SIGTN Select Review 12-20-12

download SIGTN Select Review 12-20-12

of 42

Transcript of SIGTN Select Review 12-20-12

  • 7/30/2019 SIGTN Select Review 12-20-12

    1/42

    TNSEA 1-13

    March

    13

    Special Inspections Guide for Tennessee

    M i d d l e T e n n e s s e e S t r u c t u r a l E n g i n e e r s A s s o c i a t i o n

    P . O . B o x 4 0 7 1 1

    N a s h v i l l e , T N 3 7 2 0 4

  • 7/30/2019 SIGTN Select Review 12-20-12

    2/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 ii

    Preface1

    The Special Inspections Guide for Tennessee (SIGTN) is intended to be an introduction to and guide of2

    implementation for the Special Inspections as defined in Chapter 17 of the International Building Code.3

    Since there is a range of adopted building codes in Tennessee, the committee has written the document4

    to meet the requirements of the 2006, 2009 and 2012 editions. In the event of a conflict, the adopted5

    building code shall govern. The SIGTN lists individual parties responsibilities in the Special Inspection6

    process. The parties include owners; architects; structural engineers; mechanical, electrical and7

    plumbing engineers; other design professionals; building officials; contractors; and special inspectors.8

    9

    The SIGTN was created by the Code Advisory Committee of the Middle Tennessee Structural Engineers10

    Association (MTNSEA).11

    12

    Code Advisory Committee:13

    Don Yarbrough Chair14

    Jason Perry Secretary15Steve Anderson (Deceased)16

    Kirk Hodge17

    Wilburn Honeycutt18

    Jim Parker19

    Stanley Paseur20

    Charles Raths21

    22

    The Code Advisory Committee would like to thank everyone involved in the development and creation23

    of this document. In particular, the Code Advisory committee would like to specifically thank the24

    following individuals for their time and effort:25

    John Agee Donald Friedman26

    Jim Beaudoin Boyd Johnson27

    Dan Calhoun Ted Kisselovich28

    Phillip Cameron Rick Mote29

    Phil Collins Drew Underwood30

    31

    The Code Advisory Committee would also like to thank the Code Advisory Committee of the West32

    Tennessee Structural Engineers Association (WTNSEA) and East Tennessee Structural Engineers33

    Association (ETNSEA) for their review and comments throughout the creation of the guide. The34

    members of the WTNSEA and ETNSEA Committees include:35

    WTNSEA ETNSEA36

    Julie Furr Co-Chair Eugene Adams Chair37

    Jeremy Scallion Co-Chair Chris Myers38Bob Paullus39

    Kyle Maxwell40

    Yutian Shao41

    42

    43

  • 7/30/2019 SIGTN Select Review 12-20-12

    3/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 iii

    Disclaimer and Notice44

    While it is believed to be accurate, this information should not be used or relied upon for any specific45

    application without competent professional examination and verification of its accuracy, suitability, and46applicability by a licensed professional engineer or architect. The publication of the material contained47

    herein is not intended as a representation or warranty, on the part of the Tennessee Structural48

    Engineers Association or of any other person named herein, that this information is suitable for any49

    general or particular use or of freedom from infringement of any patent or patents. Anyone making use50

    of this information assumes all liability arising from such use.51

    52

    Caution must be exercised when relying upon other specifications and codes developed by other bodies53

    and incorporated by reference herein since such material may be modified or amended from time to54

    time subsequent to the printing of this edition. The TNSEA bears no responsibility for such material55

    other than to refer to it and incorporate it by reference at the time of the initial publication of this56

    edition.5758

  • 7/30/2019 SIGTN Select Review 12-20-12

    4/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 iv

    Dedication59

    60

    6162

    6364

    The members of the Code Advisory Committee respectfully dedicate this guide in memory of Steven65

    Charles Anderson, P.E., S.E., who passed away unexpectedly on April 28, 2011 at the age of 33. Through66

    his technical ability, leadership, and great sense of humor, Steve contributed greatly to the creation of67

    this guide. His advice, humor and knowledge will be sorely missed.68

    69

  • 7/30/2019 SIGTN Select Review 12-20-12

    5/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 v

    Table of Contents70

    Preface .............................................................................................................................................. ii71

    Disclaimer and Notice ....................................................................................................................... iii72

    Dedication ........................................................................................................................................ iv73

    Part 1 Glossary ................................................................................................................................174

    Part 2 Special Inspection Requirements ...........................................................................................475

    Introduction .............................................................................................................................................. 576

    Owner Responsibilities ............................................................................................................................. 577

    Registered Design Professional in Responsible Charge Responsibilities .................................................. 578

    Architect Tasks .......................................................................................................................................... 679

    Structural Engineer Tasks .......................................................................................................................... 780

    Mechanical, Electrical and Plumbing Systems Engineer Tasks ................................................................. 781

    Building Official Responsibilities ............................................................................................................... 882Contractor Responsibilities ....................................................................................................................... 883

    Special Inspector(s) Responsibilities ......................................................................................................... 984

    Part 3 Special Inspections Quick Reference .................................................................................... 1085

