Leaders in Life. Safety. Technology. Leaders in Life. Safety. Technology. Signaling Line Circuit

Transcript of Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and...

Page 1: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

Leaders in Life. Safety. Technology.Leaders in Life. Safety. Technology.

Signaling Line Circuit

Page 2: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

2Leaders in Life. Safety. Technology.

Section # 1

Review of style 4,

6 & 7 SLC loops.

Page 3: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

3Leaders in Life. Safety. Technology.

Quick-Reference Chart

Style

IDC / In NAC / Out SLC / NFN

Class B B

DClass A

Y

Z

4

6, 7

IDC = Initiating Device Circuits

NAC = Notification Appliance Circuits

Page 4: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

4Leaders in Life. Safety. Technology.

FACP

M M M

M M M

M M M

NFPA Style 4 SLC

Branch Line Resistor from End of Line to FACP

Shall Not Over 50 ohms per Branch

Twisted Unshielded Pair 12 to 18 AWG

SLC Distance

12 AWG 3810 M 16 AWG 1828 M

14 AWG 2895.6 M 18 AWG 1127 M

5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG)

Page 5: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

5Leaders in Life. Safety. Technology.

Isolator Application - Style 4 Riser

Max 25 standard devices between Isolators

Page 6: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

6Leaders in Life. Safety. Technology.

M M

M

M

MM

M

M

M

FACP

NFPA Style 6 SLC

Loop Resistor from End of Line to FACP

Shall Not Over 50 ohms

5000 ft ( 1500 M) for Shield Twisted Pair Cable

(12 to 18 AWG)

Twisted Unshielded Pair 12 to 18 AWG

SLC Distance

12 AWG 3810 M 16 AWG 1828 M

14 AWG 2895.6 M 18 AWG 1127 M

Page 7: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

7Leaders in Life. Safety. Technology.

Isolator Application - Style 6

Max 25 standard devices between Isolators

Page 8: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

8Leaders in Life. Safety. Technology.

M M

M

M

MM

M

M

M

FACP

Style 6 with Isolators

Page 9: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

9Leaders in Life. Safety. Technology.

Isolator Application - Style 7

• SLC address capacity of loop is reduced by 2

addresses for every isolator device in excess of 200.

Page 10: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

10Leaders in Life. Safety. Technology.

SLC Installation

SLC Loop Connections and Wiring

Page 11: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

11Leaders in Life. Safety. Technology.

(+) SLC Channel A

no connection

(-) SLC Channel A

NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030

Floating Shield

Page 12: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

12Leaders in Life. Safety. Technology.

Notifier System Basics – Types of Cables

Page 13: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

13Leaders in Life. Safety. Technology.

LED Operation

CLIP Mode FlashScan Mode

Control Panel

Device Standby Activated Standby Activated

Onyx Panels

Monitor Module

Control Module

Detector

Blink Red

Blink Green

Blink Red

Steady Red

Steady Green

Steady Red

Blink Green

Blink Green

Blink Green

Steady Red

Steady Green

Steady Red

FDM-1 Blink Red Steady Red Blink Red Steady Red

Page 14: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

14Leaders in Life. Safety. Technology.

Section # 2

Data Format and

Loop Capacity

Page 15: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

15Leaders in Life. Safety. Technology.

How many devices per SLC?

A

B

CLIP 99 DET/99 MOD

D

E

FLASHSCAN 159 DET/159 MOD

Page 16: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

16Leaders in Life. Safety. Technology.

Section # 3

Detectors

Page 17: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

17Leaders in Life. Safety. Technology.

Detectors

FSI 851 Ionization Detector

FSP851 Photoelectric Detector

FSP 851T Photo detector w/(135oF) Fixed Heat

FST 851 Fixed Heat detector (135oF)

FST 851R Fixed and Rate-of-rise (15oF/minute)

FAPT 851 Acclimate™ Photo/Heat detector

DNR/FSP 851 Duct Detector/ Photo, Low Flow

FSB200 Beam detector w/Test Function

FSL 751 Laser detector ( VIEW)

FSC 851 COPTIR Multi Sensor

Page 18: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

18Leaders in Life. Safety. Technology.

Detectors

Rotary Address Switches

Address = 33

Page 19: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

19Leaders in Life. Safety. Technology.

Section # 3.1

Bases

Page 20: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

20Leaders in Life. Safety. Technology.

Flash Scan Detector Bases

B501(A) Standard European flangeless mounting base Dia 4.0”

B210LP(A) Flangeless mounting base Dia 6.0”

B200S Sounder base,,

85dBA internal horn.

B224RB Detector base, relay.

B224BI Detector base, Isolator

Page 21: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

21Leaders in Life. Safety. Technology.

B501 or B210LP Flangeless mounting base

Page 22: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

22Leaders in Life. Safety. Technology.

B200S Sounder base

Page 23: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

23Leaders in Life. Safety. Technology.

