET

    Physics RS 485 / PROFIBUS Ethernet RJ45

    Isolated Yes Yes

    Integrated switch Yes

    Number of ports 2

    Power supply to interface(15 to 30 V DC), max.

    150 mA

    Automatic detection of transmissionspeed

    Yes; Autosensing

    Autonegotiation Yes

    Autocrossing Yes

    Media redundancy

    supported Yes

    Switchover time on line break,typically

    200 ms

    Number of stations in the ring, max. 50

    Change of IP address at runtime,supported

    Yes; Assignment by higher-level IOcontroller or by the user programwith SFB104 "IP_CONF"

    Number of connection resources 16 48

    Functionality

    DP master Yes No

    DP slave Yes No

    PROFINET IO controller Yes

    PROFINET IO device Yes

    PROFINET CBA Yes

    Open IE communication Yes

    Web server Yes

    - Number of HTTP clients 5

    Local Operating Network No

    DP master

    Number of connections, max. 16

    Services

    - PG/OP communication Yes

    - Routing Yes

    - Global data communication No

    - S7 basic communication Yes

    - S7 communication Yes

    - S7 communication, as client Yes

    - S7 communication, as server Yes

    - Equidistance mode support Yes

    - Isochronous mode Yes

    - SYNC/FREEZE Yes

    - Activation/deactivation ofDP slaves

    Yes

    - Direct data exchange(slave-to-slave communication)

    Yes

    - DPV1 Yes

    Transmission rate, max. 12 Mbit/s

    Number of DP slaves, max. 64

    Address area

    - Inputs, max. 4 Kibyte

    - Outputs, max. 4 Kibyte

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    13/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/13Siemens ST 70 2011

    Technical specifications(continued)

    User data per DP slave

    - User data per DP slave, max. 244 byte

    - Inputs, max. 244 byte

    - Outputs, max. 244 byte- Slots, max. 244

    - per slot, max. 128 byte

    DP slave

    Number of connections 16

    Services

    - Routing Yes

    - Programming Yes

    GSD file http://support.automation.siemens.com/WW/view/en/113652

    Transmission rate, max. 12 Mbit/s

    Transfer memory

    - Inputs 244 byte

    - Outputs 244 byte

    Address area, max. 32

    User data per address area, max. 32 byte User data per address area, of

    which consistent, max.32 byte

    PROFINET IO controller

    Services

    - PG/OP communication Yes

    - S7 routing Yes

    - S7 communication Yes

    - Isochronous mode Yes; Only with IRT and the HighPerformance option

    - Open IE communication Yes

    Transmission rate, min. 10 Mbit/s

    Transmission rate, max. 100 Mbit/s

    Number of connectable IO devices,max.

    256

    Max. number of connectable IO

    devices for RT

    256

    - of which in line, max. 256

    Number of IO devices with IRT andthe option "high flexibility"

    256

    - of which in line, max. 61

    Number of IO devices with IRT andthe option "high performance", max.

    64

    - of which in line, max. 64

    IRT, supported Yes

    Shared device, supported Yes

    Prioritized startup supported Yes

    - Number of IO devices, max. 32

    Activation/deactivation ofIO devices

    Yes

    - Number of IO devices that can besimultaneously activated/deacti-

    vated, max.

    8

    IO devices changing duringoperation (partner ports),supported

    Yes

    - Max. number of IO devices pertool

    8; 8 parallel calls of the SFC 12"D_ACT_DP" possible per line.Max. 32 IO devices changingduring operation (partner ports)are supported.

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    14/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/14 Siemens ST 70 2011

    Technical specifications(continued)

    Device replacement without swapmedium

    Yes

    Send clock times 250 s, 500 s, 1 ms, 2 ms, 4 ms

    additionally with IRT with highperformance: 250 s to 4 ms in125 s frame

    Updating time 250 s to 512 ms; minimum valuedepends on preset communicationshare for PROFINET IO, on thenumber of IO devices and on theamount of configured user data,see PROFINET system description

    Address area

    - Inputs, max. 4 Kibyte

    - Outputs, max. 4 Kibyte

    User data per address area, max.

    - User data consistency, max. 1 024 byte

    PROFINET IO device

    Services

    - PG/OP communication Yes

    - S7 routing Yes

    - S7 communication Yes

    - Isochronous mode No

    - Open IE communication Yes

    - IRT, supported Yes

    - Prioritized startup supported Yes

    - Shared device, supported Yes

    - Number of IO controllers withshared device, max.

    2

    Transfer memory

    - Inputs, max. 1 440 byte; Per IO controller withshared device

    - Outputs, max. 1 440 byte; Per IO controller withshared device

    Submodules

    - Number, max. 64- User data per submodule, max. 1 024 byte

    PROFINET CBA

    acyclic transmission Yes

    cyclic transmission Yes

    Open IE communication

    Open IE communication, supported Yes

    Number of connections, max. 46

    Local port numbers used at thesystem end

    0, 20, 21, 25, 80, 102, 135, 161,34962, 34963, 34964, 65532,65533, 65534, 65535

    Keep-alive function, supported Yes

    Isochronous mode

    Isochronous mode Yes; For PROFIBUS only Yes; For PROFIBUS only Yes; Via PROFIBUS DP orPROFINET interface

    Number of DP masters withisochronous mode

    1 2 1

    User data per isochronous slave,max.

    244 byte 244 byte 244 byte

    Equidistance Yes Yes Yes

    Shortest clock pulse 1.5 ms; 0.5 ms without use of SFC126, 127

    1.5 ms; 0.5 ms without use of SFC126, 127

    1.5 ms; 0.5 ms without use of SFC126, 127

    Max. cycle 32 ms 32 ms 32 ms

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    15/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 412

    6/15Siemens ST 70 2011

    Technical specifications(continued)

    CiR - Configuration in RUN

    CiR synchronization time, basic load 100 ms 100 ms 100 ms

    CiR synchronization time, time perI/O slave

    30 s; Time per I/O byte 200 s; Time per I/O byte 30 s; Time per I/O byte

    Programming

    Configuration software

    STEP 7 Yes Yes Yes

    Programming language

    STEP 7 Yes Yes Yes

    LAD Yes Yes Yes

    FBD Yes Yes Yes

    STL Yes Yes Yes

    SCL Yes Yes Yes

    CFC Yes Yes Yes

    GRAPH Yes Yes Yes

    HiGraph Yes Yes Yes

    Nesting levels 7 7 7

    Know-how protection User program protection/password

    protectionYes Yes Yes

    Block encryption Yes; With S7 block privacy

    EMC

    Emission of radio interference acc. toEN 55 011

    Limit value class A, for use inindustrial areas

    Yes Yes

    Limit value class B, for use inresidential areas

    No No

    Dimensions

    Required slots 1 1 1

    Dimensions and weight

    Dimensions

    Width 25 mm 25 mm 25 mm Height 290 mm 290 mm 290 mm

    Depth 219 mm 219 mm 219 mm

    Weight

    Weight, approx. 0.7 kg 0.7 kg 750 g

    6ES7 412-1XJ05-0AB0 6ES7 412-2XJ05-0AB0 6ES7 412-2EK06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    16/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 412

    6/16 Siemens ST 70 2011

    Ordering data Order No. Order No.

