SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be...

8
GRIDTIED SOLAR INSTALLATION SUNNY DAYS DEMO SUNNY LN, SUNNYVILLE, JO 44444 SHEET INDEX PROJECT SITE G-001 SUNNY LN SUNNYVILLE, JO 44444 SUNNY DAYS DEMO ---- ---- 01/01/18 REVIEW ---- ---- RB CC TITLE SHEET SCOPE OF WORK PROJECT INFORMATION APPLICABLE CODES AREIAL VIEW VICINITY MAP INSTALL GRID-TIE PHOTOVOLTAIC SYSTEMS WITH AC SOLAR MODULES LOCATED ON TWO TILE ROOFS. AC CONNECTION IS MADE ON THE LOAD SIDE OF THE METER AT THE MAIN ELECTRICAL PANEL. MAJOR COMPONENTS OF THE SYSTEM CONSIST OF LISTED PV MODULES WITH FACTORY INSTALLED MICRO INVERTERS & PV MOUNTING SYSTEM. A NEW MONITORING IS PROVIDED AT THE REMOTE DISPLAY AND WEB BASED BROWSER VIA DATA CONNECTION TO THE CLIENT'S EXISTING INTERNET ROUTER. ALL WORK SHALL COMPLY WITH: (CURRENT YEAR) BUILDING CODE (CURRENT YEAR) ELECTRICAL CODE (CURRENT YEAR) MECHANICAL CODE (CURRENT YEAR) PLUMBING CODE (CURRENT YEAR) FIRE CODE ROOF MOUNTED PHOTOVOLTAIC MODULES ---- Printed: 5/9/2018 11:30 AM SHEET NUMBER: SHEET NAME: DRAWN BY: CHECKED BY: COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED ANSI "B" 11" X 17" (279 ラ 432) SHEET SIZE: PROJECT NAME: 0 .5 1 BELLINGHAM, WA 98226 PHONE: 360-255-0678 www.rbpowerdesign.com DATE DESCRIPTION REV 0 1 2 PROJECT ADDRESS: Logo STREE ADDRESS CITY, STATE ZIP PHONE NUMBER WWW.WEBSITE.BIZ X______________________ LIC # XXXXXXX EXP. XX/XX/XX CONTRACTOR G-001 TITLE SHEET G-100 SITE PLAN G-110 ROOF PLAN E-001 NOTES AND SYMBOLS E-110 ROOF ELECTRICAL PLAN E-600 SINGLE LINE DRAWING E-700 LABELS 1 OF 2 MODULE WATTAGE (Wp DC): 327 TOTAL MODULES: 23 SYSTEM SIZE (Wp DC): 7521 INVERTER WATTAGE (Wp AC): 320 INVERTER QUANTITY: 23 MAX OUTPUT (Wp AC) : 7360 ARRAY LOCATION: ROOF ARRAY TILT ANGLE (ー): 13 & 12 ARRAY AZIMUTH: 191 & 281

Transcript of SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be...

Page 1: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

GRIDTIED SOLAR INSTALLATION SUNNY DAYS DEMO

SUNNY LN, SUNNYVILLE, JO 44444

SHEET INDEX

PROJECT SITE

G-001

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

TITLE SHEET

SCOPE OF WORK

PROJECT INFORMATIONAPPLICABLE CODES

AREIAL VIEW

VICINITY MAP

INSTALL GRID-TIE PHOTOVOLTAIC SYSTEMS WITHAC SOLAR MODULES LOCATED ON TWO TILEROOFS. AC CONNECTION IS MADE ON THE LOADSIDE OF THE METER AT THE MAIN ELECTRICALPANEL. MAJOR COMPONENTS OF THE SYSTEMCONSIST OF LISTED PV MODULES WITH FACTORYINSTALLED MICRO INVERTERS & PV MOUNTINGSYSTEM. A NEW

MONITORING IS PROVIDED AT THE REMOTEDISPLAY AND WEB BASED BROWSER VIA DATACONNECTION TO THE CLIENT'S EXISTINGINTERNET ROUTER.

