Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf ·...

20
English English Deutsch Français Español Warranty Information ............................................................................... 2 Product Registration ................................................................................ 2 Chemical Compatibility ............................................................................ 2 Safety Information ................................................................................... 2 Dimensions .............................................................................................. 2 Specifications .......................................................................................... 3 Installation ............................................................................................... 3 Wiring ...................................................................................................... 6 Battery Installation and Replacement ...................................................... 6 Operation................................................................................................. 7 Standard Menu Settings .......................................................................... 7 Security Codes ........................................................................................ 8 Totalizer Operation .................................................................................. 9 Automatic Calibration ............................................................................ 11 Flow K-Factor ........................................................................................ 11 Total K-Factor ........................................................................................ 12 Timebase ............................................................................................... 13 Decimal Point Placement ...................................................................... 13 Sensitivity .............................................................................................. 14 Speed .................................................................................................... 15 Flow and Totalizer K-Factor Selection ................................................... 15 K-Factor Charts ..................................................................................... 16 Troubleshooting ..................................................................................... 18 Ordering Information.............................................................................. 20 Operating Instructions Description Table of Contents The Signet 8150 Flow Totalizer is a battery-powered instrument capable of providing uninterrupted flow and total volume information for 4 years and beyond. The unique features of the 8150 include: Easy setup and display selection with 4-button keypad. User selectable security access to prevent unwanted programming changes. Displays flow rate from 0.001 to 9999 engineering units with an auto-ranging decimal point. Three totalizers, one permanent and two that are independently resettable. Displays elapsed time between operating periods. Integral mount and panel mount options. 3.6 V lithium batteries last 4 years nominal in most applications. Non-volatile memory stores all programming and totalizer values even when batteries are removed. Signet 8150 Flow Totalizer 3-8150.090-1 Rev. K 9/14 English *3-8150.090-1*

Transcript of Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf ·...

Page 1: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

English

• English• Deutsch• Français• Español

WarrantyInformation...............................................................................2ProductRegistration................................................................................2ChemicalCompatibility............................................................................2SafetyInformation...................................................................................2Dimensions..............................................................................................2Specifications..........................................................................................3Installation...............................................................................................3Wiring......................................................................................................6BatteryInstallationandReplacement......................................................6Operation.................................................................................................7StandardMenuSettings..........................................................................7SecurityCodes........................................................................................8TotalizerOperation..................................................................................9AutomaticCalibration............................................................................11FlowK-Factor........................................................................................11TotalK-Factor........................................................................................12Timebase...............................................................................................13DecimalPointPlacement......................................................................13Sensitivity..............................................................................................14Speed....................................................................................................15FlowandTotalizerK-FactorSelection...................................................15K-FactorCharts.....................................................................................16Troubleshooting.....................................................................................18OrderingInformation..............................................................................20

Operating Instructions

Description

Table of Contents

TheSignet8150FlowTotalizerisabattery-poweredinstrumentcapableofprovidinguninterruptedflowandtotalvolumeinformationfor4yearsandbeyond.Theuniquefeaturesofthe8150include:

• Easysetupanddisplayselectionwith4-buttonkeypad.• Userselectablesecurityaccesstopreventunwantedprogrammingchanges.• Displaysflowratefrom0.001to9999engineeringunitswithanauto-ranging

decimalpoint.• Threetotalizers,onepermanentandtwothatareindependentlyresettable.• Displayselapsedtimebetweenoperatingperiods.• Integralmountandpanelmountoptions.• 3.6Vlithiumbatterieslast4yearsnominalinmostapplications.• Non-volatilememorystoresallprogrammingandtotalizervaluesevenwhen

batteriesareremoved.

Signet 8150 Flow Totalizer

3-8150.090-1 Rev.K9/14 English

*3-8150.090-1*

Page 2: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

2 Signet 8150 Flow Totalizer

Caution / Warning / DangerIndicatesapotentialhazard.Failuretofollowallwarningsmayleadtoequipmentdamage,injury,ordeath

Electrostatic Discharge (ESD) / Electrocution DangerAlertsusertoriskofpotentialdamagetoproductbyESD,and/orriskofpotentialofinjuryordeathviaelectrocution.

Hand tighten only!

Hand Tighten OnlyOvertighteningmaypermanentlydamageproductthreadsandleadtofailureoftheretainingnut.

Do Not Use ToolsUseoftool(s)maydamageproductbeyondrepairandpotentiallyvoidproductwarranty.

Dimensions

RefertoyourlocalGeorgFischerSalesofficeforthemostcurrentwarrantystatement.

Allwarrantyandnon-warrantyrepairsbeingreturnedmustincludeafullycompletedServiceFormandgoodsmustbereturnedtoyourlocalGFSalesofficeordistributor.ProductreturnedwithoutaServiceFormmaynotbewarrantyreplacedorrepaired.

Signetproductswithlimitedshelf-life(e.g.pH,ORP,chlorineelectrodes,calibrationsolutions;e.g.pHbuffers,turbiditystandardsorothersolutions)arewarrantedoutofboxbutnotwarrantedagainstanydamage,duetoprocessorapplicationfailures(e.g.hightemperature,chemicalpoisoning,dry-out)ormishandling(e.g.brokenglass,damagedmembrane,freezingand/orextremetemperatures).

ThankyouforpurchasingtheSignetlineofGeorgFischermeasurementproducts.Ifyouwouldliketoregisteryourproduct(s),youcannowregisteronlineinoneofthefollowingways: • Visitourwebsitewww.gfsignet.com.

UnderService and SupportclickonProduct Registration Form

• Ifthisisapdfmanual(digitalcopy),click here

Chemical Compatibility

Warranty Information

Product Registration

Safety Information

Integral Mount

96 mm(3.8 in.)

96 mm(3.8 in.)

FRONT VIEW

106 mm(4.2 in.)

82 mm(3.2 in.)

Universal Mount

92 mm(3.6 in.)

97 mm(3.8 in.)

56 mm(2.2 in.)

41 mm (1.6 in.)

OptionalRearCover

Panel MountSIDE VIEW

102 mm(4.0 in.)

42 mm (1.7 in.)

60 mm (2.3 in.)

96 mm(3.8 in.)

Theretainingnutsofpaddlewheelsensorsarenotdesignedforprolongedcontactwithaggressivesubstances.Strongacids,causticsubstancesandsolventsortheirvapormayleadtofailureoftheretainingnut,ejectionofthesensorandlossoftheprocessfluidwithpossiblyseriousconsequences,suchasdamagetoequipmentandseriouspersonalinjury.Retainingnutsthatmayhavebeenincontactwithsuchsubstances,e.g.,duetoleakageorspilling,mustbereplaced.