    D: Subject to export regulations AL: N and ECCN: 5D992

    J: Subject to export regulations AL: N and ECCN: EAR99S

    CPU 412-1 6ES7 412-1XJ05-0AB0

    Work memory 288 KB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot for

    memory card, incl. slot numberlabels

    CPU 412-2 6ES7 412-2XJ05-0AB0

    Work memory 512 KB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot formemory card, incl. slot numberlabels

    CPU 412-2 PN 6ES7 412-2EK06-0AB0

    Work memory 1 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFINETinterface, slot for memory card,incl. slot number labels

    Memory card RAM

    64 KB 6ES7 952-0AF00-0AA0

    256 KB 6ES7 952-1AH00-0AA0

    1 MB 6ES7 952-1AK00-0AA0

    2 MB 6ES7 952-1AL00-0AA0

    4 MB 6ES7 952-1AM00-0AA0

    8 MB 6ES7 952-1AP00-0AA0

    16 MB 6ES7 952-1AS00-0AA0

    64 MB 6ES7 952-1AY00-0AA0

    FEPROM memory card

    64 KB 6ES7 952-0KF00-0AA0

    256 KB 6ES7 952-0KH00-0AA0

    1 MB 6ES7 952-1KK00-0AA0

    2 MB 6ES7 952-1KL00-0AA04 MB 6ES7 952-1KM00-0AA0

    8 MB 6ES7 952-1KP00-0AA0

    16 MB 6ES7 952-1KS00-0AA0

    32 MB 6ES7 952-1KT00-0AA0

    64 MB 6ES7 952-1KY00-0AA0

    MPI cable 6ES7 901-0BF00-0AA0

    for connection of SIMATIC S7 andPG via MPI; 5 m in length

    Slot number labels 6ES7 912-0AA00-0AA0

    1 set (spare part)

    Manual "SIMATIC S7-400programmable controller"

    incl. instruction list

    German 6ES7 498-8AA05-8AA0

    English 6ES7 498-8AA05-8BA0

    S7-400 operation list

    German 6ES7 498-8AA05-8AN0

    English 6ES7 498-8AA05-8BN0

    Manual "Communication forSIMATIC S7-300/-400"

    German 6ES7 398-8EA00-8AA0

    English 6ES7 398-8EA00-8BA0

    French 6ES7 398-8EA00-8CA0

    Spanish 6ES7 398-8EA00-8DA0

    Italian 6ES7 398-8EA00-8EA0

    SIMATIC manual collection J 6ES7 998-8XC01-8YE0

    Electronic manuals on DVD,multilingual: LOGO!, SIMADYN,SIMATIC bus components,SIMATIC C7,SIMATIC distributed I/O,SIMATIC HMI, SIMATIC Sensors,SIMATIC NET, SIMATIC PC BasedAutomation, SIMATIC PCS 7,SIMATIC PG/PC, SIMATIC S7,SIMATIC Software, SIMATIC TDC

    SIMATIC manual collection

    update service for 1 year

    D 6ES7 998-8XC01-8YE2

    Current "Manual Collection" DVDand the three subsequentupdates

    Brochure "SIMATIC S7-400programmable controller -Design and application"

    German 6ES7 498-8AA00-8AB0

    English 6ES7 498-8AA00-8BB0

    RS 485 bus connector with90 cable outlet

    Max. transfer rate 12 Mbit/s

    Without PG interface 6ES7 972-0BA12-0XA0

    With PG interface 6ES7 972-0BB12-0XA0

    RS 485 bus connector withangled cable outlet

    Max. transfer rate 12 Mbit/s

    Without PG interface 6ES7 972-0BA42-0XA0

    With PG interface 6ES7 972-0BB42-0XA0

    RS 485 bus connector with90 cable outlet forFast Connect system

    Max. transfer rate 12 Mbit/s

    Without PG interface

    1 unit 6ES7 972-0BA52-0XA0

    100 units 6ES7 972-0BA52-0XB0

    With PG interface

    1 unit 6ES7 972-0BB52-0XA0 100 units 6ES7 972-0BB52-0XB0

    RS 485 bus connector withaxial cable outlet

    For SIMATIC OP, for connection toPPI, MPI, PROFIBUS

    6GK1 500-0EA02

    PROFIBUS FastConnect buscable

    Standard type with special designfor quick mounting, 2-core,shielded, sold by the meter, max.delivery unit 1000 m, minimumordering quantity 20 m

    6XV1 830-0EH10

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    17/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/17Siemens ST 70 2011

    Overview

    CPUs for high demands in the mid-level performance range

    Applicable for plants with additional demands onprogramming scope and processing speed

    Integrated PROFINET functions in CPU 414-3 PN/DP

    Technical specifications6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Product type designation CPU 414-2 CPU 414-3 CPU414-3 PN/DP

    Product version

    Hardware product version 03 03 01

    Firmware version V5.3 V5.3 V6.0

    associated programming package STEP7 V 5.3 SP2 or higher with HWupdate

    STEP7 V 5.3 SP2 or higher with HWupdate

    STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher

    Supply voltages

    Rated value

    24 V DC No; Power supply via systempower supply

    No; Power supply via systempower supply

    No; Power supply via systempower supply

    Feeding of external backup voltageto CPU

    5 to 15 V DC 5 to 15 V DC 5 to 15 V DC

    Current consumption

    from backplane bus 5 V DC, max. 1.1 A 1.3 A 1.5 A

    from interface 5 V DC, max. 90 mA; At each DP interface 90 mA; At each DP interface 90 mA; At each DP interface

    Power losses

    Power loss, typ. 4.5 W 5.5 W 6.5 W

    Power loss, max. 5 W 6 W 7.5 W

    Backup battery

    Battery operation not relevant not relevant not relevant

    Backup current, typ. 125 A; (up to 40 C) 125 A 125 A; (up to 40 C)

    Backup current, max. 550 A 550 A 450 A

    Memory

    Work memory

    integrated (for program) 0.5 Mbyte 1.4 Mbyte 2 Mbyte integrated (for data) 0.5 Mbyte 1.4 Mbyte 2 Mbyte

    expandable No No No

    Load memory

    expandable FEPROM Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH) Yes; with Memory Card (FLASH)

    expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    integrated RAM, max. 512 Kibyte 512 Kibyte 512 Kibyte

    expandable RAM Yes; with Memory Card (RAM) Yes; with Memory Card (RAM) Yes; with Memory Card (RAM)

    expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    Backup

    present Yes Yes Yes

    with battery Yes; All data Yes; All data Yes; All data

    without battery No No No

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    18/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/18 Siemens ST 70 2011

