Simply smart:First choice for standard applications
www.siemens.com/lowvoltage
Circuitbreakers_GB_Proof.indd 3Circuitbreakers_GB_Proof.indd 3 25.02.2008 7:37:07 Uhr25.02.2008 7:37:07 Uhr
-
Highlights at a glance
Flexibility All components can be combined in a modular way Available in 3- or 4-pole, fixed-mounted, plug-in or withdrawable design
Ease of use User-friendliness in planning, configuration, installation and operation Only a few components to cover the entire spectrum from 10 A to 1,600 A
Safety and reliability Conforms to international standards and approvals Compatibility and safe interaction between products and systems
Connecting sets
Accessories
1. 3VT1 circuit breaker 2. Circular conductor terminals with cover 3. Front connection 4. Rear connection 5. Auxiliary wiring terminals 6. Connecting busbars with increased pole spacing 7. Adapter to install on 35 mm DIN rail 8. Insulating barriers 9. Signaling switch10. Auxiliary switch11. Shunt trip unit12. Undervoltage trip unit13. Locking-type lever
14. Front hand drive unit15. Front hand drive unit16. Right side hand drive unit17. Left side hand drive unit18. Non-locking hand drive lever19. Locking hand drive lever20. Locking hand drive lever21. Hand drive bearing22. Hand drive bearing23. Telescopic extension shaft24. Extension shaft25. Mechanical interlocking26. Mechanical parallel switching
Auxiliary trips
Locking type lever
Switches
Hand drives
2
34
56
8
11 12
1
7
139
10
26
25
14 1516
17
23 24
21 22
18 19 20
Circuitbreakers_GB_Proof.indd 4Circuitbreakers_GB_Proof.indd 4 25.02.2008 7:39:52 Uhr25.02.2008 7:39:52 Uhr
-
Exchangeable electronic trip units: 3VT2 (250 A) to 3VT5 (1,600 A)
Wide range of electronic trip units coinciding with application loads Authorized persons can easily exchange electronic trip units on their own Adjustment range from 40 to 100 In A switch disconnector block can be used in place of electronic trip units as a switch disconnector in MCCB design, and to have access to the complete range of MCCB accessories
Wide range of operating mechanisms:
Rotary handles (front- or side-operated) Motor mechanism with or without cycle counter
3VT molded-case circuit breakers are an intelligent and cost-effective way to achieve high performance and availability. These 3VT circuit breakers feature a compact design to save space, thanks to the modular versatility of the circuit breakers ranging from 10 A to 1,600 A. You can choose either thermal-magnetic or electronic trip units. In addition, the entire range has only three families of internal accessories. The result: maximum benefit, minimum expense.
3VT molded-case circuit breakers Compact and safe up to 1,600 A
Technical features1
Rated current range from 10 A to 1,600 A Electronic overcurrent trip units from 250 A (3VT250) upwards 3- and 4-pole versions Fixed-mounted, plug-in and draw-out versions Wide range of standard external accessories Conforms to the following standards: IEC 60947-1, IEC 60947-2, IEC 60947-3
1 In cases where higher ratings and communications capabilities are required, please see SENTRON 3VL circuit breakers
Fra
Rat
Rat
Rat
Nu
Rating
Ratcap
End
Ov
Ou
Circuitbreakers_GB_Proof.indd 5Circuitbreakers_GB_Proof.indd 5 25.02.2008 7:40:28 Uhr25.02.2008 7:40:28 Uhr
-
Technical specifications
3VT1 3VT2 N 3VT2 H 3VT3 N 3VT3 H 3VT4 H 3VT5 H
Frame size maximum rated currentA 160 250 630 1,000 1,600
Rated current ln A 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160
100, 160, 200, 250 250, 315, 400, 500, 630
315, 630, 800, 1,000
630, 1,000, 1,250, 1,600
Rated insulation voltage Ui V 690 690 690 690 690
Rated operational voltage Ue V max. 690 V AC max. 690 V AC max. 690 V AC max. 690 V AC max. 690 V AC
Number of poles 3/4 3/4 3/4 3 3
Rated ultimate short-circuit break-ing capacity lcu up to 415 V AC/50 Hz
kA 25 36 65 36 65 65 55
Rated service short-circuit breaking capacity lcs up to 415 V AC/50 Hz
kA 13 18 36 18 36 36 36
Endurance Electrical 20,000 30,000 20,000 10,000 10,000
Mechanical 6,000 3,000 5,000 4,000 4,000
Overcurrent release Thermal- magnetic
trip unit
- - - -
Electronic
trip unit-
Outline Dimension Width 3-pole 75 mm 105 mm 140 mm 210 mm 210 mm
4-pole 100 mm 140 mm 185 mm - -
Height 130 mm 225 mm 275 mm 494 mm 494 mm
Depth 70 mm 117 mm 117 mm 157 mm 157 mm
Circuitbreakers_GB_Proof.indd 6Circuitbreakers_GB_Proof.indd 6 25.02.2008 7:40:50 Uhr25.02.2008 7:40:50 Uhr
-
Today, the economic success of industrial and infrastructure projects more than ever depends on the power supply a key aspect for availability, performance and productivity, and a lever to boost overall economic efficiency. Thats why choosing the right circuit breakers is so crucial to keeping expenses down while, at the same time, optimizing performance.
Highly efficient and economical: 3VT circuit breakers
With the new standard line of 3VT circuit breakers, Siemens offers an economic solution for the entire power range from 10 A to 1,600 A the smart solution to protect plants, capacitors, transformers and generators. Both for infrastructure applications as well as in the area of industrial switchgear technology,
3VT circuit breakers can be used as incoming and outgoing circuit breakers to distribute power in low-voltage switchgear. Available in several design variations, the modular circuit breakers are highly user-friendly, while also offering a high degree of safety and reliability.
Circuitbreakers_GB_Proof.indd 1Circuitbreakers_GB_Proof.indd 1 25.02.2008 7:36:30 Uhr25.02.2008 7:36:30 Uhr
-
Siemens AGIndustry SectorIndustry AutomationP.O. Box 48 4890327 NUREMBERGGERMANY
www.siemens.com/automation
Fax order +49 (911)978-3321 CD/Z1366
Company/department
Name
Street, ZIP/city/country
Telephone/Fax
E-mail
Information material
Please send the selected information material to the following address
DIS
TRIB
UTI
NG
SWIT
CH
ING
, PR
OTE
CTI
NG
&
MEA
SURI
NG
MA
NA
GIN
GPO
WER
DIS
TRIB
UTI
ON
SOFT
WA
RE
Power Management System
SIVACON switchboards
SIVACON busbar trunking systems
SIVACON cubicle systems
SENTRON circuit breakers
SENTRON switch disconnectors
SENTRON power monitoring devices
Dimensioning with SIMARIS design
Con guring, visualizing and controllingwith SIMATIC powercontrol
Totally Integrated Power
The information provided in this brochure contains merely general descriptions or characteristics of performance which in actual case of use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective char-acteristics shall only exist if expressly agreed in the terms of contract.All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.