Integral Mount

96 mm(3.8 in.)

96 mm(3.8 in.)

FRONT VIEW

106 mm(4.2 in.)

82 mm(3.2 in.)

Universal Mount

92 mm(3.6 in.)

97 mm(3.8 in.)

56 mm(2.2 in.)

41 mm (1.6 in.)

OptionalRearCover

Panel MountSIDE VIEW

102 mm(4.0 in.)

42 mm (1.7 in.)

60 mm (2.3 in.)

96 mm(3.8 in.)

Page 3: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

3Signet 8150 Flow Totalizer

SpecificationsGeneralCompatibility...................... Signet515,525FlowSensorsInputFrequencyRange..... 1to400HzAccuracy............................ ±0.5%ofreading

EnclosureDimensions........................ 1/4DIN(96mm×96mm×50mm) (3.8in.×3.8in.×2.0in.)Casematerial.................... PBTresinKeypadmaterial................. Sealed4-keysiliconrubber

Display: LCD type4-digitupperline................ Flowrate8-digitlowerline................. Threetotalizeroptions: PermanentTotalizer....... forlifeofinstrument Totalizer1...................... resettablefromkeypadorremote 30m(100ft) Totalizer2...................... ResettablewithsecuritycodeonlyDisplayContrast................ Automatic

ElectricalBattery............................... Two3.6Vlithiumthionylchloride, AA-size(UseSAFTLS14500 LithiumBatteriesorEquivalentOnly)Sensorpoweroutput......... +3.6VDC@20µABatterylife.......................... 4yearsnominal@50°C(122°F)LowBatteryindication....... BatterysymbolonLCDdisplayEnvironmentalOperatingTemperature...... -10°Cto65°C(14°Fto149°F)StorageTemperature......... -40°Cto100°C(-40°Fto212°F)RelativeHumidity.............. 0to95%,non-condensingRating................................ NEMA4X/IP65(frontpanel)

Shipping Weight.............. 0.5kg(1.1lbs.)

Quality StandardsCE,CUL,ULManufacturedunderISO9001forQuality,ISO14001forEnvironmentalManagementandOHSAS18001foroccupationalhealthandsafety.

ChinaRoHS(Gotowww.gfsignet.comfordetails)

Declaration of Conformity according to FCC Part 15ThisdevicecomplieswithPart15oftheFCCrules.Operationissubjecttothefollowingtwoconditions:(1)Thisdevicemaynotcauseharmfulinterference,and,(2)Thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation.

Panel cutout

92 x 92 mm(3.62 x 3.62 in.)

Output -

Output +

System Pwr

Loop -

System Pwr

Loop +

2

1

4

3

Sensr Gnd

(SHIELD)

Sensr IN

(RED)

Sensr V+

(BLACK)

7

6

5

quick-clips

gasketpanel

terminalsmountingbracket

latch

Panel MountInstallation Detail

The8150-1PpanelmountTotalizerisastandard¼DINpackage.Usea92×92mmpunchtooltomakethepanelcutout.Minimumspacingof25mm(1in.)betweenpanelunitsisrecommended.

Panel Mount Installation Detail

Installation

PanelCutout

PanelMountInstallationDetail

Page 4: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

4 Signet 8150 Flow Totalizer

InstallationIntegral Installation with Field Mount Totalizer

3-8150-P03-8150-P13-8150-T03-8150-V0

(3-8510-XX)

(3-8051-X)

(3-8150-1)

FlowTotalizer

IntegralMounting Kit

IntegralFlow Sensor

SignetFittings

Integral Mount

• LubricateO-ringswithanon-petroleumbased,viscouslubricant(grease)compatiblewiththesystem.

• Usinganalternating/twistingmotion,lowerthesensorintothefitting,makingsuretheinstallationarrowsontheblackcaparepointinginthedirectionofflow.

• Engageonethreadofthesensorcapthenturnthesensoruntilthealignmenttabisseatedinthefittingnotch.

Hand tighten the sensor cap.DO NOT use any tools on the sensorcap or the cap threads and/or fi ttingfl ange threads will be damaged,

1. Insertthewiresfromthesensorthroughtheyellowconduitbaseandlockingring.

2. Insertthelockingringintotheconduitbase,aligningitsothesquaretabisclosetotheconduitports.

3. Insertthemountingscrewintotheconduitbasesotheheadofthescrewpressesdownonthelockingringwhentightened.

4. Connectsensorwirestotheterminalconnectionsontheintegraltotalizerorterminalcover.

5. Removetheplasticpulltabsprotectingthebatteries,thiswillcausethetotalizerunittopowerup.

6. Forremoteassembly,connectoutputwirestoterminalcoveroutput.

7. Routetheoutputwiresthroughtheconduitportintheconduitbase.Usealiquid-tightconnectororconduitconnectortopreventmoisturefromenteringtheassembly.

8. Placetotalizerorcoverontoconduitbaseandtwisttolockinplace.

Conduit Base Assembly Detail

The Mounting Screw for the Locking Ring goes into the Conduit Base (not the Locking Ring) -- the screw head rests on the lip of the Locking Ring.

Do not use this hole.

Sensor wires

Locking Ring

Conduit Base

Conduit Ports

Mounting Screw

ConduitBase Kit

3-8150 Flow Totalizer

Square Tab

sensor bale

sensor cap

tab

blackconduit

cap

notch

Hand tighten only!

Plastic Sensor Installation Tips

Page 5: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

5Signet 8150 Flow Totalizer

UniversalConduit Base(3-8050)

Terminal Cover(4-3111)

Liquid-tight Connector(3-9000.392-1)

FlowTotalizer(3-8150-1)

IntegralFlow Sensor(3-8510)

SignetFittings

IntegralMounting Kit(3-8051-X)

Remote Field Mount on Wall

Thepartsidentifiedinbold typearerequiredfortheinstallation.Otherpartsareshownforreferenceonly.Use2-conductorshieldedcablenomorethan30m(100ft)long.

Remote Field mount on Pipe

FlowTotalizer

(3-8150-1)

SignetFittings

Standard MountPaddlewheel(P51530-X)

Universal Mounting Kit(3-8050)

NOTE: Pipe strapsnot included

Remote Installation with Panel Mount Totalizer

TotalizerPanel Mount(3-8150-1P)

SignetFittings

Standard MountPaddlewheel(P51530-X)

Installation

Page 6: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

6 Signet 8150 Flow Totalizer

1 2 3 4 5 6

+

-

+

-

RED#1 #2

Totalizer 1Remote reset

Connect shieldto Ground wire

Splice BLK and SHLDtogether outside of terminal

BLACK

SHIELD

515 525

Battery Installation and ReplacementWiringThewiringisidenticalforthepanelmountandthefieldmountversionsoftheTotalizer.• Onlyonewireshouldbeinsertedintoaterminal.Splice

doublewiresoutsidetheterminal.• External Reset for Total #1:Usenomorethan

30m(100ft)of2-conductortwisted-paircableconnectedtoadrycontact(forexample,anordinarydoor-bellbuttonorrelaycontact).