    Part 4 Suggested Minimum Special Inspector Qualifications ........................................................... 1286

    Part 5 Sample Documents .............................................................................................................. 2087

    Sample Document Introduction .............................................................................................................. 2188

    Statement of Special Inspections and Special Inspection Schedules...................................................... 2289

    Structural Observations Notification Letter ............................................................................................ 3190

    Contractors Statement of Responsibilities ............................................................................................ 3291

    Daily Special Inspection Report .............................................................................................................. 3392Weekly Special Inspection Report .......................................................................................................... 3493

    Special Inspection Discrepancy Notice ................................................................................................... 3594

    Final Structural Observation Letter......................................................................................................... 3695

    Final Special Inspection Report ............................................................................................................... 3796

    97

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 7/30/2019 SIGTN Select Review 12-20-12

    6/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 1

    Part 1 Glossary98

  • 7/30/2019 SIGTN Select Review 12-20-12

    7/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 2

    Unless otherwise noted, all definitions will be as defined by Chapters 2 and 17 of the International99

    Building Code (IBC).100

    101

    Approved Acceptable to the code official or authority having jurisdiction.102103

    Approved Agency An established and recognized agency regularly engaged in conducting tests or104

    furnishing inspection services, when such agency has been approved.105

    106

    Building Official The officer or other designated authority charged with the administration and107

    enforcement of this code, or a duly authorized representative.108

    109

    Construction Documents - Written, graphic and pictorial documents prepared or assembled for110

    describing the design, location and physical characteristics of the elements of a project necessary for111

    construction.112

    113

    Contractor The entity under a legal contract to construct the facility as shown in the contract114documents prepared by the Registered Design Professionals.115

    116

    Designated Seismic System Those architectural, electrical and mechanical systems and their117

    components that require design in accordance with Chapter 13 of ASCE 7 and for which the component118

    importance factor, Ip, is greater than 1 in accordance with Section 13.1.3 of ASCE 7.119

    120

    Intumescent Fire-Resistant Coatings Thin film liquid mixture applied to substrates by brush, roller,121

    spray or trowel which expands into a protective foamed layer to provide fire-resistant protection of the122

    substrates when exposed to flame or intense heat.123

    124

    Jurisdiction The governmental unit that has been given the responsibility of enforcing the building125code.126

    127

    Main Windforce-Resisting System An assemblage of structural elements assigned to provide support128

    and stability for the overall structure. The system generally receives wind loading from more than one129

    surface.130

    131

    Mastic Fire-Resistant Coatings Liquid mixture applied to a substrate by brush, roller, spray or trowel132

    that provides fire-resistant protection of a substrate when exposed to flame or intense heat.133

    134

    Registered Design Professional An individual who is registered or licensed to practice their respective135

    design profession as defined by the statutory requirements of the professional registration laws of the136

    state or jurisdiction in which the project is to be constructed.137

    138

    Registered Design Professional in Responsible Charge A registered design professional engaged by139

    the owner to review and coordinate certain aspects of the project, as determined by the building140

    official, for compatibility with the design of the building or structure, including submittal documents141

    prepared by others, deferred submittal documents and phased submittal documents. Generally, this142

    entity is the Architect.143

    144

  • 7/30/2019 SIGTN Select Review 12-20-12

    8/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 3

    Special Inspection Inspection of construction requiring the expertise of an approved special inspector145

    in order to ensure compliance with the Building Code and the approved construction documents.146

    Special Inspections do not include or waive the responsibility for the inspections required by the147

    Construction Documents, other sections of the Building Code, or referenced standards.148149

    Special Inspection, Continuous Special inspection by the special inspector who is present when and150

    where the work to be inspected is being performed.151

    152

    Special Inspection, Periodic Special inspection by the special inspector who is intermittently present153

    where the work to be inspected has been or is being performed.154

    155

    Special Inspector A qualified person employed or retained by an approved agency and approved by156

    the building official as having the competence necessary to inspect a particular type of construction157

    requiring special inspection.158

    159

    Sprayed Fire-Resistant Materials Cementitious or fibrous materials that are sprayed to provide fire-160resistant protection of the substrates.161

    162

    Structural Observation The visual observation of the structural system by a registered design163

    professional for general conformance to the approved construction documents. Structural observation164

    does not include or waive the responsibility for the inspection required by Chapter 1, 17, or other165

    sections of the Building Code.166

  • 7/30/2019 SIGTN Select Review 12-20-12

    9/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 4

    Part 2 Special Inspection Requirements167

  • 7/30/2019 SIGTN Select Review 12-20-12

    10/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 5

    Introduction168

    The International Building Code (IBC) Chapter 17, Structural Tests and Special Inspections, requires169

    Special Inspections for all projects with the exceptions listed below:170

    1. When exempted by the Building Official for work of minor nature and not required by the171Registered Design Professional in Responsible Charge.172

    2. Building components that do not require the services of a licensed Professional Engineer or173Architect.174

    3. Occupancy Group R-3 (one and two family dwellings) and Occupancy Group U structures that175are accessories to Occupancy Group R-3 structures.176