    Technical specifications(continued)

    CPU-blocks

    DB

    N umber, max. 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FB

    Number, max. 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FC

    Number, max. 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999 3 000; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    OB

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Nesting depth

    per priority class 24 24 24

    additional within an error OB 1 1 1

    CPU processing times

    for bit operations, min. 45 ns 45 ns 45 ns

    for word operations, min. 45 ns 45 ns 45 ns

    for fixed point arithmetic, min. 45 ns 45 ns 45 ns

    for floating point arithmetic, min. 135 ns 135 ns 135 ns

    Counters, timers and theirretentivity

    S7 counter

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7

    Counting range

    - lower limit 0 0 0

    - upper limit 999 999 999

    IEC counter

    Present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    S7 times

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset No times retentive No times retentive No times retentive

    Time range

    - lower limit 10 ms 10 ms 10 ms

    - upper limit 9 990 s 9 990 s 9 990 s

    IEC timer

    present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    Unlimited (limited only by workmemory)

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    19/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/19Siemens ST 70 2011

    Technical specifications(continued)

    Data areas and their retentivity

    retentive data area, total Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Flag

    Number, max. 8 Kibyte; Size of bit memoryaddress area

    8 Kibyte; Size of bit memoryaddress area

    8 Kibyte; Size of bit memoryaddress area

    Retentivity available Yes Yes Yes

    Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)

    Data blocks

    N umber, max. 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000 6 000; Number range: 1 to 16,000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Local data

    adjustable, max. 16 Kibyte 16 Kibyte 16 Kibyte

    preset 8 Kibyte 8 Kibyte 8 Kibyte

    Address area

    I/O address area

    overall 8 Kibyte 8 Kibyte 8 Kibyte

    Outputs 8 Kibyte 8 Kibyte 8 Kibyte of which, distributed

    - MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte

    - MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte

    - DP interface, inputs 6 Kibyte 6 Kibyte 6 Kibyte

    - DP interface, outputs 6 Kibyte 6 Kibyte 6 Kibyte

    - PN interface, inputs 8 Kibyte

    - PN interface, outputs 8 Kibyte

    Process image

    Inputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte

    Outputs, adjustable 8 Kibyte 8 Kibyte 8 Kibyte

    Inputs, preset 256 byte 256 byte 256 byte

    Outputs, preset 256 byte 256 byte 256 byte

    consistent data, max. 244 byte 244 byte 244 byte

    Access to consistent data inprocess image

    Yes Yes Yes

    Subprocess images

    Number of subprocess images,max.

    15 15 15

    Digital channels

    Inputs 65 536 65 536 65 536

    Outputs 65 536 65 536 65 536

    Inputs, of which central 65 536 65 536 65 536

    Outputs, of which central 65 536 65 536 65 536

    Analog channels

    Inputs 4 096 4 096 4 096

    Outputs 4 096 4 096 4 096

    Inputs, of which central 4 096 4 096 4 096

    Outputs, of which central 4 096 4 096 4 096

    Hardware configuration

    connectable OPs 31 31 63

    Central devices, max. 1 1 1

    Expansion devices, max. 21 21 21

    Multicomputing Yes; 4 CPUs max. (with UR1 orUR2)

    Yes; 4 CPUs max. (with UR1 orUR2)

    Yes; 4 CPUs max. (with UR1 orUR2)

    Interface modules

    Number of connectable IMs (total),max.

    6 6 6

    Number of connectable IM 460s,max.

    6 6 6

    Number of connectable IM 463s,max.

    4; IM 463-2 4; IM 463-2 4; IM 463-2

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    20/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/20 Siemens ST 70 2011

    Technical specifications(continued)

    Number of DP masters

    integrated 2 2 1

    via IM 467 4 4 4

    via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended Mixed mode IM + CP permitted No; IM 467 not suitable for use with

    CP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    via interface module 0 1 1; IF 964-DP

    Number of pluggable S5 modules(via adapter capsule in centraldevice), max.

    6 6 6

    Number of IO controllers

    integrated 0 0 1

    via CP 4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

    4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

    4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

    Number of operable FMs and CPs(recommended)

    FM Limited by number of slots and

    number of connections

    Limited by number of slots and

    number of connections

    Limited by number of slots and

    number of connections CP, point-to-point CP 440: limited by number of slots;

    CP 441: limited by number ofconnections

    CP 440: limited by number of slots;CP 441: limited by number ofconnections

    CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections

    PROFIBUS and Ethernet CPs 14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum

    14; Of which 10 CPs max. or IMsas DP master, 4 PN controllermaximum

    14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller

    Time

    Clock

    Hardware clock (real-time clock) Yes Yes Yes

    Battery-backed and synchronizable Yes Yes Yes

    Resolution 1 ms 1 ms 1 ms

    Runtime meter

    Number 16 16 16

    Clock synchronization supported Yes Yes Yes

    to MPI, master Yes Yes Yes

    to MPI, slave Yes Yes Yes

    to DP, master Yes Yes Yes

    to DP, slave Yes Yes Yes

    in AS, master Yes Yes Yes

    in AS, slave Yes Yes Yes

    on Ethernet via NTP No; via CP No; via CP Yes; as client

    to IF 964 DP No Yes Yes

    S7 message functions

    Number of login stations formessage functions, max.

    31; max. 31 with alarm_S andalarm_D (OP's); max. 8 withalarm_8 and alarm_P (e.g. WinCC)

    31; max. 31 with alarm_S andalarm_D (OP's); max. 8 withalarm_8 and alarm_P (e.g. WinCC)

    63; max. 63 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 withAlarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)

    Symbol-related messages Yes Yes Yes

    SCAN procedure Yes Yes Yes

    Number of messages

    overall, max. 512 512 512

    Block related messages Yes Yes Yes

    Process diagnostic messages Yes Yes Yes

    Alarm 8-blocks Yes Yes Yes

    Process control messages Yes Yes Yes

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    21/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/21Siemens ST 70 2011

    Technical specifications(continued)

    Test commissioning functions

    Status/control

    Status/control variable Yes; Up to 16 variable tables Yes; Up to 16 variable tables Yes; Up to 16 variable tables

    Forcing

    Forcing Yes Yes Yes

    Status block Yes; Up to 2 simultaneously Yes; Up to 2 simultaneously Yes; Up to 16 simultaneously

