Achim Hobl Monday, 23 September 2013 No 1 Nexans SuperConductors Achim Hobl , Joachim Bock, Steffen Elschner Nexans SuperConductors GmbH Chemiepark Knapsack 50351 Hürth, Germany SFCL for Power Grid

Transcript of SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26...

Page 1: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 1 Nexans SuperConductors

Achim Hobl, Joachim Bock, Steffen Elschner

Nexans SuperConductors GmbH

Chemiepark Knapsack

50351 Hürth, Germany

SFCL for Power Grid

Page 2: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 2 Nexans SuperConductors

Outline

1. Motivation

2. Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6. Summary

Page 3: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 3 Nexans SuperConductors

Outline

1.Motivation

2. Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6. Summary

Page 4: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 4 Nexans SuperConductors

Need for Fault Level Control

in the Grids

Increase in distributed generation

„Energiewende“

Ageing of grid

infrastructure

Page 5: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 5 Nexans SuperConductors

Equipment malfunction or failure

Caused by environmental effects

At any position

At arbitraty short circuit resistance

Short Circuits

Page 6: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 6 Nexans SuperConductors

Outline

1. Motivation

2.Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6. Summary

Page 7: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 7 Nexans SuperConductors

SFCL

Type

Superconductor

Material

Application

SFCL

Type

Saturated

core

Shielded

core

Resistive

type

Superconductor

Material

BSCCO

bulk

BSCCO

tape

YBCO

tape

MgB2

Application

Auxiliary

Supply

Bus bar

coupling

Transformer

feeder

HTS cable

protection

Different Classifications of SFCL

Page 8: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 8 Nexans SuperConductors

Classification Type

Pre-Saturated Iron Core

+ no quench of the superconductor

+ can be without interruption

– large volume and weight

– low level of limitation

– relatively high impedance

FCL

Page 9: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 9 Nexans SuperConductors

Classification Type

Shielded Iron Core

+ no current leads to cryogenics

+ can be without interruption

– large volume and weight

– needs non-metal cryostat

– relatively high impedance

FCL

Page 10: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 10 Nexans SuperConductors

Classification Type

Resistive Limitation

+ compact

+ intrinsically safe

+ strong limitation

+ independent of short circuit level

– current leads to low temperature

– may need interruption

FCL

Page 11: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 11 Nexans SuperConductors

Classification Type

Limitation Comparison

Saturated Iron Core

current

im

ped

an

ce

Resistive FCL

resista

nce

in

du

cta

nce

Page 12: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 12 Nexans SuperConductors

Classification Type

SFCL Projects / Installations Realized

Saturated Core

(S)FCL

• InnoPower

• Zenergy ASL

• GridON

• …

Shielded Core

SFCL

• ABB

(stopped)

• Bruker EST

(stopped)

• …

Resistive SFCL

• Siemens/AMSC

• Varian Power

Systems

• KEPRI

• RSE

• Nexans

• …

Industrial Activities / In-grid Installations

Superconducting FCL

(selected examples)

Also first HV Installation / Concepts

Page 13: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 13 Nexans SuperConductors

Classification

Superconductor

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1 1.2

Vo

lta

ge

I/Ic

U bulk (n=9)

U tape (n=20)

Properties Tape

(in comparison):

• “Sharper”

transition

• Faster limitation

• Stronger

limitation

• Potentially lower

AC losses

• More sensitive

to overcurrent

Page 14: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 14 Nexans SuperConductors

Parameter Tape "A" Tape "B" Tape "C" Tape "D"

Sin

gle

ta

pe

@ 7

7 K

Critical current (A) 340 250 500 470

Type of substrate nonmagn. magn. magn. nonmagn.

Tape dimensions w x t (mm x mm) 12 x 0.11 12 x 0.25 12 x 0.32 10 x 0.12

Limited peak short circuit current (Ip/Ic)

2.4 5.5 3.7 3.1

Limited short circuit current (Irms/Ic)

0.78 1.5 1.0 0.85

Limitation Behavior of

Different YBCO HTS Tapes

Page 15: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 15 Nexans SuperConductors

Sh

ort circu

it cu

rren

t (I/Ic)

Time (ms)

Limitation Behavior of

Different YBCO HTS Tapes

Page 16: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 16 Nexans SuperConductors

1 Generator feeder

2 Power station auxiliaries

3 Network coupling

4,5 Busbar coupling

6 Shunting current limiting reactor

7 Transformer feeder

8 Outgoing feeder

9 Combination with other SC devices,

especially SC cables

10 Coupling local generating units

11 Closing ring circuits

© Mathis Noe, KIT

Transmission network (e.g. 380 kV)

Distribution

Network

(e.g. 110 kV)

Distribution

Network

(e.g. 110 kV)