• OnlyTotalizer#1canberesetbytheexternalconnection.• Total#1willnotbedisplayedunlessitisthestandard

totalizerselection.

Instructions1. Remove10mm(3/8in.)ofinsulationfrom

sensorcableconductors.2. Pressdownonorangelevertoopenterminal.3. Insertwireintoterminaluntilithitsbottom.4. Releasethelevertosecurewire.

10 mm

Input WiringUsethiswiringschemeforSignetmodels515and525.

Terminal Function 1 SignalGround 2 Sensorsignal 3 OpenCollectorSignal 4 DCPowertosensor 5 Ground 6 Ext.Reset

Two3.6 V lithium thionyl chloride batteries,AA-size(7400-0011)areinstalledintheTotalizer.

NOTE: The8150willnotoperatewithstandard1.5Valkalinebatteries.USE3.6VSAFTLS14500LITHIUMBATTERIESOREQUIVALENTONLY!

CAUTION When replacing batteries,

remove and replace one battery at a time

Remove and replace this battery first.

1 2 3 4 5 6

Note: Lithium Batteries Dispose of properly!

Replace with 3.6 V Lithium battery

+ +

- -

1. Removepulltabsfromthebatteriestopowerupthe8150.2. Note:Observe polarity!Bothbatteriesshouldfacethe

samedirection.3. Whenthe“lowbattery”indicatorappearsonthedisplay,

bothbatteriesshouldbereplacedwithin90days.4. Removeandreplacebattery#1first,thenremoveand

replacebattery#2.Thisensuresthatallsettingsandtotalizervaluesaresaved.

5. Ifthelowbatterysymbolreappearsformorethan10secondsafterinstallingnewbatteries,onebatteryisreversed,orbattery#2wasinstalledbeforebattery#1.

6. Securethebatteriesbyfasteningthehook-and-loopstraps.

DISPOSE OF EXPENDED BATTERIES PROPERLY!Lithiumbatteriescontainhazardouschemicals.Disposeofbatteriesinaccordancewithlocalregulation.

Shipping Notice:Ifthebatterypulltabshavebeenremoved,removethebatteriesfromthetotalizerpriortoshipping.

Page 7: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

7Signet 8150 Flow Totalizer

Totalizersareshippedfromthefactorywiththesestandardsettings:

No Flow and ELAPSED TIME DisplayIftheflowstops,theFlowRatedisplaysthenumberofhourssinceflowwaslastdetected.ThisdisplaywillalternatewiththenormalTotalizedValueandstandard"noFLo"displayeveryfiveseconds.AnymovementoftherotorinthepipewillresettheELAPSEDTIMEdisplay.

The8150-1displayshowstheflowrateinlargenumeralsandatotalizervalueinsmallernumerals.Anyoneofthreedifferenttotalizerscanbeselectedasthestandarddisplay(Seepage9fordetailedinformationonthetotalizers).

Pressthe▲or▼keystoscrollthroughallthreetotalizervaluesduringnormaloperation.

Illustrated:Noflowfor3hours

Operation Standard Menu Settings

ENTER

5 sec.

Function Factoryset Description

AUTO CALIBRATION Nosetting Seepage11fordetailed

information.

FLOW K-FACTOR 60

Numberofsensorpulsespervolumetricunit;Refertosensormanual.

TOTAL K-FACTOR 1

Setthenumberofvolumetricunitspertotalizercount;seepage12.

TIMEBASE Minutes

Selectflowrateinseconds,minutes,hoursordays.Page13.

DECIMAL XXX.XSetthemaximumdecimalresolution.Page13.

SPEED 30s

Zeroto120secondsaveragingstabilizesreadingsinerraticflowconditions.Page15.

SENSITIVITY 6

MomentarilyoverridesSPEEDwhenflowratechangessignificantly.Page14.

SECURITY CODE 0-0-0-0

Setaprivatecodetopreventtampering.Page8.

DEFAULT TOTALIZER Permanent

Selectfromthreetotalizeroptions.Page9.

TOTALIZER #2 RESET

ResetTotalizer#2afterenteringthesecuritycode.Page9.

Page 8: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

8 Signet 8150 Flow Totalizer

Changing the Security Code

Thesecuritycodepreventsunauthorizedtamperingwithcalibrationandoperationalsettingsinthe8150.Thefactorystandardcodeis0-0-0-0.Changethecodetoany4-digitnumberbyfollowingthesesteps:

Example: Change the security code from the factory standard 0-0-0-0 to custom setting 1-0-0-1

NOTE:Record and store your security code in a safe place!

12 s

2 3

4 5

6 7

8

3x

3x

Enter Security code

1. HoldtheENTERkeyfor2seconds,thenenterthecurrentSECURITYCODE.Ifworkingwithanewunit,presstheENTERkeyagain.Thedisplayshowsthefirstmenuitem(AutoCal)

2. Pressthe▲keythreetimestoscrolltoSecCode.3. Press►toeditthecode.

Theleadingdigitonthedisplaywillflash.4. Pressthe▲keyonetimetoscrolltheflashingdigitto1.5. Pressthe►keythreetimestoadvancetheflashingelement

tothelastdigit.6. Pressthe▲keyonetimetoscrolltheflashingdigitto1.7. PresstheENTERkeytocompletetheeditprocess.8. Pressthe▲and▼keystogethertoexitthe

Calibratemenu,storethenewsettingsandreturntonormaloperation.

Using the Security Code• Anumericalcode(0-0-0-0to9-9-9-9)mustbeentered

beforeanyofthemenuselectionscanbemodified.• Thecodeissetat0000fromthefactory.Tochangethe

code,seeabove.• Tousethefactorysetting,completestep1andthenstep8

above.

Example: Enter security code of 1001:

1. HoldtheENTERkeyfor2seconds.Thedisplayshowsfactorystandardaccesscodeof0000,withthefirstzeroflashing.

2. Pressthe▲keyonetimetoscrolltheflashingzeroto1.3. Pressthe►keythreetimestoadvancetheflashing

charactertothelastplacevalue.4. Pressthe▲keyonetimetoscrolltheflashingzeroto1.5. PresstheENTERkey.Thedisplaynowshowsthefirstitem

intheEDITMENU.