    Single step Yes Yes Yes

    Number of breakpoints 4 4 16

    Diagnostic buffer

    present Yes Yes Yes

    Number of entries, max. 400 3 200 3 200

    - adjustable Yes Yes Yes

    - preset 120 120 120

    Service data

    can be read out Yes

    Communication functions

    PG/OP communication Yes Yes Yes

    Data record routing Yes Yes Yes

    Routing Yes; S7 routing Yes; S7 routing Yes; S7 routing

    Global data communication

    supported Yes Yes Yes

    Size of GD packets, max. 54 byte 54 byte 54 byte

    S7 basic communication

    supported Yes Yes Yes

    User data per job, max. 76 byte 76 byte 76 byte

    S7 communication

    supported Yes Yes Yes

    as server Yes Yes Yes

    as client Yes Yes Yes

    User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte

    S5-compatible communication

    supported Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5

    Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5

    Yes; Via FC AG_SEND andAG_RECV, max. via 10 CP 443-1 or443-5

    User data per job, max. 8 Kibyte 8 Kibyte 8 Kibyte

    Standard communication (FMS)

    supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB

    Web server

    supported No No Yes

    Number of HTTP clients 5

    User-defined websites Yes

    Open IE communication

    TCP/IP Yes; Via integrated PROFINETinterface and loadable FBs

    - Number of connections, max. 62

    - Data length, max. 32 Kibyte

    - Several passive connections perport, supported

    Yes

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    22/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/22 Siemens ST 70 2011

    Technical specifications(continued)

    ISO-on-TCP (RFC1006) Via CP 443-1 and loadable FB Via CP 443-1 and loadable FB Yes; Via integrated PROFINETinterface or CP 443-1 Adv. andloadable FBs

    - Number of connections, max. 62- Data length, max. 1452 bytes via CP 443-1 Adv. 1452 bytes via CP 443-1 Adv. 32 Kibyte; 1452 bytes via CP 443-1

    Adv.

    UDP Yes; Via integrated PROFINETinterface and loadable FBs

    - Number of connections, max. 62

    - Data length, max. 1 472 byte

    Number of connections

    overall 32 32 64

    PROFINET CBA (at set setpointcommunication load)

    Number of remote interconnectionpartners

    32

    Number of functions, master/slave 150

    Total of all Master/Slave connec-tions

    4 500

    Data length of all incomingconnections master/slave, max.

    45 000 byte

    Data length of all outgoingconnections master/slave, max.

    45 000 byte

    Number of device-internal andPROFIBUS interconnections

    1 000

    Data length of device-internal andPROFIBUS interconnections, max.

    16 000 byte

    Data length per connection, max. 2 000 byte

    Remote interconnections withacyclic transmission

    - Sampling frequency: Samplingtime, min.

    200 ms; Depending on presetcommuncation load, number ofinterconnections and data lengthused

    - Number of incominginterconnections

    250

    - Number of outgoinginterconnections

    250

    - Data length of all incominginterconnections, max.

    8 000 byte

    - Data length of all outgoinginterconnections, max.

    8 000 byte

    - Data length per connection, max. 2 000 byte

    Remote interconnections withcyclic transmission

    - Transmission frequency:Transmission interval, min.

    1 ms; Depending on presetcommunication load, number ofinterconnections and data lengthused

    - Number of incominginterconnections

    300

    - Number of outgoinginterconnections

    300

    - Data length of all incominginterconnections, max.

    4 800 byte

    - Data length of all outgoinginterconnections, max.

    4 800 byte

    - Data length per connection, max. 450 byte

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    23/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/23Siemens ST 70 2011

    Technical specifications(continued)

    HMI variables via PROFINET(acyclic)

    - Number of stations that can log on

    for HMI variables (PN OPC/iMap)

    2x PN OPC/1x iMap

    - HMI variable updating 500 ms

    - Number of HMI variables 1 000

    - Data length of all HMI variables,max.

    32 000 byte

    PROFIBUS proxy functionality

    - supported Yes; 32 PROFIBUS slaves max.connectable

    - Data length per connection, max. 240 byte; Slave-dependent

    1st interface

    Type of interface Integrated Integrated Integrated

    Physics RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI RS 485 / PROFIBUS + MPI

    Isolated Yes Yes Yes

    Power supply to interface(15 to 30 V DC), max.

    150 mA 150 mA 150 mA

    Number of connection resources MPI: 32, DP: 16 MPI: 32, DP: 16 MPI: 32, DP: 16

    Functionality

    MPI Yes Yes Yes

    DP master Yes Yes Yes

    DP slave Yes Yes Yes

    MPI

    Number of connections 32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    32; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    Services

    - PG/OP communication Yes Yes Yes

    - Routing Yes Yes Yes

    - Global data communication Yes Yes Yes

    - S7 basic communication Yes Yes Yes

    - S7 communication Yes Yes Yes- S7 communication, as client Yes Yes Yes

    - S7 communication, as server Yes Yes Yes

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    DP master

    Number of connections, max. 16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    16; if a diagnostic repeater is usedon the line, the number ofconnection resources on the line isreduced by 1

    Services

    - PG/OP communication Yes Yes Yes

    - Routing Yes Yes Yes

    - Global data communication No No No

    - S7 basic communication Yes Yes Yes

    - S7 communication Yes Yes Yes

    - S7 communication, as client Yes Yes Yes- S7 communication, as server Yes Yes Yes

    - Equidistance mode support Yes Yes Yes

    - Isochronous mode Yes Yes Yes

    - SYNC/FREEZE Yes Yes Yes

    - Activation/deactivation of DPslaves

    Yes Yes Yes

    - Direct data exchange(slave-to-slave communication)

    Yes Yes Yes

    - DPV1 Yes Yes Yes

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    24/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/24 Siemens ST 70 2011

    Technical specifications(continued)

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    Number of DP slaves, max. 32 32 32

    Address area

    - Inputs, max. 2 Kibyte 2 Kibyte 2 Kibyte- Outputs, max. 2 Kibyte 2 Kibyte 2 Kibyte

    User data per DP slave

    - User data per DP slave, max. 244 byte 244 byte 244 byte

    - Inputs, max. 244 byte 244 byte 244 byte

    - Outputs, max. 244 byte 244 byte 244 byte

    - Slots, max. 244 244 244

    - per slot, max. 128 byte 128 byte 128 byte

    DP slave

    Number of connections 16 16 16

    Services

    - PG/OP communication Yes; with interface active Yes; with interface active Yes; with interface active

    - S7 routing Yes; With interface active Yes; With interface active Yes; With interface active

    - Global data communication No No No

    - S7 basic communication No No No

    - S7 communication Yes Yes Yes- S7 communication, as client Yes Yes Yes

    - S7 communication, as server Yes Yes Yes

    - Direct data exchange(slave-to-slave communication)

    No No No

    - DPV1 No No No

    GSD file http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    Transmission rate, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s

    Automatic baud rate search No No No

    Transfer memory

    - Inputs 244 byte 244 byte 244 byte

    - Outputs 244 byte 244 byte 244 byte

    Address area, max. 32; Virtual slots 32; Virtual slots 32; Virtual slots

    User data per address area, max. 32 byte 32 byte 32 byte

    User data per address area, of

    which consistent, max.