B224RB Detector base, relay

Page 24: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

24Leaders in Life. Safety. Technology.

B224BI Detector base, Isolator

Page 25: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

25Leaders in Life. Safety. Technology.

Section # 4

Modules

Page 26: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

26Leaders in Life. Safety. Technology.

8

9 0

1

2

3

4

7

6

5

ADDRESSLOOP

8 9

01

2

3

4

5

67

ONES

8 910

11

12

13

14150

1

2

3

4

5

67

TENS

Monitor Modules and Control Modules

Monitor conventional alarm initiating device Circuits

FMM-1 Open Contact Class A or Class B

FMM-101 Open Contact Class B only

FDM-1 Dual Address Open Contact Class B only

FZM-1 Conventional Detectors Class A or B

FCM-1 Bell output circuit

FRM-1 Relay volt-free

NBG-12LX Addressable Manual Station

FMM-4-20mA 4-20mA Input Module

FTM-1 Telephone Module

0

10

11

12

1314 15 ADDRESS

LOOP

12

3

4

TENS ONES

6789

5

0 12

3

4

6789

5

Page 27: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

27Leaders in Life. Safety. Technology.

XP10-M

10 Class B Initiating Device Circuits

Uses 10 addresses

5 Class A IDC’s

Uses 5 addresses

Use for tamper & flow switches, 4 wire detectors,

pull stations

Page 28: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

28Leaders in Life. Safety. Technology.

XP6-MA

2-wire smoke detector circuits

6 Class B conventional detector circuits

3 Class A conventional detector circuits

Compatible with Honeywell & SSD detectors

Also with Cerberus,Kidde-Fenwal,Hochicki, & Simplex

Great for retrofit applications

Page 29: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

29Leaders in Life. Safety. Technology.

FZM-1 Interface Modules

FZM-1 Class A or B IDC, for zone of 2-wire smoke detectors or

heat detectors

Page 30: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

30Leaders in Life. Safety. Technology.

FMM-1 Monitor Modules

FMM-1 Class A or B IDC, for dry-contact input devices or zone of

four-wire smoke detectors

Page 31: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

31Leaders in Life. Safety. Technology.

FMM-101 Miniature Monitor Modules

FMM-101 Class B IDC, for dry-contact input devices or zone of

four-wire smoke detectors

Page 32: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

32Leaders in Life. Safety. Technology.

FDM-1 Interface Module

FZM-1 Class B IDC, for Heat Conventional Detector or Manual Pull Station

Page 33: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

33Leaders in Life. Safety. Technology.

FMM-4-20

4-20mA Analog Input Module

Page 34: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

34Leaders in Life. Safety. Technology.

Strategy

Focus on new applications

FMM-4-20mA Gas Detection Monitoring and Control

Pressure Monitoring in Pharmaceutical / Industrial

Air Pressurization in Staircase / Fan Controls

Temperature Monitoring in Data Centre or Critical

Process

UV Flame

Sensor

Gas Sensor

NFS2-3030

Page 35: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

35Leaders in Life. Safety. Technology.

FMM 4-20mA Module – Available Now

Process

Area

Smoke, exit points, pull stations, etc.

Gas DetectorsFlame Detectors

Safe

Area

Horns & Strobes

Page 36: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

37Leaders in Life. Safety. Technology.

Flash Control Modules

Control Module

FCM-1 Class A or B NAC, Speaker or Telephone

Page 37: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

38Leaders in Life. Safety. Technology.

XP6-C

6 Class B Notification Appliance Circuits

Uses 6 addresses

3 Class A NAC’s

Uses 3 addresses

Ratings:

63 watts @ 70.7 VAC per circuit

37.5 watts @ 25 VAC per circuit

3 amps @ 30 VDC per circuit

Page 38: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

39Leaders in Life. Safety. Technology.

FRM - 1 Class A or B NAC, for dry-contact output Dual Form-C

operation (DPDT) such as fans, dampers, control equipment, etc.

FRM - 1 Relay Modules

Page 39: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

40Leaders in Life. Safety. Technology.

XP6-R

6 Form-C relays

3A @ 30 VDC

0.9A @ 125 VAC

General purpose switching

Page 40: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

41Leaders in Life. Safety. Technology.

FTM-1 FlashScanTelephone Module

SLC Loop

FFT-7

Tele

ph

on

e

FTM - 1 Class A or B, used to connect a remote firefighter

telephone to a centralized telephone console

Page 41: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

42Leaders in Life. Safety. Technology.

Pull Stations

Dual Action

Key lock/reset

NBG-12LX

Addressable

Field replaceable, plug-in monitor module

Page 42: Signaling Line Circuit - CONTECH...FST 851 Fixed Heat detector (135oF) FST 851R Fixed and Rate-of-rise (15oF/minute) FAPT 851 Acclimate Photo/Heat detector DNR/FSP 851 Duct Detector

Leaders in Life. Safety. Technology.Leaders in Life. Safety. Technology.