ENTER

ENTER

Signet Total Flow

Signet Total Flow

Signet Total Flow

Signet Total Flow

Signet Total Flow1 2

4

5

3

3x

2 s

Page 9: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

9Signet 8150 Flow Totalizer

Totalizer Setup and OperationDuringnormaloperationthe8150displaystheflowrateandoneselectedtotalizervalue.Anyoneofthethreetotalizerscanbesetasthestandarddisplay:Theothertwototalizerscanbeviewedbypressingthekeypad.Thedisplaywillautomaticallyreturntothestandardselectionafterfiveminutes.

• ThePERMANENT TotalizerisidentifieddirectlyontheLCD.• Thistotalizerrecordsallinputfromthetimeofmanufacture.• Thepermanenttotalizercannotbereset.

Application:Thepermanenttotalizershouldbeselectedasthestandardifthesystemismonitoredandthetotalrecordedregularly.

• Total 1 (tot1)canberesetfromthekeypadorfromtheexternalRESET(seewiring,page6)withoutthesecuritycode.

• Total 1 isidentifiedbyaflashingdisplayeverysixseconds.

Application:UseTotal1tomeasurewaterusageforarecurringperiod,asforadailydischargevolume.

• Total 2 (tot2)canberesetonlybyenteringthesecuritycodeinthecalibrationmenu.

• Total 2 isidentifiedbyaflashingdisplayeverysixseconds.

Application:UseTotal2forextendedmeasurementperiods,asforamonthlydischargevolume.

Define the Standard TotalizerAnyofthethreetotalizerfunctionscanbesetasthestandarddisplay,orselectSCANtodisplayallthreetotalizersinsequence.ThePERMANENTtotalizeristhefactorystandardselection.

Example: Change the standard Totalizer from PERMANENT to Totalizer #1

1. PressENTERkeyfor2seconds.(Displayshowssecuritykeysymboland0-0-0-0.SetsecuritycodeandpressENTERkey.)

2. Press▲keytwotimes.Displayshows"deftot"andthe"PERMANENT"label.)

3. Press►key.(PERMANENTlabelbeginstoflash.4. Press▲keyonetime.Displaychanges

toflashing"tot1".5. PressENTERkeytocompletetheeditprocess.6. Press▲and▼keystogethertostorenewvalue

inthememory.7. Thedisplaywillshow"Storing"forafewseconds,

thenreturntonormaloperation.

NOTE:Thenewtotalizerselectionwillappearaftera5minutedelay.

2x

5 m

Enter security code2 s

1 2

3 4 5

6

Page 10: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

10 Signet 8150 Flow Totalizer

Resetting Totalizer 11. Press▲keytoscrollto"total 1" display.2. Pressandholdthe►keyuntilthedisplayshows

"rst tot1".Thetotalizerwillflashfor8secondsandthenitwillautomaticallyresetto00000000.• PresstheENTERkeywhilethedisplayisflashingtoresetimmediately.

• Whilethetotalvalueisflashing,youcancanceltheresetbypressing▲and▼keystogether.

• Totalizer#1willbedisplayedfor5minutesafterthereset,thenthestandardtotalizerselectionwillreturn.

• Pressthe▲or▼keytoscrollbacktothestandarddisplayimmediately.

External Reset:Seepage6:WiringforinformationonresettingTotalizer#1remotelyfromupto30metersdistance.

NOTE:WhenTotal#1isresetfromanexternalswitch,thedisplaywillnotshowtotalizer#1unlessithasbeensetasthestandardtotalizer.

Resetting Totalizer 2 Totalizer#2canberesetONLYbyenteringthesecuritycode.1. PressENTERkeyfor2seconds.(Displayshowssecurity

keysymboland0-0-0-0)2. Setthesecuritycodeintheflashingdisplayandthenpress

theENTERkey.3. Press▲keyonetime.(Displayshows"tot2reset")4. Press►key.Thetotalizervaluewillbeginflashing.

Thetotalizerwillautomaticallyresetto00000000in8seconds.Whilethedisplayisflashing,youcancanceltheresetbypressing▲and▼keystogether.

5. Press▲and▼keystogethertoreturntonormaloperation.

Saving Totalizer ValuesToconservebatterylife,totalizervaluesarestoredinthememoryevery12hours.Ifbothbatteriesareremovedfromtheunit,thetotalizersretainthelastsavedvalues,sotheunitmayloseseveralhoursofdata.Topreventthisloss,enterthesecuritycode,thenenteranymenuitemandstorethesetting.

Wheneverthe8150storesasetting,italsostoresallcurrenttotalizerdata:

1. Enterthesecuritycode.2. Pressthe▲keytoscrolltothelastiteminthemenu

(DEFAULTTOTALIZER)3. Pressthe►keytoentertheeditmode

(flashingdisplaymode)4. PresstheENTERkeytoretainthecurrentsettings.5. Pressthe▲and▼keyssimultaneouslytoinitiatethe

"Storing"function.Thebatteriescannowberemovedandreplacedwithoutlosinganytotals.

1 2

8 s 5 m

2 s

1 2 3

4

5

8 s

2 sEnter security code

Totalizer Setup and Operation

Pressthe▲and▼keyssimultaneouslyfromthemainmenutoreturntonormaloperation.

Aslongasanyelementisflashing,youcanabortthechangeandreturntotheoriginalvaluebypressing▲and▼keyssimultaneously.

Exit Without Changing?* Finished Editing?**

Page 11: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

11Signet 8150 Flow Totalizer

TheAutoCALfeatureallowstheTotalizertobeadjustedtomatchtheflowratetoanyexternalreference.• Flowinthepipeshouldbeasstableaspossibleforbest

results.• Iftheflowratedisplayiserratic,settheSPEED

(page15)to120secondsduringtheAutoCALprocedure.• Thetimebaseonthereferencemetermustbethesameas

the8150Totalizer.

Example: The Totalizer flow rate shows 60 GPM, while an external reference indicates a true flow rate of 70 GPM. Change the flow rate from 60 GPM to 70 GPM using AutoCAL.

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.AutoCAListhefirstiteminthemenu.

2. Pressthe►keytoselecttheAutoCALfunction.ThedisplaywillshowAutoCALandthecurrentflowratewillbeflashing.

3. Pressthe►keyagaintochangetheflowrate.Thedisplayshows"SetFlo"andthefirstdigitoftheflowratewillbeginflashing.

4. Pressthe►keytoadvancetheflashingelementtothe"6".

5. Pressthe▲keyonetimetochangethe"6"to"7".6. PresstheENTERkeytocompletetheautomatic

calibrationprocess.ThedisplayshowsanewK-Factorwiththefirstdigitflashing.ThisK-Factorisbasedonthechangeinflowrate.

