What Is Side Stream Filtration?
• Side Stream Filtration is used to remove suspended solids and sludge from a closed loop system, including Biofilms and Pseudomonas (Bacteria)
• Amazon Filters generally specifies a cartridge system, but other technologies such as hydro-cyclones, separators etc are suitable for removing large debris, but lack the high efficiency of cartridges
![Page 3: Side Stream Filtration Systems](https://reader036.fdocuments.us/reader036/viewer/2022080213/55a0fe0f1a28ab1e2e8b4592/html5/thumbnails/3.jpg)
What Are The Sources of Contamination?
• Corrosion of pipework and components leads to abrasive wear, resulting in fouling of heat exchangers and valve malfunction
• The bacteria and biofilm can be chemically treated with biocides which stops bacteria growth, but the dead material (sludge) only adds to the re-circulating mass
• Amazon Filters Side Stream systems are a practical and cost effective solution to these problems
![Page 4: Side Stream Filtration Systems](https://reader036.fdocuments.us/reader036/viewer/2022080213/55a0fe0f1a28ab1e2e8b4592/html5/thumbnails/4.jpg)
Where We Fit Side Stream Filters
• Typical systems for side stream filtration are Low Temperature Hot Water (LTHW), Chilled Water (CHW) and Condenser Circuits
• Each system will generally have primary and secondary circuits, supplying radiators, heating coils and air conditioning units
• Examples - Kings Cross Station, Paddington Central, State Street Bank, Great Ormond St Hospital, New Olympic Stadium, T5 Heathrow
![Page 5: Side Stream Filtration Systems](https://reader036.fdocuments.us/reader036/viewer/2022080213/55a0fe0f1a28ab1e2e8b4592/html5/thumbnails/5.jpg)
What Is a Typical Closed Loop Circuit?
![Page 6: Side Stream Filtration Systems](https://reader036.fdocuments.us/reader036/viewer/2022080213/55a0fe0f1a28ab1e2e8b4592/html5/thumbnails/6.jpg)
Side Stream System Design
• 5 -15% of primary circuit flow rate• Amazon 60 Series Filter Housing• SupaSpun II and SupaGard Cartridges • 2 bar minimum working pressure, or booster
pumps may be required• Cartridge change–out recommended at 1bar
pressure differential• Typically installed inside Building Plant Room
![Page 7: Side Stream Filtration Systems](https://reader036.fdocuments.us/reader036/viewer/2022080213/55a0fe0f1a28ab1e2e8b4592/html5/thumbnails/7.jpg)
Main and Booster Pump Systems