Distribution

Network

(e.g. 110 kV)

FCL FCL

FCL

FCL

FCL

FCL FCL

FCL

FCL

FCL

7

8

6 FCL

9 9

1

2

5

10

11

3

4

FCL

Applications of SFCL

Vattenfall,

Ensystrob

ECCOFLOW

AmpaCity

}

Page 17: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 17 Nexans SuperConductors

12 kV, 800 A 12 kV, 100 A 12 kV, 400 A

11/2009 2011 10/2009

Bi 2212 bulk

State-of-the-Art

SFCL

12 kV, 600 A 12 kV, 2.3 kA 24 kV, 1 kA

10/2011 2013

YBCO tapes

2013

Page 18: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 18 Nexans SuperConductors

Outline

1. Motivation

2. Classification of SFCLs

3.SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6. Summary

Page 19: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 19 Nexans SuperConductors

Why SFCL in Power Stations?

e.g. Vattenfall Station Boxberg

Very low impedance netwoks for high voltage stability

Huge lengths of MV cables

One SFCL protects > 20 circuit breakers

Page 20: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 20 Nexans SuperConductors

Component Module One phase Assy into a

cryostat

FCL

System Assembly

Page 21: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 21 Nexans SuperConductors

Realisation of the SFCL for Vattenfall

BSCCO Bulk SFCL

System Assembly

Open System

Page 22: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 22 Nexans SuperConductors

SFCL installation

In Boxberg Power Station

Page 23: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 23 Nexans SuperConductors

Limiter

component

Module

System

ENSYSTROB

Worldwide first YBCO cc FCL in-grid

Page 24: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 24 Nexans SuperConductors

Tests:

• 12 kV/ 63 kA (prosp. peak)

• 3 x 3-phase short circuit

• 2 x 2-phase short circuit

ENSYSTROB

High Power Test

Page 25: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 25 Nexans SuperConductors

L1, L2, L3

-20

-15

-10

-5

0

5

10

15

20

0.36 0.41 0.46 0.51

time [s]

cu

rre

nt

[kA

]

L1 L2 L3

L1, L2, L3

-20

-15

-10

-5

0

5

10

15

20

0.36 0.41 0.46 0.51

time [s]

cu

rre

nt

[kA

]

L1, L2, L3

-20

-15

-10

-5

0

5

10

15

20

0.36 0.41 0.46 0.51

time [s]

cu

rre

nt

[kA

]

L1 L2 L3 prospective [A]

Page 26: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 26 Nexans SuperConductors

Outline

1. Motivation

2. Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4.SFCL in Distribution Grids:

ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6. Summary

Page 27: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 27 Nexans SuperConductors

Partners of the ECCOFLOW Project

Page 28: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 28 Nexans SuperConductors

Palma

Kosice

ECCOFLOW

Installation Sites

Page 29: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 29 Nexans SuperConductors

ECCOFLOW

Specification

ENDESA VSE ECCOFLOW

rated voltage 16.5 kV 24 kV 24 kV

rated current 1000 A 1005 A 1005 A

max. prospective current (peak) 22 kA 26 kA 26 kA

max. limited current (peak) 10.8 kA 17 kA 10.8 kA

fault duration 1 s 120 ms 1 s

HTS limitation time 80 ms 80 ms 80 ms

recovery time < 30 s < 30 s < 30 s

AC withstand voltage 50 kV 50 kV 50 kV

lightning impulse 125 kV 125 kV 125 kV

Page 30: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 30 Nexans SuperConductors

..

. HTS component

Cryostat

HTS module

Bushing

Current leads

LN2

Circuit breaker Air coil

Cooling

SCFCL system

Grid impedance

..

.

LN2

..

.

LN2

GM cryocooler

Grid interface

Grid interface

System Overview

Cryostat 3-in-1

Page 31: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 31 Nexans SuperConductors

Conductor Quench Modelling

Including Inhomogeneity

Hot spots are the highest risk in a tape for FCL application

Occurs on the weakest parts of the tape

Tape is never perfectly homogenous, but how much inhomogeneous?

Measurements on 600 m provided by manufacturer

Inhomogeneity included in modelling randomized distribution

Model itself «included» in a grid model

Page 32: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 32 Nexans SuperConductors

Conductor Quench Modelling Results

Selected cc-tape:

Tape width: 12 mm

Critical current: 380 A

Silver thickness: 4 µm

Model used to determine the safest and most economic

stabilization

No problems occur for low

impedance faults (high fault

currents)

Problems most critical at about

15 Ω impedance in

ECCOFLOW grid

configurations

Stabilization must sustain most

critical events

Page 33: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 33 Nexans SuperConductors

