Sheet List Table Sheet Number Sheet Title 34.00.00 Drawing ...
Transcript of Sheet List Table Sheet Number Sheet Title 34.00.00 Drawing ...
Scale
Sheet
Date
Drawing Name
1 : 2 @ A4
34.00.00Drawing Register
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
18 August 2021
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Timber Frame Terraced Houses
Sheet List Table
Sheet Number Sheet Title
34.00.00 Drawing Register
34.19.01Typical Uses
34.19.04Intertenancy Bracket
34.19.05 Vertical Cross Section
34.19.06 Wall Plan
34.19.07 Wall Plan - Panel Join
34.19.08 Wall Elevation
34.19.10 Foundation or Intermediate Floor Slab
34.19.20 Corner - Internal Linings both Sides
34.19.43 Wall Projection - Plan View
34.19.60 T-Junction - Internal Wall meeting Intertenancy Wall
34.19.61Intertenancy Wall meeting External Wall - Option 1
34.19.62 Intertenancy Wall meeting External Wall - Option 2
34.19.65 T-Junction - Intertenancy Wall meeting Internal Corner
34.19.67 X-Junction - Intersecting Walls
34.19.70Mid-Floor
34.19.80 Roof Valley
34.19.82Roof Ridge
34.19.83 Roof Parapet
34.19.84Roof Apron
34.19.90 Truss Section
34.19.94Sloping Roof End
34.19.95 Sloping Eave
34.19.96 Eave
36.19.50Deflection Head Detail (Less than 20mm)
Scale
Sheet
Date
Drawing Name
NTS
34.19.01Typical Uses
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Resene Construction Systems
Integra Lightweight Concrete
Intertenancy System
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
75
499
50
3
10
29
10
75mm Screw
45mm Screw
Intertenancy Dampner
Intertenancy Clip
50
Scale
Sheet Drawing Name
1 : 2 @ A4
34.19.04Intertenancy Bracket
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Date
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel,
these should be installed on every
2nd stud with the opposing timber
framed wall having the brackets
installed on the alternating studs
Scale
Sheet
Date
Drawing Name
1:30 @ A4
34.19.05Vertical Cross Section
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Refer to detail 34.19.10
Refer to detail 34.19.82
Refer to detail 34.19.70
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel,
these should be installed on every
2nd stud with the opposing timber
framed wall having the brackets
installed on the alternating studs
Scale
Sheet
Date
Drawing Name
NTS
34.19.06Wall Plan
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
AAC Adhesive to
panel join
2 Brackets per full size panel,
these should be installed on
every 2nd stud with the opposing
timber framed wall having the
brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 10 @ A4
34.19.07Wall Plan - Panel Join
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
Ensure 2 brackets per full size panel.
The location of these brackets in the roof
space do not have to meet the same
requirements as the liveable areas
Mineral Wool or other
appropriate method for
fire and acoustic
insulation/protection to
edge of Intertenancy
Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
6
0
0
1
2
0
0
1
2
0
0
Firestopping to end of Intertenancy
Wall to prevent horizontal spread of
fire
Scale
Sheet
Date
Drawing Name
1 : 20 @ A4
34.19.08Wall Elevation
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
AAC Adhesive
INTEGRA Lightweight Concrete
Intertenancy System
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.10Foundation or Intermediate Floor Slab
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
20
50
20
Acoustic/Fire
Rated Sealant
INTEGRA Lightweight
Concrete Intertenancy
System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.20Corner - Internal Linings both Sides
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
Facade
205020
INTEGRA Lightweight Concrete
Intertenancy System
Firestopping to edge of
Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.43Wall Projection - Plan View
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
205020
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel,
these should be installed on
every 2nd stud with the
opposing timber framed wall
having the brackets installed
on the alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.60T-Junction - Internal Wall meeting Intertenancy Wall
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
205020
Facade
INTEGRA Lightweight Concrete
Intertenancy System
Timber batten to prevent
Horizontal Fire Spread in the
cavity
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
System
Substrate
34.19.61Intertenancy Wall meeting External Wall - Option 1
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
1 : 5 @ A4INTEGRA Lightweight Concrete
Intertenancy System
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
205020
Facade
INTEGRA Lightweight Concrete
Intertenancy System
Mineral Wool or Ceramic Fibre
Cavity Insulation for fire and
acoustic insulation/protection
to edge of Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.62Intertenancy Wall meeting External Wall - Option 2
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
Firewall
20 50 20
INTEGRA Lightweight Concrete
Intertenancy System
Fire stopping to edge of
Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.65T-Junction - Intertenancy Wall meeting Internal Corner
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
205020
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Sheet Drawing Name
34.19.67X-Junction - Intersecting Walls
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
Scale
Date
Drawing Name
1 : 5 @ A4
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.70Mid-Floor
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
Mineral Wool or Ceramic
Fibre Cavity Insulation for
fire and acoustic
insulation/protection to
edge of Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.80Roof Valley
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
Mineral Wool or Ceramic
Fibre Cavity Insulation for
fire and acoustic
insulation/protection to
edge of Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.82Roof Ridge
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight
Concrete Intertenancy
System
Mineral Wool or Ceramic
Fibre Cavity Insulation for
fire and acoustic
insulation/protection to
edge of Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Ensure 2 brackets per full size
panel.