    177

    Special Inspections are defined by IBC as Inspectionrequiring special expertise to ensure compliance178

    with approved construction documents and referenced standards. The Special Inspection process is a179

    Quality Assurance program that is mandated by the Building Code. Special Inspections are relatively180

    new to Tennessee, first introduced in the International Building Code, 2000 Edition. Thus, many design181professionals, owners, contractors and building officials are unaware of the requirements and their182

    complexity. There also seems to be a wide variation in the interpretation of the provisions contained in183

    Chapter 17. This document outlines the basic responsibilities of all parties involved in a project and184

    provides sample documents that can be used to meet the IBC requirements.185

    186

    Special Inspections are not intended to alter, replace, or supersede the responsibilities of the Registered187

    Design Professionals. Variations from the construction documents or reviewed shop drawings are to be188

    reviewed by the Registered Design Professional of Record prior to implementation.189

    Owner Responsibilities190

    IBC Chapter 17 states that the Owner, or the Registered Design Professional in Responsible Charge191

    (RDPRC) acting as the owners agent, shall employ the Special Inspector(s) for the project. This removes192

    the inspection services from the contractors scope of services and eliminates any conflict of interest.193

    194

    The owner is also responsible for contracting with the design team. The code mandates Structural195

    Observations be performed by a structural engineer for certain high seismic and high wind design196

    conditions that are defined in the Structural Observation section of Chapter 17. Where Structural197

    Observations are required, the owner is responsible for engaging a Registered Design Professional to198

    perform said observations. The Registered Design Professional engaged is to be adequately qualified to199

    perform structural observations. Note that Structural Observations may also be performed by the200

    Structural Engineer.201

    202

    The owner shall engage a design professional to be the RDPRC. The RDPRC is often times a member of203

    the design team.204

    Registered Design Professional in Responsible Charge Responsibilities205

    Typically, the entity that fits the definition of the RDPRC is the Design Professional that has the primary206

    contract with the owner. It is common for this entity to be the Architect. Since a Registered Design207

  • 7/30/2019 SIGTN Select Review 12-20-12

    11/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 6

    Professional can only practice in their respective field of expertise, the tasks of the RDPRC shall be208

    delegated to the appropriate design professionals.209

    210

    Per IBC Chapter 17, the RDPRC shall prepare a Statement of Special Inspections. It is recommended that211 the Architect of Record, Structural Engineer of Record, and MEP Engineer of Records prepare the212

    architectural, structural, and MEP portions of the Statement of Special Inspections, respectively. It is213

    recommended that the Statement of Special Inspections be included in the respective disciplines214

    drawings. When included in the specifications or as a stand-alone document, they are often overlooked215

    or not given to the appropriate parties.216

    The Statement of Special Inspections must include:217

    1. The materials, systems, components and work required to have special inspections2182. The type and extent of each special inspection2193. The type and extent of each test2204. The additional wind and seismic tests required2215. Identification of the special inspection test frequency (periodic or continuous)222

    223In addition to the Statement of Special Inspections, it suggested that the RDPRC define the minimum224

    tests and inspections required for the project specific Statement of Special Inspections. This criteria may225

    be included as part of the drawings, project specifications or a stand alone document.226

    227

    The additional seismic testing is not required when the structure is assigned to a Seismic Design228

    Category (SDC) of A or B. The amount of seismic testing increases as the SDC increases.229

    230

    The additional wind testing is required when either a) the Exposure Category is C or D and the wind231

    speed is 110 mph or greater or b) the Exposure Category is B and the wind speed is 120 mph or greater.232

    Architect Tasks233

    Prepare a Statement of Special Inspections and establish testing and inspection criterion that234

    encompasses the following types of materials/construction.235

    1. Sprayed Fire-Resistant Materials2362. Mastic and Intumescent Fire-Resistant Coating2373. Exterior Insulation and Finish Systems (EIFS)2384. For projects designated a Seismic Design Category D, E or F:239

    a. Exterior wall panels and their anchorage240b. Suspended ceiling systems and their anchorage241c. Access floors and their anchorage242d. Steel storage racks and their anchorage (when I = 1.5 in accordance with Sec. 15.5.3 of243

    ASCE 7)244

    e. Designated Seismic Systems2455. For projects requiring additional wind testing:246

    a. Roof Cladding247b. Wall Connections to Roof and Floor Diaphragms and Framing coordinate with the248

    Structural Engineer249

    c. Fabrication and Installation of Impact Resistant Systems/Components250251

  • 7/30/2019 SIGTN Select Review 12-20-12

    12/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 7

    In addition to the Statement of Special Inspections, the Architect shall review the Special Inspection252

    Reports and address any indicated discrepancies.253

    Structural Engineer Tasks254

    Prepare a Statement of Special Inspections and establish testing and inspection that encompasses the255

    following types of materials/construction.256

    1. Steel Construction2572. Concrete Construction2583. Masonry Construction2594. Wood Construction2605. Soils in conjunction with the Geotechnical Engineer2616. Pile Foundations in conjunction with the Geotechnical Engineer2627. Pier Foundations in conjunction with the Geotechnical Engineer2638. For projects designated a Seismic Design Category C, D, E or F:264

    a. Seismic-Force-Resisting System2659. For projects requiring additional wind testing:266

    a. Roof Framing Connections267b. Wall Connections to Roof and Floor Diaphragms and Framing coordinate with the268