    32 byte 32 byte 32 byte

    2nd interface

    Type of interface Integrated Integrated PROFINET

    Physics RS 485 / PROFIBUS RS 485 / PROFIBUS Ethernet RJ45

    Isolated Yes Yes Yes

    Integrated switch Yes

    Number of ports 2

    Power supply to interface(15 to 30 V DC), max.

    150 mA 150 mA

    Automatic detection of transmissionspeed

    Yes; Autosensing

    Autonegotiation Yes

    Autocrossing Yes

    Media redundancy

    supported Yes

    Switchover time on line break,typically

    200 ms

    Number of stations in the ring, max. 50

    Change of IP address at runtime,supported

    Yes; Assignment by higher-level IOcontroller or by the user programwith SFB104 "IP_CONF"

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    25/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/25Siemens ST 70 2011

    Technical specifications(continued)

    Number of connection resources 16 16 64

    Functionality

    DP master Yes Yes No

    DP slave Yes Yes No

    PROFINET IO controller Yes

    PROFINET IO device Yes

    PROFINET CBA Yes

    Open IE communication Yes

    Web server Yes

    - Number of HTTP clients 5

    Local Operating Network No

    DP master

    Number of connections, max. 16 16

    Services

    - PG/OP communication Yes Yes

    - Routing Yes Yes

    - Global data communication No No

    - S7 basic communication Yes Yes

    - S7 communication Yes Yes

    - S7 communication, as client Yes Yes

    - S7 communication, as server Yes Yes

    - Equidistance mode support Yes Yes

    - Isochronous mode Yes Yes

    - SYNC/FREEZE Yes Yes

    - Activation/deactivation of DPslaves

    Yes Yes

    - Direct data exchange(slave-to-slave communication)

    Yes Yes

    - DPV1 Yes Yes

    Transmission rate, max. 12 Mbit/s 12 Mbit/s

    Number of DP slaves, max. 96 96

    Address area

    - Inputs, max. 6 Kibyte 6 Kibyte

    - Outputs, max. 6 Kibyte 6 Kibyte User data per DP slave

    - User data per DP slave, max. 244 byte 244 byte

    - Inputs, max. 244 byte 244 byte

    - Outputs, max. 244 byte 244 byte

    - Slots, max. 244 244

    - per slot, max. 128 byte 128 byte

    DP slave

    Number of connections 16 16

    Services

    - Routing Yes Yes

    - Programming Yes Yes

    GSD file http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    Transmission rate, max. 12 Mbit/s 12 Mbit/s

    Transfer memory

    - Inputs 244 byte 244 byte

    - Outputs 244 byte 244 byte

    Address area, max. 32 32

    User data per address area, max. 32 byte 32 byte

    User data per address area, ofwhich consistent, max.

    32 byte 32 byte

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    26/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/26 Siemens ST 70 2011

    Technical specifications(continued)

    PROFINET IO controller

    Services

    - PG/OP communication Yes

    - S7 routing Yes- S7 communication Yes

    - Isochronous mode Yes; only with IRT and the HighPerformance option

    - Open IE communication Yes

    Transmission rate, min. 10 Mbit/s

    Transmission rate, max. 100 Mbit/s

    Number of connectable IO devices,max.

    256

    Max. number of connectableIO devices for RT

    256

    - of which in line, max. 256

    Number of IO devices with IRT andthe option "high flexibility"

    256

    - of which in line, max. 61

    Number of IO devices with IRT and

    the option "high performance", max.

    64

    - of which in line, max. 64

    IRT, supported Yes

    Shared device, supported Yes

    Prioritized startup supported Yes

    - Number of IO devices, max. 32

    Activation/deactivation ofIO devices

    Yes

    - Number of IO devices that canbe simultaneously activated/deactivated, max.

    8

    IO devices changing duringoperation (partner ports),supported

    Yes

    - Max. number of IO devices pertool

    8; 8 parallel calls of the SFC 12"D_ACT_DP" possible per line.Max. 32 IO devices changing

    during operation (partner ports)are supported.

    Device replacement without swapmedium

    Yes

    Send clock times 250 s, 500 s, 1 ms, 2 ms, 4 msadditionally with IRT with highperformance: 250 s to 4 ms in125 s frame

    Updating time 250 s to 512 ms; minimum valuedepends on preset communicationshare for PROFINET IO, on thenumber of IO devices and on theamount of configured user data,see PROFINET system description

    Address area

    - Inputs, max. 8 Kibyte

    - Outputs, max. 8 Kibyte

    User data per address area, max.- User data consistency, max. 1 024 byte

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    27/200

  • 8/14/2019 Simatic St70 Chap06 English 2011

    28/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/28 Siemens ST 70 2011

    Technical specifications(continued)

    DP master

    Number of connections, max. 16 16

    Services

    - PG/OP communication Yes Yes- Routing Yes; S7 routing Yes; S7 routing

    - Global data communication No No

    - S7 basic communication No Yes

    - S7 communication Yes Yes

    - S7 communication, as client Yes Yes

    - S7 communication, as server Yes Yes

    - Equidistance mode support Yes Yes

    - Isochronous mode Yes Yes

    - SYNC/FREEZE Yes Yes

    - Activation/deactivation of DPslaves

    Yes Yes

    - Direct data exchange(slave-to-slave communication)

    Yes Yes

    - DPV0 Yes Yes

    - DPV1 Yes Yes

    Transmission rate, max. 12 Mbit/s 12 Mbit/s

    Transmission rate, min. 9.6 kbit/s 9.6 kbit/s

    Number of DP slaves, max. 96 96

    Address area

    - Inputs, max. 6 Kibyte 6 Kibyte

    - Outputs, max. 6 Kibyte 6 Kibyte

    User data per DP slave

    - User data per DP slave, max. 244 byte 244 byte

    - Inputs, max. 244 byte 244 byte

    - Outputs, max. 244 byte 244 byte

    - Slots, max. 244 244

    - per slot, max. 128 byte 128 byte

    DP slave

    Number of connections 16 16

    Services

    - PG/OP communication Yes Yes

    - S7 routing Yes; With active interface Yes; With active interface

    - Global data communication No No

    - S7 basic communication No No

    - S7 communication Yes Yes

    - S7 communication, as client Yes Yes

    - S7 communication, as server Yes Yes

    - SYNC/FREEZE No No

    - Direct data exchange(slave-to-slave communication)

    No No

    - DPV1 No No

    - Status/control Yes; When interface active Yes; When interface active

    GSD file http://support.automation.siemens.com/WW/view/en/113652

    http://support.automation.siemens.com/WW/view/en/113652

    Transmission rate, min. 9.6 kbit/s 9.6 kbit/s

    Transmission rate, max. 12 Mbit/s 12 Mbit/s Automatic baud rate search No No

    Transfer memory

    - Inputs 244 byte 244 byte

    - Outputs 244 byte 244 byte

    Address areas, max. 32 32; Virtual slots

    User data per address area, max. 32 byte 32 byte

    User data per address area, ofwhich consistent, max.