ALL WORK SHALL COMPLY WITH:(CURRENT YEAR) BUILDING CODE(CURRENT YEAR) ELECTRICAL CODE(CURRENT YEAR) MECHANICAL CODE(CURRENT YEAR) PLUMBING CODE(CURRENT YEAR) FIRE CODE

ROOF MOUNTEDPHOTOVOLTAIC

MODULES

----

Prin

ted:

5/9

/201

8 11

:30

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTORG-001 TITLE SHEETG-100 SITE PLANG-110 ROOF PLANE-001 NOTES AND SYMBOLSE-110 ROOF ELECTRICAL PLANE-600 SINGLE LINE DRAWINGE-700 LABELS 1 OF 2

MODULE WATTAGE (Wp DC): 327TOTAL MODULES: 23SYSTEM SIZE (Wp DC): 7521INVERTER WATTAGE (Wp AC): 320INVERTER QUANTITY: 23MAX OUTPUT (Wp AC) : 7360ARRAY LOCATION: ROOFARRAY TILT ANGLE (°): 13 & 12ARRAY AZIMUTH: 191 & 281

Page 2: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:30

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

G-100

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

SITE PLAN

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 3: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:31

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

G-110

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

ROOF PLAN

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 4: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:32

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

PV MODULE

MID CLAMP

END CLAMP

GROUND LUG

TILE MOUNT

COMP MOUNT

84" RAIL

126" RAIL

RAIL COUPLING

ACTIVATIONJ-BOX

DISCONNECT

INVERTER

WEEB GROUND CLIP

GROUND STRAP

METERMAIN PANEL

162" RAIL

SYMBOL LEGEND

CABLE CLIP - MODULE

CABLE CLIP - RAIL

NEGATIVE CABLECONNECTOR

POSITIVE CABLECONNECTOR

A

ELECTRICAL NOTES FOR NEW PHOTOVOLTAlC SYSTEM

1.THIS PROPOSED SOLAR ELECTRIC SYSTEM IS INTENDED TO OPERATE INPARALLEL WITH POWER RECEIVED FROM THE UTILITY SERVICE PROVIDER.

2. THE PHOTOVOLTAIC SOURCE CIRCUITS AND PHOTOVOLTAlC OUTPUTCIRCUITS OF THIS PROPOSED SOLAR SYSTEM SHALL NOT BE CONTAINED INTHE SAME RACEWAY CABLE TRAY, CABLE, OUTLET BOX, JUNCTION BOX, ORSIMILAR FITTING AS FEEDERS OR BRANCH CIRCUITS OF OTHER SYSTEMSUNLESS THE CONDUCTORS OF THE DIFFERENT SYSTEMS ARE SEPARATEDBY A PARTITION OR ARE CONNECTED TOGETHER.

3. THE CONNECTION TO THE MODULE OR PANEL OF THIS PROPOSED SOLARELECTRIC SYSTEM SHALL BE SO ARRANGED THAT REMOVAL OF A MODULEOR A PANEL FROM THE PHOTOVOLTAIC SOURCE CIRCUIT DOES NOTINTERRUPT A GROUNDING CONDUCTOR.

4. THE INVERTER FOR THE PROPOSED SOLAR ELECTRIC SYSTEM SHALL BEIDENTIFIED FOR USE IN SOLAR PHOTOVOLTAlC SYSTEMS. ALL EQUIPMENTSHALL BE UL APPROVED PER UL 1741.

5. THIS SYSTEM IS INTENDED TO CONNECT TO THE EXISTING FACILITYPOWER SYSTEM AT ONE POINT. THIS CONNECTION SHALL BE INCOMPLIANCE WITH THE NEC NFPA 70 ARTICLES 690.64.

6. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUITPROTECTION FOR TESTING AND ISOLATION. ALL COMBINER BOXES SHALLHAVE DISCONNECTION MEANS AT THE INVERTER FOR ISOLATION ANDTESTING (MAINTENANCE DC DISCONNECTS).