    Architect269

    c. Roof and Floor Diaphragm Systems270d. Wind-Force-Resisting System271e. Wind-Force-Resisting System Connections to the Foundation272

    273

    Perform Structural Observations required by the building code (Section 1709 of IBC 06 or Section 1710274

    of IBC 09). Prior to commencement of observations, the Structural Engineer shall submit to the Building275

    Official a written statement, the Statement of Structural Observations, identifying the frequency and276extent of the Structural Observations. At the conclusion of work, the Structural Engineer shall submit a277

    Final Structural Observation Statementto the Building Official that states that site visits have been made278

    and identify any deficiencies that to the best of the Structural Engineers knowledge have not been279

    resolved.280

    281

    In addition to the Statement of Special Inspections, the Structural Engineer shall review the Special282

    Inspection Reports and address any indicated discrepancies.283

    Mechanical, Electrical and Plumbing Systems Engineer Tasks284

    Prepare a Statement of Special Inspections and establish testing and inspection that encompasses the285 following types of materials/construction.286

    1. Smoke Control Systems2872. For projects designated a Seismic Design Category C or D:288

    a. HVAC ductwork that contains hazardous materials and its anchorage289b. Piping systems and mechanical units containing flammable, combustible or highly toxic290

    materials291

    c. Anchorage of electrical equipment used for emergency or standby power systems292

  • 7/30/2019 SIGTN Select Review 12-20-12

    13/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 8

    d. Vibration isolation systems where the construction documents require a nominal293clearance of or less between the equipment support frame and the restraint294

    e. Designated Seismic Systems2953.

    For projects designated a Seismic Design Category E or F:296 a. All of the systems required for Seismic Design Category C or D297

    b. Electrical Equipment298299

    In addition to the Statement of Special Inspections, the Mechanical, Electrical and Plumbing Systems300

    Engineer shall review the Special Inspection Reports and address any indicated discrepancies.301

    Building Official Responsibilities302

    Chapter 17 states that the Building Official has the following responsibilities.303

    1. Approve the special inspection agency by verifying the agencys objectivity, competence, and304independence305

    2. Keep records of all approvals3063. Keep records of required tests, inspections, and certificates of compliance for prefabricated307

    assemblies308

    4. Receive test reports of tests performed in accordance with the references listed in Chapter 35 of309the Building Code310

    5. Review the Statement ofSpecial Inspections prior to permit issuance3116. Review the Statement of Structural Observations, if required, prior to permit issuance3127. Receive the Contractors written Statement of Responsibility, if required3138. Receive the Special Inspection Reports3149. Review the Final Structural Observation Reportfrom the Structural Engineer prior to Certificate315

    of Occupancyissuance316

    10.Review the Final Special Inspection Report from the Special Inspector prior to Certificate of317Occupancyissuance318

    11.Accept duly authenticated reports from approved agencies in respect to the quality and manner319of use of new materials or assemblies320

    12.Approve fabricators, as required, to perform work without Special Inspections at the fabricators321shop.322

    323

    To aid the Building Official in the task of approving the Special Inspectors, suggested minimum324

    qualifications for Special Inspectors have been included as Part 4. Building Officials may elect to adopt325

    these qualifications or develop their own.326

    Contractor Responsibilities327

    The Contractor shall build the structure in accordance with the contract documents. The Contractor328

    shall notify the Special Inspector in a timely manner as determined by the Special Inspector of the work329

    being performed. The Contractor is to coordinate the required notice with the Special Inspector. The330

    contractor is to maintain, on site, a complete set of contract documents, including all addenda, as well331

    as a complete set of final submittals. The Special Inspector is to have access to these documents. The332

  • 7/30/2019 SIGTN Select Review 12-20-12

    14/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 9

    contractor shall maintain at the jobsite all Special Inspection Reports submitted by the Special Inspector333

    and provide these records to the Owner, RDPRC and the Building Official upon request.334

    335

    For projects that included additional seismic and/or wind inspections, the contractor responsible for a336 component designated as a seismic system or a wind system in the Statement of Special Inspections337

    shall submit a written Statement of Responsibilityto the Building Official and Owner. The Statement of338

    Responsibility shall include the acknowledgement of awareness of the requirements of the Statement of339