    32 byte 32 byte

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    29/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/29Siemens ST 70 2011

    Technical specifications(continued)

    Isochronous mode

    Isochronous mode Yes; For PROFIBUS only Yes; For PROFIBUS only Yes; Via PROFIBUS DP orPROFINET interface

    Number of DP masters withisochronous mode

    2 3 2

    User data per isochronous slave,max.

    244 byte 244 byte 244 byte

    Equidistance Yes Yes Yes

    Shortest clock pulse 1 ms; 0.5 ms without use ofSFC 126, 127

    1 ms; 0.5 ms without use ofSFC 126, 127

    1 ms; 0.5 ms without use ofSFC 126, 127

    Max. cycle 32 ms 32 ms 32 ms

    CiR - Configuration in RUN

    CiR synchronization time, basic load 100 ms 100 ms 100 ms

    CiR synchronization time, time perI/O slave

    15 s; Time per I/O byte 15 s 15 s; Time per I/O byte

    programming

    Configuration software

    STEP 7 Yes Yes Yes

    Programming language

    STEP 7 Yes Yes Yes

    LAD Yes Yes Yes

    FBD Yes Yes Yes

    STL Yes Yes Yes

    SCL Yes Yes Yes

    CFC Yes Yes Yes

    GRAPH Yes Yes Yes

    HiGraph Yes Yes Yes

    Nesting levels 7 7 7

    Know-how protection

    User program protection/passwordprotection

    Yes Yes Yes

    Block encryption Yes; With S7 block PrivacyEMC

    Emission of radio interference acc. toEN 55 011

    Limit value class A, for use inindustrial areas

    Yes

    Limit value class B, for use inresidential areas

    No

    Dimensions

    Required slots 1 2 2

    Dimensions and weight

    Dimensions

    Width 25 mm 50 mm 50 mm

    Height 290 mm 290 mm 290 mm

    Depth 219 mm 219 mm 219 mm

    Weight Weight, approx. 0.7 kg 0.9 kg 900 g

    6ES7 414-2XK05-0AB0 6ES7 414-3XM05-0AB0 6ES7 414-3EM06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    30/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 414

    6/30 Siemens ST 70 2011

    Ordering data Order No. Order No.

    CPU 414-2 6ES7 414-2XK05-0AB0

    Work memory 1 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, slot for

    memory card, incl. slot numberlabels

    CPU 414-3 6ES7 414-3XM05-0AB0

    Work memory 2.8 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFIBUSDP master interface, slot formemory card, module slots for1 IF module, incl. slot numberlabels

    CPU 414-3 PN/DP 6ES7 414-3EM06-0AB0

    Work memory 4 MB, powersupply 24 V DC, MPI/PROFIBUSDP master interface, PROFINETinterface, slot for memory card,module slot for 1 IF module, incl.slot number labels

    Memory card RAM

    64 KB 6ES7 952-0AF00-0AA0

    256 KB 6ES7 952-1AH00-0AA0

    1 MB 6ES7 952-1AK00-0AA0

    2 MB 6ES7 952-1AL00-0AA0

    4 MB 6ES7 952-1AM00-0AA0

    8 MB 6ES7 952-1AP00-0AA0

    16 MB 6ES7 952-1AS00-0AA0

    64 MB 6ES7 952-1AY00-0AA0

    FEPROM memory card

    64 KB 6ES7 952-0KF00-0AA0

    256 KB 6ES7 952-0KH00-0AA01 MB 6ES7 952-1KK00-0AA0

    2 MB 6ES7 952-1KL00-0AA0

    4 MB 6ES7 952-1KM00-0AA0

    8 MB 6ES7 952-1KP00-0AA0

    16 MB 6ES7 952-1KS00-0AA0

    32 MB 6ES7 952-1KT00-0AA0

    64 MB 6ES7 952-1KY00-0AA0

    MPI cable 6ES7 901-0BF00-0AA0

    for connection of SIMATIC S7 andPG via MPI; 5 m in length

    IF 964-DP interface module 6ES7 964-2AA04-0AB0

    To connect an additional DP line;for CPU 414-3, CPU 414-3 PN/DP,CPU 416-3, CPU 416-3 PN/DP,

    CPU 417-4Slot number labels 6ES7 912-0AA00-0AA0

    1 set (spare part)

    Manual "SIMATIC S7-400programmable controller"

    incl. instruction list

    German 6ES7 498-8AA05-8AA0

    English 6ES7 498-8AA05-8BA0

    S7-400 operation list

    German 6ES7 498-8AA05-8AN0

    English 6ES7 498-8AA05-8BN0

    Manual "Communication forSIMATIC S7-300/-400"

    German 6ES7 398-8EA00-8AA0

    English 6ES7 398-8EA00-8BA0

    French 6ES7 398-8EA00-8CA0

    Spanish 6ES7 398-8EA00-8DA0

    Italian 6ES7 398-8EA00-8EA0

    SIMATIC manual collection J 6ES7 998-8XC01-8YE0

    Electronic manuals on DVD,multilingual: LOGO!, SIMADYN,SIMATIC bus components,SIMATIC C7,SIMATIC distributed I/O,SIMATIC HMI, SIMATIC Sensors,SIMATIC NET, SIMATIC PC BasedAutomation, SIMATIC PCS 7,SIMATIC PG/PC, SIMATIC S7,

    SIMATIC Software, SIMATIC TDC

    SIMATIC manual collectionupdate service for 1 year

    D 6ES7 998-8XC01-8YE2

    Current "Manual Collection" DVDand the three subsequentupdates

    Brochure "SIMATIC S7-400programmable controller -Design and application"

    German 6ES7 498-8AA00-8AB0

    English 6ES7 498-8AA00-8BB0

    D: Subject to export regulations AL: N and ECCN: 5D992

    J: Subject to export regulations AL: N and ECCN: EAR99S

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    31/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 414

    6/31Siemens ST 70 2011

    Ordering data Order No. Order No.

