Shared Services Partnership F iliti S i Facilities Services Fire Compartmentation i H lth in Healthcare Prince Philip Hospital - Thursday 7 th November 2013 Ysbyty Glan Clwyd - Tuesday 19 th November 2013 Royal Glamorgan Hospital Thursday 21 st November 2013 Royal Glamorgan Hospital - Thursday 21 st November 2013

Transcript of Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared...

Page 1: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Shared Services PartnershipF iliti S iFacilities Services

Fire Compartmentationi H lthin Healthcare

Prince Philip Hospital - Thursday 7th November 2013Ysbyty Glan Clwyd - Tuesday 19th November 2013

Royal Glamorgan Hospital Thursday 21st November 2013Royal Glamorgan Hospital - Thursday 21st November 2013

Page 2: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Shared Services PartnershipF iliti S iFacilities Services

Common Problems&

S SFire Stopping Solutions

Page 3: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Standards & Guidance(S ) f fAD B3 (Sect 10) - Protection of openings and fire stopping

10 2 ‘If a fire-separating element is to be effective10.2 If a fire-separating element is to be effective, every joint or imperfection of fit, or opening to allow services to pass through the element, should be adequately protected by sealing or fire stopping soadequately protected by sealing or fire-stopping so that the fire resistance of the element is not impaired’

10.17 adds the requirement that:Joints between fire separating elements should be fire stopped; andp g pp ;All openings for pipes, ducts, conduits or cables to pass through any part of a fire separating element should be:• Kept as few in number as possible; and• Kept as small as practical; and• Fire stopped (which in the case of a pipe or duct should allow for• Fire stopped (which in the case of a pipe or duct, should allow for

thermal movement).

Page 4: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Pipe Wraps & Collarsp pHTM05/02 Clause 6.16 - To maintain the integrity of compartmentation, openings should be limited to:

b. openings for pipes of not more than 160mm diameter which, if exposed to a temperature of

p g

diameter which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flames or hot gases will pass through the wall of the pipe;wall of the pipe;

c. pipes of materials other than those in (b) above of not more than 40mm diameter;;

d. pipes of any diameter which are provided with a proprietary seal which has been shown by test (for the diameter of pipe proposed) to maintain the fire resistance of the compartment structure;

Page 5: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Pipe Wraps & C llCollars

SleevingCast in slab or belowCast in slab or belowOne or both sides of wall

Hilti CP645PFC CorofilPFC CorofilRockwool Fire Pro

Page 6: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Pipe WrapsPipe Wraps

Page 7: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin
Page 8: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin
Page 9: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Pipe WrapsPipe Wraps

Page 10: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Check the fieldof application

Ensure installationi t ti f ll dof application instructions are followed

If in doubt refer toIf in doubt refer to product testing details

Refer to allRefer to all documentation

Page 11: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Coordination issues

Solution to maintain FRReposition or ‘box-out’

Page 12: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

PU Expanding FoamPolyurethane Foamp gy

Normal PU Expanding Foam is not an intumescent productan intumescent product

(i.e. It will not expand when heated).

Page 13: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Which of these is ‘fire rated’?

A B C

Methods for identification: -Coloured pigmentsPot of paint, and/orLabels

R l ti 38 P i i f i f tiRegulation 38 – Provision of information.

Page 14: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

PU ‘Fire-Block’ Foam

Page 15: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

PU ‘Fire Rated’ Foam Many ‘fire-rated’ PU foams are available

& product identification difficult‘Reaction to Fire’ B1 & B2 Rating

DIN 4102 Claimed periods of fire resistance are

achieved under strictly controlled test conditions, with a high standard of quality

DIN 4102

, g q ycontrol for installation of sample tested

Products used on site Often used on irregular shaped openings

of varying widths beyond scope of application (hollow stud partitions)

Do contractors understand the limitations of products in use?Littl lit t l ( id l t l Little quality control (are voids completely filled?)

Before specifying/using any product p y g g y pensure it’s fit for the intended application review test reports. Up to 5 hours protection

Page 16: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Fire Test 117611Horizontal exposure220mm Masonry Wall220mm Masonry Wall

Vertical exposureVertical exposure250mm Concrete Floor

Page 17: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Horizontal Apertures Through Wall220 M W ll220mm Masonry Wall

Integrity Insulation (mins) (mins)

71 69

240 240

86 86

240 240

240 240

Page 18: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Vertical Apertures Through Floor250 C t Sl b250mm Concrete Slab

Integrity 240 240 115 59 206

Insulation 240 240 113 58 206

Page 19: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

PU Foam and Stud PartitionsAd-hoc fire resistance test f ll i i i l ffollowing principles of BS476:20:1987 testing regime

Integrity 94 minutesg yInsulation 69 minutes

Page 20: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

PU Expanding Foamp g

Page 21: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Expanding / Intumescent FoamExpanding / Intumescent Foam

Re-penetrable

Graphite and PU based, two part,

intumescent sealant

Tested in unlined dry wall openings up towall openings up to

400 x 400mm

Page 22: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Fire Seals for Electrical P t tiPenetrations

IET Regs (17th edition):–IET Regs (17th edition):527.1.2 A wiring system shall be installed so that the general

building structural performance and fire safety are g p ynot reduced

527.2.1 Where a wiring system passes through elements of g y p gbuilding construction such as floors, walls ...., the opening remaining after passage of wiring system shall be sealed according to the degree of fireshall be sealed according to the degree of fire resistance (if any) prescribed for the respective element of building construction before penetration

611.3 vii Requires inspection of the presence of fire barriers and suitable seals – before being put into service.

Page 23: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Trays, Cables & Pillowsy ,

Polystyrene infill at head of wall

Page 24: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Trays, Cables & Pillowsy ,

Page 25: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Trays, Cables & Pillowsy ,

Pl ti bl ti ?Plastic cable ties?

Date, size and unique reference numberreference number

Page 26: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Trays, Cables & Pillowsy ,

Page 27: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Removable pillow secured to cable traysecured to cable tray

Page 28: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Innovative ProductsHILTI - CFS-SL Fire SleeveHILTI - CFS-SL Fire Sleeve

Page 29: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Wiremold LegrandWiremold LegrandFlamestopper (US Product)

Page 30: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Abesco - CT120 Cable Transit System Easy Retro-fit

Page 31: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Fire Seals for Electrical P t tiPenetrations

IET Regs (17th edition)527.2.2 A wiring system such as a conduit system, cable

ducting system, .... which penetrates elements of building construction having specified fire resistance shall beconstruction having specified fire resistance shall be internally sealed to the degree of fire resistance of the respective element before penetration ....p p

Page 32: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Intumescent Putty Insertsy

Page 33: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Fire Dampersp

HTM05 02 D1 t tHTM05-02 D1 states: -

All fire dampers should be installed so that they maintain their integrity against the passage of fire for the required period of fire resistanceagainst the passage of fire for the required period of fire resistance

A fire damper should be adequately fixed into, or to, the construction it is protecting.

Page 34: Shared Services Partnership F iliti S iFacilities Services problems.pdf · 2015-10-27 · Shared Services Partnership F iliti S iFacilities Services Fire Compartmentation iH lthin

Fire/Smoke or Fire dampers dependent on wall designation

Fire rated ductwork in-lieu of dampers Kitchens, Isolation Rooms, Fume Cupds

Future workshops will specifically address Fire Dampers.