    Special Inspections.340

    341

    The Contractor shall keep work requiring special inspections accessible and exposed for special342

    inspection purposes until the completion of the required special inspections.343

    Special Inspector(s) Responsibilities344

    In addition to performing all of the Special Inspections indicated in the Statement of Special Inspections,345

    the Special Inspector has the following responsibilities.346

    1. Obtain Building Official approval of the agency to perform Special Inspections. The agency shall347provide documentation demonstrating the objectivity, competency, and independence of the348

    inspector for the particular type of construction. In addition, any possible conflicts of interest349

    shall be disclosed to the building official (including if the owner and contractor are the same350

    entity). See Part 4 for suggested minimum Special Inspector qualifications351

    2. Furnish reports to the Building Official, the Registered Design Professional in Responsible352Charge, and other parties as directed by the project requirements that indicate the work353

    inspected conforms to the approved construction documents354

    3. Immediately bring any deficiencies found to the attention of the Contractor for correction.355Notify the Building Official and Registered Design Professional in Responsible Charge of any356

    deficiencies not corrected prior to the completion of that phase of work3574. Submit the Final Special Inspection Reportdocumenting the required special inspections and the358

    corrections of any discrepancies found359

  • 7/30/2019 SIGTN Select Review 12-20-12

    15/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 10

    Part 3 Special Inspections Quick Reference360

  • 7/30/2019 SIGTN Select Review 12-20-12

    16/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 11

    Special Inspections Quick Reference361Owner362

    Contract with Design Professionals to provide construction administration services including Structural363Observations364

    Contract with a Special Inspector to provide Special Inspections365Registered Design Professional in Responsible Charge (Typically the Architect)366

    Verify that all Disciplines have prepared a Statement of Special Inspections367 Coordinate said statement with the Building Official368

    Architect369

    Prepare a Statement of Special Inspections relating to the architectural components370 Review the Special Inspection Reports and any indicated discrepancies371

    Structural Engineer372

    Prepare a Statement of Special Inspections relating to the structural components373 Perform Structural Observations as required by the building code374 Submit Statement of Structural Observations and Final Structural Observation Report to the Building375

    Official as required376 Review the Special Inspection Reports and any indicated discrepancies377

    MEP Systems Engineers378

    Prepare a Statement of Special Inspections relating to the MEP Systems components379 Review the Special Inspection Reports and any indicated discrepancies380

    Building Official381

    Approve the special inspection agency by verifying the agencys objectivity, competence, and382independence383

    Keep records of all approvals384 Keep records of required tests, inspections, and certificates of compliance for prefabricated assemblies385 Receive test reports of tests performed in accordance with Building Code references386 Review the Statement of Special Inspections and Statement of Structural Observations (if required) prior387

    to permit issuance388 Receive the Contractors written Statement of Responsibility, if required389 Receive Special Inspection Reports390 Review Final Special Inspection Report and Final Structural Observation Report (if required) prior to391

    certificate of authorization issuance392

    Accept reports from approved agencies for the quality and manner of use of new materials or assemblies393 Approve fabricators, as required, to perform work without Special Inspections at the fabricators shop.394

    Contractor395

    Adequately notify the Special Inspector of the work being performed396 Submit a written Statement of Responsibilityas required397 Build the structure in accordance with the approved construction documents398 Keep work requiring special inspections accessible and exposed for until special inspections are completed399

    SpecialInspector400 Obtain Building Official approval of the agency to perform Special Inspections401 Perform the required Special Inspections402 Furnish Special Inspection Reports to the Building Official and the RDPRC403 Bring any deficiencies to the attention of the Contractor. Notify Building Official and RDPRC if the404

    Contractor does not correct the deficiencies.405

    Submit a final report documenting the Special Inspections and correction of any discrepancies found.406

  • 7/30/2019 SIGTN Select Review 12-20-12

    17/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 12

    Part 4 Suggested Minimum Special Inspector Qualifications407

  • 7/30/2019 SIGTN Select Review 12-20-12

    18/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 13

    Suggested Special Inspector Minimum Qualifications408The Code Advisory Committee has compiled a list of inspector certifications and has determined the409

    minimum qualification level for each inspection/verification task. These minimum qualification levels410may be enforced by the Building Official or the Building Official may create their own qualification. The411

    Registered Design Professional in Responsible Charge may enforce these qualifications if the Building412

    Official does not. In the event of conflicting requirements, the more stringent would apply. The413

    Building Official and the RDPRC may accept other certifications at their discretion.414

    415

    Below is a list of organizations that provide certifications that have been included in this guide along416

    with their web site address. This list is not all inclusive and does not preclude acceptance of certification417

    by entities not listed.418

    419

    Board of Architectural and Engineering Examiners (www.tn.gov/commerce/boards/ae/)420

    ACI American Concrete Institute (www.concrete.org)421 AISC American Institute of Steel Construction (www.aisc.org)422

    ASNT American Society for Nondestructive Testing (www.asnt.org)423

    AWS American Welding Society (www.aws.org)424

    BIA Brick Industry Association (www.bia.org)425

    ICC International Code Council (www.iccsafe.org)426

    NCMA National Concrete Masonry Association (www.ncma.org)427

    NICET National Institute for Certification in Engineering Technologies (www.nicet.org)428

    PCI Precast/Prestressed Concrete Institute (www.pci.org)429

    PTI Post-Tensioning Institute (www.post-tensioning.org)430

    431

    Below is the acronyms and brief descriptions for each certification used.432

    433Professional Engineer Professional Engineer in the State of Tennessee434

    A Professional Engineer is an engineer registered as such with the State of Tennessee. To become a PE,435

    an engineer has met the education, experience and examination requirements as set forth by the436