7. PresstheENTERkeyagaintoacceptthenewvalue.NOTE:Ifthedisplayshows"ERR SetFlo" theprocedurewasunsuccessfulbecausethecalculatedK-Factorislessthan0.001orgreaterthan999999.VerifytheflowrateandstarttheAutoCALprocedurefromstep1.

8. Press▲and▼keystogethertostorethenewvalueinthememory.Thedisplaywillshow"storing"forafewseconds,thenreturntonormaloperation.

AutoCAL Calibration

Enter security code2 s

1 2

3 4 5

6 7

8

TheK-Factoristhenumberofpulsesgeneratedbytheflowsensorforeachmeasureofwaterthatmovespastthesensor.YourflowsensormanualcontainsK-FactordataintermsofU.S.gallonsandliters.LocatetheK-Factorthatmatchesyourpipesizematerial.Ifnecessary,youcanconverttheK-Factorintootherunitsofmeasure.TheminimumK-Factorvalueis0.001,maximumis999999.

Example: Change the Flow K-Factor from 060.000 to 095.000

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.(Factorydefaultis0-0-0-0)Thedisplayshowsthefirstiteminthemenu(AutoCAL).

2. Pressthe▼keytoscrolltotheFlowK-Factor(thedisplayshowsthecurrentK-Factorsetting).

3. Pressthe►keytoselecttheFlowK-Factorforediting.(ThefirstelementoftheK-Factorwillbeginflashing.)

4. Pressthe►key1timetoadvancetheflashingelementtothe"6".

5. Pressthe▲keythreetimestochangethe"6"to"9".6. Pressthe►keytoadvancetheflashingelementto

the"0."7. Pressthe▼keyfivetimestochangethe"0"to"5".8. PresstheENTERkeytoreturntothe

CALIBRATEmenu.9. Press▲and▼keystogethertostorethenewvalue

andreturntonormaloperation.

Flow K-Factor

2 s

1 2

3 4 5

6 7 8

9

Enter security code

**

****

Page 12: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

12 Signet 8150 Flow Totalizer

Total K-Factor

TheTOTALK-FactorisamultipleoftheFLOWK-Factor.UseittoprogramtheincrementalcountsizeoftheTotalizer.

Example:IftheflowRATEregistersinlitersperminute,thetotalizermaybesetto1(factorystandard),soitcountsin1-literincrements,oritmaybesetto1000soitcountsin1kiloliter(1m3)increments.ByconvertingtheFlowK-Factor,thetotalizercanalsobesettocountinotherengineeringunits.Seepage15foradditionalinformationaboutTotalK-Factoradjustments.

Example: Change the totalizer from 1-kiloliter increments to count in 10-kiloliter increments.

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.Thedisplayshowsthefirstiteminthemenu,AutoCAL.

2. Pressthe▼keytwotimestoscrolltotheTotalK-Factor.3. Pressthe►keytoselecttheTotalK-Factorforediting.

ThefirstelementoftheTotalK-Factorwillbeginflashing.4. Pressthe►keysixtimestoadvancetheflashingelementto

thedecimalpoint.5. Pressthe▼keyonetimetomovethedecimalpointone

positiontotheright.6. PresstheENTERkeytoreturntothemenu.7. Press▲and▼keystogethertoexitthemenuandreturn

tonormaloperation.Thedisplayshows"Storing"forafewseconds,thenreturnstothenormaloperatingdisplay.

ENTER

6x

2x2 s

1

3 4 5

6 7

2

Sicherheitscode eingeben

Adjusting the Flow K-FactorIftheTotalizeryieldsaconsistenterror,makecorrectionsbyeitherusingtheAutoCALfunction(page11)orbymanuallyadjustingtheFlowK-Factorbythepercentageoferror.AsmallerK-Factorincreasestheflowrate,whilelargerK-Factorsreducetheflowrate.

Example:• TheFlowK-Factorissetat480.19pulsespergallon.• Thetotalizerregisters10gallonswhentheactualvolumeisknowntobe11gallons.• Theerroris1gallondividedby10gallons,or-10%.(Thetotalizeriscounting10%low,andtheflowrateisreading10%slow.)• ReducetheFlowK-Factorby10%:480.19-10%=432.17.• ChangetheFlowK-Factorto432pulsespergallon.

Theresult:Thetotalizermustcount10%fewerpulsesfromtheflowsensortoregisteronegallon,soboththetotalizerandtheflowratewillincreaseby10%.

Flow K-Factor

Page 13: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

13Signet 8150 Flow Totalizer

Selectthetimebasefortheflowrate.Theavailableselectionsareseconds,minutes,hoursordays.

Example: Change the Timebase from MINUTES (factory standard) to DAYS

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.ThedisplayshowsthefirstitemintheCALIBRATEmenu,AutoCAL.

2. Pressthe▼keythreetimestoscrolltotheTimebase.3. Pressthe►keytoselecttheTimebaseforediting.4. Pressthe▲keytwotimetoscrollfromMINtoDAY.5. PresstheENTERkeytoreturntothemenu.6. Press▲and▼keystogethertoexitthemenuandreturn

tonormaloperation.Thedisplayshows"Storing"forafewseconds,thenreturnstothenormaloperatingdisplay.

Enter security code2 s

1

3 4 5

6

2

2x

3x

*

**

Timebase

Decimal Point for Flow Display

Selectthemaximumdecimalresolutionfortheflowratedisplay.Theavailableselectionsarehundredths(xx.xx),tenths(xxx.x)orwholenumbersonly(xxxx.).Thedecimalwillauto-rangedowntothissetting.• Ifthedecimalissettowholenumbers,theflowrate

displaywillnotauto-range.• Ifthedecimalissettotenths,theflowratedisplaywill

showtenthsupto999.9,thentheauto-rangewillswitchtowholenumbers(1000to9999.)

• Ifthedecimalissettohundredths,theflowratedisplaywillshowhundredthsupto99.99,thententhsfrom100.1to999.9,thenwholenumbersto9999.

Example: Change the maximum decimal display from hundredths to tenths:

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.Thedisplayshowsthefirstiteminthemenu,AutoCAL.