7. ALL DISCONNECTS AND COMBINERS SHALL BE SECURED FROMUNAUTHORIZED & UNQUALIFIED PERSONNEL BY LOCK OR LOCATION.

8. ALL EXPOSED CABLES, SUCH AS MODULE LEADS SHALL BE SECUREDWITH MECHANICAL OR OTHER SUNLIGHT RESISTANT MEANS.

9. INVERTER AND PV EQUIPMENT SHALL BE INSTALLED IN A SECURE AREA,SUCH AS A FENCED AREA.

10. MECHANICAL AND ELECTRICAL SUPPORT COMPONENTS, INCLUDINGSTRUT, SHALL HAVE GALVANIZED FINISH.

11. HARDWARE SHALL BE STAINLESS STEEL OR PLATED STEEL.

12. DRAINAGE SHALL BE PROVIDED AS NECESSARY FOR ALL EXTERIOREQUIPMENT ENCLOSURES.

13. DAMAGE TO FINISHES SHALL BE PROPERLY RESTORED

WIRING AND WIRING METHODS

1. EXPOSED PV MODULE WIRING WILL BE USE-2 UV RESISTANT, 90 DEGREECELSIUS, WET RATED.

2. WIRING NOT EXPOSED TO SUNLIGHT WILL BE THWN-2, 90 DEGREECELSIUS, WET RATED.

3. ALL GROUNDED CONDUCTORS ARE WHITE AND EQUIPMENT GROUNDINGCONDUCTORS ARE GREEN OR BARE PER (NEC 200-6 (A), EX 5)

4. ALL D.C. FIELD WIRING SHALL BE TAGGED AT BOTH ENDS WITHPERMANENT WIRE MARKERS

5. LIQUID TIGHT FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FORINSTALLATION IN WET AND DRY LOCATIONS. SHOULD IT BE EMPLOYED,SUPPORTS WILL BE NO MORE 12 INCHES FROM BOXES (JUNCTION BOX,CABINETS, OR CONDUIT FITTING) AND NO MORE THAN 54 INCHES APARTPER NEC.

6. ALL CONDUCTORS BELOW 100A SHALL BE COPPER.

7. EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED STEEL (R.G.S.).INTERIOR CONDUIT SHALL BE E.M.T.

8. LONG STRAIGHT EXPOSED CONDUIT RUNS, 100 FEET OR MORE, SHALLHAVE EXPANSION FITTINGS.

9. UNDERGROUND CONDUIT SHALL BE SUITABLE FOR DIRECT BURIAL ORCONCRETE ENCASEDINSTALLATIONS

DETECTION AND ISOLATION

1. THE INVERTERS ARE CAPABLE OF DETECTING AND INTERRUPTINGGROUND FAULT CURRENTS PER NEC 690-5.

DISCONNECTING MEANS

1. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYINGCONDUCTORS OF THE PHOTOVOLTAlC POWER SOURCE FROM ALL OTHERCONDUCTORS IN THE BUILDING.

2. THE GROUNDED CONDUCTOR MAY HAVE A BOLTED OR TERMINALDISCONNECTING MEANS TO ALLOW MAINTENANCE OR TROUBLESHOOTINGBY QUALIFIED PERSONNEL.

3. THE DISCONNECTING MEANS SHALL NOT BE REQUIRED TO BE SUITABLEAS SERVICE EQUIPMENT AND SHALL BE RATED IN ACCORDANCE WITHSECTION 690-17.

4. EQUIPMENT SUCH AS PHOTOVOLTAIC SOURCE CIRCUITS, OVER CURRENTDEVICES, AND BLOCKING DIODES SHALL BE PERMITTED ON THEPHOTOVOLTAlC SIDE OF THE PHOTOVOLTAlC DISCONNECTING MEANS.

DISCONNECTION OF PHOTOVOLTAlC EQUIPMENT

1. MEANS SHALL BE PROVIDED TO DISCONNECT EQUIPMENT SUCH ASINVERTERS, AND THE LIKE FROMALL UNGROUNDED CONDUCTORS OF ALL SOURCES. IF THE EQUIPMENT ISENERGIZED FROM MORE THANONE SOURCE, THE DISCONNECTING MEANS SHALL BE GROUPED ANDIDENTIFIED.

2. 690-16. FUSES. DISCONNECTING MEANS SHALL BE PROVIDED TODISCONNECT A FUSE FROM ALLSOURCES OF SUPPLY IF THE FUSE IS ENERGIZED FROM BOTH DIRECTIONSAND IS ACCESSIBLE TO OTHERTHAN QUALIFIED PERSONS. SUCH A FUSE IN A PHOTOVOLTAlC SOURCECIRCUIT SHALL BE CAPABLE OF BEING DISCONNECTED INDEPENDENTLY OFFUSES IN OTHER PHOTOVOLTAlC SOURCE CIRCUITS.