    Tennessee Board of Architectural and Engineering Examiners. The PE is to have relevant experience437

    with the inspections being made.438

    439

    Engineer Intern Engineer Intern440

    An Engineer Intern is an engineer who has met the education requirements as set forth by the441

    Tennessee Board of Architectural and Engineering Examiners as well as passed the NCEES Fundamentals442

    of Engineering Examination. An Engineer Intern has not completed the requirements to become a443

    Professional Engineer. An Engineering Intern is to be registered with the Board of Architectural and444Engineering Examiners. The Engineering Intern is to have relevant experience with the inspections being445

    made.446

    447

    Registered Architect Registered Architect in the State of Tennessee448

    A Registered Architect is an architect registered as such with the State of Tennessee. To become an RA,449

    an architect has met the education, experience and examination requirements as set forth by the450

    Tennessee Board of Architectural and Engineering Examiners as well as completed the Intern-Architect451

    http://www.tn.gov/commerce/boards/ae/http://www.tn.gov/commerce/boards/ae/http://www.concrete.org/http://www.concrete.org/http://www.aisc.org/http://www.aisc.org/http://www.asnt.org/http://www.asnt.org/http://www.aws.org/http://www.aws.org/http://www.bia.org/http://www.bia.org/http://www.iccsafe.org/http://www.iccsafe.org/http://www.ncma.org/http://www.ncma.org/http://www.nicet.org/http://www.nicet.org/http://www.pci.org/http://www.pci.org/http://www.post-tensioning.org/http://www.post-tensioning.org/http://www.post-tensioning.org/http://www.pci.org/http://www.nicet.org/http://www.ncma.org/http://www.iccsafe.org/http://www.bia.org/http://www.aws.org/http://www.asnt.org/http://www.aisc.org/http://www.concrete.org/http://www.tn.gov/commerce/boards/ae/
  • 7/30/2019 SIGTN Select Review 12-20-12

    19/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 14

    Development Program of NCARB. The RA is to have relevant experience with the inspections being452

    made.453

    454

    ACI Grade 1 ACI Field Testing Technician Grade 1455 A Concrete Field Testing Technician Grade 1 is certified by American Concrete Institute and has456

    demonstrated knowledge and ability to perform basic field tests on freshly mixed concrete. This457

    requires a working understanding of: Temperature of freshly mixed concrete; Sampling freshly mixed458

    concrete; measuring concrete slump; Determining unit weight, yield and air content; Air content of fresh459

    concrete by the pressure method; Air content of fresh concrete by the volumetric method; and, field460

    making and curing concrete test specimens.461

    462

    ACI SI ACI Special Concrete Construction Inspector463

    A Concrete Construction Special Inspector is a person qualified to inspect and record the results of464

    concrete construction inspection based on codes and job specifications. This inspector requires being465

    certified by the American Concrete Institute Inspector Certification Program in accordance with its466

    testing, education and work experience requirements. Knowledge is required of concrete materials,467testing concretes, concrete construction practices, formwork, tolerances, reinforcements, embedments,468

    reading of plans, understanding the ACI 318 Building Code Requirements for Reinforced Concrete, and469

    other related aspects of concrete and its construction.470

    471

    ASIC Certified Erector AISC Certification for Erectors472

    AISC Certification for Erectors verifies has systems in place for: safety program compliant with473

    governmental regulations; welders are qualified according to AWS D1.1 and follow written procedures;474

    bolting procedure follow written requirements complying with Research Council on Structural475

    Connection Specifications; written procedures are in place for fall protection; crane operators are CCO476

    certified or equivalently trained or experienced; and, project-specific erection plans for hoisting and477

    erection requirements are field undertaken.478479

    AISC Certified Fabricator AISC Certification for Fabricators480

    AISC Certification For Fabricators verifies has systems in place for: contract document review; document481

    control for shop drawings and other requirements; purchasing of materials to comply with project and482

    fabrication specifications; welders are qualified according to AWS D1.1 and follow written procedures;483

    bolting procedure follow written requirements complying with Research Council on Structural484

    Connection Specifications; and, both inspection and quality assurance plans are implemented.485

    486

    ASNT Level II ASNT Level II Technician487

    An American Society for Nondestructive Testing (ANST) Level II Technician certified by the ANST Central488

    Certification Program (ACCP) requires an ACCP Level II, or an ACCP Level III for a given NDT testing489

    method. NDT test methods specified by ASNT are: Magnetic Particle Testing; Liquid Penetrant Testing;490

    Radiographic Testing; Ultrasonic Testing; Visual and Optical Testing; and, Electromagnetic Testing.491

    492

    AWS CWI AWS Certified Welding Inspector493

    A Certified Welding Inspector certified by the American Welding Society requires knowledge of: all494

    welding fundamentals; welding quality requirements; welding metallurgy; understand AWS welding495

    standards; procedure qualifications (equipment, joint preparation and geometry); welder performance496

    qualifications and compliance with standards and codes; perform inspections (visual and provide NDE497

  • 7/30/2019 SIGTN Select Review 12-20-12

    20/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 15

    inspection planning and verifying implementation); and, perform quality assurance surveillance.498