2. Pressthe▼keyfourtimestoscrolltotheDecimalsetting.Thedisplayshowsfourdashesandthecurrentdecimalsetting.

3. Pressthe►keytoselectthedecimalforediting.Thedecimalpointwillbegintoflash.

4. Pressthe▼keyonetimetomovetheflashingdecimalfromhundredthstotenths.

5. PresstheENTERkeytoreturntothemenu.Thedecimalwillstopflashing.

6. Press▲and▼keystogethertoexitthemenuandreturntonormaloperation.

7. Thedisplayshows"Storing"forafewseconds,thenreturnstothenormaloperatingdisplay.

Available Display Selections

Your Flow rate

will read on display as:

hundredths(XX.XX) 10.55 10.55

tenths(XXX.X) 10.55 10.6wholenumbers(XXXX.) 10.55 11

2 s

1

3 4 5

6

2

4xEnter Security code

**

*

Page 14: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

14 Signet 8150 Flow Totalizer

Sensitivity

TheSENSITIVITYsettingdetermineshowthe8150respondstosuddensurgesintheflowrate.It"overrides"theSPEEDfunctionjustlongenoughtoallowanactualchangeinflowratetobedisplayed,thenresumestheaveraging.Theresultisasmoothflowdisplayandaquickresponsetolargeshiftsintheflowrate.

No AVERAGING, no SENSITIVITY

AVERAGING and SENSITIVITY

AVERAGING only

10 s 2 s 20 s 30 s 40 s 50 s 60 s 70 s

No SPEED, no SENSITIVITY

SPEED and SENSITIVITY

SPEED only

No SPEED, no SENSITIVITY

SPEED and SENSITIVITY

SPEED only

WithSPEEDaveragingsetto0(zero)andwithSENSITIVITYsettozero,theflowratemaybeveryunstable.Thislinerepresentstheactualoutputoftheflowsensorasitrespondstounstableflowconditionsinthepipe.

WithSPEEDsetto60secondsandSENSITIVITYstillsettozerotheflowrateisstabilized,butasharpchangeinflowrateisnotrepresentedfor60secondsorlonger.(dottedgreenline).

WithSPEEDat60secondsandSENSITIVITYsetto6,theflowrateisstabilized,whilethesuddenshiftinflowisreflectedveryquickly(dottedblueline).

NOTE:TheSENSITIVITYfunctionisineffectiveiftheSPEEDfunctionissettozero(seconds).

No SPEED, no SENSITIVITY

SPEED and SENSITIVITY

SPEED only

ENTER

3x

Enter Security code2 s

1

3 4 5

6

2

Example: Change the SENSITIVITY from 5 to 8

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.Thedisplayshowsthefirstiteminthemenu,AutoCAL.

2. Pressthe▲keyoncetoscrolltoSENSITIVITY.ThedisplayshowsDISPSENSandthecurrentsensitivitysetting.

3. Pressthe►keytoselecttheSENSITIVITYforediting.ThecurrentSENSITIVITYsettingbeginsflashing.

4. Pressthe▲keythreetimestoscrollfrom5to8.5. PresstheENTERkeytoreturntothemenu.6. Press▲and▼keystogethertoexitthemenuandreturn

tonormaloperation.Thedisplayshows"Storing"forafewseconds,thenreturnstothenormaloperatingdisplay.

Page 15: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

15Signet 8150 Flow Totalizer

SpeedSPEEDaveragingservestosmoothoutfluctuationsintheflowratethatmaybecausedbyinadequatestraightpiperunsafterpumps,valves,andelbowsinthepipe.Theselectionsare0,7,15,30,60and120seconds.Thefactorystandardsettingis30seconds.

• Usefaster(0s-30s)averagingforwell-established,stableflowconditions.

• Useslower(60s-120s)averagingiftheflowconditionsareunstable.

Note: WhiletheSPEEDsettinghelpstosmoothoutthefluctuationscausedbypipingconditions,italsocausesadelayinshowingactualchangesinflowrate.TheSENSITIVITYfunction(section15)isdesignedtohelpoffsetthiseffect.

Example: Change the SPEED setting from 60 seconds to 30 seconds.

1. HoldtheENTERkeyfor2seconds,thenentertheSECURITYCODE.ThedisplayshowsthefirstitemintheCALIBRATEmenu,AutoCAL.

2. Pressthe▼keyfivetimestoscrolltoDISPSPEED.ThedisplayshowsDISPSPEED,the"sec"annunciator,andthecurrentspeedsetting.

3. Pressthe►keytoselecttheDisplayspeedforediting.Thecurrentspeedselectionbeginsflashing.

4. Pressthe▼keyonetimetoscrollfrom60secondsto30seconds.

5. PresstheENTERkeytoreturntothemenu.6. Press▲and▼keystogethertoexitthemenuandreturn

tonormaloperation.Thedisplayshows"Storing"forafewseconds,thenreturnstothenormaloperatingdisplay.

2 s

1

3 4 5

6

2

5xEnter Security code

*

**

Pages16-18provideK-FactorsfortheSignet515and525flowsensors.UsethistabletoconverttheK-Factortootherunitsofmeasure,andtosettheTotalK-Factor.

NOTE:ThemaximumK-Factoris999999.TheminimumK-Factoris0.001.

Flow and Total K-Factor Selection If you want the

FLOW RATE to read in:

and you want the TOTALIZER

to count in:

Set the Flow K-Factor to:

and set the Total

K-Factor to:

Liters Liters K(Liter) 1Liters Kiloliters K(Liter) 1000Liters cubicmeters K(Liter) 1000

cubicmeters cubicmeters K(Liter)x1000 1cubicmeters Megaliters K(Liter)x1000 1000Kiloliters Kiloliters K(Liter)x1000 1Kiloliters Megaliters K(Liter)x1000 1000Megaliters Megaliters K(Liter)x1000

0001

U.S.gallons U.S.gallons K(gal) 1U.S.gallons U.S.gallons

x1000K(gal) 1000

U.S.gallons cubicfeet K(gal) 7.4805U.S.gallons acre-inches K(gal) 27154U.S.gallons Acre-feet K(gal) 325848U.S.gallons Kiloliters K(gal) 264.2Acre-Inches Acre-Inches K(gal)x27154 1

Acre-Inches Acre-feet K(gal)x27154 12Acrefeet Acre-feet K(gal)x325848 1Acrefeet Acre-Inches K(gal)x325848 0.083cubicfeet cubicfeet K(gal)x7.4805 1

Page 16: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

16 Signet 8150 Flow Totalizer

K-Factor Charts515 Paddlewheel Flow SensorThefollowingcalibrationdataisreprintedfromtheinstructionmanualfortheSignet515Flowsensorforyourconvenience.

PIPESIZE(IN.)