3. ALL DISCONNECTS AND COMBINERS SHALL BE SECURED FROMUNAUTHORIZED AND UNQUALIFIEDPERSONNEL BY EITHER LOCK OR LOCATION.

GROUNDING

1. ONLY ONE CONNECTION TO DC CIRCUITS (GROUNDED CONDUCTOR) ANDONE CONNECTION TO AC CIRCUITS WILL BE USED FOR SYSTEM GROUNDING(NEC 250-21) REFERENCED TO THE SAME POINT

2. EQUIPMENT GROUNDING CONDUCTORS AND SYSTEM GROUNDINGCONDUCTORS WILL HAVE AS SHORT A DISTANCE TO GROUND AS POSSIBLEAND A MINIMUM NUMBER OF BENDS

3. NON·CURRENT CARRYING METAL PARTS SHALL BE CHECKED FORPROPER GROUNDING; NOTING THAT TERMINAL LUGS BOLTED ON ANENCLOSURE'S FINISHED SURFACE MAY BE INSULATED BECAUSE OFPAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLYREMOVED.

4. MODULES SHALL BE GROUNDED WITH EQUIPMENT GROUNDINGCONDUCTOR USING THE LISTED GROUNDING POINT AND MATERIAL FIT FORTHIS PURPOSE OR RACKING MANUFACTURER'S LISTED GROUNDING MEANS.GROUND LUGS SHALL BE RATED FOR OUTDOOR USE.

5. EXACT LOCATION OF GROUND RODS AND EQUIPMENT RODS ANDEQUIPMENT SHALL BE DETERMINED IN FIELD. AVOID EXISTINGUNDERGROUND UTILITIES.

6. INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST NATIONALELECTRICAL CODE SECTION 250.

7. NO WELDING OF COLUMN ANCHOR BOLTS OR FOUNDATION REBARSSHALL BE ALLOWED. ALL WELDED CONNECTIONS SHALL BE MADE USINGSEPARATE GROUNDING RODS AND BOLTS TO FACILITATE WELDING.GROUNDING RODS AND BOLTS SHALL CONFORM TO ASTM A 307 OR A 36.GROUNDING BOLTS OR RODS EXPOSED TO THE WEATHER SHALL BEGALVANIZED, STAINLESS STEEL, OR BRASS.

8. THE INSTALLED SYSTEM SHALL BE TESTED BY THE FALL-OF-POTENTIALMETHOD. THE CONTRACTOR SHALL BE REQUIRED TO FURNISH WRITTENCERTIFICATION OF THE TEST.

9. GROUND RESISTANCE SHALL NOT EXCEED 25 OHMS. THE RESISTANCE TOGROUND SHALL BE MEASURED BY A LOW RESISTANCE TYPE "BIDDLE"GROUND TESTER OR EQUAL. GROUND FAULT

E-001

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

NOTES & SYMBOLS

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 5: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:32

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

E-110

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

ROOF ELECTRICAL

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 6: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:33

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

E-600

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

SINGLE LINE

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 7: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:33

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

E-700

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

LABLES 1 OF 2

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR

Page 8: SHEET INDEX Logo - RB POWER DESIGN · 2018. 5. 18. · 7. all disconnects and combiners shall be secured from unauthorized & unqualified personnel by lock or location. 8. all exposed

----

Prin

ted:

5/9

/201

8 11

:34

AM

SHEET NUMBER:

SHEET NAME:

DRAWN BY:

CHECKED BY:

COPYRIGHT STATEMENT: THIS DOCUMENT AND ITS CONTENTS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE IS THE PROPERTY OF WWW.RBPOWERDESIGN.COM, COPY RIGHTS RESERVED

ANSI "B"11" X 17" (279 × 432)

SHEET SIZE:

PROJECT NAME:

0 .5 1

BELLINGHAM, WA 98226PHONE: 360-255-0678

www.rbpowerdesign.com

DATEDESCRIPTIONREV

0

1

2

PROJECT ADDRESS:

E-701

SUNNY LNSUNNYVILLE, JO 44444

SUNNY DAYSDEMO

----

----

01/01/18REVIEW

----

----

RBCC

LABELS 2 OF 2

LogoSTREE ADDRESSCITY, STATE ZIPPHONE NUMBER

WWW.WEBSITE.BIZ

X______________________LIC # XXXXXXX EXP. XX/XX/XX

CONTRACTOR