    499

    AWS CAWI AWS Certified Associate Welding Inspector500

    A Certified Associate Welding Inspector certified by the American Welding Society requires a knowledge501 of: basic welding fundamentals; verify standard compliance for base and filler materials; verify material502

    compatibility; verify welding equipment appropriateness and edge preparation and joint geometry;503

    provide visual inspections; and provide NDE planning.504

    505

    ICC SI: Masonry ICC Structural Masonry Special Inspector506

    An inspector requiring masonry knowledge of: materials; masonry placement and practices;507

    reinforcement and connector placement; grout placement; code interpretation; plan reading;508

    International Building Code; ASTM Masonry Standards; ACI 530 Building Code Requirements for Masonry509

    Structures; and, ACI 530.1 Specification for Masonry Structures.510

    511

    ICC SI: Prestressed ICC Prestressed Concrete Special Inspector512

    An inspector required to be certified as a Reinforced Concrete Special Inspector and requires overall513concrete knowledge of: concrete quality; reinforcement; prestressing and grouting; formwork; joints;514

    embeds; concrete placement, protection and curing; code interpretation; plan reading; the International515

    Building Code; ACI 318 Building Code Requirements for Structural Concrete and Commentary; PCI MNL -516

    116 Manual for Quality Control for Plants and Production of Structural Precast Concrete Products ;517

    appropriate ASTM prestressing steel standards; and, PTI post-tensioning standards for field518

    procedures(M10.3-00), unbonded tendons (M55.1-03), and rock and soil anchors (DC35.1-04).519

    520

    ICC SI: Reinforced Concrete ICC Reinforced Concrete Special Inspector521

    An inspector required to be certified by ACI as an Concrete Field Testing Technician - Grade 1, achieve522

    certification as an ICC Reinforced Concrete Special Inspector Associate (Associate lacks needed work523

    experience to qualify as a Reinforced Concrete Special Inspector), meet ACI education and work524experience requirements, and have overall concrete knowledge of: concrete quality; reinforcement;525

    formwork; joints; embeds; concrete placement, protection and curing; code interpretation; plan526

    reading; the international Building Code, ACI 318 Building Code Requirements for Structural Concrete527

    and Commentary; appropriate ASTM Standards; and, ICC Concrete Manual.528

    529

    ICC SI: Fireproofing Spray-applied Fireproofing Special Inspector530

    A certified inspector requiring fire-proofing knowledge of: materials; application preparation,531

    application procedures; testing of installed product; International Building Code; Association of the Wall532

    and Ceiling Industry (AWCI) Technical Manual 12-A for testing and inspection for sprayed-on materials;533

    and AWCI Technical Manual 12-B for testing and inspection for applied thin-filmed materials.534

    535

    ICC SI: Soils ICC Soils Special Inspector536

    A certified inspector requiring soils knowledge of: sampling; classification; evaluating laboratory test537

    results; reading grading plans; site preparation; fill monitoring and testing; the International Building538

    Code; and all applicable ASTM Standards.539

    540

    ICC SI: Steel and Bolts International Code Council Structural Steel and Bolting Special Inspector541

    A certified inspector requiring structural steel knowledge of: material sampling, testing and verification;542

    high-strength bolting; steel framing observations; code interpretation; plan reading; the International543

  • 7/30/2019 SIGTN Select Review 12-20-12

    21/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 16

    Building Code; and, AISC Steel Construction Manual including Specification for Structural Joints Using544

    ASTM A325 or A490 Bolts.545

    546

    ICC SI: Welding International Code Council Structural Welding Special Inspector547 An inspector required to be certified a Structural Steel and Bolting Special Inspector and requires weld548

    knowledge of: material sampling, testing and verification; structural steel, rebar reinforcement and549

    sheet steel welding; the ICC International Building Code; AWS Structural Welding Codes D1.1, D1.3 and550

    D1.4; and, ANSI/AWS A2.4-98 or A2.4-2007 Standard Symbols for Welding, Brazing, and Nondestructive551

    Examination.552

    553

    NCMA/BIA Inspector NCMA/BIA Masonry Inspectors554

    This inspector is be knowledgeable and familiar with NCMA TEK technical publications including TEK 3-555

    8A (Concrete Masonry Construction) and 18-3B (Concrete Masonry Inspection), and BIA Technical Notes556

    including Notes 3 (Overview of Building Code Requirements for Masonry Structures), 17A (Reinforced557

    Brick Masonry - Materials and Construction), and 39B (Testing for Engineered Brick Masonrt - Quality558