    I: Subject to export regulations AL: N and ECCN: EAR99H

    PROFIBUS bus components

    RS 485 bus connector with90 cable outlet

    Max. transfer rate 12 Mbit/s

    Without PG interface 6ES7 972-0BA12-0XA0

    With PG interface 6ES7 972-0BB12-0XA0

    RS 485 bus connector withangled cable outlet

    Max. transfer rate 12 Mbit/s

    Without PG interface 6ES7 972-0BA42-0XA0

    With PG interface 6ES7 972-0BB42-0XA0

    RS 485 bus connector with90 cable outlet forFast Connect system

    Max. transfer rate 12 Mbit/s

    without PG interface

    1 unit 6ES7 972-0BA52-0XA0

    100 units 6ES7 972-0BA52-0XB0

    with PG interface

    1 unit 6ES7 972-0BB52-0XA0

    100 units 6ES7 972-0BB52-0XB0

    RS 485 bus connector withaxial cable outlet

    For SIMATIC OP, for connection toPPI, MPI, PROFIBUS

    6GK1 500-0EA02

    PROFIBUS FastConnect buscable

    Standard type with special design

    for quick mounting, 2-core,shielded, sold by the meter, max.delivery unit 1000 m, minimumordering quantity 20 m

    6XV1 830-0EH10

    RS 485 repeater for PROFIBUS 6ES7 972-0AA02-0XA0

    Transfer rate up to 12 Mbit/s;24 V DC; IP20 enclosure

    PROFINET bus components

    IE FC TP standard cable GP 2x2 6XV1 840-2AH10

    4-core, shielded TP installationcable for connection to IE

    FC Outlet RJ45/ IE FC RJ45 Plug;PROFINET-compatible; with ULapproval;

    Sold by the meter

    FO standard cable GP (50/125) 6XV1 873-2A

    Standard cable, splittable, ULapproval, sold by the meter

    SCALANCE X204-2 IndustrialEthernet switch

    I 6GK5 204-2BB10-2AA3

    Industrial Ethernet Switches withintegral SNMP access, webdiagnostics, copper cablediagnostics and PROFINETdiagnostics for configuring line,star and ring topologies; four10/100 Mbit/s RJ45 ports and twoFO ports

    IE FC RJ45 plugs

    RJ45 plug connector for IndustrialEthernet with a rugged metalenclosure and integratedinsulation displacement contactsfor connecting Industrial EthernetFC installation cables

    IE FC RJ45 plug 180

    180 cable outlet

    1 unit 6GK1 901-1BB10-2AA0

    10 units 6GK1 901-1BB10-2AB0

    50 units 6GK1 901-1BB10-2AE0

    PROFIBUS/PROFINET buscomponents

    see Catalogs IK PI, CA 01

    For establishing MPI/PROFIBUS/PROFINET communication

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    32/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 416

    6/32 Siemens ST 70 2011

    Overview

    High-performance CPUs in the high-end performance range

    Applicable for plants with high requirements in the high-endperformance range

    Integrated PROFINET functions in CPU 416-3 PN/DP

    Technical specifications6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0

    Product type designation CPU416-3 PN/DP

    Product version

    Hardware product version 01

    Firmware version V5.0 V5.0 V6.0

    Associated programming package STEP7 V 5.3 SP2 or higher withHW update

    STEP7 V 5.3 SP2 or higher withHW update

    STEP7 V5.5 or higher/iMap V3.0 +iMap STEP7 Add-on V3.0 SP5 orhigher

    Supply voltages

    Rated value

    24 V DC No; Power supply via systempower supply

    Feeding of external backup voltageto CPU

    5 to 15 V DC 5 to 15 V DC 5 to 15 V DC

    Current consumption

    from backplane bus 5 V DC, max. 1.1 A 1.3 A 1.5 A

    from interface 5 V DC, max. 90 mA; at each DP interface 90 mA; at each DP interface 90 mA; at each DP interface

    Power losses

    Power loss, typ. 4 W 4.5 W 6.5 W

    Power loss, max. 7.5 W

    Backup battery

    Battery operation not relevant

    Backup current, typ. 125 A; valid up to 40C 125 A; valid up to 40C 125 A; (up to 40 C)

    Backup current, max. 550 A 550 A 450 A

    Memory

    Work memory

    integrated (for program) 2.8 Mbyte 5.6 Mbyte 8 Mbyte integrated (for data) 2.8 Mbyte 5.6 Mbyte 8 Mbyte

    expandable No No No

    Load memory

    expandable FEPROM Yes Yes Yes; with Memory Card (FLASH)

    expandable FEPROM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    integrated RAM, max. 1 Mbyte 1 Mbyte 1 Mbyte

    expandable RAM Yes Yes Yes; with Memory Card (RAM)

    expandable RAM, max. 64 Mbyte 64 Mbyte 64 Mbyte

    Backup

    present Yes Yes Yes

    with battery Yes Yes Yes; all data

    without battery No No No

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    33/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 416

    6/33Siemens ST 70 2011

    Technical specifications(continued)

    CPU-blocks

    DB

    Number, max. 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FB

    Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    FC

    Number, max. 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999 5 000; Number range: 0 to 7999

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    OB

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Nesting depth

    per priority class 24 24 24

    additional within an error OB 2 2 2

    CPU processing times

    for bit operations, min. 30 ns 30 ns 30 ns

    for word operations, min. 30 ns 30 ns 30 ns

    for fixed point arithmetic, min. 30 ns 30 ns 30 ns

    for floating point arithmetic, min. 90 ns 90 ns 90 ns

    Counters, timers and theirretentivity

    S7 counter

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset Z 0 to Z 7 Z 0 to Z 7 Z 0 to Z 7

    Counting range

    - lower limit 0 0 0

    - upper limit 999 999 999

    IEC counter

    present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    S7 times

    Number 2 048 2 048 2 048

    Retentivity

    - adjustable Yes Yes Yes

    - lower limit 0 0 0

    - upper limit 2 047 2 047 2 047

    - preset No times retentive No times retentive No times retentive

    Time range

    - lower limit 10 ms 10 ms 10 ms

    - upper limit 9 990 s 9 990 s 9 990 s

    IEC timer

    Present Yes Yes Yes

    Type SFB SFB SFB

    Number Unlimited (limited only by workmemory)

    6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    34/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 416

    6/34 Siemens ST 70 2011

    Technical specifications(continued)

    Data areas and their retentivity

    retentive data area, total Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Total working and load memory(with backup battery)

    Flag

    Number, max. 16 Kibyte 16 Kibyte 16 Kibyte; Size of bit memoryaddress area

    Retentivity available Yes Yes Yes

    Number of clock memories 8; (in 1 memory byte) 8; (in 1 memory byte) 8; (in 1 memory byte)

    Data blocks

    Number, max. 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000 10 000; Number range: 1 to 16000

    Size, max. 64 Kibyte 64 Kibyte 64 Kibyte

    Local data

    adjustable, max. 32 Kibyte 32 Kibyte 32 Kibyte

    preset 16 Kibyte 16 Kibyte 16 Kibyte

    Address area

    I/O address area

    overall 16 Kibyte 16 Kibyte 16 Kibyte

    Outputs 16 Kibyte 16 Kibyte 16 Kibyte of which, distributed

    - MPI/DP interface, inputs 2 Kibyte 2 Kibyte 2 Kibyte

    - MPI/DP interface, outputs 2 Kibyte 2 Kibyte 2 Kibyte

    - DP interface, inputs 8 Kibyte 8 Kibyte 8 Kibyte

    - DP interface, outputs 8 Kibyte 8 Kibyte 8 Kibyte

    - PN interface, inputs 8 Kibyte

    - PN interface, outputs 8 Kibyte

    Process image

    Inputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte

    Outputs, adjustable 16 Kibyte 16 Kibyte 16 Kibyte

    Inputs, preset 512 byte 512 byte 512 byte

    Outputs, preset 512 byte 512 byte 512 byte

    Consistent data, max. 244 byte 244 byte 244 byte

    Access to consistent data inprocess image

    Yes Yes Yes

    Subprocess images

    Number of subprocess images,max.