The location of these brackets in
the roof space do not have to
meet the same requirements as
the liveable areas
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.83Roof Parapet
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
35m
m
Building Underlay
Apron Flashing supplied and installed
by the main contractor, building
underlay wrapped over flashing
(75mm cover to cladding)
External Firewall
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Scale
Sheet
Date
Drawing Name
System
Substrate
1 : 2 @ A4
34.19.84Roof Apron
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Integra Facade System
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Mineral Wool or Ceramic
Fibre Cavity Insulation for
fire and acoustic
insulation/protection to
edge of Intertenancy Wall
Scale
Sheet
Date
Drawing Name
System
Substrate
1 : 2 @ A4
34.19.90Truss Section
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Integra Facade System
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight Concrete
Intertenancy System
RCS Intertenancy Bracket to
be installed so that is
staggered from the opoosing
wall
Mineral Wool or Ceramic
Fibre Cavity Insulation for
fire and acoustic
insulation/protection to
edge of Intertenancy Wall
Ensure 2 brackets per full size
panel.
The location of these brackets in
the roof space do not have to meet
the same requirements as the
liveable areas
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.94Sloping Roof End
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight
Concrete Intertenancy
System
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Facade
Small section of Integra to be cut and
installed to rafter ends. Fasten the
Integra to the panel before securing to
the rafter/truss ends
Firestopping to the cavity
where the Intertenancy
Wall is located
Integra Panel to be taken as closed to
the underside of the underlay as
possible, any gaps to be packed with a
Mineral Wool
Purlins should be not be continued
across the Intertenancy Wall
Scale
Sheet
Date
Drawing Name
1 : 2 @ A4
34.19.95Sloping Eave
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight
Concrete Intertenancy
System
Firestopping to the cavity
of the Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Facade
Integra Panel to be taken as closed to
the underside of the underlay as
possible, any gaps to be packed with a
Mineral Wool
Purlins should be not be continued
across the Intertenancy Wall
Scale
Sheet
Date
Drawing Name
1 : 5 @ A4
34.19.96Eave - Corrugated Iron
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped
System
INTEGRA Lightweight Concrete
Intertenancy System
Substrate
18 August 2021
Timber Frame Terraced Houses
INTEGRA Lightweight
Concrete Intertenancy
System
Firestopping to the cavity
of the Intertenancy Wall
2 Brackets per full size panel, these
should be installed on every 2nd stud
with the opposing timber framed wall
having the brackets installed on the
alternating studs
Facade
Integra Panel to be taken as closed to
the underside of the underlay as
possible, any gaps to be packed with a
Mineral Wool
Scale
Sheet
Date
Drawing Name
System
Substrate
1 : 2 @ A4
34.19.97Eave - Metal Tile
CONFIDENTIALITY: No part of this publication may be
reproduced or transmitted other than the intended use by
Resene Construction Systems without written consent from
the author.
TradeSpec™ and RenderSpec™ are Registered Trademarks, both Documents are available on the Resene Construction Systems
Integra Facade System
Integra Panel 50mm (20mm Cavity)1 November 2017
Plaster Systems AAC Adhesive to be used to Mortar all Panel
Joins
Cavity size to be 20-40mm wide
Studs to be located at a maximum of 600 centre and
dwangs/nogs at 800mm centres.
Where there is a need for fire-stopping, mineral wool or
ceramic fibre cavity insulation must be used, the
wool/insulation should have a minimum density of 100kg/m³,
or as specified by a fire engineer
Where fire separations meet other fire separations or fire
rated parts of external walls, they shall have the junction fire
stopped over its full length
The Integra Intertenancy System shall terminate as close as
possible to the external roof cladding and primary elements
providing roof support, with any gaps fully fire stopped