Tested @ 1 kArms / 800 Vrms

Warm-cold cycles : > 10 times

limitation behaviour: > 60 full short-circuit faults

nominal current: 1005 A for 30 minutes

partial loads: 2.5 x Ic to 1 x Ic

Component testing

Page 34: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 34 Nexans SuperConductors

Closed Cooling System

• Cooling ensured by two

Cryocoolers:

– Cryomech AL600

– Oerlikon Leybold 250MD

Cryostat 3-in-1

• Temperature

control:

– Circulation ensured by the

condensation of the GN2

– LN2 bath controlled with

the cryocoolers and heater

regulation

Page 35: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 35 Nexans SuperConductors

Container with

• Cryostat

• 2 cold heads

• Water chiller

• Control system

• UPS

Cryostat Assembly to Container

Page 36: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 36 Nexans SuperConductors

3 D CAD View

CB2 CB1

Air Core Reactors

SFCLL

SFCL Device

Page 37: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 37 Nexans SuperConductors

VSE

Graph of limited

current, Endesa

Total current and

current through SFCL,

Endesa.

Spec. < 10.8 kA peak

Total current and

current through SFCL,

VSE.

Spec. < 17 kA peak

ECCOFLOW

Results of Limitation Tests

Page 38: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 38 Nexans SuperConductors

ECCOFLOW

AC Losses

ECCOFLOW: AC-losses

0

50

100

150

200

250

300

0 200 400 600 800 1000 1200

Po

we

r [W

]

Curren [A]

L1 (R) [W]

L2 (S) [W]

L3 (T) [W]

CL (calc.) [W]

Page 39: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 39 Nexans SuperConductors

SFCL Container arrived in Palma

Page 40: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 40 Nexans SuperConductors

Outline

1. Motivation

2. Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5.SFCL in HTS Cable

Protection: AmpaCity

6. Summary

Page 41: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

AmpaCity

HTS Cable for Inner City Applications

Page 42: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 42 Nexans SuperConductors

Substation

Herkules

Substation

Dellbrügge

Joint

Technical specifications:

Rated voltage: 10 kV

Design current: 2310 A (40 MVA)

Lenght: 1 km

Luftbild: "Darstellung aus HK Luftbilder / Karten Lizenz Nr. 197 / 2012 mit

Genehmigung vom Amt für Geoinformation, Vermessung und Kataster der

Stadt Essen vom 13.02.2012"

Cable track in Essen

• FCL

• Cooling System

• HTS Cable

Termination

• HTS Cable

Termination No more HV transformer in city centre

Page 43: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 43 Nexans SuperConductors

Completed FCL

Transportation to High Power Test Lab

Page 44: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 44 Nexans SuperConductors

-60000

-40000

-20000

0

20000

40000

60000

0.29 0.3 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38

Cu

rre

nt

[A]

Time [s]

Prospective and limited currents - AmpaCity

iL1

iL2

iL3

AmpaCity FCL

Limitation

High Power Test at the IPH, Berlin

-60000

-40000

-20000

0

20000

40000

60000

0.29 0.3 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38

Cu

rre

nt

[A]

Time [s]

Prospective and limited currents - AmpaCity

iL1

iL2

iL3

iL1, lim

iL2, lim

iL3, lim

-16000

-12000

-8000

-4000

0

4000

8000

12000

16000

0.29 0.3 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38

Cu

rre

nt

[A]

Time [s]

Prospective and limited currents - AmpaCity

iL1

iL2

iL3

iL1, lim

iL2, lim

iL3, lim

Page 45: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 45 Nexans SuperConductors

AmpaCity

AC Losses

0

50

100

150

200

250

300

350

400

0 200 400 600 800 1000 1200 1400 1600

Po

we

r [W

]

Current [A]

L1 [W]

L2 [W]

L3 [W]

CL (calc.) [W]

AmpaCity FCL: AC-losses

Page 46: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 46 Nexans SuperConductors

Outline

1. Motivation

2. Classification of SFCLs

3. SFCL in Power Station:

Vattenfall - Ensystrob

4. SFCL in Distribution Grids: ECCOFLOW

5. SFCL in HTS Cable Protection: AmpaCity

6.Summary

Page 47: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 47 Nexans SuperConductors

• MV SFCLs can be well applied for

– Protection of HTS cable

– Burbar coupling

– Transformer feeder

– Power station auxiliaries

– Local networks

– Additional in-feed (renewable generation)

• Proven application in different in-grid installations

• Experience with different cooling options (open/closed)

• First HV applications coming up

Summary

Page 48: SFCL for Power Grid · rated current 1000 A 1005 A 1005 A max. prospective current (peak) 22 kA 26 kA 26 kA max. limited current (peak) 10.8 kA 17 kA 10.8 kA fault duration 1 s 120

Achim Hobl

Monday, 23 September 2013

No 48 Nexans SuperConductors