    15 15 15

    Digital channels

    Inputs 131 072 131 072 131 072

    Outputs 131 072 131 072 131 072

    Inputs, of which central 131 072 131 072 131 072

    Outputs, of which central 131 072 131 072 131 072

    Analog channels

    Inputs 8 192 8 192 8 192

    Outputs 8 192 8 192 8 192

    Inputs, of which central 8 192 8 192 8 192

    Outputs, of which central 8 192 8 192 8 192

    6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    35/200

    SIMATIC S7-400Central processing units

    Standard CPUsCPU 416

    6/35Siemens ST 70 2011

    Technical specifications(continued)

    Hardware configuration

    connectable OPs 63 63 95

    Central devices, max. 1 1 1

    Expansion devices, max. 21 21 21

    Multicomputing Yes; 4 CPUs max.(with UR1 or UR2)

    Yes; 4 CPUs max.(with UR1 or UR2)

    Yes; 4 CPUs max.(with UR1 or UR2)

    Interface modules

    Number of connectable IMs (total),max.

    6 6 6

    Number of connectable IMs 460,max.

    6 6 6

    Number of connectable IMs 463,max.

    4; IM 463-2 4; IM 463-2 4; IM 463-2

    Number of DP masters

    integrated 2 2 1

    via IM 467 4 4 4

    via CP 10; CP 443-5 Extended 10; CP 443-5 Extended 10; CP 443-5 Extended

    Mixed mode IM + CP permitted No; IM 467 cannot be used withCP 443-5 Ext.; IM 467 cannot beused with CP 443-1 EX40 inPN IO mode

    No; IM 467 cannot be used withCP 443-5 Ext.; IM 467 cannot beused with CP 443-1 EX40 inPN IO mode

    No; IM 467 not suitable for use withCP 443-5 Ext. and CP443-1 EX4x,EX20, GX20 (in PNIO mode)

    via interface module 0 1 1; IF 964-DP

    Number of pluggable S5 modules(via adapter capsule in centraldevice), max.

    6 6 6

    Number of IO controllers

    integrated 1

    via CP 4; Via CP 443-1 EX 41 in PN mode;max. 4 in central controller

    4; Via CP 443-1 EX 41 in PN mode;max. 4 in central controller

    4; No mixed operation of CP443-1EX40 and CP443-1 EX 41/EX20/GX20, max. 4 in central controller

    Number of operable FMs and CPs(recommended)

    FM Limited by number of slots andnumber of connections

    Limited by number of slots andnumber of connections

    Limited by number of slots ornumber of connections

    CP, point-to-point Limited by number of slots andnumber of connections

    Limited by number of slots andnumber of connections

    CP 440: Limited by number ofslots; CP 441: Limited by numberof slots and number of connections

    PROFIBUS and Ethernet CPs 14; Of which 10 CP or IM max. asDP master and PN controller

    14; Of which 10 CP or IM max. asDP master and PN controller

    14; In total max. 10 CPs as DPmaster and PN controller, of whichup to 10 IMs or CPs as DP masterand up to 4 CPs as PN controller

    Time

    Clock

    Hardware clock (real-time clock) Yes Yes Yes

    battery-backed and synchronizable Yes Yes Yes

    Resolution 1 ms 1 ms 1 ms

    Runtime meter

    Number 8 8 16

    Clock synchronization

    supported Yes Yes Yes to MPI, master Yes Yes Yes

    to MPI, slave Yes Yes Yes

    to DP, master Yes Yes Yes

    to DP, slave Yes Yes Yes

    in AS, master Yes Yes Yes

    in AS, slave Yes Yes Yes

    on Ethernet via NTP Via CP Via CP Yes; as client

    to IF 964 DP Yes Yes

    6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0

    Siemens AG 2011 Siemens AG 2011

  • 8/14/2019 Simatic St70 Chap06 English 2011

    36/200

    SIMATIC S7-400Central processing unitsStandard CPUsCPU 416

    6/36 Siemens ST 70 2011

    Technical specifications(continued)

    S7 message functions

    Number of login stations formessage functions, max.

    63; Max. 63 with ALARM_S andALARM_D (OPs); max. 12 with

    ALARM_8 and ALARM_P(e.g. WinCC)

    63; Max. 63 with ALARM_S andALARM_D (OPs); max. 12 with

    ALARM_8 and ALARM_P(e.g. WinCC)

    95; Max. 95 with Alarm_S/SQ andAlarm_D/DQ (OPs); max. 8 with

    Alarm, Alarm_8, Alarm_8P, Notifyand Notify_8 (e.g. WinCC)

    Symbol-related messages Yes Yes Yes

    SCAN procedure Yes

    Number of messages

    overall, max. 1 024 1 024 1 024

    Block related messages Yes Yes Yes

    Process diagnostic messages Yes

    Alarm 8-blocks Yes Yes Yes

    Process control messages Yes Yes Yes

    Test commissioning functions

    Status/control

    Status/control variable Yes Yes Yes; Up to 16 variable tables

    Forcing Forcing Yes Yes Yes

    Status block Yes Yes Yes; Up to 16 simultaneously

    Single step Yes Yes Yes

    Number of breakpoints 4 4 16

    Diagnostic buffer

    present Yes Yes Yes

    Number of entries, max. 3 200 3 200 3 200

    - adjustable Yes Yes Yes

    - preset 120 120 120

    Service data

    can be read out Yes

    Communication functions

    PG/OP communication Yes Yes Yes

    Data record routing Yes

    Routing Yes Yes Yes; S7 routing

    Global data communication

    supported Yes Yes Yes

    Size of GD packets, max. 54 byte 54 byte 54 byte

    S7 basic communication

    supported Yes Yes Yes

    User data per job, max. 76 byte 76 byte 76 byte

    S7 communication

    supported Yes Yes Yes

    as server Yes

    as client Yes

    User data per job, max. 64 Kibyte 64 Kibyte 64 Kibyte

    S5-compatible communication supported Yes; (via CP max. 10 and FC

    AG_SEND and FC AG_RECV)Yes; (via CP max. 10 and FCAG_SEND and FC AG_RECV)

    Yes