FITTING515/8510-XX

U.S. GAL LITERS

SCH 80 PVC TEES FOR SCH 80 PVC PIPE

1/2 MPV8T005 520.12 137.42

3/4 MPV8T007 297.52 78.61

1 MPV8T010 172.07 45.46

1-1/4 MPV8T012 91.54 24.19

1-1/2 MPV8T015 62.22 16.44

2 MPV8T020 36.32 9.60

2-1/2 PV8T025 21.833 5.7683

3 PV8T030 13.541 3.5775

4 PV8T040 7.6258 2.0147

SCH 80 CPVC TEES FOR SCH 80 CPVC PIPE

1/2 MCPV8T005 520.12 137.42

3/4 MCPV8T007 297.52 78.61

1 MCPV8T010 172.07 45.46

1-1/4 MCPV8T012 91.54 24.19

1-1/2 MCPV8T015 62.22 16.44

2 MCPV8T020 36.32 9.60

SCH 80 PVC SADDLES FOR SCH 80 PVC PIPE

2 PV8S020 32.480 8.5812

2-1/2 PV8S025 21.833 5.7683

3 PV8S030 13.541 3.5775

4 PV8S040 7.6258 2.0147

6 PV8S060 4.1623 1.0997

8 PV8S080 2.3705 0.6263

10 PV8S100 1.5300 0.4042

12 PV8S120 1.0600 0.2801

SCH 80 PVC SADDLE ON SCH 40 PVC PIPE

2 PV8S020 27.350 7.2259

2-1/2 PV8S025 18.874 4.9866

3 PV8S030 12.638 3.3389

4 PV8S040 6.7282 1.7776

6 PV8S060 3.7297 0.9854

8 PV8S080 2.1527 0.5688

10 PV8S100 1.3500 0.3567

12 PV8S120 0.9600 0.2536

PIPESIZE(IN.)

FITTING515/8510-XX

U.S. GAL LITERS

CARBON STEEL TEES ON SCH 40 PIPE

1/2 CS4T005 370.20 97.808

3/4 CS4T007 212.06 56.027

1 CS4T010 141.14 37.289

1-1/4 CS4T012 60.655 16.025

1-1/2 CS4T015 45.350 11.982

2 CS4T020 26.767 7.0717

STAINLESS STEEL TEES ON SCH 40 PIPE

1/2 CR4T005 358.96 94.838

3/4 CR4T007 202.61 53.530

1 CR4T010 127.14 33.590

1-1/4 CR4T012 61.910 16.357

1-1/2 CR4T015 40.410 10.676

2 CR4T020 22.300 5.8917

GALVANIZED IRON TEES ON SCH 40 PIPE

1 IR4T010 104.54 27.619

1-1/4 IR4T012 62.979 16.639

11/2 IR4T015 46.688 12.335

2 IR4T020 29.459 7.7832

BRONZE TEES ON SCH 40 PIPE

1 BR4T010 104.54 27.619

1-1/4 BR4T012 62.979 16.639

1-1/2 BR4T015 46.688 12.335

2 BR4T020 29.459 7.7832

COPPER TEE FITTINGS ON COPPER PIPE SCH K

1/2 CUKT005 443.21 117.10

3/4 CUKT007 212.16 56.052

1 CUKT010 127.18 33.600

1-1/4 CUKT012 88.218 23.307

1-1/2 CUKT015 56.962 15.049

2 CUKT020 29.370 7.7595

COPPER TEE FITTINGS ON COPPER PIPE SCH L

1/2 CUKT005 414.41 109.49

3/4 CUKT007 191.09 50.485

1 CUKT010 119.84 31.662

1-1/4 CUKT012 85.451 22.576

1-1/2 CUKT015 55.160 14.573

2 CUKT020 28.605 7.5575

PIPESIZE(IN.)

FITTING515/8510-XX

U.S. GAL LITERS

STAINLESS STEEL WELDOLETS ON SCH 40 PIPE

2-1/2 CR4W025 18.800 4.9670

3 CR4W030 12.170 3.2153

4 CR4W040 6.9600 1.8388

5 CR4W050 5.2600 1.3897

6 CR4W060 3.6900 0.9749

8 CR4W080 2.1300 0.5627

10 CR4W100 1.3500 0.3567

12 CR4W120 0.9600 0.2536

CARBON STEEL WELDOLETS ON SCH 40 PIPE

2-1/2 CS4W025 18.800 4.9670

3 CS4W030 12.170 3.2153

4 CS4W040 6.9600 1.8388

5 CS4W050 5.2600 1.3897

6 CS4W060 3.6900 0.9749

8 CS4W080 2.1300 0.5627

10 CS4W100 1.3500 0.3567

12 CS4W120 0.9600 0.2536

COPPER/BRONZE BRAZOLETS ON SCH 40 PIPE

2-1/2 BR4B025 18.800 4.9670

3 BR4B030 12.170 3.2153

4 BR4B040 6.9600 1.8388

5 BR4B050 5.2600 1.3897

6 BR4B060 3.6900 0.9749

8 BR4B080 2.1300 0.5627

10 BR4B100 1.3500 0.3567

12 BR4B120 0.9600 0.2536

SCH 80 IRON SADDLES ON SCH 80 PIPE

2 IR8S020 32.360 8.5495

2-1/2 IR8S025 22.220 5.8705

3 IR8S030 13.420 3.5456

4 IR8S040 7.6600 2.0238

5 IR8S050 5.8600 1.5482

6 IR8S060 4.0900 1.0806

8 IR8S080 2.3300 0.6156

10 IR8S100 1.5300 0.4042

12 IR8S120 1.0600 0.2801

SCH 80 IRON SADDLE ON SCH 40 PIPE

2 IR8S020 26.820 7.0859

2-1/2 IR8S025 18.800 4.9670

3 IR8S030 11.990 3.1678

4 IR8S040 6.8500 1.8098

5 IR8S050 5.3300 1.4082

6 IR8S060 3.7600 0.9934

8 IR8S080 2.1300 0.5627

10 IR8S100 1.3500 0.3567

12 IR8S120 0.9600 0.2536

Page 17: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

17Signet 8150 Flow Totalizer

ThefollowingdataisreprintedfromtheSignet525MetalexFlowsensormanualforyourconvenience.