    Control).559560

    NICET Soils Level II NICET Soils Inspector Level II561

    This NICET certified inspector requires at least two years of experience with at least one year in soils562

    quality assurance and quality control. The other year of experience may be in related activities, or in563

    construction inspection and/or materials testing.564

    565

    NICET Soils Level III NICET Soils Inspector Level III566

    This NICET certified inspector requires Level II work experience plus having a total of three years567

    involving soils quality assurance and quality control as the primary activity. The other two years of568

    experience may be in construction and/or materials testing.569

    570NICET Concrete Level II NICET Concrete Inspector Level II571

    This NICET certified inspector requires two years of construction experience with at least one year572

    involving concrete testing, concrete quality assurance and concrete quality control. The other year of573

    experience may be in related activities or other specialties such as construction inspection and/or other574

    materials testing.575

    576

    PCI Inspector PCI Concrete Inspector577

    PCI plant personnel certification has three distinct levels. Level I requires six months of precast578

    concrete experience; understanding of basic plant quality control aspects; and certification by ACI in579

    Concrete Field Testing Technician Program Level 1. Level II requires Level 1 certification; at least one-580

    year of precast concrete experience; knowledge of strand tensioning/elongation requirements;581

    comprehension of accelerated curing; understanding of material control tests; and, welding basics.582

    Level III require two years of precast concrete industry experience; attendance at a special four-day PCI583

    school; and, PCI Level II certification.584

    585

    PTI Level 2 Bonded PTI Level 2 Bonded Inspector586

    Level 2 bonded P/T inspector is required to be certified by the Post-Tensioning Institute and requires587

    knowledge of: P/T systems and components; material properties and testing; installation procedures;588

    tendon stressing operations; grouting of system; inspection procedures and record keeping;589

  • 7/30/2019 SIGTN Select Review 12-20-12

    22/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 17

    construction documents; tendon corrosion protection; and, field safety. Work experience for a Level 2590

    bonded P/T inspector requires a total of 1500 hours in P/T (500 in placing, 500 in stressing and 500 in591

    grouting).592

    593 PTI Level 2 Unbonded PTI Level 2 Unbonded Inspector594

    Level 2 unbonded P/T inspector is required to be certified by the Post-Tensioning Institute and requires595

    knowledge of: P/T systems and components; installation procedures; tendon stressing operations;596

    inspection procedures and record keeping; construction documents; tendon corrosion protection; and,597

    field safety. Work experience for a Level 2 unbonded P/T inspector requires a total of 500 hours in P/T.598

    599

  • 7/30/2019 SIGTN Select Review 12-20-12

    23/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 18

    600

    601

  • 7/30/2019 SIGTN Select Review 12-20-12

    24/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 19

    602

    603

  • 7/30/2019 SIGTN Select Review 12-20-12

    25/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 20

    Part 5 Sample Documents604

  • 7/30/2019 SIGTN Select Review 12-20-12

    26/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 21

    Sample Document Introduction605

    The following sample documents provide a means to present the information required by Chapter 17.606

    As with many things, there are multiple ways to accomplish the various requirements of Chapter 17.607These documents present just one method and are not intended to preclude the use of other forms.608

    609

    There are three methods to present the Statement of Special Inspections: on the contract drawings, in610

    the specifications, as a stand-alone document. In order to eliminate lost documents, it is not611

    recommended that the Statement of Special Inspections be a separate document. Instead it is612

    recommended that it be included either on the contract drawings or in the spefications. The example613

    Statement of Special Inspections was created utilizing that implementation method. If the forms are to614

    be used as a stand-alone document, the RDPRC shall sign and seal the Statement of Special Inspections.615

  • 7/30/2019 SIGTN Select Review 12-20-12

    27/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 22

    Statement of Special Inspections and Special Inspection Schedules616

    617

    Edit form as required for the appropriate discipline. It is recommended that this be placed in the

    contract drawings.

  • 7/30/2019 SIGTN Select Review 12-20-12

    28/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 23

    618

  • 7/30/2019 SIGTN Select Review 12-20-12

    29/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 24

    619620

  • 7/30/2019 SIGTN Select Review 12-20-12

    30/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 25

    621622

  • 7/30/2019 SIGTN Select Review 12-20-12

    31/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 26

    623

  • 7/30/2019 SIGTN Select Review 12-20-12

    32/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 27

    624

  • 7/30/2019 SIGTN Select Review 12-20-12

    33/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 28

    625

  • 7/30/2019 SIGTN Select Review 12-20-12

    34/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 29

    626

  • 7/30/2019 SIGTN Select Review 12-20-12

    35/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 30

    627

  • 7/30/2019 SIGTN Select Review 12-20-12

    36/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 31

    Structural Observations Notification Letter628

    629

  • 7/30/2019 SIGTN Select Review 12-20-12

    37/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 32

    Contractors Statement of Responsibilities630

    631

  • 7/30/2019 SIGTN Select Review 12-20-12

    38/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 33

    Daily Special Inspection Report632

    633

  • 7/30/2019 SIGTN Select Review 12-20-12

    39/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 34

    Weekly Special Inspection Report634

    635

  • 7/30/2019 SIGTN Select Review 12-20-12

    40/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 35

    Special Inspection Discrepancy Notice636

    637

  • 7/30/2019 SIGTN Select Review 12-20-12

    41/42

    Special Inspection Guide for Tennessee

    Select Review 12/20/12 36

    Final Structural Observation Letter638

    639

  • 7/30/2019 SIGTN Select Review 12-20-12

    42/42

    Special Inspection Guide for Tennessee

    Final Special Inspection Report640