525 Metalex Flow Sensor515 Paddlewheel Flow Sensor (continued)

PIPESIZE FITTING

515/8510-XX

U.S. GAL LITERS

POLYPROPYLENE FITTINGS (DIN/ISO AND BS AND ANSI)

DN15 PPMT005 481.55 127.23

DN20 PPMT007 277.09 73.207

DN25 PPMT010 141.18 37.300

DN32 PPMT012 83.540 22.071

DN40 PPMT015 51.265 13.544

DN50 PPMT020 29.596 7.8193

DN65 PPMT025 20.658 5.4579

DN80 PPMT030 13.330 3.5218

DN100 PPMT040 8.7077 2.3006

DN125 PPMT050 5.0667 1.3386

DN150 PPMT060 3.6892 0.9747

DN200 PPMT080 2.0398 0.5389

PVDF FITTINGS (DIN/ISO AND BS AND ANSI)

DN15 SFMT005 420.87 111.19

DN20 SFMT007 228.15 60.277

DN25 SFMT010 136.70 36.116

DN32 SFMT012 79.294 20.950

DN40 SFMT015 43.490 11.490

DN50 SFMT020 25.908 6.8450

DN65 SFMT025 18.067 4.7732

DN80 SFMT030 12.357 3.2648

DN100 SFMT040 8.0599 2.1294

DN125 SFMT050 4.4312 1.1707

DN150 SFMT060 3.2271 0.8526

DN200 SFMT080 2.0360 0.5379

PVC FITTINGS (DIN/ISO) - EUROPE ONLY

DN15 PVMT005 486.18 128.45

DN20 PVMT007 242.85 64.160

DN25 PVMT010 148.64 39.270

DN32 PVMT012 85.125 22.490

DN40 PVMT015 51.855 13.700

DN50 PVMT020 29.750 7.8600

DN65 PVMT025 17.487 4.6200

DN80 PVMT030 12.491 3.3000

DN100 PVMT040 8.1377 2.1500

DN150 PVMT060 4.0878 1.0800

DN200 PVMT080 2.0439 0.5400

SCH 40S STAINLESS STEEL PIPE PER ANSI B36.19

K-FACTOR

PIPESIZE

PULSES/U.S. GAL

PULSES/LITER

1/2IN. 873.03 230.66

3/4IN. 515.41 136.17

1IN. 266.17 70.322

11/4IN. 148.84 39.324

11/2IN. 107.98 28.528

2IN. 64.808 17.122

21/2IN. 44.685 11.806

3IN. 28.579 7.5506

4IN. 16.302 4.3070

5IN. 10.237 2.7046

6IN. 7.0057 1.8509

8IN. 3.9641 1.0473

10IN. 2.4690 0.6523

12IN. 1.6894 0.4463

K-Factor Charts

Page 18: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

18 Signet 8150 Flow Totalizer

Troubleshooting

Display Condition Probable Cause Suggested Solutions

Batteriesaredeadormissing. Replacebothbatteries.

Pulltabshavenotbeenremoved. Removeplasticpulltabsprotectingthebatteries.

Theflowrateisgreaterthan“9999”.

1. Reducetheflowrate.2. ChangetheTimebasetoasmallervalue. (Example:Changefrom“Day”to“Hour”)3. Changetheflowunitstoalargermeasure. (Example:Changefrom“Liters”to“Gallons”) NOTE:IftheFlowK-Factorischanged,be

suretomakeacorrespondingchangetotheTOTALK-Factor.

8150isnotreceivingasignalfromtheflowsensor.

1. Thereisnoflowinthepipe.2. Flowsensorisnotturningduetoblockage

ordamage.3. Sensorwiringislooseorincorrect.

InAutoCal,thecalculatedK-Factorisoutsidetherangeofthe8150(lessthan0.001orgreaterthan99999).

Press►keytostartAutoCALprocedureagain.Makesurethattheflowrateenteredisaccurate.

Theflowratedisplayiserraticandnon-linear

Usuallycausedbyinadequatestraightpiperunupstreamofsensor.

1. Correctpipinglayouttoprovidemorestraightpipeupstreamofsensor.

2. SettheSPEEDtohighersettingtoaverageoutthefluctuationscausedbypipingconditions(seeSpeed,section14).

Bothbatteriesaretoodepletedtosafelystoresettings. Replacebattery#1,thenreplacebattery#2.

Page 19: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

19Signet 8150 Flow Totalizer

Notes

Page 20: Signet 8150 Flow Totalizer *3-8150.090-1* - Gilson Eng Manuals/Signet/8150_manual.pdf · 2016-04-25 · 3-8150-P0 3-8150-P1 3-8150-T0 3-8150-V0 (3-8510-XX) (3-8051-X) (3-8150-1) Flow

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090For the most up-to-date information, please refer to our website at www.gfsignet.com

3-8150.090RevK09/14English ©GeorgFischerSignetLLC2014

Mfr. Part No. Code Description3-8150-1 159000929 FlowTotalizer3-8150-1P 159000930 FlowTotalizer,PanelMount3-8150-P0 159000931 FlowTotalizersystem,Integral,for0.5to4in.pipes,PPhousing,BlkPVDFrotor,Titaniumpin3-8150-P1 159000932 FlowTotalizersystem,Integral,for0.5to8in.pipes,PPhousing,BlkPVDFrotor,Titaniumpin3-8150-T0 159001011 FlowTotalizersystem,Integral,for0.5to4in.pipes,naturalPVDFhousing,rotorandpin

Parts and AccessoriesMounting3-8050 159000184 Universalmountingkit3-0000.596 159000641 Heavydutywallmountbracket(forpanelmountonly)3-5000.598 198840225 Surfacemountbracket3-8050.395 159000186 Splashproofrearcoverforpanelmounttotalizer3-9000.392 159000368 Liquidtightconnectorkit(includes3connectors)3-9000.392-1 159000839 Liquidtightconnector,NPT(1connector)3-9000.392-2 159000841 Liquidtightconnector,PG13.5(1connector)3-8050.390-1 159001702 RetainingNutReplacementKit,NPT,Valox®

3-8050.390-3 159310116 RetainingNutReplacementKit,NPT,PP3-8050.390-4 159310117 RetainingNutReplacementKit,NPT,PVDF3-8050.392 159000640 Model200retrofitadaptor7400-0011 159000935 Lithiumbattery,3.6V,AAsizeNote:UseSaftLS14500LithiumBatteriesorequivalentONLY.5523-0222 159000392 Cable,twoconductorshielded,22AWG

Replacement parts for integral mount units3-8051 159000187 FlowSensorIntegralMountingKit,NPT,Valox®

3-8051-1 159001755 FlowSensorIntegralMountingKit,NPT,PP3-8051-2 159001756 FlowSensorIntegralMountingKit,NPT,PVDF3-8510-P0 198864504 Sensorfor0.5to4in.pipes,Polypropylenehousing,titaniumpin,BlackPVDFrotor3-8510-P1 198864505 Sensorfor5to8in.pipes,Polypropylenebody3-8510-T0 159000622 Sensorfor0.5to4in.pipes,naturalPVDFhousing,rotorandpin3-8510-V0 198864506 Sensorfor0.5to4in.pipes,PVDFbody

Ordering Information